• No results found

300 Process Control

N/A
N/A
Protected

Academic year: 2021

Share "300 Process Control"

Copied!
23
0
0

Loading.... (view fulltext now)

Full text

(1)

Abstract

Abstract

This section is an introductory reference to process control. It discusses control This section is an introductory reference to process control. It discusses control theory, control modes and problems and includes guidelines for typical process theory, control modes and problems and includes guidelines for typical process control situations. This section also discusses controller tuning and control mode control situations. This section also discusses controller tuning and control mode selection. selection. C Coonntteennttss PPaaggee 3 3110 0 IInnttrroodduuccttiioon n 330000--22 3 3220 0 CCoonnttrrool l LLoooopps s 330000--22 3 32121 OOpepen Ln Loooop Cp Cononttroroll 32 3222 ClClososed ed LoLoop op CoContntroroll 3 3330 0 CCoonnttrrool l MMooddees s 330000--55 33 3311 PrPropoporortitiononal Cal Conontrtrolol 3 33232 IIntnteeggraral Col Contntrrooll 333

333 PrPropooportrtionionalal-Pl-Plus-us-InIntetegrgral Coal Contrntrolol

33 3344 DeDeririvvatatiivve Coe Contntroroll 3 3440 0 AAddvvaanncceed d CCoonnttrrool l 330000--1144 3 34141 CCaascscaadde Ce Conontrtrolol 34 3422 FeFeeded-f-fororwaward Cord Contntroroll 3 3550 0 CCoonnttrroolllleer r TTuunniinng g 330000--1188 35 3511 QuQuaartrter er DeDecacay My Metethohodd 35 3522 UlUltitimamate Ste Senensisititivivity Mety Meththodod 353

353 PrProceocess ss ReReacactiotion n CurCurve ve MeMethothodd

3

(2)

331100 IIn

nttrro

od

du

uc

cttiio

on

n

Process control is fundamental to most industrial processes. Although control Process control is fundamental to most industrial processes. Although control tech-nology has evolved greatly in arriving at today’s microprocessor and digital nology has evolved greatly in arriving at today’s microprocessor and digital imple-mentations, all control methods rely on the same basic structure, called a “control mentations, all control methods rely on the same basic structure, called a “control loop.” Control loops have six basic constituents, as follows:

loop.” Control loops have six basic constituents, as follows: •• Controlled Controlled variablevariable. The condition that is being controlled. The condition that is being controlled

••   Setpoint  Setpoint. The value at which a controlled variable must be maintained. The value at which a controlled variable must be maintained

•• Manipulated Manipulated variable.variable. A condition (variable) that can be changed to cause the A condition (variable) that can be changed to cause the controlled variable to change

controlled variable to change

••   Controller  Controller. A device that keeps the controlled variable at the setpoint. A device that keeps the controlled variable at the setpoint

•• Final Final control control elementelement. The device adjusted by the controller(s) to change the. The device adjusted by the controller(s) to change the manipulated variable

manipulated variable

••   Disturbances  Disturbances. Process conditions that tend to change the value of the. Process conditions that tend to change the value of the controlled variable

controlled variable

332200 C

Co

on

nttrro

ol L

l Lo

oo

op

pss

Control loops can be either

Control loops can be either manualmanual oror automatic automatic. A manual control loop requires a. A manual control loop requires a human being to observe the value of the controlled variable. If this variable is not at human being to observe the value of the controlled variable. If this variable is not at the setpoint, the human observer adjusts a

the setpoint, the human observer adjusts a manipulated variablemanipulated variable (see (see Figu

Figurere300-300-11).).

An automatic control loop employs a controller to keep the controlled variable at An automatic control loop employs a controller to keep the controlled variable at the setpoint. In

the setpoint. In FiguFigurere300-300-22, the controller receives a signal from a transmitter (the, the controller receives a signal from a transmitter (the circled X) representing the condition of the controlled variable, and sends an output circled X) representing the condition of the controlled variable, and sends an output signal to a valve regulating the manipulated variable.

signal to a valve regulating the manipulated variable.

In a refinery furnace, a controller monitors the outlet temperature (controlled In a refinery furnace, a controller monitors the outlet temperature (controlled

vari-Fig. 300-1

(3)

changes the fuel flow (manipulated variable) by changing the position of the fuel valve (final control element). Automatic control may be open loop (feed forward) or closed loop (feedback).

321 Open Loop Control

In open loop control, the controller adjusts the final control element without

measuring the process. An example of open loop control is a cycle timer that oper-ates a drain valve, as in the simple gas-liquid separation process shown in

Figure 300-3. At predetermined intervals, the timer causes the drain valve to open even if there is nothing to drain.

A more common example of open loop control would be an automatic lawn sprin-kler system. Here a clock timer opens a water valve for several minutes each day. It would not check to see if the lawn needed water and would even turn on the sprin-klers in the rain. Open loop control like these examples is not widely used. Open loop control operating in a feed forward mode is frequently used along with closed loop control. Feed forward control is discussed in Section 342.

322 Closed Loop Control

Closed loop control, also known as feedback control, is the most widely used type of automatic control. If feedback control were used in Figure 300-3, the controller would open the drain valve only when the liquid level rose above the controller setpoint and would continue to adjust the valve as needed to keep the liquid drained from the vessel.

The gas separation process in Figure 300-4 has a feedback (closed loop) level control system in which the controller LC receives a signal from the level trans-mitter LT. The controller compares this measurement with the setpoint and adjusts the outlet valve as necessary. The difference between the controller measurement and controller setpoint is the error signal. When the error is not zero, the level controller opens or closes the outlet valve to return the level to the setpoint.

(4)

On/Off Control

On/off control is the simplest mode of automatic control. It has only two outputs— on (100%) or off  (0%)—and only responds to the sign of the error—positive or negative; i.e., whether it is above or below the setpoint.

Because of an effect known as constant cycling, on/off control is not generally suit-able for continuous automatic feedback control. If the control valve in Figure 300-4 were to remain completely open when the level is above setpoint, and completely closed when the level drops below setpoint, a constant cycling of valve position and level would result (see Figure 300-5). As with open loop control, the varying level resulting from constant cycling may be acceptable in some noncritical level applica-tions.

Differential Gap Control

Differential gap control is a refinement of on/off control. Instead of changing output from on (100%) to off  (0%) at a single setpoint, differential gap action changes output at high and low limits called boundaries. As long as the

measure-Fig. 300-4 Closed Loop Control

(5)

extends the period and limits the amplitude of the controlled variable oscillations (see Figure 300-6). On many controllers the size and position of the differential gap is adjustable, permitting fine-tuning.

Differential gap control is suitable for some continuous automatic feedback control loops. It slows the rapid cycling of on/off control, reducing wear on the final

control element while maintaining much of the simplicity of on/off control. A typical application of differential gap control is the operation of a dump valve or pump to keep a vessel level within an acceptable range.

330 Control Modes

Controllers can be adjusted to function correctly in many different applications. Each controller usually has three adjustment modes:

•   Proportional. Controller output changes by an amount related to the size of the error

•   Integral. Controller output changes by an amount related to the size and dura-tion of the error

•   Derivative. Controller output changes by an amount related to the rate of measurement change

With pneumatic controllers and early electronic controllers, each mode added to a controller made it more expensive. Most electronic controllers available today are equipped with all three modes at no additional cost. The unneeded modes can be turned off.

Most control applications use proportional-plus-integral control. Proportional-plus-integral-plus-derivative is sometimes used for temperature control with delays (deadtime) of several minutes. Proportional-only control is sometimes used in noncritical services such as draining vessels.

(6)

Note that the proportional and integral actions depend on the error (defined as setpoint measurement), but the derivative action only depends on the measurement. Controllers are constructed this way so there will be no large change in controller output when the operator enters a new setpoint for the controller.

331 Proportional Control

(Controller output can go directly to a valve or to the setpoint of another controller. In the following discussions, it is assumed that controllers send their output directly to a valve.)

Figure 300-7 shows the relationship between valve position and error that is charac-teristic of proportional control: The valve position changes in exact proportion to the amount of error, not to its rate or duration. The response is almost instanta-neous, and the valve returns to its initial value when the error returns to zero.

Control Algorithm

The linear relationship between the setpoint deviation (error) and the valve position (controller output) for proportional action can be expressed as follows:

O = KcE

(Eq. 300-1) where:

O = Controller output

Kc = Controller Gain =

Output /

Error E = Error = (Setpoint - Measurement)

This equation is called the control algorithm. The gain, Kc, is also called the controller sensitivity. It represents the proportionality constant between the control valve position and controller error.

(7)

Proportional Band

Another way of characterizing a proportional controller is to describe its propor-tional band. The proporpropor-tional band is the percent change in value of the controlled variable necessary to cause full travel of the final control element. The proportional band, PB, is related to its gain as follows:

Kc= 100/PB

(Eq. 300-2) Both proportional band and gain are expressions of proportionality. Manufacturers may call their adjustments gain, sensitivity, or proportional band. Figure 300-8 shows the relationship between valve opening and proportional bands of different percentages. High percentage proportional bands (wide bands) have a less sensitive response than low percentage proportional bands (narrow bands).

Bias

Bias is the amount of output from a proportional controller when the error is zero. Equation 300-1 implies that when the error is zero, controller output is zero. The valve is either fully open or fully closed and provides no throttling action. Adding a bias provides this throttling action. Equation 300-1 then becomes:

O = KcE + B

(Eq. 300-3) where:

B = Bias (percent of full output)

Typically, manufacturers set the bias at 50%. To prevent a process bump, the oper-ator is sometimes allowed to adjust the bias before putting the controller in auto-matic. Figure 300-9 shows controller output versus error at different proportional bands with a 50% bias. At zero error, the controller output is 50% of full range for any proportional band.

(8)

Offset

A controller’s error is the difference between its setpoint and measurement. In a proportional-only controller, a change in setpoint or load introduces a permanent error called offset (see Figure 300-10). It is impossible for a proportional-only controller to return the measurement exactly to its setpoint, because proportional output only changes in response to a change in the error, not to the error’s duration.

Assume that a proportional-only controller controls the outlet temperature of a furnace and that the temperature is at the setpoint. If the feed rate to the furnace increases, more fuel will be needed. This disturbance represents a load change to the furnace. To get more fuel, the fuel valve must be opened more. As is suggested by Equation 300-3, the only way that the valve can be at some value other than its starting point is for an error to exist. Thus, the proportional controller alone cannot return the outlet temperature to its setpoint. As mentioned, some controllers allow the operator to adjust the bias until the value of E (the error, or offset) is zero. Offset is determined by the proportional band value for the controller and the change in valve position that occurs when a disturbance takes place:

E = PB (

O) / 100

(Eq. 300-4) where:

E = Change in error PB = Proportional band

O = Change in valve position

The proportional-only controller is the easiest continuous controller to tune. It provides rapid response and is relatively stable. If offset can be tolerated (loose control), proportional-only control can be used.

Fig. 300-9 Effects of Proportional Band with 50% Bias Fig. 300-10 Proportional Control Response to a Load Change

(9)

332 Integral Control

Integral (reset) action is the result of an integration of controller error with time. With integral action, controller output is proportional to both the size and duration of the error. As long as a deviation from setpoint exists, the controller continues to drive its output in the direction that reduces the deviation. The rate of change of controller output is proportional to the magnitude of the error. Figure 300-11 illus-trates the open loop response of integral action.

Integral action is normally used in conjunction with proportional action; it is rarely used by itself. Integral action is quantified as the time (the reset time) required to change controller output by an amount equal to the change caused by proportional action. In other words, it is the time required to repeat the contribution of the proportional action.

On some controllers, integral settings are in repeats, meaning repeats per minute; on others, settings are in minutes, meaning minutes per repeat. One setting is the reciprocal of the other; decreasing the integral time increases the amount of integral action.

(10)

333 Proportional-Plus-Integral Control

Proportional-plus-integral control is the recommended control action for most appli-cations. Often called PI control, it combines proportional action and integral action in one controller. The resulting control action has the fast response and stability of proportional action, but no offset. In eliminating offset, integral action serves as an automatic bias adjustment.

The output from a proportional-plus-integral controller may be expressed as follows: (Eq. 300-5) where: O = controller output Kc = controller gain E = error

TR = reset time, minutes per repeat

Σ

= summation from time 0 to time n

T = interval between summations

Figure 300-12 shows the open loop response of proportional-plus-integral control. Proportional control immediately acts to reverse the error. Integral action then continues to change controller output until the error equals zero.

m Kc E 1 TR --- E

T o n

+

 

 

 

 

=

(11)

Figure 300-13 depicts proportional-plus-integral control for a closed loop. In

response to a step change in load (top graph), the controlled variable (middle graph) falls below the setpoint. The integral action adjusts the bias from 50% initially to about 75% after the load change and shifts the position of proportional band (shaded area) on the scale. Notice that the percentage value of the proportional band is not changed. The lower graph shows the output of the controller.

 Wind-up

A basic problem with integral controllers is that integral action continues as long as an error exists. Assume a proportional-plus-integral controller is used to maintain the level in the gas-liquid separator vessel in Figure 300-4. If a valve is closed upstream of the vessel, the level drops below the setpoint. The controller then closes the control valve in the outlet line to maintain the level setpoint. With no inlet flow, the control valve closes completely and the vessel level is still less than the setpoint.

A pneumatic control valve will typically be fully closed at a controller output of 15 psig. Since the measured vessel level is less than the setpoint, the integral action of the controller continues to increase the controller output to the air supply pressure (typically 20-30 psig). The action of the integral controller trying to exceed the normal range of the controller output is called wind-up.

If the upstream valve is opened and flow is restored, the vessel level will rise above the setpoint. The response of the controller to this high level will be delayed by the wind-up. When the controller does respond, the output goes to the opposite limit. In this case, the control valve will fully open and the vessel level will drop sharply. The controller may oscillate through several cycles, stroking the control valve from stop to stop on each cycle, before the oscillations cease and control is restored.

(12)

Such oscillations overwork the control valve and, depending on the fluid and pres-sures involved, can cause mechanical damage and seriously disrupt the process downstream on the valve. An anti-wind-up feature may be included on controllers that are frequently subject to this type of disturbance. This limits the controller output range and thus prevents wind-up. When the process returns to normal, the controller lag is eliminated and the oscillations are no worse than those in a propor-tional controller.

Integral Time

Integral time should be proportional to the time it takes for the process to respond to control action. When the process responds quickly, the integral time can be shorter. If the integral time is too short, the control valve reaches its limit before the measurement has time to respond. When the measurement does respond, it will overshoot the setpoint, causing the integral to drive the valve to its opposite limit. The time lag built into the gradual response of integral action lengthens the period of oscillation of a loop. For a loop with proportional-plus-integral control, the period of oscillation after a load change is longer than for proportional alone. For loops where the exact value of the controlled variable is not critical, the shorter period of the proportional-only controller can be an advantage. For example, a vessel may operate within a wide range of liquid level without adversely affecting pressure or gas quality. Therefore, the system level does not have to be accurately controlled, and proportional control is often sufficient.

334 Derivative Control

With derivative action (also called rate action), the controller output is proportional to the rate of change of the error. This means the faster the change in level, the faster the change in controller output and control valve settings. By the same token, if the level remains constant, even with a large error, the controller output would be zero. This makes the use of derivative action by itself impractical.

Derivative action is normally combined with proportional action or proportional-plus-integral action. Derivative action, being proportional to the rate of change of the measured variable, introduces a “lead” (anticipation) element into the controller. This increases the speed of response of the controller and compensates for the lags introduced by proportional and integral actions. Figure 300-14 illustrates derivative action.

The output from a proportional-plus-derivative controller may be expressed as follows: (Eq. 300-6) where: O Kc En TD Mn–Mn1 S

---

 

 

+ =

(13)

Kc = controller gain En = error at time n

TD = derivative time, minutes Mn = measurement at time n

Mn-1 = measurement at previous sampling time S = Time between measurements (sampling time)

The derivative action is greatest when integral and proportional action are just beginning to respond. Derivative action also responds to the change in sign of the measured variable. This opposes the tendency of integral and proportional action to overshoot the setpoint and enables the controlled variable to settle out faster than with either proportional or proportional-plus-integral action.

In Figure 300-14, area A represents the proportional component of controller output. Note that the proportional response is a function of the difference between the setpoint and the measured variable. Areas B and C represent the component added or subtracted by derivative action. As the measured variable stops decreasing and starts increasing, the sign of the derivative function changes. The integral action (area D) eliminates offset by not returning to zero when the proportional and derivative actions return to zero output. Areas E and F represent the corrections that result from all three actions taken together.

(14)

Derivative action, being sensitive to the rate of change of the measured variable, cannot be used in processes that require fast response, or that have rapid fluctua-tions or high noise levels. These condifluctua-tions cause instability through large increases in the derivative gain, and rapidly change direction (sign). Although derivative action is difficult to tune because of its extreme sensitivity to measurement noise and other high frequency disturbances, it does have some applications. Most impor-tantly, it is used with proportional and integral action in temperature processes that have large time lags.

Derivative action can be very helpful in controlling processes that have significant deadtime, but using it can be difficult. Sometimes adding derivative action can make the control loop appear slow and inactive with some types of process distur-bances. This sluggishness might lead one to increase the amount of derivative and perhaps also increase the controller gain. However, these new tunings might make the controller unstable when a different disturbance occurs in the plant.

340 Advanced Control

Because this section of the Instrumentation and Control Manual is meant to be introductory in nature, we will define the term “advanced control” to be anything more sophisticated than simple, single-loop feedback control. Advanced control would therefore include cascade control, feed forward control, signal selector control, adaptive gain control, self-tuning controllers, multivariable control, matrix control, and many other techniques too numerous to mention.

We will only deal here with cascade. The reader is encouraged to consult the refer-ences listed in Section 360 for additional information. The Monitoring and Control Systems Division in the Engineering Technology Department is also available for consultation.

341 Cascade Control

Cascade control should also be considered when the primary control variable is slow to react to disturbances. Like any feedback control loop, a cascade control loop has a controlled variable, a setpoint and a controller. However, instead of having a valve as its final control element, a cascade controller sends its output to the setpoint of another controller, adjusting this setpoint to correct an error in the controlled variable. This other controller is called the secondary or slave

controller. The cascade controller is called the primary or master controller.

If disturbances in the process can be recognized and quickly corrected, the primary control loop will not be affected. This suggests that the secondary control loop must operate faster than the primary loop. In fact, general guidelines suggest that the secondary loop should respond at least five times faster than the primary loop. Looking again at the example of the furnace, let us assume that the fuel system provides fuel to several other furnaces as well. Over the course of hours, the pres-sure in the system might well vary as the fuel demand in all of the furnaces

(15)

Because heat transfer is a slow process, the outlet temperature controller cannot be tuned well enough to eliminate the effect of changing fuel flow (see Figure 300-15). (For details on controller tuning, see Section 350.)

On the other hand, if the fuel flow remains steady while the pressure is changing, the furnace temperature will be more constant. Fuel flow changes almost immedi-ately when the control valve is moved. Therefore, the flow controller can be tuned to eliminate most of the disturbances in fuel flow.

Such circumstances lend themselves to the use of cascade control: a fast process (fuel flow), a slow process (furnace heat transfer), and a disturbance (fuel pressure) that affects the fast loop. Figure 300-16 shows the cascade control system for the furnace.

Fig. 300-15 Feedback Control Performance

(16)

Compare Figure 300-17 to 300-15. With cascade control the outlet temperature is much more steady. The fuel gas controller (secondary controller) has eliminated almost all fuel pressure disturbance from the furnace.

342 Feed-forward Control

Feed-forward control measures a disturbance before it can affect the controlled vari-able, and changes the manipulated variable to compensate for the disturbance. Of course, for feed-forward control to work properly, the magnitude and timing of the effect on the controlled variable must be known. The process might be worse off if the manipulated variable is changed too much or too quickly.

In Figure 300-18, a gas-fired furnace process is equipped with a temperature controller (TC), a feed-forward controller (FFC), and a summer, which adds the two controller outputs together. The feed-forward controller, also called a flow frac-tion controller, operates like a simple multiplier: The output of the FFC consists of its input (from the flow transmitter FT) multiplied by a ratio entered by the operator.

Fig. 300-17 Cascade Control Performance

(17)

Figure 300-19 shows what might happen in a real furnace as the feed rate is

changed. In the top graph, the feed rate to the furnace is raised at time 1. By time 2, the furnace outlet temperature begins to drop below setpoint. The fuel valve then begins to open and raises the outlet temperature back to the setpoint by time 3. In the bottom graph, the fuel valve has begun to open by time B, and by time C the furnace temperature is back to the original setpoint. With forward and feed-back control, the process has recovered from the feed rate disturbance much faster than with feedback control alone. Note that the temperature’s period of oscillation is the same in both cases. This period is a dynamic characteristic of the furnace and cannot be changed by the control system. However, the feed-forward controller has been able to reduce the size of the temperature disturbance and has speeded up the recovery.

Feed-forward control should not be used by itself, but always with feedback

control, because the rate and magnitude of the reaction of a process to a disturbance is rarely consistent.

(18)

350 Controller Tuning

Several methods are available to tune a controller to function in a specific loop. The following discussion considers some of the methods commonly used. Several of the references in Section 360, particularly Reference 5, should be useful when difficult situations are encountered.

351 Quarter Decay Method

The quarter decay method is a closed loop controller tuning method. This means that the controller remains in automatic while tuning adjustments are made. The quarter decay method defines the ultimate limit for tight controller tuning. Often, the tuning constants it produces are too tight (too sensitive) in processes that have sticky valves and noisy measurements.

To prevent controllers from going unstable unexpectedly, tuning constants should be set to values one-half as sensitive as those obtained with the quarter decay

method. After these less sensitive tunings are exposed to actual upsets and irregular-ities, and the operators gain confidence in the controller tuning, it may be appro-priate to make the tunings more sensitive.

The general tuning sequence is as follows:

1. With the controller in automatic, adjust all tuning constants to their least sensi-tive (least effecsensi-tive) setting. Proportional band should be at its highest value (proportional gain should be at its lowest value). Integral time should be at its highest value (most minutes per repeat or least repeats per minute). Derivative time should be at its highest value.

2. Make a small step change in controller setpoint and record the controller measurement until it settles out.

3. Change the setpoint back to its original value. Record the measurement as before.

4. Increase the proportional gain (reduce the proportional band) in small steps and repeat steps 1-3 until the recording of the output resembles Figure 300-20, curve B; that is, until the amplitude of the first positive excursion of curve B is approximately four times that of the second (thus the name, quarter decay method).

5. Measure the period of oscillation. Set the reset and derivative:

TR = P/1.5 minutes

(Eq. 300-7)

TD = P/6 minutes

(19)

6. With TR and TD set at above values, reestablish controller gain for quarter decay.

Figures 300-21, 300-22, and 300-23 show how the three tuning parameters affect the response of a controller. With proportional-only control, settling time is fairly long and there is a permanent offset from the setpoint. Adding integral control reduces settling time and eliminates offset. Adding derivative control to propor-tional control reduces settling time but not offset. Only integral control eliminates the offset.

Fig. 300-20 Quarter Decay Method Tuning

Fig. 300-21 Proportional-only Controller Response Fig. 300-22 Proportional-Plus-Integral Controller Response

(20)

352 Ultimate Sensitivity Method

The ultimate sensitivity method ( Figure 300-24) is also a closed loop test. Adjust the integral time and/or the derivative time to their minimum values. Then narrow the proportional band (increase gain) in small steps, each time changing the

setpoint as described in Section 351, until the controller measurement just begins to cycle continuously. This proportional band setting is called the ultimate propor-tional band, denoted “PBu.” The period of oscillation at the ultimate proportional band is called the ultimate period, measured in minutes and denoted “Pu.” The amplitude of the oscillations in Figure 300-24 has been exaggerated for clarity. The ultimate proportional band, PBu, and the ultimate period, Pu, are then used to calculate tuning constants as shown in Figure 300-25. These constants give the quarter damping response already discussed.

Note that Figures 300-25 and 300-26 show two sets of equations for a proportional-plus-integral-plus-derivative controller. The set identified as “Commercial” should be used for controllers encountered in industry. The set identified as “Ideal” is based on an ideal control algorithm equation commonly used in universities. They are included here for completeness.

353 Process Reaction Curve Method

This is an open loop tuning method. The controller remains in manual while response tests are made. The tuning method measures two parameters to describe the response characteristic of the process: process deadtime and process time constant.

The deadtime is the delay between a change in valve position and the resulting change in the controlled variable. The process time constant is the time required for

(21)

To perform this test, change the controller valve position by a small amount and record the controlled variable. The deadtime, TD, and time constant, TC, are measured and their values used to calculate the controller tuning constants. Figure 300-26 shows how the measurements are made and used.

Fig. 300-24 Ultimate Sensitivity Method

Fig. 300-25 Ultimate Sensitivity Method Tuning Constants Proportional Band (%) Reset Time (minutes) Derivative Time (minutes) Proportional Controller 0.5 PBu — —

Proportional + Integral Controller 0.45 PBu Pu /1.2 —

Proportional + Integral + Derivative Controller

Ideal

0.6 PBu Pu /2.0 Pu / 8.0

Proportional + Integral + Derivative Controller

Commercial

0.3 PBu Pu /4.0 Pu / 4.0

Notes PBu = Ultimate Proportional Band, % Pu= Ultimate Period, minutes

(22)

Note that the process reaction curve method cannot be used to integrate processes such as level control; when a valve controlling a level is changed the level

continues to change until the vessel overflows or empties. Level controllers can be tuned using the ultimate sensitivity method or more advanced methods discussed in Reference 5.

Figure 300-27 gives typical ranges of controller tuning constants for various

(23)

exact values must be determined by one of the above methods. For future reference, always record the control loop ID number (e.g., FRC-123), the date, and the tuning constant when you have finished tuning a control loop.

360 References

1. Fundamentals of Process Control Theory. Instrument Society of America, 1981.

2. Process Control Systems.McGraw-Hill, 1979.

3. Process Instruments and Controls Handbook . McGraw-Hill, 1974.

4. Controllers & Control Theory. Production Facility Bookware Series, Interna-tional Human Resources Development Corp., 1987.

5. Tuning and Control Loop Performance. Instrument Society of America, 1983.

Fig. 300-27 Tuning Constants for Typical Process LOOP TYPE PROPORTIONAL BAND % RESET TIME (MINUTES) DERIVATIVE TIME (MINUTES) Flow 100-500 0.02-0.1 none

Liquid Pressure 100 - 500 0.02 - 0.1 none

Gas Pressure 1- 50 0.1 - 0.5 none

Level 1-50 0.05-0.25 none

References

Related documents

The 6 most important factors include the insufficient readiness for change, lack of systematic plan for organization change, fast solution expectation, the focus of change

The present study explores whether and to what extent individual differences (i.e., gender and personality traits of perceiver) predict inferences of trustworthiness from

From these identified contrasted performances of VI for monitoring vegetation moisture across ecosystems with varying LAI, main objectives of our study are: (1)

As the segmentation and labeling step assumes only a single human user and segmentation does not incorporate information about movement, a single frame is used in each example..

After partitioning of the stem extract into the various solvents, we found that all the solvents showed the presence of saponins and oxalates; terpenoids and

khinjuk seeds extract for 48 h when compared with negative control group, and non significant differences was detected when the cells treated with aqueous and methanolic extracts

2.0 DEFINITION OF SELLER - The consultant, contractor, supplier, vendor or other provider of goods and/or services, its officers, agents, servants, employees, contractors

Experimental evidence reveals that there is a strong willingness to trust and to act in both positively and negatively reciprocal ways. So far it is rarely analyzed whether