Features
Hardware
Operation
System Setup and Simulator (HANDS ON)
Operation (continued)
Variables
Interconnect
HMI & Simulator (HANDS ON)
InPower
Applications (GROUP)
Control and Component Mode Panels New
What are the capabilities of the MCM3320?
What are the board connections?
How does it operate?
How do I apply it?
Lotus Notes Database “Commercial ESB
Controls”
Sort by “Category”
Look for “MCM3320”
This presentation and other technical
information located there
An Application Guide is in the works to provide
a one-stop document
Documentation
PGA Controls Engineering:
1. Kevin Aufderhar
2. Paul Dahlen
G1
G2
G3
G4
Load1 Load2 Load3 Load4 Load5 Load6
MCM3320 AUX101 AUX102 HMI211 Operator Panel #2 GM UM Customer I/O Breakers or ATS AC Metering Source Failure Gensets Start/Stop Main Breaker Control Sync/Volt Match Open/Closed Transition Load Ramping Extended Paralleling kW and kVAR Control Load Demand Load Add / Shed Scheduler Modbus Diagnostics HMI112 Gensets Bargraph HMI211 Utility Bargraph HMI211 Operator Panel #1
Feature Validation
All available features have been tested
Firmware test
Bench test w/simulator
Live test at Fridley Endurance Pad test facility
Live test at Fridley with real Utility Source
(transfers, sync, base load / peak shave)
AC Metering
3 Phase metering of genset bus and utility bus
simultaneously
Phase and Total/avg metering of V, A, kW, kVAR,
kVA, PF, Hz
Phase and total metering of +kWh, kWh, +kVARh,
-kVARh, kVAh for each source
CT secondaries of 1A or 5A
PT accepts 0-480VLL directly; external PT for higher
voltages (up to 35000V)
Master Sync / Volt Match
both phase synchronization and voltage matching
20 genset limit for synchronizer
frequency offset range: +/- 1.0 Hz min; up to +/- 3.0Hz
output voltage offset range: +/- 6% min; up to +/- 10%
Master Sync / Volt Match
controls frequency and voltage via PCC kW and kVAR
load share lines
selectable phase synchronization (default) or slip
frequency synchronization
sync enable input for manual control mode
option to invert synchronizer polarity if genset and
utility swap positions in synchronizer only application
(via Modbus)
Permissive Sync Check
sync check function is independent of synchronizer
adjustable frequency window, phase window, voltage
window, and window time for permissive check
includes configurable dead bus logic
sync check output
fail to synchronize diagnostic
Breaker Control
interface for both genset main and utility main
close and open control – momentary energization until
desired position is achieved
a/b and tripped breaker position inputs
adjustable breaker recharge time delay to prevent fail
to close due to inadequate charge time
Breaker Control
utility paralleling enable output
breaker inhibit control input
breaker diagnostics with appropriate system control
reaction
adjustable fail to close and fail to open time delays
paralleling fail to disconnect diagnostic with
configurable system control reaction
Breaker Control
anti-pump avoidance logic – external breaker position
contacts not required in series with trip coil
breaker inhibit output to control individual genset
paralleling breakers in applications with no gen main,
and for backup disconnect protection capability
Power Transfer Control
open transition w/pgm transition delay, hard closed
transition (<100msec), soft load closed transition
sensors (uv, ov, freq, phase rot, loss of phase, gen
bus capacity, and breaker failure)
adjustable time delays (pgm transition, transfer,
retransfer, max parallel, gensets start delay, gensets
stop delay)
source availability determination for both utility and
genset
Power Transfer Control
gensets start/stop logic with single relay output
transfer and retransfer inhibit inputs
override input to override timers and
transfer/retransfer inhibits for immediate transfer,
retransfer or genset start
Power Transfer Control
test start input
adjustable test with or without load
option to do open transition retransfer if fail to sync
occurs
System Topologies
Transfer Pair (UM / GM)
Common Bus (UM / no GM)
Isolated Bus (GM)
Isolated Bus (no GM)
System Topologies
Transfer Pair (System Types 2,3,4,8,10,11)G1 G2 G3 G4
UM GM
MCM 3320
System Topologies
Common Bus (System Type 9)Load
G1 G2 G3 G4
UM
MCM 3320
System Topologies
Isolated Bus w/GM (System Type 7)G1 G2 G3 G4
GM
MCM 3320
System Topologies
Isolated Bus Without GM (System Types 5,6)Load
G1 G2 G3 G4
MCM 3320
System Topologies
Master Synchronizer Only (metering optional)Source G1 G2 G3 G4 MCM 3320 Sync Check
Multiple MCM3320s
master inhibit input will inhibit the synchronizer andpower transfer control functions
use in complex systems with multiple transfer pairs andmultiple MCM3320s
external logic device is required to assert the masterinhibit as required (e.g. during a retransfer sequence of multiple pairs)
future enhancement will allow automatic priority controlthrough interconnected MCM3320s (similar to First Start Bus PT logic)
Extended Paralleling
MANY options available for controlling kW and kVAR in
extended paralleling mode (kVAR not applicable for
PCC3100)
kW and kVAR can be independently controlled in any
combination of base load (control the power @ gen bus)
or peak shave (control the power @ utility bus)
load control operates independently of the number of
gensets that are online
Maximum of 20 gensets
kW base load control selectable as open loop or closed
loop
Extended Paralleling
setpoints can be set from InPower, HMI, Modbus, or via analoghardware 0-5V inputs
extended parallel start input starts/stops the mode
soft load ramping
separate diagnostic for kW and kVAR if unable to acheiveSystem Scheduler
12 program run schedules
run schedules configurable for start day, start
time, duration, repeat interval, and run mode
run modes: without load, with load, or extended
parallel
provides up to 6 different schedule exceptions
Real Time Clock
on-board RTC used by Scheduler function
clock keeps track of year, month, day, date, hour,minute, and second
user must set the clock on first power-up
clock automatically accounts for leap year
configurable automatic Daylight Savings Time clockcorrection
clock setting will remain valid for at least 24 hourswithout B+ to the board
diagnostic fault occurs if clock needs to be set (schedulerLoad Demand
Use to match online generating capacity to load in orderto optimize fuel use and genset life
load demand for up to 4 gensets
fixed sequence OR run-hours based
adjustable shutdown and restart thresholds as well astime delays and run hour differential
4 load demand driver outputs to connect to PCC gensetcontrol's load demand inputs
requires genset paralleling breaker position 'a' contactsLoad Add/Shed
adds loads in steps as gensets come online
sheds loads to unload an overloaded genset bus
Requires external module: AUX101/2 PCCNet I/OModule for feeder breaker and/or ATS control
supports up to 6 levels
supports up to 4 gensets
control up to 6 feeder breakers or ATS directly in anycombination
Modbus RTU
intended for PLC interface
published register map
read/write access
operational data, control, and setup variables
MCM3320 is Modbus slave
RS232 or RS485 connection
settable address (allowing multiple MCM3320 slaves onRS485)
Diagnostics
individual On-Board LEDs for:Utility Available Utility Connected Genset Available Genset Connected Not In Automatic Common Warning Heartbeat Synchronizing Synchronized Fail To Sync
Diagnostics
Genset Connected Utility Connected Genset Available Utility Available Common Alarm Not In Automatic Heartbeat (blink) Fail to Sync Blink = Sync Solid = Ok to Close LED Indicators Modbus ActivityDiagnostics
On-Board seven segment LED for indication of:System State indication of what the control is currently doing
Fault Code Readout (hold fault reset switch active for >5sec to change to fault code readout mode)
Diagnostics
Decimal Point = Off
System State
Seven Segment LED Indicator
Decimal Point = On
Active Fault Code Flashout
System State LED Output Character
Not Available - (center segment) TD Start 1 TD Stop 2 TD Pgm Tran 3 TD Transfer 4 TD Retransfer 5 Synchronizing 6 Sync Check OK 7 Inhibit 8 Unassigned 9 Ramp Unload A Ramp Load b
Code Event Nam e Response
343 Har d w ar e Failu r e War n in g War n in g 353 EEPROM Wr it e Er r o r War n in g War n in g 1121 Fail To Disco n n ect War n in g War n in g 1219 Ut ilit y Main Br eaker Tr ip p ed War n in g War n in g 1222 No t In Au t o m at ic Even t Even t 1223 Ut ilit y Bu s Fr eq u en cy War n in g War n in g 1224 Gen set Bu s Over vo lt ag e War n in g War n in g 1225 Gen set Bu s Un d er vo lt ag e War n in g War n in g 1226 Gen set Bu s Fr eq u en cy War n in g War n in g 1328 Gen set Main Br eaker Tr ip p ed War n in g War n in g 1335 AC Met er in g Ou t Of Ran g e War n in g War n in g 1444 Gen set Bu s Over lo ad War n in g War n in g 1452 Gen set Main Br eaker Fail To Clo se War n in g War n in g 1453 Gen set Main Br eaker Fail To Op en War n in g War n in g 1454 Gen set Main Br eaker Po sit io n Co n t act War n in g War n in g 1455 Ut ilit y Main Br eaker Po sit io n Co n t act War n in g War n in g 1456 Syn ch r o n izer Ou t p u t Lim it War n in g War n in g 1457 Fail To Syn ch r o n ize War n in g War n in g 1458 Syn ch r o n izer Ph ase Ro t at io n Mism at ch War n in gWar n in g 1483 Co m m o n War n in g Even t Even t 1534 Lo ad Co n t r o l Ou t p u t Even t Even t 1541 Gen set Failed To Co m e On lin e War n in g War n in g 1689 Real Tim e Clo ck Po w er In t er r u p t War n in g War n in g 1912 Ut ilit y Bu s Lo ss Of Ph ase War n in g War n in g 1913 Gen set Bu s Lo ss Of Ph ase War n in g War n in g 1914 Ut ilit y Bu s Ph ase Ro t at io n War n in g War n in g 1915 Gen set Bu s Ph ase Ro t at io n War n in g War n in g 1916 Syn ch r o n ized Even t Even t 1989 kW Lo ad Co n t r o l Ou t p u t Lim it War n in g War n in g 1991 kVAR Lo ad Co n t r o l Ou t p u t Lim it War n in g War n in g 1999 Maxim u m Par allel Tim e War n in g War n in g 2328 Ut ilit y Bu s Availab le Even t Even t 2331 Ut ilit y Bu s Un d er vo lt ag e War n in g War n in g
Diagnostics
42 diagnostics (warnings and events)
each event or warning is mappable to 8 customer low sidedriver outputs
active warning codes can be read out on 7segment LED onboard
some warnings alter control operation
warnings are latched until user fault resetDiagnostics
Common Alarm EventGenset Available Event Genset Connected Event Synchronized Event
Test / Extended Parallel Event Utility Available Event
Utility Connected Event
AC Metering Out of Range Warning Calibration Checksum Warning EEPROM Write Error Warning Fail To Disconnect Warning Fail To Synchronize Warning
Genset Main Breaker Fail To Close Warning Genset Main Breaker Fail To Open Warning Genset Main Breaker Position Contact Warning Genset Main Breaker Tripped Warning
Genset Frequency Warning Genset Loss of Phase Warning Genset Overvoltage Warning
kVAR Load Control Output Limit Warning kW Load Control Output Limit Warning Maximum Parallel Time Warning
Not In Automatic Warning
Real Time Clock Power Interrupt Synchronizer Output Limit Warning
Synchronizer Phase Rotation Mismatch Warning Utility Main Breaker Fail To Close Warning
Utility Main Breaker Fail To Open Warning Utility Main Breaker Position Contact Warning Utility Main Breaker Tripped Warning
Utility Frequency Warning Utility Loss of Phase Warning Utility Overvoltage Warning Utility Phase Rotation Warning Utility Undervoltage Warning Load Demand Setup Warning
Remote IO Communications Warning Genset Bus Overload Warning
InPower V5.5
MON RS485 interface
standard InPower folders: Adjustments, Faults,
Monitor, Test
built in Setup Tool
download new firmware
InPower V5.5 Setup Tool
special application
to assist with setup
of the MCM3320
user friendly
screens
High/Low Battery Voltage
Flexible Topology
High/Low Battery Voltage
Provide faults for high and low battery voltage
as sensed at the MCM3320
Flexible Topology
Make the MCM3320 more flexible for use in
complex system topologies
Provide Extended Parallel w/o breaker control
Provide outputs for source unloaded for utility
and generator
Eliminates need for Bitronics transducer
Feature Limits Quiz
How many gensets can be supported by the
following features ?
•AC Metering
•Synchronizing
•Load Demand
•Load Add / Shed
•Utility Paralleling
32000kW, 10000A
20
4
4
20
Annunciator Support
Utility Available Utility Connected Gen Bus Available Gen Bus connected Not In Auto Common Alarm Fail to Sync Gen 1 Running Gen 2 Running Gen 3 Running Gen 4 Running Test Extended Parallel Gen Bus Overload Load Demand Priority 1 Load On Priority 2 Load On Priority 3 Load On Priority 4 Load On Priority 5 Load On Priority 6 Load On Shed Level 1 Shed Level 2 Shed Level 3 Shed Level 4 Shed Level 5
Feature Limits Quiz
What can Load Add / Shed support ?
•Load Device Types
•Load Add Levels
•Load Shed Levels
•# of Gensets
Breaker, ATS
6
6
4
Part Numbers
Part Number Model Released? Description
0327-1520-01 MCM3320 Yes fully featured master control module
0327-1520-02 SYNC1320 Yes depopulated/defeatured synchronizer only module 0300-6090 HMI 211 Yes operator interface panel (can use one or two)
300-6050-01 HMI 112 Yes Bargraph panel (use 2 – one for genset bus, one for utility bus)
0541-1342 AUX101/2 Yes PCCNet IO Module with Expansion card for use with Load Add
Shed Feature (one only)
0338-4747 Yes 12 foot harness for connecting HMI to MCM3320; can be cut to
length
0630-3133 Yes MCM3320 Interconnect Wiring Diagram and Outline
0630-3136 Yes SYNC1320 Interconnect Wiring Diagram and Outline
0541-1199 Yes Cable and RS485/232 Converter Kit for connecting to controller
with InPower, Engineering Tool, or Setup Tool (Kit is for PCC1301 product, but will work with MCM3320 or SYNC1320)
MCM3320
Genset CT Inputs (1A or 5A) Modbus RTU (RS232) TB6 Genset PT Input (480V LL Max) Utility PT Input (480V LL Max) Utility CT Inputs (1A or 5A) TB9 Analog IO TB3 TB1 TB10 TB8 TB15 TB2 TB7 L1* L2* L3* L1* L2* L3* GEN UTILITY Switch IO / PCCNet (TB1) Switch IO / CAN (TB3)Breaker Status Inputs (TB10) Breaker Control / Start Gensets (TB8)
InPower or Modbus RTU (RS485) Switch IO / DC Power In J14 J17
Hardwired IO
G e n O p e n G e n C l o s e G e n P o s i t i o n AExtended Para Start Sync Enable Utility Source Failure Transfer Inhibit Retransfer Inhibit Gen CB Tripped Util CB Tripped G e n P o s i t i o n B Manual Test Start Fault Ack/Reset Gen1 Available Gen2 Available Gen3 Available Gen4 Available kVAR Load Setpoint
Master Freq Bias Master Volt Bias Master Inhibit
Load Govern Enable Load Demand Gen1 Load Demand Gen2 Load Demand Gen3 Load Demand Gen4 Start Gensets Relay
kW Master Load Control Gen CB Inhibit
Util CB Inhibit
Cfg Out1 (com warn) Cfg Out2 (fail to sync) Cfg Out3 (gen avail) Cfg Out4 (util avail) Cfg Out5 (fail to discon) Cfg Out6 (sync‟d) Cfg Out7 Cfg Out8 Relay Supply B+ Input1 Gnd RS485 PCCNet RS485/232 Mon/MB B+ Input2 Gnd CAN (Master) BIDIRECTIONAL B+ POWER DISCRETE INPUTS (active low w/ pullup) DISCRETE OUTPUTS (low side drivers)
ANALOG INPUTS (0-5V) ANALOG OUTPUTS GEN V/I BUS/UTIL V/I COMMUNICATIONS Override RELAY OUTPUTS B+ OUTPUTS BREAKER INTERFACE (discrete inputs / relay outputs) U t i l O p e n U t i l C l o s e U t i l P o s i t i o n A U t i l P o s i t i o n B Paralleling Gensets Breaker Inhibit MCM3320 Hardware I/O kW Load Setpoint
B+ Power
2 separate B+ power inputs for redundant supply ofcontrol; station battery suggested
On-board diode-OR
Range: 9-32V
Will ride-through starter dip
Less than 1 Adc load (no external B+ loads)
On-board backup of Real Time Clock (minimum 24hours)
No wakeup input; board is always awake
Removal of B+ will not cause loss of any historical dataPT Inputs
Nominal Range 110 – 480 V LL
External Transformer to 35 kV LL
Sensing to 125% of Nominal
CT Inputs
Primary from 5 to 10000 Amps
Secondary 1 Amp OR 5 Amp
No terminal block; CT on-board with hole
Recommend shorting block nearby
2 passes through hole for 1 Amp
1 pass for 5 Amp
HW Discrete Inputs
22 hardwire switch inputs
Inactive State: Open circuit / high impedance
(not B+)
Active State: Connect to Return
Can use local B- for return
HW Discrete Inputs
Discrete Input Active State
(to Gnd)
Inactive State (open cicuit)
Description
Fault Reset Reset Not Reset reset faults; engage fault readout
Auto/Manual Manual Auto manual or auto breaker / sync operation
Test Start Start Stop test load transfer start / stop
Extended Parallel Start Start Stop extended paralleling start / stop
Synchronizer Enable Active Inactive sync enable (applies in manual only)
Utility Source Failure Active Inactive use if external device determines failure
Transfer Inhibit Inhibit No Inhibit inhibit transfers to gens (some exceptions)
Retransfer Inhibit Inhibit No Inhibit inhibit retransfers to util (some exceptions)
Override Override No Override override timers and tran/retran inhibits
Gen Main CB Inhibit Inhibit No Inhibit open gen main / inhibit closure
Util Main CB Inhibit Inhibit No Inhibit open util main / inhibit closure
Gen Main CB Tripped Tripped Not Tripped gen main breaker tripped; source not avail
Util Main CB Tripped Tripped Not Tripped util main breaker tripped; source not avail
Gen1 CB Position Breaker Closed Breaker Open genset #1 breaker position ('a' contact)
Gen2 CB Position Breaker Closed Breaker Open genset #2 breaker position ('a' contact)
Gen3 CB Position Breaker Closed Breaker Open genset #3 breaker position ('a' contact)
Gen4 CB Position Breaker Closed Breaker Open genset #4 breaker position ('a' contact)
Util Main CB PositionA Breaker Closed Breaker Open util main breaker position ('a' contact)
Util Main CB PositionB Breaker Open Breaker Closed util main breaker position ('b' contact)
Gen Main CB PositionA Breaker Closed Breaker Open gen main breaker position ('a' contact)
Gen Main CB PositionB Breaker Open Breaker Closed gen main breaker position ('b' contact)
HW Discrete Outputs
19 hardwire discrete outputs
5 relays; 14 low-side drivers
low-side drivers can sink 200mA
breaker relays (4) can drive coils directly in
HW Discrete Outputs
Output Signal Name(hardware) Active State (Low / Energized) Inactive State (High Impedance / Deenergized) Description
Start Gensets Relay Run Stop form C relay to start / stop gensets (via Remote Start) Util Main CB Close Relay Active Inactive N.O. relay contact for utility main close coil Util Main CB Open Relay Active Inactive N.O. relay contact for utility main open coil Gen Main CB Close Relay Active Inactive N.O. relay contact for gen main close coil Gen Main CB Open Relay Active Inactive N.O. relay contact for gen main open coil
Load Govern Enable Driver Enabled Disabled low-side driver to PCC genset's util cb position input to put PCC in load govern mode when utility paralleled Paralleling Gensets Breaker
Inhibit Driver
Inhibit All Gensets No Inhibit low-side driver to PCC genset's paralleling breaker inhibit input
Load Demand Gen1 Driver Load Demand Stop Run low-side driver to PCC genset #1 load demand input Load Demand Gen2 Driver Load Demand Stop Run low-side driver to PCC genset #2 load demand input Load Demand Gen3 Driver Load Demand Stop Run low-side driver to PCC genset #3 load demand input Load Demand Gen4 Driver Load Demand Stop Run low-side driver to PCC genset #4 load demand input Configurable Output1 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output2 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output3 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output4 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output5 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output6 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output7 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output8 Driver Driver On Driver Off activated by programmable event/warning code Relay Supply B+ Output B + Output B + output for supplying relay coil high side; low side
HW Bidirectional Discrete
Bidirectional discrete I/O for priority arbitration
(like 1
stStart Bus PT)
Used in Phase 2 for priority control among
multiple MCM3320s
Same connection as “Master Inhibit” (externally
controlled sequencing)
HW Analog Inputs
2 hardwire analog inputs
kW Load Setpoint (0-5V)
kVAR / PF Load Setpoint (0-5V)
used for base load / peak shave setpoints
alternatively set via Modbus or Trim
load setpoint profiles same as
PCC3100/3200/3201
HW Analog Outputs
2 hardwire analog outputs
kW Master Load Control (0-5V)
kVAR Master Load Control (0-5V)
Used for load control commands to PCC genset load setinputs to control soft ramping and base load / peak shave
kVAR control only available on PCC3200/3201,PCC3300 genset controllers
New Rev D board supports interconnection of analogHW Bidirectional Analog
Two bidirectional analogs for synchronizer
Master Frequency Bias senses/drives kW load
share line to affect gen bus frequency
Master Voltage Bias senses/drives kVAR load
share line to affect gen bus voltage
Output range -2.5 to + 5.0 V
Communications
Controller has 2 serial ports
Port1
– Protocol Options
• PCCNet – for HMI, IO Modules (default protocol)
• Mon – for troubleshooting only (cannot download); set to
Mon mode via Modbus on Port2 or through InPower
– Physical
• RS485 on TB1
Communications
Port2:
– Protocol Options
• Modbus RTU (MCM3320 is SLAVE)
• Mon (Service Port for InPower/Setup Tools)
• Controller automatically detects protocol
– Physical
• RS232 on J14 (DB9 pins); Null Modem cable • RS485 2-wire on TB15
• RS485 is default; control switches to RS232 when RS232 RTS to CTS pins are jumpered by cable
HMI211 Operator Panel
HMI211 PCCNet interface(4wires):
B+ / GND RS485 A / B
•
Up to two HMI211‟s can beconnected to one MCM3320
•
Use harness 0338-4747 toconnect; cut to length or extend (12ft / 3.6m)
HMI112 Bargraph
HMI112 Bargraph PCCNetinterface (4wires):
B+ / GND RS485 A / B
•
Connect two HMI211‟s to oneMCM3320 to get both source data
AUX101/2 IO Module
P11 (Inputs)
P10 (Ground for Inputs)
P2 (Relays) P3 (Relays) P4 (Relays) P14 (B+ / Gnd) P1 (PCCNet, Wakeup) P4 (Inputs) P3 (Relays - NC) P2 (Relays - Com) P1 (Relays - NO) AUX101 AUX102 Connect to Grounded Chassis
Device Number: Must Read “0” for MCM3320 Applications.
To Change Device Number, Press and hold pushbutton until decimal point is illuminated. Then push button repeatedly to cycle through numbers until it reads “0”.
Green LED: PCCNet Communcations OK Red LED: PCCNet Communcations Not
OK
Relay LEDs ON = Energized
Aux102 Board Revision Level: First letter on barcode
(read from left to right) must be “C” or higher letter.
Relay LEDs ON = Energized
Connections
•
Modules required for Load Add Shed feature•
MCM3320 to AUX101 PCCNet interface (4 wires):B+ / GND RS485 A / B
•
12 discrete inputs used for breaker / ATS positionmonitoring
MCM3320 can completely manage simple
systems – breaker control, synchronizing, load
control, gensets start/stop, diagnostics, etc.
MCM3320 can be used as a component in more
complex systems with whichever features are
appropriate; a PLC can orchestrate the actions
of the MCM3320
MCM3320 Major Functional Blocks – Application Configuration – System Information – IO Processing – AC Metering – Breaker Control
– Power Transfer Control
– Synchronizer & Sync Check
– Load Control – Scheduler – Load Demand – Load Add/Shed – Communications – Diagnostics / History – HMI 211
Application Configuration
Primary Settings:
System Topology
Transition Type
Extended Parallel Enable
Test With Load Enable
Settings are trims (can be saved) or can
be dynamically set via Modbus, InPower
or HMI
Application Configuration
MOST IMPORTANT SETTING (set it 1
st)
System Topology
Transfer Pair Common Bus
Isolated Bus with GM Isolated Bus without GM
Application Configuration
Transition Type
Open Transition (default)
Hard Closed Transition (<100msec overlap) Soft Closed Transition
Extended Parallel Enable
Disabled (default) Enabled
Test With Load Enable
Disabled (default)Application Configuration
Must be in Manual mode to set
System
Topology
Hard Closed Transition not applicable in
Common Bus topology
Transition Type only applies to load transfers
Thus Transition Type = (Open Transition OR
Hard Closed) is compatible with Extended
Parallel Enable = Enabled
System Information
Settings
for
System Phase Rotation
,
System
Frequency
, Individual
Genset kW Ratings
Derived
Information such as
Total System
Capacity
,
Total Online Capacity, Spare Online
Capacity
, etc. for use in other control function
blocks
System State
derived variable
– Shows what system is currently doing that is most
relevant
System Information
System Lockout derived variable indicating that normal control logic has been altered due to a fault
Active / Inactive
latched until user fault reset
must be reset for normal control operation to resume
LED on HMI
Conditions which make it active:Utility Breaker Fail to Close Fault State = Active Utility Breaker Fail to Open Fault State = Active Utility Breaker Position Contact Fault State = Active Genset Breaker Fail to Close Fault State = Active Genset Breaker Fail to Open Fault State = Active Genset Breaker Position Contact Fault State = Active
(Fail to Synchronize Fault State = Active AND Fail to Sync Lockout Enable = Enabled) Maximum Parallel Time Fault State = Active
System Information
Genset Bus Overload
is detected by kW level or
frequency or both (configurable)
Fault Code 1444
Used internally by Load Demand and Load Shed
functions
Adjustable %kW threshold: 80-140% of online
capacity
Adjustable kW delay: 0-120 sec
Adjustable Hz threshold: 0.1-10 Hz below System
IO Processing – Discrete Inputs
Most discrete inputs can be controlled from a hardwired
input OR from a communications link such as Modbus or
InPower (“<name> + Vol”)
Controller will always logically OR the two inputs
Result of OR is readable at “<name> + Sw”
HW SW
Conditioning & Level
Detection Sample
<Signal Name> DebounceFunction <Signal Name>
+ " Sw"
For testing and troubleshooting purposes, most discrete outputs can be directly overriden using InPowerSW HW
HW Update RegisterOutput (enabled)
(disabled)
<Output Signal Name> <Input Signal Name>
<Output Signal Name> + " Override Cmd"
AC Metering Setup
PT Primary Voltage
= 110-45000 VLL
PT Secondary Voltage
= 110-500 VLL
CT Primary Current
= 5-10000 A
CT Secondary Current
= 5 or 1 A
Nominal Voltage
= 110-45000 VLL
AC Metering - Voltage
Hardware inputs autoranging: 120,240,or 480
VLL = 100% at board
Input Range: 5% to 125% of above ranges
Sampled every line cycle on all 3 phases
LN, LL, LN-Avg, LL-Avg, % of nominal
3 or 4 Wire Connections
Factory calibrated to better than 1% of full scale;
field adjustable
AC Metering - Current
Hardware inputs autoranging: 5 A or 1A = 100% at board
Input Range: 0% to 125% of above ranges
Sampled every 10th line cycle
L1, L2, L3 and Average
True RMS with 14kHz Bandwidth
1A requires two pass thru on-board CT
Factory calibrated to better than 1% of full scale; fieldAC Metering - Power
kW, kVAR, kVA, PF
True power readings; 14kHz bandwidth If harmonics present, kW2 + kVAR2 may not equal kVA2
Sampled every 10th line cycle
Per phase and totalized to +/- 32767k
Sign Convention is with respect to the Source– Positive kW = real power delivered by source
– Positive kVAR = lagging vars delivered by source – Positive PF = lagging; Negative PF = leading
AC Metering - Energy
kWh positive, negative, net
kVARh positive, negative, net
kVAh net
Per phase and totalized to +/- 2
31
Permanently stored
AC Metering – Time Based
Precise frequency reading 25 to 80Hz
Precise sync phase angle reading -180 to +180
degrees
Precise voltage phase angle readings
AC Metering Calibration
• MCM3320 is
factory
calibrated
• Voltage and
Current can
be adjusted in
the field if
needed
Breaker Control
Main Breaker Positions
Main Breaker Control
Main Breaker Position
„a‟ and „b‟ contact used to determine position (default)this may change
If conflict between „a‟ and „b‟:1. Contact fault active
2. If current on all 3 phases > threshold, then breaker
considered closed, else unknown
3. Source deemed not available if current based breaker
position is „unknown‟
Can configure for „a‟ contact only operation, this maybecome the default
Breaker rack-out will cause fault and source notMain Breaker Position
In applications without GM, a virtual GM is created bycollection of genset paralleling breakers
In this case, if any one or more genset parallelingbreaker is closed, virtual GM is closed.
IMPORTANT: If #gens <= 4, use individual genset cbposition inputs. If #gens > 4 connect cb contacts in parallel to GM position inputs.
Main Breaker Control
Separate relays for close and open
Relays energize until desired position achieved
Adjustable recharge time delay
Built-in software interlock for open transition
In applications without GM, the MCM3320 controls thevirtual gen main via the paralleling gen cb inhibit inputs on the genset controls
Breakers can be controlled manually when Auto/ManualMain Breaker Diagnostics
Breaker Diagnostics:
Fail to Close (adjustable delay) Fail to Open (adjustable delay) Breaker Contacts
Breaker Tripped Fail to Disconnect
Diagnostics results in warning and appropriate
control reaction
Power Transfer Control
Sensors and Source Availability
Operating Mode
PTC State Machine
Sensors
Both sources have these sensors:• Undervoltage • Overvoltage *
• Under/Over Frequency * • Phase Rotation *
• Loss of Phase *
• Main Breaker Tripped • Fail to Close
• Position Contact Failure
If any sensor is dropped-out, the source is not availableSensor - Undervoltage
Sensor is always enabled
Configurable L-L or L-N sensing
Settings:
– Dropout Percentage – Pickup Percentage – Dropout Delay
Pickup is instantaneous
Take note how settings are converted into
actual voltages (next page)
Sensor - Undervoltage
Voltage, V UnderVoltage Sensor Status Nominal System Voltage (100%) Pickup Voltage Dropout Voltage PICKED UP (good) DROPPED OUT (bad)Sensor - Overvoltage
Sensor is optionally enabled
Configurable L-L or L-N sensing
Settings:
– Dropout Percentage – Pickup Percentage – Dropout Delay
Pickup is instantaneous
Take note how settings are converted into
actual voltages (next page)
Sensor - Overvoltage
Voltage, V OverVoltage Sensor Status Nominal System Voltage Pickup Voltage Dropout Voltage PICKED UP (good) DROPPED OUT (bad)Sensor - Frequency
Sensor is optionally enabled
Over and Under combined in one sensor
Settings: – Center Frequency – Dropout Bandwidth – Pickup Bandwidth – Dropout Delay
Pickup is instantaneous
Take note how settings are converted into actualSensor - Frequency
Frequency, Hz Frequency Sensor Status Center Frequency Upper Pickup Freq Lower Pickup Freq PICKED UP (good) DROPPED OUT (bad) Lower Dropout Freq Upper Dropout FreqSensor – Phase Rotation
Sensor is optionally enabled
Compares source‟s phase rotation to System PhaseRotation setting when source is at least 60% voltage and 30Hz
Once sensor is picked up (good), sensor does notrecheck until voltage/freq drop below and then back above 60%, 30Hz
Settings:– System Phase Rotation
– Dropout Delay
Sensor – Loss of Phase
Sensor is optionally enabled
Dropout (bad) when any phase angle between
LL phasors does not fall within 90 to 150
degrees
Settings:
– Dropout Delay
Pickup is instantaneous
Sensors - Misc
If
Main Breaker Tripped
input is active, source is
Not Available
If
Main Breaker Fail to Close
fault state is active,
source is Not Available
If
Main Breaker Position Contact
fault state is
active and current does not indicate breaker is
closed, source is Not Available
Sensors – Source Unique
Utility source additional sensor:
• Utility Source Failure switch input
Genset source additional sensor:
• Genset Online Capacity Sensor *• sensor picks-up when online kW capacity exceeds threshold. Once gen main is closed, sensor stops checking.
Operating Mode
Evaluates utility source status, test start / stop,
and extended parallel start / stop to decides
whether or not to start or stop the gensets
Prioritizes and lets PTC core logic know which
direction a transfer should be going, if any
PTC State Machine
The core of the power transfer control
Four possible states defined by four possible
combinations of GM and UM breaker positions
In each state, logic unique to that state decides
whether to turn on synchronizer and whether to
open or close a breaker
PTC State Machine
No Command Close Utility Close Genset No Command Open Utility Close Genset No Command Close Utility Open Genset No Command Open Utility Open Genset NO SOURCE CONNECTED UTILITY CONNECTED GENSET CONNECTED PARALLELED T2B T1B T4A T3A T4B T1A T2A T3B N1 N2 N3 N4 U1 U2 U3 U4 P1 P2 P3 P4 G1 G2 G3 G4 PTC NOT ENABLED Powerup T-INIT T99 T0Timers
Start Timer
Stop Timer
Timer in each PTC State:
– Programmed Transition Timer (No Source Connected)
– Transfer Timer (Utility Connected)
– Retransfer Timer (Genset Connected)
Override
Override switch input (hardwired or Modbus)
Forces pending action to occur immediately
Useful in certain situations / applications
Overrides (bypasses) the following:– Transfer Inhibit – Retransfer Inhibit – Start Delay
– Transfer Delay – Retransfer Delay
Does NOT override:– Stop Delay
– Programmed Transition Delay – Maximum Parallel Time
– Gen Main CB Inhibit – Utility Main CB Inhibit
Synchronizer & Sync Check
Synchronizer On / Off
Synchronizer Control
Sync Check
Synchronizer On / Off
In all cases, both sources must be „available‟
for the synchronizer to run
With PTC function, Synchronizer turns on
automatically when needed if in „Auto‟ mode
In „Manual‟, Sync Enable input must be active
to turn on
Synchronizer Control
Synchronizer matches phase, frequency and voltage ofgen bus to utility bus
Freq Match Closed loop PI drives kW load share lines tomatch freq/phase
Volt Match Closed loop PI drives kVAR load share linesto match voltage
Tuning is fairly tolerant; field adjustment not expected to be required normally
Performance is very good – much improved over existingSynchronizer Control
Two Synchronizing Options:
– Phase Sync (default) => gen bus phase is driven to match utility bus
– Slip Frequency => gen bus frequency is driven to be fixed Hz higher or lower than utility bus (e.g. 0.1Hz)
Use Slip Freq option with difficult to sync applications
such as natural gas
Nominal System Frequency
= 45-65 Hz
– Used by synchronizer – must be set to nominal operating genset frequency
Sync Check
Permissive sync check with adjustable frequency, phase,voltage and dwell time window
Runs independently of synchronizer
PTC function uses this to decide when to close breaker
Can get sync check output by mapping sync event to aconfigurable output (#6 by default)
In synchronizer only applications, can also enable synccheck individually for different dead bus scenarios (dead bus sensor is included)
Synchronizer Diagnostics
Fail to Synchronize Warning
= synchronizer has
been on for Fail to Sync time (adjustable)
without achieving sync check ok
Synchronizer Output Limit Warning
= freq bias
or volt bias drive output has been at maximum
and unable to achieve sync
Load Control
kW and kVAR are controlled during soft
transfers and extended paralleling
MCM3320 has one analog output for kW, one
for kVAR
MCM3320 drives all gensets to same %
command value
PCC Genset controllers perform ramping and
load governing
Load Control
Soft Loading
Extended Paralleling
kW Control
kVAR Control
Diagnostics
Performance / Tuning
Soft Loading
Closed transition transfer / retransfer
MCM3320 either drives load set line to +5V or 0Vdepending on desired ramp direction
PCC genset controllers perform the ramp based on theirown ramp time settings
PCC genset controllers are doing the closed loop controlof kW and kVAR (load governing)
MCM3320 disconnects appropriate source when itExtended Paralleling
Many options for how / where to control kW and
kVAR
Open loop or closed loop options
Control points at gen bus or utility bus
Setpoints from analog input, trim setting, or
Modbus
MCM3320 controls load without knowledge of
which gensets are online
kW Control Options
Gen Bus % Level (open loop)» MCM3320 puts out fixed %kW command
Gen Bus kW (closed loop)» MCM3320 adjusts output command to get desired kW at gen bus metering point
Gen Bus kW w/Utility Constraint (closed loop)» MCM3320 adjusts output command to get desired kW at gen bus metering point subject to maintaining utility kW greater than a threshold
Utility Bus kW (closed loop)» MCM3320 adjusts output command to get desired kW at utility bus metering point
kVAR Control Options
Genset Controllers» MCM3320 does nothing
» ONLY OPTION WHICH WILL WORK ON PCC3100 GENSETS
Gen Bus % Level (open loop)» MCM3320 puts out fixed %kVAR command
Gen Bus Power Factor (open loop)» MCM3320 puts out %kVAR command based on power factor setting and what is currently being put out on the %kW command output
Gen Bus kVAR (closed loop)» MCM3320 adjusts output command to get desired kVAR at gen bus metering point
Gen Bus Power Factor (closed loop)» MCM3320 adjusts output command to get desired power factor at gen bus metering point
kVAR Control Options (cont.)
Utility Bus kVAR (closed loop)
» MCM3320 adjusts output command to get desired kVAR at utility bus metering point
Utility Bus Power Factor (closed loop)
» MCM3320 adjusts output command to get desired power factor at utility bus metering point
Load Setpoints - Source
kW, kVAR/PF setpoints can come from
hardwired analog inputs or internal setting
Internal setting can be changed from Inpower,
HMI, or Modbus
analog input (hardwired)
internal
process value
Load Setpoints – Scaling
%kW, kVAR, Power Factor vs. Input Voltage
0 10 20 30 40 50 60 70 80 90 100 110 120 0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75 3 3.25 3.5 3.75 4 4.25 4.5 4.75 5 Input Voltage, Vdc %kW / %k VAR 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Power Factor %kW/kVAR PowerFactor
Load Setpoints – Scaling
If
open loop
load control, scaling of hardwired analog
input is per graph
If
closed loop
load control, kW command level = % from
graph * Total System Capacity
If
power factor control
, scaling always follows red line
Definitions:
– Total System Capacity = sum of individual genset kW ratings – %kW = kW / Total System Capacity
Load Control Diagnostics
kW Load Control Output Limit Warning
» kW command output has been at minimum or maximum value for longer than 60 seconds » Only applicable to closed loop modes
» means that the desired kW setpoint cannot be achieved either due to inadequate capacity or operator error
kVAR Load Control Output Limit Warning
» analogous to kW diagnostic» Means that the desired kVAR or Power Factor setpoint cannot be achieved either due to
Scheduler
Scheduler operates based on up to 12 programs
and 6 exceptions
Each program specifies a day of the week/time to
start, how long to run, how often to repeat, and what
mode to run in
Run modes are: test without load, test with load, and
extended parallel
Each exception is defined by a start date/time,
duration, and repeat interval
An exception will block a scheduled program from
Scheduler
To use Extended Paralleling with the Scheduler, theExtended Parallel Enable must be set to Enabled
If program run mode = Extended Parallel, but ExtendedParallel Enable = Disabled, there will never be extended paralleling (nothing will happen when program becomes active)
Some applications do not allow extended paralleling, sothis provides one setting to disable all extended paralleling
Scheduler
Scheduler will follow the Program Run Mode setting– If Program #1 Run Mode = With Load, system will run with load – If Program #1 Run Mode = Without Load, system will run without
load
The setting of Test With Load Enable variable does NOT apply to Scheduler– E.G. If Test With Load Enable = Disabled, but Program #1 Run Mode = With Load, program will run with load
Test With Load Enable only applies to Test Start switch input (hardwired or Modbus or HMI)
This may be confusing because it is different than how the Extended Parallel Enable is used by the MCM3320Program Overlapping
Do not overlap programs; overlapped program will be ignoredProgram1
Program2
Program1 Program2
Program1 runs for its entire period Program2 does NOT run
Program1 runs and ends. Some time later Program2 runs and ends.
Exception Operation
Exceptions only block the START of a program; a programstarted outside of the exception period will not be canceled by an exception
Program1
Exception1
Program1 runs for its entire period
Program1
Priorities
Utility Failure will supersede any scheduler program
An active program will resume when the utility source has become available again
Two examples are shown below
Program1 (no load) Utility Failed
EXAMPLE#1:
Utility fails while gensets running no load due to Program1. System will transfer load to gensets. When utility returns, system load will remain on gensets until Program1 ends. (It does NOT retransfer until Program1 ends.)
Program1 (extended parallel) Utility Failed
EXAMPLE#2:
Utility fails while gensets running in parallel to utility due to Program1. System will open utility main breaker. When utility returns,
UM Breaker GM Breaker Closed Open Closed Open Open Closed
Operating Sequences
Normal Sequences1
Utility Fail / Return Extended Parallel
Test (with or without load)
Sequences are affected by
Transition Type Operating priority Faults2
1Refer to MCM3320 Operating Sequences document for listing of normal sequences
Normal Sequence Example
Scenario:
Transfer Pair; Soft Closed Transition; Utility Fail / Return
1. Utility Failure
2. TD Start
3. Gensets Start / Close 4. Gen Bus Available 5. TD Transfer
6. Open Utility Main
7. TD Program Transition 8. Close Gen Main
9. Loads Powered by Gen Bus
10.Utility Available
11.TD Retransfer 12.Synchronizer On 13.Sync Check OK 14.Close Utility Main
15.Ramp Unload Gensets 16.Open Gen Main
17.TD Stop
18.Stop Gensets
Abnormal Condition Example
Scenario:
Transfer Pair; Soft Closed Transition; Test With Load;
UM Fails to Open
1. Test Start Initiated 2. TD Start
3. Gensets Start / Close 4. Gen Bus Available 5. TD Transfer
6. Synchronizer On 7. Sync Check OK 8. Close Gen Main
9. Ramp Load Gensets
10.Utility Unloaded 11.Open Utility Main
12.Utility Main Fails to Open
13.Open Gen Main 14.Gen Main Opens
15.Open Utility Canceled 16.Loads Powered by Utility 17.Gensets Remain Running 18.User Intervention Required
Operating Priorities
Operating priorities from highest to lowest:
1. Utility Failure
2. Extended Parallel 3. Test
Load Demand
Supports 2, 3, or 4 genset systems
4 hardwired outputs to drive gensets load demand stop
4 hardwired inputs to read genset paralleling breakerpositions
Shuts down/Restarts gensets based on genset bus totalkW load level
Adjustable shutdown / restart thresholds and time delays
Genset Sequence configurable as Fixed Sequence orLoad Demand Interconnect G1 PCC3xxx G2 PCC3xxx G3 PCC3xxx G4 PCC3xxx
Gen1 Load Demand
Gen1 Breaker Position
Gen2 Load Demand
Gen2 Breaker Position
Gen3 Load Demand
Gen3 Breaker Position
Gen4 Load Demand
Gen4 Breaker Position
MCM3320
Genset Bus Currents Genset Bus Voltages
Load Demand Operation
Genset Sequence defines shutdown order:– GenA, GenB, GenC, GenD
GenA always runs; GenD is first to shut down, last torestart, etc.
Sequence Determination:– Fixed Sequence, or Run Hours Based
Fixed Sequence is set by the operator
Run Hours Based Sequence changes dynamically as runhours accumulate on gensets – system attempts to equalize running hours on all gensets
Load Demand Operation
Fixed Sequence • GenA = Gen2 • GenB = Gen1 • GenC = Gen4 • GenD = Gen3
Sequence can be changed any time – even when load demandis operating
Must issue “Refresh Sequence” command after defining the newsequence in order for it to take effect (HMI211 does this for you).