• No results found

Box and Conduit Fill Calculations

N/A
N/A
Protected

Academic year: 2021

Share "Box and Conduit Fill Calculations"

Copied!
32
0
0

Loading.... (view fulltext now)

Full text

(1)

Box & conduit Fill Calculations

Box and

Box and

Conduit Fill

Conduit Fill

Calculations

Calculations

(2)
(3)

Box & conduit Fill Calculations

Volume required per

(4)
(5)
(6)

Box & conduit Fill Calculations

Conduit fill - Box sizing

Table 314.16(a) : Number of conductors in box 600v, nominal or less

CONDUCTORS:

1. Conductors originating outside box, terminating in box count as 1 conductor

2. Conductors originating outside box, spliced in box counts as 1 conductor

3. A conductor entering a box, spliced to a conductor leaving box counts as 2 conductors

4. Conductors passing through box without splices or terminations count as 1 conductor

(7)

Box & conduit Fill Calculations

Conduit fill - Box sizing

2005 NEC Change

Looped conductors now count as 2

conductors

(8)

Box & conduit Fill Calculations

EQUIPMENT GROUNDING CONDUCTOR:

1. One, two or more bare, insulated or covered system

grounding conductors all count the same size, count as 1

conductor

2. One, two or more bare, insulated or covered system grounding conductors of various sizes, count as one conductor based upon largest equipment grounding conductor

3. A separate ‘ISOLATED’ equipment grounding conductor counts as 1 conductor in addition to system grounding conductor. Count as size of ‘ISOLATED’ grounding conductor or largest if various sizes.

(9)

Box & conduit Fill Calculations

CLAMPS:

1. Clamps installed inside box by factory count as 1 conductor

2. Clamps installed in box in the field count as 1 conductor (Conductor size based on largest conductor in box)

SUPPORT FITTINGS:

1. Fixture studs count as 1 conductor 2. Fixture hickeys count as 1 conductor

(10)

Box & conduit Fill Calculations

DEVICE(S) IN BOX:

1. Yoke or strap with switch, counts as 2 conductors 2. Yoke or strap with duplex receptacle counts as 2

conductors

3. Yoke or strap with triplex receptacle counts as 2 conductors

4. Yoke or strap with switch & light on same yoke or strap counts as 2 conductors

5. Yoke with any combination of three devices on same yoke or strap counts as 2 conductors

(Conductor size based on LARGEST conductor connected to device or equipment)

(11)

Box & conduit Fill Calculations

Yoke or Strap

(12)

Box & conduit Fill Calculations

Conductor Counts for other than wire

Conductor Counts for other than wire

Cable Clamps Fixture Stud Hickey NM 12-2 W/GRD

Fixture Stud = 1 Conductor Hickey = 1 Conductor Cable Clamps (2) = 1 Conductor Total Conductor Count = 3 Conductors

(13)

Box & conduit Fill Calculations

Counting Devices

Counting Devices

1 Yoke 1 Device 1 Conductor 1 Yoke 1 Device 1 Conductor 1 Yoke 2 Devices 1 Conductor 1 Yoke 3 Devices 1 Conductor
(14)

Box & conduit Fill Calculations Through Box Terminate in Box All Conductors Terminate in Box Count 6 total Through Box 2 Terminate in Box 4

(15)

Box & conduit Fill Calculations

Factory installed clamps

Factory installed clamps

8

8

-

-

12

12

s & 1 clamp = 9

s & 1 clamp = 9

Factory or Field Installed Clamps

(16)

Box & conduit Fill Calculations

EGC

EGC = Equipment Grounding Conductor

IEGC = Insolated Equipment Grounding Conductor BJ = Bonding Jumper BJ IEGC EGC = 1 IEGC = 2 BJ = 0 Total = 2

(17)

Box & conduit Fill Calculations Octagonal / 4/0 Box 2 - #8 AWG 2 - #12 AWG 2 - #12 AWG

2 - #8 @3.00 Cu = 6 Cu in

Fix Stud @3.00 Cu in = 3 Cu in

4 - #12 @2.25 Cu in = 9 Cu in

Total = 18 Cu in

(18)

Box & conduit Fill Calculations

#14 Bare EGC

#8 AWG

#12 AWG

#18 AWG fixture wire #10 AWG #18 = 1.5 cu in x 2 = 3.00 cu in #14 = 2.0 cu in x 1 = 2.00 cu in #12 = 2.25 cu in x 4 = 9.00 cu in #10 = 2.50 cu in x 2 = 5.00 cu in #8 = 3.00 cu in x 2 = 6.00 cu in Fix Stud = #8 = 3.00 cu in = 3.00 cu in

(19)

Box & conduit Fill Calculations

Bad Planning

(20)

Box & conduit Fill Calculations

314.16(b)(1) Exception

314.16(b)(1) Exception

Canopy Cover

Canopy Cover

EGC Terminations in Canopy Cover To Fan To Fixture

4 - Smaller than #14 Fixture wires

(21)

Box & conduit Fill Calculations

Counting with a device

Counting with a device

2 - #8 AWG 2 - #12 AWG 2 - #12 AWG

2 - #8 @3.00 cu in = 6 cu in

4 - #12 @2.25 cu in = 9 cu in

Yoke @2.25 cu in = 4.5 cu in

Total Volume Required = 19.5 cu in

Largest conductor allowed = #10 NEC 110.14(A)

(22)

Box & conduit Fill Calculations

Conduit Fill

Calculations

(23)

Box & conduit Fill Calculations

Major Fraction Change

(24)

Box & conduit Fill Calculations

What size EMT is needed for 3 - 2/0 AWG THW Cu

conductors and 4 - 4/0 AWG THHN Cu conductors ?

(25)

Box & conduit Fill Calculations

Table 5 – Cross-Sectional Area of Individual Conductors

2/0 AWG THW Cu = .2624 X 3 = .7872 4/0 AWG THHN Cu = .3237 X 4 = 1.2984 Total Square Inches for Conductors = 2.0820

Table 4 – 40% fill column for “Over 2 wires”.

2.0820 Sq.In. Requires a 2 ½ inch EMT Conduit 40% fill for 2 ½ inch EMT = 2.343 Sq. In.

Answer = 2 ½ Inch EMT

What size EMT is needed for 3 - 2/0 AWG THW Cu

conductors and 4 - 4/0 AWG THHN Cu conductors ?

(26)

Box & conduit Fill Calculations

What size IMC is required for 6 - 12 AWG RHH Cu

conductors without outer covering and 4 -14 AWG

(27)

Box & conduit Fill Calculations

What size IMC is required for 6 - 12 AWG RHH Cu

conductors without outer covering and 4 -14 AWG

RHH Cu Conductors with outer covering ?

Table 5 – Cross-Sectional Area of Individual Conductors

14 AWG RHH Cu With Outer Covering = .0293 X 4 = .1172 12 AWG RHH Cu Without Outer Covering = .0260 X 6 = .1560 Total Square Inches for Conductors = .2732

Table 4 – 40% fill column for “Over 2 wires”.

.2732 Sq.In. Requires a 1 inch IMC Conduit 40% fill for 1 inch IMC = .384 Sq. In.

(28)

Box & conduit Fill Calculations

Box & Conduit Fill Exam

Box & Conduit Fill Exam

10 Questions

10 Questions

30 Minutes

(29)

Box & conduit Fill Calculations

Box fill Answers

Box fill Answers

1. (b) 10.75 cu in 314.16(b) 3 - #12’s @ 2.25 cu in = 6.75 cu in 2 - #14’s @ 2.00 cu in = 4.00 cu in 10.75 cu in 2. (b) 2 conductors 314.16 (b) 3. (b) 4 Table 314.16(a) 4. (d) 17.5 cu in Table 314.16(b) #10 = 2.5 cu in 7 - #10’s x 2.5 cu in = 17.5 cu in

5. (a) 0.0181 in2 Table 5 (note * notations by insulations)

(30)

Box & conduit Fill Calculations 6. (d) 39.75 cu in Table 314.16(b) #8 = 3.00 cu in #12 = 2.25 cu in Clamps - #8 = 3.00 cu in 7 - #8 @ 3.00 cu in = 21.00 cu in 1 - #8 @ 3.00 cu in = 3.00 cu in 7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in

Box fill Answers

(31)

Box & conduit Fill Calculations

3 - #8 ungrounded conductors count as 3 {314.16(b)(1)} 3 - #8 grounded conductors count as 3 {314.16(b)(1)} 3 - #8 grounding conductors count as 1 {314.16(b)(5)}

4 - clamps count as 1 {314.16(b)(2)}

3 - #12 ungrounded conductors count as 3 {314.16(b)(1)} 3 - #12 grounded conductors count as 3 {314.16(b)(1)} 3 - #12 grounding conductors count as 1 {314.16(b)(5)}

#8 conductors 7 - #8 @ 3.00 cu in = 21.00 cu in Clamps 1 - #8 @ 3.00 cu in = 3.00 cu in #12 conductors 7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in

(32)

Box & conduit Fill Calculations

7. (b) 2.2831 in² T.5

8. (b) 1 1/4” IMC T.4

9. (a) .384in² T.4

References

Related documents

Conductors used as grid conductors, grounding electrode conductors, equipment ground conductors, or bonding conductors in grounding systems shall:.. - Be soft or

Metal Water Service Pipe: Provide insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service

Exercise 1.3: Sketching using Rectangle and Circle (5 minutes) Create this sketch on the Front Plane using rectangle and circle, automatic relations and dimensions.. Exercise

our approach to the Holocaust, particularly its presentation as somehow a uniquely and exclusively 'Jewish' event. On the other hand, this insistence on the uniqueness of the

54 NEC 25032 Buildings supplied by a branch circuit or feeder shall have an equipment grounding conductor run with the supply conductors and connected to the

 Accordingly, waste management is to be done through following systems.  Minimum production of waste.  Maximizing reuse of waste and recycling.  Green accounting systems:

Masson’s trichrome staining of representative heart sections showed that 1) no fibrosis was observed in 6- month-old wild rats, 2) mild transmural fibrosis of RV free-wall and

Two to apply, evaluation service lsac warrants that service must be provided on topics including academic opportunities and instructions and documenting education.. Shifting