0
0
04.04.2016
04.04.2016
First
First Submission.
Submission.
Rev.
Date
Rev.
Date
JS
JS
PCP
PCP
PCP
PCP
Remarks/Reasons for Revision
Remarks/Reasons for Revision
Prepared
Checked
Approved
Prepared
Checked
Approved
CLIENT
CLIENT :
:
HINDUSTAN
HINDUSTAN ZINC
ZINC LIMITED
LIMITED
CONSULTANT
CONSULTANT:
:
DEVELOPMEN
DEVELOPMENT
T CONSULTAN
CONSULTANTS
TS PVT.
PVT. LTD.
LTD.
TITLE
TITLE :
:
SHORT
SHORT CIRCUIT
CIRCUIT CALCULATION
CALCULATION
PLANT : 1.5 MTPA LEAD-ZINC BENEFICIATION PLANT
PLANT : 1.5 MTPA LEAD-ZINC BENEFICIATION PLANT
AT S.K.MINES, RAJASTHAN
AT S.K.MINES, RAJASTHAN
L&T DOC. No.
L&T DOC. No.
DRAWING ISSUED FOR
DRAWING ISSUED FOR
APPROVAL
APPROVAL
REFERENCE/INFORMATION
REFERENCE/INFORMATION
CONSTRUCTION
CONSTRUCTION
DISTRIBUTION
DISTRIBUTION
L&T
L&T Document Document No.: No.: Rev. Rev. No. No. 00 PREPARED
PREPARED BY BY REVIEWED REVIEWED BYBY
Short circuit calculation is worked out considering the following conditions:
Short circuit calculation is worked out considering the following conditions:
1.
1. We have considered 1000MVA as source fault level of grid as IS
We have considered 1000MVA as source fault level of grid as IS 2026-I,1977
2026-I,1977
2.
2. Cables are not considered, however this will
Cables are not considered, however this will reduce further SC level.
reduce further SC level.
3.
3. Lumped load at 0.415kV bus is derived from Latest load list.
Lumped load at 0.415kV bus is derived from Latest load list.
4.
4. SC calculations are done in accordance with IEC 60909
SC calculations are done in accordance with IEC 60909
Detailed short circuit calculation result for each bus is indicated as below:
Detailed short circuit calculation result for each bus is indicated as below:
Sr.
Sr. No.
No.
Bus
Bus levels
levels
Rated Fault level
Rated Fault level
(RMS)
(RMS)
Type of Fault
Type of Fault
Attained
Attained
Fault Level
Fault Level
as per
as per
calculation
calculation
1
1
6.6kV,
6.6kV, {with
{with 33
33 kV
kV I/C-2
I/C-2 open
open &6.6kV
&6.6kV
us coupler closed}
us coupler closed}
40
40
Symmetrical 3
Symmetrical 3
phase
phase
23.16 KA
23.16 KA
2
2
6.6kv
6.6kv {with
{with 33kV
33kV I/C
I/C -2
-2 Closed
Closed &
& 6.6kV
6.6kV
us coupler open}
us coupler open}
40
40
Symmetrical 3
Symmetrical 3
phase
phase
20.9 KA
20.9 KA
PMCC- 2 MAIN PROCESS -ECR
PMCC-3 SER/TER HOUSE PMCC- 1 MAIN PROCESS-EPR 0.433 kV 8 4 .7 0.433 kV 0. 04 k V 4 2 0.433 kV 0. 0 7 k V 4 1. 2 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0. 0 7 k V 4 1. 2 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0. 0 7 k V 4 1. 2 TR#2 2 MVA BusDuct8 TR#3 2 MVA BusDuct14 7.8 Lump4 1. 5 MVA 7.8 Open Lump3 0. 5 MVA Lump2 0. 5 MVA Open Lump1 1. 5 MVA 7.8 7.8 BusDuct7 TR#1 2 MVA TR#5 2 MVA BusDuct11 TR#6 2 MVA BusDuct10 Lump8 1. 5 MVA Open Lump7 0. 5 MVA Lump6 0. 5 MVA Open Lump5 1. 5 MVA 7.8 7.8 BusDuct9 TR#4 2 MVA Open Lump9 900 kVA 4.99 4.99 BusDuct12 TR#7 2 MVA fl oat air blower -1
750 kW ball mil l
2850 kW regrind mil l 375 kW
Float air blower-2 750 kW Secondary c one crusher
200 kW TR#8 2 MVA BusDuct15 Lump10 900 kVA Lump1 1. 5 MVA Lump2 0. 5 MVA Lump3 0. 5 MVA Lump4 1. 5 MVA Lump5 1. 5 MVA Lump6 0. 5 MVA Lump7 0. 5 MVA Lump8
1. 5 MVA 900 kVALump9
Lump10 900 kVA TR#1 2 MVA TR#2 2 MVA TR#3 2 MVA TR#4 2 MVA TR#5 2 MVA TR#6 2 MVA TR#7 2MVA TR#8 2 MVA 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV fl oat air blower -1
750 kW ball mil l
2850 kW regrind mil l
375kW Secondar yconecr usher
200 kW 750 kWFloat air blower-2
0. 04 k V 4 2 0. 0 7 k V 4 1. 2 0. 0 7 k V 4 1. 2 0. 0 7 k V 4 1. 2 8 4 .7 BusDuct7 BusDuct8 7.8 Open Open 7.8 BusDuct9 7.8 Open Open 4.99 Open BusDuct10 BusDuct11 BusDuct12 BusDuct14 BusDuct15 7.8 7.8 7.8 4.99
page 1 11:40:44 Apr 05, 2016 Project File: SK Mines HZL
PMCC- 2 MAIN PROCESS -ECR
PMCC-3 SER/TER HOUSE PMCC- 1 MAIN PROCESS-EPR 0.433 kV 8 4 .7 0.433 kV 0. 04 k V 4 2 0.433 kV 0. 0 7 k V 4 1. 2 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0. 0 7 k V 4 1. 2 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0. 0 7 k V 4 1. 2 TR#2 2 MVA BusDuct8 TR#3 2 MVA BusDuct14 7.8 Lump4 1. 5 MVA 7.8 Open Lump3 0. 5 MVA Lump2 0. 5 MVA Open Lump1 1. 5 MVA 7.8 7.8 BusDuct7 TR#1 2 MVA TR#5 2 MVA BusDuct11 TR#6 2 MVA BusDuct10 Lump8 1. 5 MVA Open Lump7 0. 5 MVA Lump6 0. 5 MVA Open Lump5 1. 5 MVA 7.8 7.8 BusDuct9 TR#4 2 MVA Open Lump9 900 kVA 4.99 4.99 BusDuct12 TR#7 2 MVA fl oat air blower -1
750 kW ball mil l
2850 kW regrind mil l 375 kW
Float air blower-2 750 kW Secondary c one crusher
200 kW TR#8 2 MVA BusDuct15 Lump10 900 kVA Lump1 1. 5 MVA Lump2 0. 5 MVA Lump3 0. 5 MVA Lump4 1. 5 MVA Lump5 1. 5 MVA Lump6 0. 5 MVA Lump7 0. 5 MVA Lump8
1. 5 MVA 900 kVALump9
Lump10 900 kVA TR#1 2 MVA TR#2 2 MVA TR#3 2 MVA TR#4 2 MVA TR#5 2 MVA TR#6 2 MVA TR#7 2MVA TR#8 2 MVA 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV 0.433 kV fl oat air blower -1
750 kW ball mil l
2850 kW regrind mil l
375kW Secondar yconecr usher
200 kW 750 kWFloat air blower-2
0. 04 k V 4 2 0. 0 7 k V 4 1. 2 0. 0 7 k V 4 1. 2 0. 0 7 k V 4 1. 2 8 4 .7 BusDuct7 BusDuct8 7.8 Open Open 7.8 BusDuct9 7.8 Open Open 4.99 Open BusDuct10 BusDuct11 BusDuct12 BusDuct14 BusDuct15 7.8 7.8 7.8 4.99 Location: SK Mines
Engineer: Jigyesh Sharma
Study Case: CASE-1 11.1.1C
Page: 1
SN: LARTOUMUM
Filename: SK Mines HZL
Project: SC calculation
ETAP
Contract:
Date: 04-05-2016
Revision: Base Config.: Normal
Electrical Transient Analyzer Program
Short-Circuit Analysis
IEC 60909 Standard
Electrical Transient Analyzer Program
Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents
Number of Buses: Number of Branches: Number of Machines: Total 15 Tie PD Total 17 5 Impedance Lumped Load 10 0 Total Induction Machines 5 Line/Cable 0 17 Load Synchronous Motor 0 Reactor 0 15 V-Control 2 Power Grid XFMR3 0 0 Swing Synchronous Generator 0 XFMR2 10 2 Unit System: Project Filename: Output Filename: System Frequency: 50.00 Hz English SK Mines HZL
Adjustments
Transformer Impedance:
Reactor Impedance:
Tolerance
Overload Heater Resistance:
Transmission Line Length:
Cable Length:
Temperature Correction
Transmission Line Resistance:
Cable Resistance: Percent Degree C 20 20 Individual /Global Individual /Global Global Global Individual Individual Apply Adjustments Apply Adjustments Yes Yes No No No Yes Yes
Bus Input Data
ID Type
Bus InitialVoltage
%Mag. Ang. Sub-sys Base kV Nom. kV 33.000 33.000 SWNG Bus20 1 100.00 0.00 6.600 6.600 Load Bus22 1 100.00 -30.00 33.000 33.000 SWNG Bus24 2 100.00 0.00 6.600 6.600 Load Bus25 1 100.00 -30.00 0.433 0.433 Load Bus26 1 100.00 0.00 0.433 0.433 Load Bus27 1 100.00 0.00 0.433 0.433 Load Bus28 1 100.00 0.00 0.433 0.433 Load Bus29 1 100.00 0.00 0.433 0.433 Load Bus30 1 100.00 0.00 0.433 0.433 Load Bus31 1 100.00 0.00 0.433 0.433 Load Bus32 1 100.00 0.00 0.433 0.433 Load Bus33 1 100.00 0.00 0.433 0.433 Load Bus34 1 100.00 0.00 0.433 0.433 Load Bus35 1 100.00 0.00 0.433 0.433 Load Bus36 1 100.00 0.00 0.433 0.433 Load Bus37 1 100.00 0.00 6.600 6.600 Load T14~ 0 100.00 0.00 17 Buses Total All voltages reported by ETAP are in % of bus Nominal kV. Base kV values of buses are calculated and used internally by ETAP.
2-Winding Transformer Input Data
Phase Shift
ID MVA Prim.kV Sec.kV %Z X/R Prim. Sec.
Transformer %TapSetting
% Tol. Rating ZVariation +5% -5% % Z Type Angle Adjusted T10 20.000 33.000 6.600 10.00 20.00 0 0 0 0 0 10.0000 Dyn 30.000 TR#1 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#2 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#3 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#4 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#5 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#6 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#7 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#8 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 T14 20.000 33.000 6.600 10.00 20.00 0 0 0 0 0 10.0000 Dyn -30.000
2-Winding Transformer Grounding Input Data
ID MVA Prim. kV Sec. kV
Transformer Type Rating Primary Grounding Conn. Type Secondary Amp Ohm kV kV Amp Ohm Type T10 20.000 33.000 6.600 D/Y Solid D/Y 0.433 6.600 2.000 TR#1 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#2 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#3 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#4 Resistor 75.00000 D/Y 0.433 6.600 2.000 TR#5 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#6 Resistor 75.00000 D/Y 0.433 6.600 2.000 TR#7 Resistor 75.00000 D/Y 0.433 6.600 2.000 TR#8 Resistor 3.3 75.00000 D/Y 6.600 33.000 20.000 T14 Solid
Branch Connections
ID Type FromBus ToBus R X Z
CKT/Branch Connected Bus ID %Impedance,Pos.Seq.,100MVAb
Y T10 2W XFMR Bus20 Bus22 2.46 49.23 49.30 TR#1 2W XFMR Bus22 Bus26 49.42 296.51 300.60 TR#2 2W XFMR Bus25 Bus30 49.42 296.51 300.60 TR#3 2W XFMR Bus22 Bus28 49.42 296.51 300.60 TR#4 2W XFMR Bus22 Bus31 49.42 296.51 300.60 TR#5 2W XFMR Bus25 Bus32 49.42 296.51 300.60 TR#6 2W XFMR Bus25 Bus34 49.42 296.51 300.60 TR#7 2W XFMR Bus22 Bus36 49.42 296.51 300.60 TR#8 2W XFMR Bus25 Bus37 49.42 296.51 300.60 T14 2W XFMR T14~ Bus25 61.54 1230.86 1232.40
CB66 Tie Breakr Bus30 Bus27
CB69 Tie Breakr Bus30 Bus29
CB71 Tie Breakr Bus32 Bus33
CB73 Tie Breakr Bus32 Bus35
Power Grid Input Data
kV R X" Rating R/X" 100 MVA Base % Impedance MVASC ID IDPowerGrid ConnectedBus Grounding
Type 0.07
U3 Bus20 1000.000 33.000 0.71247 9.97459 Wye - Solid
0.07
U4 Bus24 1000.000 33.000 0.71247 9.97459 Wye - Solid
Induction Machine Input Data
ID
ID Type kVA kV Amp PF %R %X"
InductionMachine Rating
Qty Connected Bus R/X" MW/PP mFact. HP/kW Grounding
Conn. Type Amp
PosSeqImp (Mtr Base)
75.90
Bus22 6.600 92.37 2.16 13.72 0.16 0.38
loatairblower-1 Motor 1 750.00 867.66 Wye Open
284.61
Bus22 6.600 92.92 1.49 13.81 0.11 1.43
allmill Motor 1 2850.00 3253.59 Wye Open
38.21
Bus22 6.600 92.09 2.62 13.64 0.19 0.19
egrindmill Motor 1 375.00 436.83 Wye Open
75.90
Bus25 6.600 92.37 2.16 13.72 0.16 0.38
Floatairblower-2 Motor 1 750.00 867.66 Wye Open
20.51
Bus25 6.600 91.83 3.12 13.53 0.23 0.10
Secondaryconecrusher Motor 1 200.00 234.44 Wye Open
Total Connected Induction Machines ( = 5 ): 5660.2 kVA
Lumped Load Input Data
ID kVA kV R X" R/X"
Lumped Load Rating MachineBase
kW kvar Loading MTR STAT % Load Lumped Load Motor Loads Amp % PF % Impedance MW/PP mFact.
Conn. Type Amp
Grounding Lump1 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump2 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump3 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump4 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump5 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump6 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump7 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump8 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump9 900.0 0.433 1200.04 85.00 70 30 535.50 331.87 6.46 15.37 0.42 Delta 0.54 Lump10 900.0 0.433 1200.04 85.00 70 30 535.50 331.87 6.46 15.37 0.42 Delta 0.54
SHORT- CIRCUIT REPORT
Fault at bus:
Looking into "From Bus"
ID From Bus Symm.rms
ID Va
From Bus To Bus % V kA % Voltage at From Bus
Contribution 3-Phase Fault
Vb Vc Ia 3I0 R1 X1 R0 X0
kA Symm. rms % Impedance on 100 MVA base
Line-To-Ground Fault
Positive & Zero Sequence Impedances Nominal kV Voltage c Factor Bus22 = 1.10 (Maximum If) = 6.600
Bus22 Total 0.00 23.162 0.00 104.37 100.85 21.986 21.986 4.67E+000 4.13E+001 2.37E+000 4.73E+001
Bus20 Bus22 81.76 15.959 91.64 100.12 91.22 17.245 21.140* 3.25E+000 6.02E+001 2.46E+000 4.92E+001
Bus26 Bus22 15.98 0.512 66.38 100.56 62.11 0.327 0.000 6.64E+002 1.76E+003
Bus28 Bus22 15.98 0.512 66.38 100.56 62.11 0.327 0.000 6.64E+002 1.76E+003
Bus31 Bus22 15.98 0.512 66.38 100.56 62.11 0.327 0.000 6.64E+002 1.76E+003
Bus36 Bus22 10.23 0.327 64.16 100.60 60.53 0.209 0.000 1.07E+003 2.74E+003
float air blower -1 Bus22 100.00 0.601 100.00 100.00 100.00 0.364 0.000 2.49E+002 1.58E+003
ball mill Bus22 100.00 2.254 100.00 100.00 100.00 1.367 0.000 4.59E+001 4.24E+002
regrind mill Bus22 100.00 0.303 100.00 100.00 100.00 0.169 0.000 6.00E+002 3.12E+003
Bus30 Bus25 11.24 0.360 64.55 100.59 60.79 0.230 0.000 9.72E+002 2.49E+003
Bus32 Bus25 11.24 0.360 64.55 100.59 60.79 0.230 0.000 9.72E+002 2.49E+003
Bus34 Bus25 15.98 0.512 66.38 100.56 62.11 0.327 0.000 6.64E+002 1.76E+003
Bus37 Bus25 10.23 0.327 64.16 100.60 60.53 0.209 0.000 1.07E+003 2.74E+003
T14~ Bus25 0.00 0.000 58.23 60.26 100.66 0.282 0.846* 6.15E+001 1.23E+003
Float air blower-2 Bus25 100.00 0.601 100.00 100.00 100.00 0.364 0.000 2.49E+002 1.58E+003
Secondary cone crusher
Bus25 100.00 0.162 100.00 100.00 100.00 0.090 0.000 1.33E+003 5.77E+003
Bus25 Bus22 0.00 2.312 0.00 104.37 100.85 1.721 0.846
Bus27 Bus30 11.24 2.742 64.55 100.59 60.79 1.520 0.000
Bus29 Bus30 11.24 2.742 64.55 100.59 60.79 1.520 0.000
Bus33 Bus32 11.24 2.742 64.55 100.59 60.79 1.520 0.000
Fault at bus:
Looking into "From Bus"
ID From Bus Symm.rms
ID Va
From Bus To Bus % V kA % Voltage at From Bus
Contribution 3-Phase Fault
Vb Vc Ia 3I0 R1 X1 R0 X0
kA Symm. rms % Impedance on 100 MVA base
Line-To-Ground Fault
Positive & Zero Sequence Impedances Nominal kV Voltage c Factor Bus22 = 1.10 (Maximum If) = 6.600
Initial Symmetrical Current (kA, rms)
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer :
3-Phase L-G L-L L-L-G
23.162 Peak Current (kA), Method C
Breaking Current (kA, rms, symm) Steady State Current (kA, rms)
: : : 57.414 15.959 21.986 54.500 21.986 21.986 19.852 49.209 19.852 19.852 22.975 56.952 22.975 22.975
Short-Circuit Summary Report
3-Phase, LG, LL, LLG Fault Currents
ID kV
Bus
I"k ip Ik I"k ip Ib I"k ip Ib Ik I"k Ib
3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground
Ik ip Ik
Bus22 6.600 23.162 57.414 15.959 21.986 54.500 21.986 21.986 19.852 49.209 19.852 19.852 22.975 56.952 22.975 22.975
All fault currents are in rms kA. Current ip is calculated using Method C. * LLG fault current is the larger of the two faulted line currents.
Sequence Impedance Summary Report
ID kV
Bus
Resistance Reactance Impedance
P os it iv e S eq. I mp . (o hm) Ne ga ti ve S eq . I mp . (o hm)
Resistance Reactance Impedance
Zero Seq. Imp. (ohm)
Resistance Reactance Impedance
Fault Zf (ohm)
Resistance Reactance Impedance
Electrical Transient Analyzer Program
Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents
Number of Buses: Number of Branches: Number of Machines: Total 14 Tie PD Total 17 4 Impedance Lumped Load 10 0 Total Induction Machines 5 Line/Cable 0 16 Load Synchronous Motor 0 Reactor 0 14 V-Control 2 Power Grid XFMR3 0 0 Swing Synchronous Generator 0 XFMR2 10 2 Unit System: Project Filename: Output Filename: System Frequency: 50.00 Hz English SK Mines HZL
Adjustments
Transformer Impedance:
Reactor Impedance:
Tolerance
Overload Heater Resistance:
Transmission Line Length:
Cable Length:
Temperature Correction
Transmission Line Resistance:
Cable Resistance: Percent Degree C 20 20 Individual /Global Individual /Global Global Global Individual Individual Apply Adjustments Apply Adjustments Yes Yes No No No Yes Yes
Bus Input Data
ID Type
Bus InitialVoltage
%Mag. Ang. Sub-sys Base kV Nom. kV 33.000 33.000 SWNG Bus20 1 100.00 0.00 6.600 6.600 Load Bus22 1 100.00 -30.00 33.000 33.000 SWNG Bus24 2 100.00 0.00 6.600 6.600 Load Bus25 2 100.00 30.00 0.433 0.433 Load Bus26 1 100.00 0.00 0.433 0.433 Load Bus27 2 100.00 60.00 0.433 0.433 Load Bus28 1 100.00 0.00 0.433 0.433 Load Bus29 2 100.00 60.00 0.433 0.433 Load Bus30 2 100.00 60.00 0.433 0.433 Load Bus31 1 100.00 0.00 0.433 0.433 Load Bus32 2 100.00 60.00 0.433 0.433 Load Bus33 2 100.00 60.00 0.433 0.433 Load Bus34 2 100.00 60.00 0.433 0.433 Load Bus35 2 100.00 60.00 0.433 0.433 Load Bus36 1 100.00 0.00 0.433 0.433 Load Bus37 2 100.00 60.00 16 Buses Total All voltages reported by ETAP are in % of bus Nominal kV. Base kV values of buses are calculated and used internally by ETAP.
2-Winding Transformer Input Data
Phase Shift
ID MVA Prim.kV Sec.kV %Z X/R Prim. Sec.
Transformer %TapSetting
% Tol. Rating ZVariation +5% -5% % Z Type Angle Adjusted T10 20.000 33.000 6.600 10.00 20.00 0 0 0 0 0 10.0000 Dyn 30.000 T14 20.000 33.000 6.600 10.00 20.00 0 0 0 0 0 10.0000 Dyn -30.000 TR#1 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#2 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#3 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#4 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#5 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#6 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#7 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000 TR#8 2.000 6.600 0.433 6.25 6.00 0 0 0 0 0 6.2500 Dyn -30.000
2-Winding Transformer Grounding Input Data
ID MVA Prim. kV Sec. kV
Transformer Type Rating Primary Grounding Conn. Type Secondary Amp Ohm kV kV Amp Ohm Type T10 20.000 33.000 6.600 D/Y Solid D/Y 6.600 33.000 20.000 T14 Solid D/Y 0.433 6.600 2.000 TR#1 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#2 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#3 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#4 Resistor 75.00000 D/Y 0.433 6.600 2.000 TR#5 Resistor 3.3 75.00000 D/Y 0.433 6.600 2.000 TR#6 Resistor 75.00000 D/Y 0.433 6.600 2.000 TR#7 Resistor 75.00000 D/Y 0.433 6.600 2.000 TR#8 Resistor 3.3 75.00000
Branch Connections
ID Type FromBus ToBus R X Z
CKT/Branch Connected Bus ID %Impedance,Pos.Seq.,100MVAb
Y T10 2W XFMR Bus20 Bus22 2.46 49.23 49.30 T14 2W XFMR Bus24 Bus25 2.46 49.23 49.30 TR#1 2W XFMR Bus22 Bus26 49.42 296.51 300.60 TR#2 2W XFMR Bus25 Bus30 49.42 296.51 300.60 TR#3 2W XFMR Bus22 Bus28 49.42 296.51 300.60 TR#4 2W XFMR Bus22 Bus31 49.42 296.51 300.60 TR#5 2W XFMR Bus25 Bus32 49.42 296.51 300.60 TR#6 2W XFMR Bus25 Bus34 49.42 296.51 300.60 TR#7 2W XFMR Bus22 Bus36 49.42 296.51 300.60 TR#8 2W XFMR Bus25 Bus37 49.42 296.51 300.60
CB66 Tie Breakr Bus30 Bus27
CB69 Tie Breakr Bus30 Bus29
CB71 Tie Breakr Bus32 Bus33
Power Grid Input Data
kV R X" Rating R/X" 100 MVA Base % Impedance MVASC ID IDPowerGrid ConnectedBus Grounding
Type 0.07
U3 Bus20 1000.000 33.000 0.71247 9.97459 Wye - Solid
0.07
U4 Bus24 1000.000 33.000 0.71247 9.97459 Wye - Solid
Induction Machine Input Data
ID
ID Type kVA kV Amp PF %R %X"
InductionMachine Rating
Qty Connected Bus R/X" MW/PP mFact. HP/kW Grounding
Conn. Type Amp
PosSeqImp (Mtr Base)
75.90
Bus22 6.600 92.37 2.16 13.72 0.16 0.38
loatairblower-1 Motor 1 750.00 867.66 Wye Open
284.61
Bus22 6.600 92.92 1.49 13.81 0.11 1.43
allmill Motor 1 2850.00 3253.59 Wye Open
38.21
Bus22 6.600 92.09 2.62 13.64 0.19 0.19
egrindmill Motor 1 375.00 436.83 Wye Open
75.90
Bus25 6.600 92.37 2.16 13.72 0.16 0.38
Floatairblower-2 Motor 1 750.00 867.66 Wye Open
20.51
Bus25 6.600 91.83 3.12 13.53 0.23 0.10
Secondaryconecrusher Motor 1 200.00 234.44 Wye Open
Total Connected Induction Machines ( = 5 ): 5660.2 kVA
Lumped Load Input Data
ID kVA kV R X" R/X"
Lumped Load Rating MachineBase
kW kvar Loading MTR STAT % Load Lumped Load Motor Loads Amp % PF % Impedance MW/PP mFact.
Conn. Type Amp
Grounding Lump1 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump2 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump3 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump4 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump5 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump6 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump7 500.0 0.433 666.69 85.00 70 30 297.50 184.37 6.46 15.37 0.42 Delta 0.30 Lump8 1500.0 0.433 2000.06 85.00 70 30 892.50 553.12 6.46 15.37 0.42 Delta 0.89 Lump9 900.0 0.433 1200.04 85.00 70 30 535.50 331.87 6.46 15.37 0.42 Delta 0.54 Lump10 900.0 0.433 1200.04 85.00 70 30 535.50 331.87 6.46 15.37 0.42 Delta 0.54
SHORT- CIRCUIT REPORT
Fault at bus:
Looking into "From Bus"
ID From Bus Symm.rms
ID Va
From Bus To Bus % V kA % Voltage at From Bus
Contribution 3-Phase Fault
Vb Vc Ia 3I0 R1 X1 R0 X0
kA Symm. rms % Impedance on 100 MVA base
Line-To-Ground Fault
Positive & Zero Sequence Impedances Nominal kV Voltage c Factor Bus22 = 1.10 (Maximum If) = 6.600
Bus22 Total 0.00 20.897 0.00 102.58 100.30 20.302 20.302 4.22E+000 4.59E+001 2.46E+000 4.92E+001
Bus20 Bus22 81.76 15.959 91.41 100.11 91.07 17.194 20.302* 3.25E+000 6.02E+001 2.46E+000 4.92E+001
Bus26 Bus22 15.98 0.512 65.47 100.49 61.67 0.334 0.000 6.64E+002 1.76E+003
Bus28 Bus22 15.98 0.512 65.47 100.49 61.67 0.334 0.000 6.64E+002 1.76E+003
Bus31 Bus22 15.98 0.512 65.47 100.49 61.67 0.334 0.000 6.64E+002 1.76E+003
Bus36 Bus22 10.23 0.327 63.20 100.52 60.12 0.214 0.000 1.07E+003 2.74E+003
float air blower -1 Bus22 100.00 0.601 100.00 100.00 100.00 0.372 0.000 2.49E+002 1.58E+003
ball mill Bus22 100.00 2.254 100.00 100.00 100.00 1.398 0.000 4.59E+001 4.24E+002
regrind mill Bus22 100.00 0.303 100.00 100.00 100.00 0.172 0.000 6.00E+002 3.12E+003
Initial Symmetrical Current (kA, rms)
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer :
3-Phase L-G L-L L-L-G
20.897 Peak Current (kA), Method C
Breaking Current (kA, rms, symm) Steady State Current (kA, rms)
: : : 52.917 15.959 20.302 51.412 20.302 20.302 17.937 45.421 17.937 17.937 20.831 52.751 20.831 20.831
Short-Circuit Summary Report
3-Phase, LG, LL, LLG Fault Currents
ID kV
Bus
I"k ip Ik I"k ip Ib I"k ip Ib Ik I"k Ib
3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground
Ik ip Ik
Bus22 6.600 20.897 52.917 15.959 20.302 51.412 20.302 20.302 17.937 45.421 17.937 17.937 20.831 52.751 20.831 20.831
All fault currents are in rms kA. Current ip is calculated using Method C. * LLG fault current is the larger of the two faulted line currents.
Sequence Impedance Summary Report
ID kV
Bus
Resistance Reactance Impedance
P os it iv e S eq. I mp . (o hm) Ne ga ti ve S eq . I mp . (o hm)
Resistance Reactance Impedance
Zero Seq. Imp. (ohm)
Resistance Reactance Impedance
Fault Zf (ohm)
Resistance Reactance Impedance