Box & conduit Fill Calculations
Box and
Box and
Conduit Fill
Conduit Fill
Calculations
Calculations
Box & conduit Fill Calculations
Volume required per
Box & conduit Fill Calculations
Conduit fill - Box sizing
Table 314.16(a) : Number of conductors in box 600v, nominal or less
CONDUCTORS:
1. Conductors originating outside box, terminating in box count as 1 conductor
2. Conductors originating outside box, spliced in box counts as 1 conductor
3. A conductor entering a box, spliced to a conductor leaving box counts as 2 conductors
4. Conductors passing through box without splices or terminations count as 1 conductor
Box & conduit Fill Calculations
Conduit fill - Box sizing
2005 NEC Change
Looped conductors now count as 2
conductors
Box & conduit Fill Calculations
EQUIPMENT GROUNDING CONDUCTOR:
1. One, two or more bare, insulated or covered system
grounding conductors all count the same size, count as 1
conductor
2. One, two or more bare, insulated or covered system grounding conductors of various sizes, count as one conductor based upon largest equipment grounding conductor
3. A separate ‘ISOLATED’ equipment grounding conductor counts as 1 conductor in addition to system grounding conductor. Count as size of ‘ISOLATED’ grounding conductor or largest if various sizes.
Box & conduit Fill Calculations
CLAMPS:
1. Clamps installed inside box by factory count as 1 conductor
2. Clamps installed in box in the field count as 1 conductor (Conductor size based on largest conductor in box)
SUPPORT FITTINGS:
1. Fixture studs count as 1 conductor 2. Fixture hickeys count as 1 conductor
Box & conduit Fill Calculations
DEVICE(S) IN BOX:
1. Yoke or strap with switch, counts as 2 conductors 2. Yoke or strap with duplex receptacle counts as 2
conductors
3. Yoke or strap with triplex receptacle counts as 2 conductors
4. Yoke or strap with switch & light on same yoke or strap counts as 2 conductors
5. Yoke with any combination of three devices on same yoke or strap counts as 2 conductors
(Conductor size based on LARGEST conductor connected to device or equipment)
Box & conduit Fill Calculations
Yoke or Strap
Box & conduit Fill Calculations
Conductor Counts for other than wire
Conductor Counts for other than wire
Cable Clamps Fixture Stud Hickey NM 12-2 W/GRD
Fixture Stud = 1 Conductor Hickey = 1 Conductor Cable Clamps (2) = 1 Conductor Total Conductor Count = 3 Conductors
Box & conduit Fill Calculations
Counting Devices
Counting Devices
1 Yoke 1 Device 1 Conductor 1 Yoke 1 Device 1 Conductor 1 Yoke 2 Devices 1 Conductor 1 Yoke 3 Devices 1 ConductorBox & conduit Fill Calculations Through Box Terminate in Box All Conductors Terminate in Box Count 6 total Through Box 2 Terminate in Box 4
Box & conduit Fill Calculations
Factory installed clamps
Factory installed clamps
8
8
-
-
12
12
’
’
s & 1 clamp = 9
s & 1 clamp = 9
Factory or Field Installed Clamps
Box & conduit Fill Calculations
EGC
EGC = Equipment Grounding Conductor
IEGC = Insolated Equipment Grounding Conductor BJ = Bonding Jumper BJ IEGC EGC = 1 IEGC = 2 BJ = 0 Total = 2
Box & conduit Fill Calculations Octagonal / 4/0 Box 2 - #8 AWG 2 - #12 AWG 2 - #12 AWG
2 - #8 @3.00 Cu = 6 Cu in
Fix Stud @3.00 Cu in = 3 Cu in
4 - #12 @2.25 Cu in = 9 Cu in
Total = 18 Cu in
Box & conduit Fill Calculations
#14 Bare EGC
#8 AWG
#12 AWG
#18 AWG fixture wire #10 AWG #18 = 1.5 cu in x 2 = 3.00 cu in #14 = 2.0 cu in x 1 = 2.00 cu in #12 = 2.25 cu in x 4 = 9.00 cu in #10 = 2.50 cu in x 2 = 5.00 cu in #8 = 3.00 cu in x 2 = 6.00 cu in Fix Stud = #8 = 3.00 cu in = 3.00 cu in
Box & conduit Fill Calculations
Bad Planning
Box & conduit Fill Calculations
314.16(b)(1) Exception
314.16(b)(1) Exception
Canopy Cover
Canopy Cover
EGC Terminations in Canopy Cover To Fan To Fixture4 - Smaller than #14 Fixture wires
Box & conduit Fill Calculations
Counting with a device
Counting with a device
2 - #8 AWG 2 - #12 AWG 2 - #12 AWG
2 - #8 @3.00 cu in = 6 cu in
4 - #12 @2.25 cu in = 9 cu in
Yoke @2.25 cu in = 4.5 cu in
Total Volume Required = 19.5 cu in
Largest conductor allowed = #10 NEC 110.14(A)
Box & conduit Fill Calculations
Conduit Fill
Calculations
Box & conduit Fill Calculations
Major Fraction Change
Box & conduit Fill Calculations
What size EMT is needed for 3 - 2/0 AWG THW Cu
conductors and 4 - 4/0 AWG THHN Cu conductors ?
Box & conduit Fill Calculations
Table 5 – Cross-Sectional Area of Individual Conductors
2/0 AWG THW Cu = .2624 X 3 = .7872 4/0 AWG THHN Cu = .3237 X 4 = 1.2984 Total Square Inches for Conductors = 2.0820
Table 4 – 40% fill column for “Over 2 wires”.
2.0820 Sq.In. Requires a 2 ½ inch EMT Conduit 40% fill for 2 ½ inch EMT = 2.343 Sq. In.
Answer = 2 ½ Inch EMT
What size EMT is needed for 3 - 2/0 AWG THW Cu
conductors and 4 - 4/0 AWG THHN Cu conductors ?
Box & conduit Fill Calculations
What size IMC is required for 6 - 12 AWG RHH Cu
conductors without outer covering and 4 -14 AWG
Box & conduit Fill Calculations
What size IMC is required for 6 - 12 AWG RHH Cu
conductors without outer covering and 4 -14 AWG
RHH Cu Conductors with outer covering ?
Table 5 – Cross-Sectional Area of Individual Conductors
14 AWG RHH Cu With Outer Covering = .0293 X 4 = .1172 12 AWG RHH Cu Without Outer Covering = .0260 X 6 = .1560 Total Square Inches for Conductors = .2732
Table 4 – 40% fill column for “Over 2 wires”.
.2732 Sq.In. Requires a 1 inch IMC Conduit 40% fill for 1 inch IMC = .384 Sq. In.
Box & conduit Fill Calculations
Box & Conduit Fill Exam
Box & Conduit Fill Exam
10 Questions
10 Questions
30 Minutes
Box & conduit Fill Calculations
Box fill Answers
Box fill Answers
1. (b) 10.75 cu in 314.16(b) 3 - #12’s @ 2.25 cu in = 6.75 cu in 2 - #14’s @ 2.00 cu in = 4.00 cu in 10.75 cu in 2. (b) 2 conductors 314.16 (b) 3. (b) 4 Table 314.16(a) 4. (d) 17.5 cu in Table 314.16(b) #10 = 2.5 cu in 7 - #10’s x 2.5 cu in = 17.5 cu in
5. (a) 0.0181 in2 Table 5 (note * notations by insulations)
Box & conduit Fill Calculations 6. (d) 39.75 cu in Table 314.16(b) #8 = 3.00 cu in #12 = 2.25 cu in Clamps - #8 = 3.00 cu in 7 - #8 @ 3.00 cu in = 21.00 cu in 1 - #8 @ 3.00 cu in = 3.00 cu in 7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in
Box fill Answers
Box & conduit Fill Calculations
3 - #8 ungrounded conductors count as 3 {314.16(b)(1)} 3 - #8 grounded conductors count as 3 {314.16(b)(1)} 3 - #8 grounding conductors count as 1 {314.16(b)(5)}
4 - clamps count as 1 {314.16(b)(2)}
3 - #12 ungrounded conductors count as 3 {314.16(b)(1)} 3 - #12 grounded conductors count as 3 {314.16(b)(1)} 3 - #12 grounding conductors count as 1 {314.16(b)(5)}
#8 conductors 7 - #8 @ 3.00 cu in = 21.00 cu in Clamps 1 - #8 @ 3.00 cu in = 3.00 cu in #12 conductors 7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in
Box & conduit Fill Calculations
7. (b) 2.2831 in² T.5
8. (b) 1 1/4” IMC T.4
9. (a) .384in² T.4