FOR REFERENCE ONLY
139 KM 0.02897 Ohms 0.30720 Ohms 0.30856 Ohms 0.25697 Ohms 1.02230 Ohms 1.05410 Ohms 4.02683 Ohm 42.70080 Ohm 42.89025 Ohm 84.58 Degree 35.71883 Ohm 142.0997 Ohm 146.5202 Ohm 75.86 DegreeZero Sequence Impedence for Protected line Zero Sequence Impedence Angle
Positive sequence impedance per KM Zero Sequence Resistance per KM Zero Sequence Reactance per KM Zero Sequence Impedance per KM
Positive Sequence Impedence for Protected line Positive sequence Impedence angle
Positive Sequence Resistance for Protected line Positive Sequence Reactance for Protected line
Zero Sequence Resistance for Protected line Zero Sequence Reactance for Protected line
DETAILS OF ADJACENT LINE : (NAKODAR - MAKHU)
400kV Rajpura TPPS - Nakodar Line (Main 1)
RELAY TYPE : MiCOM P444DETAILS OF PROTECTED LINE : (RAJPURA TPPS - NAKODAR) Length of protected line
Positive Sequence Resistance per KM Positive Sequence Reactance per KM
53 KM 0.02897 Ohm 0.30720 Ohm 0.30856 Ohm 1.53541 Ohm 16.28160 Ohm 16.35384 Ohm 84.58 Degree 12.5% 315
MVA
2 400KV
63.49Ohm
31.75Ohm
2000 Amp 1 Amp 400 Kilo Volt CT & PT Details CT Primary CT Secondary PT PrimaryNO. OF ICT Circuits Voltage rating
Impedance when 2 ICT's are connected in the circuit((KV)^2)/(2*MVA ) x Percentage impedance
Pos.Seq. Resistance of Adj. Line per KM Pos.Seq. Reactance of Adj. Line per KM
Impedance when one ICT is connected in the circuit((KV)^2)/(1*MVA ) x Percentage impedance
ICT DETAILS ICT impedance ICT rating
Positive Sequence Impedence for adj.line Positive sequence Impedence angle Length of the adjacent line
Pos.Seq. Impedence of Adj. Line per KM Positive Sequence Resistance for adj.line Positive Sequence Reactance for adj.line
FOR REFERENCE ONLY
110 Volt 0.55 0.811 -12.292 Degree 0.811 -12.292 Degree 80% of protected line25% of parallel ICT Impedance 100% of parallel ICT Impedance
10% of zone 1 impedence VALUES
18.872 Ohm
VALUES Grounding Factor kg = (Z0/Z1)/(3*Z1)
ZONE SETTING CALCULATIONS ZONE 1
80% of Protected line (recommended) ZONE 2
DIST Z4 PT Secondary CT/PT Ratio GROUND FACTOR
DIST Z3 (100 of Protected line + KZ1,KZ2,KZ3…..PS1
Angle Kg
ZONE SETTINGS DIST Z1
DIST Z2 (100 of Protected line +
Magnitude of grounding factor Kg =(SQRT((X0-XL)*(X0-XL))+((R0-RL)*(R0-RL)))/ (3*(SQRT(RL*RL)+(XL*XL)))
Angle of Grounding factor Kg = (arc Tan((X0-XL/(R0-RL)))-(arc Tan(XL/RL))*180*7/22 28.087 Ohm 27.955 Ohm VALUES 32.584 Ohm 32.320 Ohm 1.887 Ohm 2000 Amp 76.982 Ohm 42.340 Ohm 25.404 Ohm 25.404 Ohm 25.404 Ohm 33.872 Ohm 33.872 Ohm 33.872 Ohm DIST R1,PG(Quad) (80% of RL) DIST R3 & R4,PG(Quad) (80% of RL) OPERATING TIME DELAY
DIST R2,PG(Quad) (80% of RL) Load Resistance (RL) in Secondary DIST R1,PP(Quad) (60% of RL) DIST R2,PP(Quad) (60% of RL) DIST R3 & R4,PP(Quad) (60% of RL)
100% of protected line + 50% of Transformer
On comparing the above values, the recommended value is the smallest of all values
10% of Zone 1 Impedence RESISTIVE REACH SETTING:
100% of protected line + 50% of Adjacent line
Primary full load current, CTR considered as Full load
Resistance at this current=(0.8*(PT Primary * 10^3) / (1.732) / (1.2*Primary full load current)
ZONE 3
100% of protected line + 100 % of longest line
ZONE 4
100% of protected line + 25% of Transformer
FOR REFERENCE ONLY
0.00 Sec 0.30 Sec 0.75 SEC 1.00 SEC 20 % of R3 5.081 Ohm 20 % of R3 5.081 OhmPOWER SWING SETTING: ΔR & ΔX
ΔR = 10 to 30% of Z3 R3,PP ΔR = 10 to 30% of Z3 R3, PP
UNBLOCKING CURRENT THRESHOLDS:
Unblocking stages using to trip if any fault when relay blocked on PSB ΔX = 10 to 30% of Z3 R3, PP
ΔX = 10 to 30% of Z3 R3, PP
The three unblocking current thresholds namely, IN>, I2> and Imax should be set above the maximum expected residual current unbalance, the maximum negative sequence unbalance and the maximum expected power swing current.
Value of Imax line = 3 Inom
NOTE: PSB Block – Zone 2, Zone 3 & Zone 4 IN> 40%
I2> 30 %
ZONE 3 OPERATING TIME(t3) ZONE 4 OPERATING TIME(t4) ZONE 1 OPERATING TIME(t1) ZONE 2 OPERATING TIME(t2)
I>1 Current setting 3A
EARTHFAULT OVERCURRENT PROTECTION
IN>1 Function IDMT
tI>1 Time delay 1.2 sec
BACK UP OVER CURRENT:
Enable Yes
I>3 Current Set 3.00A
I>3 Time delay 3sec
Disabled
Trip mode 1 pole Z1 , CR Received
SWITCH ON TO FAULT
Switch on to fault logic is pre-set in MiCOM P444
Operation on pick up of level detector method and activation of all zones is recommended.This time delay is not having role in SOTF/TOR logic. Since not possible to block time delay, keep a higher setting as 3 Sec.
Unblocking timer:
To be set to 2s typically to un block in case of a prolonged power swing. DISTANCE SCHEMES SETTING
Program Mode Standard Scheme
I>4 Status Disabled
Standard Mode PUR Permissive under reach scheme
Z1Ext Fail
FOR REFERENCE ONLY
V>1 Voltage Set 121 V (110%)
Delta I> 100 mA
OVER VOLTAGE PROTECTION:
V> Measurement Mode Ph-Ph
VTS I2> & I0> Inhibit 50 mA
Detect 3P Enabled
Threshold 3P U< 10 Volts
V>1 Function DT
Disabled BROKEN CONDUCTOR PROTECTION
I2/I1 ratio 0.20.
VT SUPERVISION
Time Set 60 Sec.
VTS Time Delay 5.000 s (alarm indication time )
IN>1 VTS Block Non Directional
IN>1 Current set 0.2 A
IN>1 Time Delay 1.2 sec
IN>1 Time VTS IN>2 status
1.2 sec
IN>1 Directional Directional Forward
V< Operation Any Phase
V<1 Pole Dead Inh Enabled
V<1 Voltage Set (80% of Nominal Voltage) 88 V (80%)
V<1 Function DT
V<1 Time Delay 2 sec
V>2 Time Delay 1 sec
V>2 Status Enabled
V>2 Voltage Set 154 V (140%)
V>1 Time Delay 2 sec
UNDER VOLTAGE PROTECTION:
V< Mode Phase-Phase
V<2 Status Enabled
V<2 Voltage Set (70% of Nominal Voltage) 77 V (80%) Stub Bus Protection (50STB)
Relay Type P444
V<2 Time Delay 0.5 sec
Pickup for Stub Bus in secondary 4.0 A
CT Secondary in Amps 1
Settings:
Stub Bus Enabled
FOR REFERENCE ONLY
df/dt>1 StatusF>2 Time delay in sec Under Frequency Protection
Over Frequency Protection
DF/DT Protection df/dt>1 Setting in Hz Enabled 0.250 1.5 F>2 Status Enabled F>2 Setting in Hz Enabled F<2 Setting in Hz 48 F>1 Status Enabled F>1 Setting in Hz 51.0 0.5 F>1 Time delay in sec
F<1 Status Enabled
F<1 Setting in Hz 48.5
50.5
F<1 Time delay in sec 2
F<2 Time delay in sec 0.5
F<2 Status
Frequency Protection:
Relay type used P141
df/dt>1 Time in sec df/dt>2 Status df/dt>2 Setting in Hz df/dt>2 Dir'n 0.200 Both Enabled 0.300 Both df/dt>1 Dir'n
Note: These settings of Frequency & DF/DT Protection are recommended based on general practice. These settings shall be adjusted if required as per the site conditions.
These settings are applicable only if the protections are enabled in P442.