App’d Ch’k’d Description Drawn Date Rev Rev Status Drawing Number Title Client Security
Project Number B/O Total
Apex Clean Energy, Inc
310 4th St. NE, Suite 300
Charlottesville, VA 22902
Heritage Wind Farm
Switching
Station
General Arrangement
Scale at ARCH D
PRELIMINARY - NOT FOR CONSTRUCTION
HER-SS-0001
A
25'-0" 66'-6" 10'-0" 33'-0" 200'-0"A
A
B
B
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATION App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved RevApex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
NOTES:
Heritage Wind Farm
Switching Station
Elevation A-A
HER-SS-002
A
PRELIMINARY - DO NOT USE FOR CONSTRUCTION
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATION App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved RevApex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
Heritage Wind Farm
Station
Switching
Elevation B-B
HER-SS-003
A
PRELIMINARY - DO NOT USE FOR CONSTRUCTION
5 3 1 6 4 2 5 3 1 6 4 2 5 3 1 6 4 2 5 3 1 6 4 2 5 3 1 6 4 2 5 3 1 6 4 2 5 3 1 6 4 2 5 3 1 6 4 2 5 3 1 6 4 2
-ROAD
-FENCE
-TRENCH (PEDESTRIAN)
-H20 TRENCH (VEHICLE)
-LIGHT LOCATION
-SHIELD WIRE
-EXPANSION RIGID BUS
CONNECTION
-FIXED RIGID BUS
CONNECTION
-SLIP RIGID BUS
CONNECTION
LEGEND
NOTES
1.
SUBSTATION LAYOUT, ARRANGEMENT, RATINGS AND
PHASING MAY VARY DEPENDING ON SPECIFIC SITE
REQUIREMENTS.
2.
REACTIVE COMPENSATION EQUIPMENT SHOWN ON
THIS DRAWING IS SUBJECT TO CHANGE BASED ON
REACTIVE POWER REQUIREMENTS DETERMINED BY
REACTIVE COMPENSATION STUDY.
3.
CONTROL ENCLOSURE SIZES ARE PRELIMINARY.
4.
EQUIPMENT IS PRELIMINARY PENDING VENDOR
SUBMITTALS.
5.
NORTH ARROW IS PRELIMINARY TO BE CONFIRMED
WITH SITE COORDINATES.
App’d Ch’k’d Description Drawn Date Rev Rev Status Drawing Number Scale at ARCH D Title Client Security
Project Number B/O Total
REPLACE THIS TEXT WITH
ENGINEER'S STAMP AT
CONSTRUCTION AND/OR
FABRICATION. ISSUE IF
REQUIRED BY PROJECT
ADMINISTRATION
MANUAL
Apex Clean Energy, Inc
310 4th St. NE, Suite
300
Charlottesville, VA 22902
Heritage Wind Farm
Collector Substation
General Arrangement
1/16" = 1'-0"
PRE
310'
150'
PRELIMINARY - NOT FOR CONSTRUCTION
15' 10' 10' 12' 15' 22' 22' 11' 20' 12' 16' 8' 4' 4' 15' 28' R50' 4' 4' 16 ' 55' 5' 30' 84' 8' 12' 8' 8' 12' 8' 12' 8' 8' 8' 8' 8' 50' 79' 47' 95' 101' 74' 27' 24' 20 ' 20 ' A 001 AØ BØ CØ AØ BØ CØ SST1
℄
H-FRAME S.A.℄
SW1℄
CCVT1℄
52-T1℄
MPT℄
NGR SST1℄
SW-T1VT1
℄
52-F1℄
52-F2℄
52-F3℄
52-F4℄
52-F5℄
52-F6℄
52-F7℄
52-F8℄
52-C1℄
SW-C1 TO 115kV SWITCHYARD SW-CSW1 SW-CSW2 CSW-2 VT-CAP-2 CSW-1 VT-CAP-1 AØ BØ CØ℄
CAP-1℄
CAP-220'-0" DRIVE GATE 20'-0" DRIVE GATE
CONTROL ENCLOSURE AØ BØ CØ 24' 25' 49' 31' 12' 33' 75' 28' 49' 4' 4' 14' 14' 18'-6" 5' 5' 5' AØ BØ CØ S F EXP F S S S EXP F S 12' 12' 9' 9' B 002 C 003 D 004
HER-SUB-000
A
45'-0" 15'-0" 20'-0" 30'-0" H-FRAME 115KV, 1200A "V" DISC SWITCH OPGW
NUMBER AND POSITION OF LIGHTS WILL VARY. nVENT ERICO DYNASPHERE 18'-0" 10'-0" 10'-0" 2-795 AAC 8'-6" MATCHLINE CONTINUED ON DWG. 0021 SA H1 CABLE SPACER
TO FLAT PAD (TYP.)
8" CABLE SPACER TO FLAT 2-3500 AAC 795 AAC (N.S., FOR NEUTRAL) 2-3500 AAC MPT POWER XFMR 115/34.5KV 140/186/232 MVA 2-795 AAC 12'-0" 15'-0" 22'-0" 17'-0" 2-795 AAC 2-795 AAC 2-795 AAC 2-795 AAC 4'-0" 4'-0" F 3" IPS AL. SCH. 40 115 KV CCVT1 115 KV BREAKER 1200A- 52-T1 SURGE ARRESTERS 7'-0" FENCE 5'-0"
(Safety clearance to live parts NESC Table 110-1) 15'-0" 954 ACSR
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATION App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved RevApex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
1. ALL STEEL STRUCTURE DIMENSIONS AND BUS HEIGHTS ARE FROM
TOP OF CONCRETE.
2. ALL OPEN TUBE ENDS TO BE CAPPED.
3. 3" IPS AL BUS TO BE BE SCHEDULE 40.
5" IPS AL BUS TO BE SCHEDULE 40 OR SCHEDULE 80 AS NOTED ON DRAWINGS.
4. CONTRACTOR TO TERMINATE THE SECONDARY STATION SERVICE
CONDUCTORS WITH A SOLID, PIN TYPE TERMINAL TO PREVENT WATER INTRUSION THROUGH THE CONDUCTOR JACKETING INTO THE FUSED DISCONNECT BOX.
TO BE COORDINATED
WITH UTILITY
Heritage Wind Farm
Collector Substation
Elevation A-A
HER-SUB-001
A
PRELIMINARY - DO NOT USE FOR CONSTRUCTION
115KV DISC SWITCH
MATCHLINE CONTINUED ON DWG.
HER-SUB-002
11'-0" 4'-0"
22'-0"
ELEVATION B-B
34.5KV SW. 4000A - SW-T1
GROUNDING REACTOR NOT SHOWN FOR CLARITY SEE SECT. C-C ON DWG. 0024
S SPEEDSLOWTCC119-2 15E TBD A FUSED DISC. SST1 TBD KVA SEE NOTE 6 #2 AAC (ONLY Aɸ) #2 AAC 6 4 2 6 4 2 2 4 6 34.5KV SW. 1200A - SW-C1 15'-0" 8'-0" 12'-0" 8'-0" 34.5KV FDR. BRKR 1200A - 52-F1 34.5KV FDR. BRKR 1200A - 52-F2 28'-0" 12'-0" 8'-0" 34.5KV FDR. BRKR 1200A - 52-F3 8'-0" 3'-6" SPEEDSLOWTCC119-2 15E 10'-0" VT1 JCT BOX VT1 VT-FUSED CUTOUTS #2 AAC #2 AAC 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" S S F R1'-3" 2-3500 AAC SW-F1-2 795 AAC (TYP.) SW-F2-2 795 AAC (TYP.) SW-F3-2 795 AAC (TYP.) VT1 25'-8" MATCHLINE CONTINUED ON DWG. HER-SUB-001 AØ BØ CØ CØ BØ AØ CØ BØ AØ 5" IPS AL, SCH. 80 5" IPS AL, SCH. 80 28'-0" 18'-0" 4'-0" 3'-8" 25'-8" 15'-0" R1'-3" R1'-3" 8'-0" SA H1 CABLE SPACER
TO FLAT PAD (TYP.)
8" CABLE SPACER TO FLAT 2-3500 AAC 8" CABLE SPACER (TYP. AS NEEDED) 795 AAC (N.S., FOR NEUTRAL) 2-3500 AAC MPT POWER XFMR 115/34.5KV 140/186/232 MVA 2-795 AAC R1'-3" F FOR X0 6 4 2 34.5KV FDR. BRKR 1200A - 52-F4 SW-F4-2 795 AAC (TYP.) BØ AØ CØ 8'-0" R1'-3"
HER-SUB-002
A
NOTES:
PRELIMINARY - DO NOT USE FOR CONSTRUCTION
1. ALL STEEL STRUCTURE DIMENSIONS AND BUS HEIGHTS ARE FROM
TOP OF CONCRETE.
2. FOR TOP OF CONCRETE ELEVATIONS SEE FOUNDATION PLAN
3. SEE GENERAL ARRANGEMENT DWG. 0010 NOTE 2.
4. ALL OPEN TUBE ENDS TO BE CAPPED.
5. 3" IPS AL BUS TO BE BE SCHEDULE 40.
5" IPS AL BUS TO BE SCHEDULE 40 OR SCHEDULE 80 AS NOTED ON DRAWINGS.
6. CONTRACTOR TO TERMINATE THE SECONDARY STATION SERVICE
CONDUCTORS WITH A SOLID, PIN TYPE TERMINAL TO PREVENT WATER INTRUSION THROUGH THE CONDUCTOR JACKETING INTO THE FUSED DISCONNECT BOX.
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATION App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved RevHeritage Wind Farm
Collecto
r Substation
Elevation B-B
Apex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
20'-0" 5" IPS AL., SCH. 40 4'-0" 4'-0" 6'-0" 6'-0" 6'-0" 4'-0" 4'-0" 6'-0" 2'-6" 20'-0" 15'-0"
ELEVATION C-C
10'-0" 10'-0" 10'-0" 10'-0" FENCE AØ BØ CØ CØ BØ AØ3" IPS AL (TYP.) 3" IPS AL (TYP.)
NOTE 2 (TYP.) 795 AAC (TYP.) 795 AAC (TYP.) F S S TOP OF SW PAD
℄
OF BUS 7'-0" 5'-0" 1' 22'-0" 37'-0"(Safety clearance to live parts NESC Table 110-1)
1. ALL STEEL STRUCTURE DIMENSIONS AND BUS HEIGHTS ARE FROM
TOP OF CONCRETE.
2. FOR TOP OF CONCRETE ELEVATIONS SEE FOUNDATION PLAN
3. SEE GENERAL ARRANGEMENT DWG. 0010 NOTE 2.
4. ALL OPEN TUBE ENDS TO BE CAPPED.
5. 3" IPS AL BUS TO BE BE SCHEDULE 40.
5" IPS AL BUS TO BE SCHEDULE 40 OR SCHEDULE 80 AS NOTED ON DRAWINGS.
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATION App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved RevApex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
Heritage Wind Farm
Collector Substation
Elevation C-C
HER-SUB-003
A
PRELIMINARY - DO NOT USE FOR CONSTRUCTION
R1'-3" 9'-0" 22'-0" 4'-0" 4'-0" 8'-0" 15'-0" 34.5KV, 1200A SW-CSW2 CØ BØ AØ
ELEVATION D-D
3" IPS AL EXP (N.S.) 23 26 TYP. 795 AAC (TYP.) GROUND STUD OPERATOR PLATFORM H2 H1 T.B.D. T.B.D. CAP2 VT-CAP CSW2 2 SA GND. SW VT-CAP2 25 24 4'-0" T.B.D. 795 AAC OPERATOR PLATFORM 31 TYP.1. ALL STEEL STRUCTURE DIMENSIONS AND BUS HEIGHTS ARE FROM
TOP OF CONCRETE.
2. FOR TOP OF CONCRETE ELEVATIONS SEE FOUNDATION PLAN
3. SEE GENERAL ARRANGEMENT DWG. 0010 NOTE 2.
4. ALL OPEN TUBE ENDS TO BE CAPPED.
5. 3" IPS AL BUS TO BE BE SCHEDULE 40.
5" IPS AL BUS TO BE SCHEDULE 40 OR SCHEDULE 80 AS NOTED ON DRAWINGS.
NOTES:
PRELIMINARY - NOT FOR CONSTRUCTION
HER-SUB-004
A
REACTIVE COMPENSATION SIZING IS PRELIMINARY. ACTUAL SIZING MAY CHANGE AFTER FINAL MODELING IS COMPLETE.
NOTE:
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATION App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved RevHeritage Wind Farm
Collector Substation
Elevation D-D
Apex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
3" IPS AL CONTINUES
T0
10'-0"
10'-0" (MAX SPACING) 10'-0" (MAX SPACING) 10'-0"
3'-0" 3'-3"
1'-0" 9"
3'-6"
TYPICAL FENCE FABRIC DETAIL
TYPICAL FENCE CORNER DETAIL
3'-0" 3'-3"
TYPICAL FENCE TENSION SECTION DETAIL
3'-3" 3'-0" 1'-0" 9" 9" 9" 9" 3" 2" 3" X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X XX XX XX X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X ίMANTENERSE FUERA! ESTA SUBESTACION UTILIZA CABLES DE ACERO RECUBIERTO PARA SU SISTEMA DE TIERRAS. ESTA MATERIAL NO TIENE VALOR DE REVENTA. KEEP OUT! THIS SUBSTATION'S GROUNDING SYSTEM UTILIZES COPPER-CLAD STEEL HARDWARE. THIS MATERIAL HAS NO SCRAP VALUE.
THEFT DETERRENT SIGN
SCALE: N.T.S. 3'-2"
1'-10"
3"
TYPICAL WARNING SIGN
1'-2"
10"
SCALE: N.T.S.
2 3/8" O.D. LINE POST (TYP.)
45° EXTENSION ARM (TYP.) 3 STRANDS BARBED WIRE SEE NOTE 1
1 5/8" TOP RAIL
TENSION BAND (TYP.) 3 STRANDS BARBED WIRE SEE NOTE 1 45° EXTENSION ARM 2 3/8" O.D. LINE POST 45° EXTENSION ARM 2 3/8" O.D. LINE POST
TENSION BAND (TYP.) 3 STRANDS
BARBED WIRE
SEE NOTE 1 1 5/8" TOP RAIL
45° EXTENSION ARM 2 3/8" O.D. LINE POST
SEE SIGN NOTE 4
WHITE BACKGROUND WITH BLACK TEXT NOTE 5
RED BACKGROUND WITH WHITE TEXT
WHITE BACKGROUND WITH BLACK TEXT
2 7/8" TERMINAL POST TENSION BAR (3/16"x3/4") TENSION BAR CLAMPS, 14" MAX. SPACING 3/8" DIA. DIAGONAL TENSION ROD WITH TURNBUCKLE (TYP.) 1 5/8" BOTTOM RAIL
1 5/8" BOTTOM RAIL 3/8" DIA. DIAGONAL TENSION ROD WITH TURNBUCKLE
2" 2"
BOLLARD
TOP VIEW
TYPICAL 20' DRIVE SLIDE GATE DETAIL
SCALE: N.T.S. SNAKE FENCE
NOT SHOWN FOR CLARITY
GATE POST GATE POST LATCH POST
INSIDE OUTSIDE 90° BARBWIRE ARM 4" POST GATE POST INLINE WITH FENCE LINE ROLLER AND ROLLER GUARD ROLLER AND ROLLER GUARD
SIDE VIEW
TYPICAL 20' DRIVE
CANTILEVER
SLIDE GATE DETAIL
7'-0"
3'-0" 3'-3"
1'-2"
TYPICAL 4' WALK GATE DETAIL
3'-6" 2" 1'-2" 3" X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X ίMANTENERSE FUERA! ESTA SUBESTACION UTILIZA CABLES DE ACERO RECUBIERTO PARA SU SISTEMA DE TIERRAS. ESTA MATERIAL NO TIENE VALOR DE REVENTA. KEEP OUT! THIS SUBSTATION'S GROUNDING SYSTEM UTILIZES COPPER-CLAD STEEL HARDWARE. THIS MATERIAL HAS NO SCRAP VALUE.
4" GATE POST
TENSION BAND (TYP.) 3 STRANDS BARBED WIRE SEE NOTE 1
3/8" DIA. DIAGONAL TENSION ROD WITH TURNBUCKLE (TYP.) 4" GATE POST 2" GATE FRAME (2 SIDES) 2 7/8" CORNER POST SCALE: 3/8" = 1'-0"
SCALE: N.T.S. SCALE: 3/8" = 1'-0" SCALE: 3/8" = 1'-0"
SCALE: 3/8" = 1'-0" 1 5/8" TOP RAIL X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 3'-0" 3'-3" 3" 3'-0" 3'-3" 3" 3 STRANDS BARBED WIRE SEE NOTE 1 4" GATE POST (N.S.) 7'-0" 5'-0" (TYP.) ίMANTENERSE FUERA! ESTA SUBESTACION UTILIZA CABLES DE ACERO RECUBIERTO PARA SU SISTEMA DE TIERRAS. ESTA MATERIAL NO TIENE VALOR DE REVENTA. KEEP OUT! THIS SUBSTATION'S GROUNDING SYSTEM UTILIZES COPPER-CLAD STEEL HARDWARE. THIS MATERIAL HAS NO SCRAP VALUE. 6" 12'-0" LATCH 4" GATE POST 2 1/2" BOTTOM RAIL 2 1/2" TOP RAIL 2" 4" GATE POST (N.S.) 1 5/8" BOTTOM RAIL OVERHANG 90 DEG. EXTENSION ARM (TYP.) POST BRACE
TYPICAL 20' DRIVE CANTILEVER SLIDE GATE DETAIL
SCALE: 3/8" = 1'-0" 1 5/8" O.D. DIAGONAL (TYP.) X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X XX XX XX XX XX
GATE BARBWIRE ENDS ON 90 DEG. EXTENSION ARM
3'-0" 3'-3" 3" 1'-2" 2" ROLLER COVER (TYP.) GATE OPENS X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 2"
FENCE FABRIC THIS SECTION OF GATE NO FENCE FABRIC THIS SECTION OF GATE
20'-0" CLEAR OPENING INNER SIDE TO INNER SIDE
1 5/8" BOTTOM RAIL POST BRACE 1 5/8" TOP RAIL 6'-0" 1'-2" 1'-2" 6'-0" TOP OF CRUSHED ROCK 1 5/8" BOTTOM RAIL 7'-0" 1'-0" ίMANTENERSE FUERA! ESTA SUBESTACION UTILIZA CABLES DE ACERO RECUBIERTO PARA SU SISTEMA DE TIERRAS. ESTA MATERIAL NO TIENE VALOR DE REVENTA. KEEP OUT! THIS SUBSTATION'S GROUNDING SYSTEM UTILIZES COPPER-CLAD STEEL HARDWARE. THIS MATERIAL HAS NO SCRAP VALUE. 3'-2"x1'-10" PLACED EVERY 75'-0" 10"x14" PLACED EVERY 75'-0"
1 1/4" POST BRACE 1 1/4" POST BRACE
SNAKE FENCE NOT SHOWN FOR CLARITY
FORKED TYPE LATCH HAVING PADLOCK LOCKING CAPABILITY FROM EITHER SIDE OF GATE. FENCE GATE HINGE
1 1/4" POST BRACE
SNAKE FENCE NOT SHOWN FOR CLARITY
1'-0" 3" 3'-6" 1'-0" 6'-0" WIDE CONCRETE APRON TOP OF CRUSHED ROCK 10'-0"
ROLLER COVER (TYP.)
App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved Rev
1. EXTENSION ARMS WITH 3 STRANDS BARBED WIRE 12-1/2 GAUGE
GALVANIZED TWISTED DOUBLE STRAND, 4 POINT ROUND BARBS SPACED AT 5" O.C. EACH ARM.
2. CROWN CONCRETE AROUND ALL POSTS, T.O.C. SHALL BE APPROXIMATELY
1" ABOVE AGGREGATE SURFACING.
3. FENCE FABRIC - 9 GAUGE, 2" MESH.
4. INSTALL CAPS ON ALL GATE, CORNER AND PULL POSTS.
5. ALL PIPE SIZES ARE O.D. AS REFERENCED IN FENCE SPECS U.N.O.
GENERAL NOTES:
1. SIGNS SHALL COMPLY WITH ANSI Z535.1-Z535.5 (LATEST REVISION).
2. THE SYMBOL/PICTORIAL PANEL SHALL BE SQUARE WITH A BLACK SYMBOL
OF A BODY WITH WIRE AND LIGHTNING BOLT ON A WHITE BACKGROUND.
3. SIGNS SHALL BE MANUFACTURED FROM AN 80 MIL ALUMINUM SHEET,
TYPE 3003 H-14 COATED FRONT AND BACK WITH AN ACRYLIC ENAMEL. ALL SHARP EDGES AND BURRS SHALL BE REMOVED. THE SIGNS SHALL HAVE A THICKNESS OF 0.080". THE MOUNTING HOLES SHALL BE PROTECTED BY BRASS FERRULES.
4. THE SIGNAL WORDS "NOTICE" AND "AVISO" SHALL BE WHITE LETTERS ON
A RECTANGULAR ANSI SAFETY BLUE BACKGROUND.
SIGN NOTES:
Heritage Wind
Collector Substation
Fence Details
HER-SUB-005
ISSUED FOR CONSTRUCTION
Apex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
A
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATIONApp’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved Rev
HER-SUB-006
ISSUED FOR CONSTRUCTION
Heritage Wind Farm
Collector Substation
Control Building
Details
Apex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATIONA
FINISHED GRADE
H-FRAME LIGHTS
CONDUIT DETAILS
(LOOKING NORTH)
SCALE: N.T.S. TO TRENCH 4'-0" (TYP.) 30'-0" (N.T.S.) (MAY VARY) 12" 18" MAX / 12" MN 12"MOUNTING HT. (MAY VARY)
1'-0"
ELEVATION
LIGHT FIXTURE WITH
PHOTOCELL MOUNTING (TYP.)
ACTUAL NUMBER OF LIGHTS VARIES
SCALE: N.T.S.
PLAN (TYPICAL)
ACTUAL NUMBER OF LIGHTS VARY
SCALE: N.T.S.
VARIES
DIRECT EMBED
AREA LIGHT POLE CONDUIT DETAIL
SCALE: N.T.S. FINISHED GRADE
4'-0"
TO TRENCH POLE TOP BRACKET FOR
LIGHTS WILL VARY FROM 2 TO 4 LIGHTS
LIGHT POLE, PIPE 8" XPS (SCH 80)
2" RGS 90 DEG. ELBOW, 24" RADIUS 2" PVC TO RGS COUPLING
2" PVC CONDUIT
1" LIQUIDTIGHT STRAIGHT CONNECTOR 2" TO 1" PVC REDUCER
2" PVC FEMALE ADAPTER 2" RGS TO PVC COUPLING 1" LIQUIDTIGHT FLEX CONDUIT
1" LIQUIDTIGHT STRAIGHT FLEX CONNECTOR SEE LP SWITCH NOTE ABOVE
THREADED NIPPLE FOR LIGHT SWITCH CONDUIT TYPICAL LIGHT FIXTURE WITH PHOTOCELL
1'-0" 1'-0"
LIGHT FIXTURE WITH PHOTOCELL
CABLE FROM BELOW
LIGHTING HANDHOLE YARD LIGHTING ARM BY STEEL VENDOR LIGHT FIXTURE WITH PHOTOCELL
SLIP FITTER KNUCKLE
H-FRAME /
LIGHTNING MAST LEG
KELLEMS GRIP CABLE SPLICE 3 PER
CONNECTION
SEE 1010-YARD LIGHTING PLAN
(2) 1" LIQUIDTIGHT STRAIGHT FLEX CONNECTOR (2) 2" TO 1" PVC REDUCER
(2) 2" PVC FEMALE ADAPTER (2) 2" RGS TO PVC COUPLING (2) 1" LIQUIDTIGHT FLEX CONDUIT
(2) 1" LIQUIDTIGHT STRAIGHT FLEX CONNECTOR SINGLE SW. BOX
SINGLE HUB
THREADED NIPPLE FOR LIGHT SWITCH CONDUIT
HANDHOLE AND COVER
2" PVC TO RGS COUPLING HANDHOLE
AND COVER THREADED NIPPLE FOR LIGHT SWITCH CONDUIT
DYNASPHERE SINGLE GANG SW. BOX DOUBLE HUB 2" RGS 90 DEG. ELBOW, 24" RADIUS 2" PVC CONDUIT 18" MAX / 12" MN
NUMBER OF LIGHTS MAY VARY
30'-0" (MAY VARY)
SEE 1010-YARD LIGHTING PLAN
45
'-0"
TYPICAL DIRECT EMBED LIGHTNING MAST
LIGHTS CONDUIT DETAILS
SCALE: N.T.S. 1'-0" 2'-10" 3'-10" 18'-0" TO TRENCH HAND HOLE & COVER THREADED NIPPLE FOR LIGHT SWITCH CONDUIT SEE LM SWITCH NOTE ABOVE
1" LIQUIDTIGHT STRAIGHT FLEX CONNECTOR
1" LIQUIDTIGHT FLEX CONDUIT
1" LIQUIDTIGHT STRAIGHT CONNECTOR 2" TO 1" PVC REDUCER 2" PVC FEMALE ADAPTER 2" RGS TO PVC COUPLING 2" PVC CONDUIT 2" PVC TO RGS COUPLING 2" RGS 90 DEG. ELBOW, 24" RADIUS NUMBER OF LIGHTS MAY VARY nVENT ERICO DYNASPHERE
PRELIMINARY
NOT FOR
CONSTRUCTION
REPLACE WITH ENGINEERS STAMP AT CONSTRUCTION AND/OR FABRICATION App’d Ch’k’d Description Drawn Date Rev Date Drawing Number Scale at ANSI D Drawn Designed Title Client Checked Approved RevApex Clean Energy, Inc
310 4th St. NE, Suite 200
Charlottesville, VA 22902
Heritage Wind Farm
Collector Substation
Lightening Mast Details
HER-SUB-007
A
PRELIMINARY - NOT FOR CONSTRUCTION
CONTROL ENCLOSURE GENERAL LAYOUT
S
2'-0" 3'-8"S
5'-3" 49'-9" 55'-0" 16'-0" 41'-9" 16'-0" 3'-9" 4'-8" 3'-0" 4'-7" 10'-9" 5'-3" 6'-0" 2'-0" 27'-6" 5'-1" 5'-3" 6'-6"S
S
S
7'-0"HER-SUB-008
A
1. MANUFACTURER AND MODEL LISTED IS SUGGESTED AND MAY BE SUBSTITUTED WITH A PRODUCT OF EQUAL QUALITY AND MATERIAL. (THIS ONLY APPLIES TO ITEMS REFERENCING THIS NOTE.)
2. CABLE TRAY IS SET AT 8'-6" FROM FLOOR TO BOTTOM OF TRAY. 3. ALL CABLES TRAYS TO BE SET AT THE SAME HEIGHT.
4. VENDOR MAY USE MANUFACTURER AND MODEL THAT MEETS DESCRIPTION AND/OR SPECIFICATIONS.
5. VENDOR TO DETERMINE EXACT EQUIPMENT LAYOUT AND SUBMIT DETAIL LAYOUT FOR APPROVAL.
6. EQUIPMENT SHOWN SHALL BE PROVIDED AND INSTALLED BY OTHERS. INSTALLATION OF THIS EQUIPMENT WILL BE ACCOMPLISHED AFTER CONTROL HOUSE IS DELIVERED AND INSTALLED AT OWNER'S SUBSTATION.
7. VENDOR TO DETERMINE CORRECT SIZE (AIR HANDLING TONNAGE AND
HEATING CAPACITY) FOR GEOGRAPHIC LOCATION OF SUBSTATION AND SUPPLY APPROPRIATE UNITS.
8. 4"x4" WIREWAY TO BE INSTALLED AROUND ENTIRE ROOM PERIMETER (BOTH ROOMS) IN CORNER OF CEILING AND WALLS. WALL MOUNTED EQUIPMENT
(SWITCHES, RECEPTACLES, ETC) TO USE THIS WIREWAY AS MUCH AS POSSIBLE.
FOR CLARITY, WIREWAY NOT SHOWN ON DRAWING.
9. VENDOR TO WIRE ALL AVAILABLE BUILDING ALARMS TO ALARM CABINET. AT A MINIMUM THESE ARE: 2x HVAC TROUBLE, 2x INTRUSION, 2x BLDG HI/LO TEMP, 2x SMOKE DETECTOR AND 2x HYDROGEN DETECTION. VENDOR TO RUN SPARE EMPTY 1.5" CONDUIT TO WIREWAY FOR CUSTOMER USE.
10. SITE PERSONNEL TO RUN GENERATOR AND STATION SERVICE POWER CABLES TOGETHER AND PARTITIONED/SEPARATED FROM OTHER CABLES IN CABLE TRAY.
11. SATELLITE CLOCK / CELL PHONE ANTENNA LOCATION SHALL BE LOW AND
CLOSE TO CONTROL HOUSE ROOF ABOVE MAXIMUM SNOW ACCUMULATION AND
AWAY FROM MAINTENANCE ACTIVITIES. ANTENNA, CABLE AND SURGE ARRESTOR MOUNTING WILL BE COMPLETED BY ONSITE PERSONNEL.
12. VENDOR TO VERIFY SIZE FOR AIRFLOW REQUIRED FOR OPERATION OF BOTH EXHAUST FANS AT ONCE.