HUAWEI
ATP
BTS 2G
(BTS 3900 (Indoor/Outdoor)
PT. HUAWEI TECH INVESTMENT
PT. NATRINDO TELEPON SELULER
APPROVED BY :
APPROVED BY :
Name : Bruce Shelton
Name : Michael J. Bullough
ATP BTS 2G
BTS 3900 (Indoor / Outdoor)
SITE REGION
:
SITE
ID
:
SITE NAME
:
SITE LOCATION
:
BTS TYPE :
TABLE OF CONTENTS
1. Acceptance Testing
2. Acceptance Test Procedure
2.1 Installation
Checklist
2.1.1 Indoor
installation check list
2.1.2 Outdoor
installation check list
2.2 Environment Monitoring Functional Test
2.2.1 Basic
Shelter
Alarms
Monitoring Test
2.2.2
Function Test for Indoor BTS
2.2.3
Function Test for Outdoor BTS
2.3 BTS VSWR Test &
Power transmitting
2.3.1
Feeder System VSWR test result
2.3.2 Power
transmitting
2.4 BTS Commissioning Record
2.4.1 Call
Tests
2.4.2 Handover
Tests
2.4.3
24 Hours Stability Test
2.4.4
Alarm query test
2.5 Punch List Summary
2.6 Revision
History
1. Acceptance Testing
1.1
Acceptance testing shall be carried out by the Contractor. The Contractor shall
perform all tests required for commissioning and integration of the Equipment,
Software and/or Services, as per the latest approved Schedule 3.
2.1. Installation Checklist
2.1.1. Indoor Installation Checklist
SITE: SITE CONFIG: DATE:
Equipment overall condition
Procedure Pass Fail N/A Remark
1 Visually inspect the cabinets for any damage. 2 Check that the cabinet doors and locks operate
correctly. Remarks
Site Documentation
Procedure Pass Fail N/A Remark
3 Check that the equipment is installed according to the as plan site design package. 4 Check that the indoor cable ladder is installed
according to the as plan side design package (applicable for Indoor Equipment)
Remarks
Civil Works Check
Procedure Pass Fail N/A Remark
5 Check that the cabinets have been securely fastened and are levelled correctly. 6 Check that indoor cable ladder above the cabinet has been installed correctly (applicable for Indoor
Equipment).
7 Check that the DDF are grounded to the main grounding bus bar.
Remarks
Equipment Specific Checks
Procedure Pass Fail N/A Remark
8 Check that all equipment internal cables are correctly installed and labelled.
9 Check that the cabinet blanking panels have been installed.
Cabinet External Cabling Check
Procedure Pass Fail N/A Remark
10 Check each the equipment rack is grounded to the main grounding bus bar and labelled. 11 Check that the Abis cables are connected to the correct position of DDF. 12 Check that the alarm cabling has been connected from the BTS to the DDF
13 Check that the support cabinet cables are correctly connected and labelled.
14 Check that the feeder jumper cables are tightened all the BTS. 15 Check that the support cabinet cabling has been cable tied to the cable ladder. 16 Check that the indoor feeder cable labelling is
correct.
17 Check that the DC power cable is the correct size and is terminated correctly. 18 Check the transmission cables, DC Cables and
feeder jumpers are be correctly labelled 19 Check that support equipment is installed
correctly. Remarks
Final Checks
Procedure Pass Fail N/A Remark
20 Check that all installation and packing materials have been removed from the site.
2.1.2. Outdoor Installation Checklist
SITE: SITE CONFIG: DATE:
Antennas
Procedure Pass Fail N/A Remark
21 Visually inspect the antennas and feeders for any installation damage.
22 Check that the correct type of antenna has been installed. Remarks
Feeders
Procedure Pass Fail N/A Remark
23 Check that the bending radius of all feeders is greater than 20 x Ǿ and all feeder clamps are tightened
24 Check that outdoor feeder labelling is correct at the top and the bottom of the tower.
25 Check that the top feeder grounding is correctly terminated.
Remarks
Connectors
Procedure Pass Fail N/A Remark
26 Check that all top feeder connectors are tight. 27 Check that all top feeders to jumper
connections are tight.
28 Check that all top jumpers to antenna connections are tight.
Weather sealing
Procedure Pass Fail N/A Remark
29 Check all top grounding kits are weather-sealed correctly. 30 Check all feeders to jumper connections are weather-sealed correctly. 31 Check all jumpers to antenna connections are weather-sealed correctly.
Remarks
Antenna Steelwork
Procedure Pass Fail N/A Remark
32 Check that the antenna supporting steelwork is correctly installed.
33 Check all antenna mounting clamps and brackets have been tightened.
Remarks
Antenna Installation Check
Procedure Pass Fail N/A Remark
34 Check that the antennas are mounted at the correct height.
35 Check that the direction of all antennas in all sectors is correct.
Antenna Installation Date
Sector
Sector 1
Sector 2
Sector 3
Antenna DFRU11
RXD12
DFRU21
RXD22
DFRU31
RXD32Height M
M
M
M
M
M
Direction
Deg
Deg
Deg
Deg
Deg
Deg
Down tilt M/E
/ Deg
/ Deg
/ Deg
Remarks
Outdoor Site Documentation
Procedure Pass Fail N/A Remark
36 Check that the antenna layout is according to the site drawing. 37 Check that the feeder cable ladder is installed as per the site drawing. 38 Check that the feeder gland plate is installed as per the site drawing (applicable for Indoor
Equipment) Remarks
SITE: SITE CONFIG: DATE:
Civil Works Inspection
Procedure Pass Fail N/A Remark
39 Check that the feeder cable ladder is correctly installed
40 Check that the feeder grand plate has been correctly installed (applicable for Indoor Equipment).
Remarks
Feeder Grounding
Procedure Pass Fail N/A Remark
41 Check number/location of feeder grounding kits. 42 Check all grounding is correctly terminated
43 Check all grounding kits are weather sealed correctly.
Remarks
Concluding Checks
Procedure Pass Fail N/A Remark
44 Check that all installation and packing materials have been removed from the site.
Remarks Notes:
2.2 Environment Monitoring Functional Test
2.2.1 Basic Shelter Alarms Monitoring Functional Test for BTS 3900
SITE: DATE:
NO Basic Shelter alarm test( only for the indoor BTS) Pass Fail Remark Audit
1 Fire alarm [BSC ID No 65384]
2 Door Open alarm [BSC ID No 65385]
3 High temperature alarm [BSC ID No 65386] 4 Spare [BSC ID No 65387] 5 AC Removal alarm [BSC ID No 65388] 6 Genset run [BSC ID No 65389] 7 Genset failure [BSC ID No 65390] 8 Genset low fuel [BSC ID No 65391] 9 Phase R failure alarm [BSC ID No 65392] 10 Phase S failure alarm [BSC ID No 65393] 11 Phase T Failure alarm [BSC ID No 65394] 12 Arrester Failure alarm [BSC ID No 65395] 13 Rectifier Module alarm [BSC ID No 65396] 14 Rectifier High voltage alarm [BSC ID No 65397] 15 Rectifier Low voltage alarm [BSC ID No 65398]
16 OBL Failure alarm [BSC ID No 65399]
* Remark: Alarm test is tested end to end to verify correct operation from sensor to OMC message
2.2.2 Function Test for Indoor BTS
SITE:
SITE CONFIG:
DATE:
No. Huawei
Procedure
Test Description Pass Fail Remark Audit
1 T01-0101 Power-On Test
2 T01-0201 Fan check
3 T01-0202 Board Indicators check
4 T01-0301 Transmission Test
5 T02-0101 Logging In to the Site Maintenance Terminal System
6 T02-0201 Board Software Loading
7 T02-0202 Board Software Activation
8 T02-0301 Site Reset Hierarchically
9 T02-0302 Cell Management State Changes
10 T02-0303 Cell Performance
11 T02-0401 BT Management State Change
12 T02-0402 BT Test
13 T02-0403 Viewing Channel State
14 T02-0501 RC Attribute Management
15 T02-0502 Changing RC Management State
16 T02-0601 Board Operation
17 T02-0602 Board Loopback Test
18 T02-0603 Board Alarm
19 T03-0101 Switching On an MS
2.2.3 Function Test for Outdoor BTS
SITE:
SITE CONFIG:
DATE:
No.
Huawei
Procedure
Test Description
Pass
Fail
Remark
Audit
1 T01-0101 Power-On
Test
2
T01-0102
Charging and Discharging of Storage
Batteries
3
T01-0201
Board Indicators check
4
T01-0202
Running Status of the DPMU
4 T01-0301 Transmission
Test
5
T02-0101
Logging In to the Site Maintenance
Terminal System
6
T02-0201
Board Software Loading
7
T02-0202
Board Software Activation
8
T02-0301
Site Reset Hierarchically
9
T02-0302
Cell Management State Changes
10 T02-0303 Cell
Performance
11 T02-0401
BT Management State Change
12 T02-0402 BT
Test
13 T02-0403 Viewing
Channel
State
14 T02-0501 RC
Attribute
Management
15 T02-0502
Changing RC Management State
16 T02-0601 Board
Operation
17 T02-0602
Board Loopback Test
18 T02-0603 Board
Alarm
19 T03-0101
Switching On an MS
20 T03-0102 Calls
21 T03-0103 Basic
Data
Services
23 T03-0201
Door Status Alarm
24 T03-0202 Water
Alarm
25 T03-0203 Smoke
Alarm
26 T03-0204 Power Supply Failure
27 T04-0101 VSWR of the Antenna System
28 T04-0102 DTF
Test
2.3. BTS VSWR Test & Power transmitting power
2.3.1 Feeder
system
VSWR test result
SITE: SITE CONFIG: D AT E :
V S W R a n d R e t u r n L o s s No. Cell Feeder
VSWR Feeder Length(m) Distance To Fault (DTF) Return Loss (dB) Audit 1 Cell 1 RXD12 TRX11 2 Cell 2 RXD22 TRX 21 3 Cell 3 RXD32 TRX 31 Notes:
1. VSWR value shall be refer to the specification manual from the supplier
2. Setting at site master for cable 7/8" (vf and cable loss shall be refer to the specification manual from supplier)
3. Setting at site master for cable 1-5/8" (vf and cable loss shall be refer to the specification manual from supplier)
4. VSWR < 1.3
5. DTF test will be carried out according to the test procedure and test result included in the test documentation.
2.3.2 Power transmitting
DRFU Transmitting Power Test as per T04-0103
DFRU Power level
No. ARFCN (dBm) W dBm DRFU0 Cell 1 DRFU1 DRFU2 Cell 2 DRFU3 DRFU4 Cell 3 DRFU5 * BTS3900 is 40W TX power
2.4 BTS Commissioning Record
2.4.1. Call Tests
DFRU TS0 TS1 TS2 TS3 TS4 TS5 TS6 TS7 Audit NO. DFRU 0 BCCH SDDCH CELL0 DFRU 1 DFRU 2 BCCH SDDCH CELL1 DFRU 3 DFRU 4 BCCH SDDCH CELL2 DFRU 52.4.2 Handover
Tests
Call Test Target Cell Origin Cell Target Cell BCCH BSICPass Fail Remark Audit
CELL2 CELL1 CELL3 CELL1 CELL2 CELL3 CELL1 CELL3 CELL2
2.4.3 24
Hours Stability Test
Site ID:
The purpose of this test is to confirm that the BTS 2G is able to run for 24 hours without any faults.
RESULT: Date:
Remark :
Notes: The 24 hours is to be monitored from the TOC/NOC, and will be passed if BTS is in normal operation with no alarms.
2.5 Punch List Summary
Site ID:
Note:
Record any items which do not pass the test, or cannot be tested, together with a detailed description..