GYPSUM BOARD 092900 ‐ 1 SECTION 092900 ‐ GYPSUM BOARD PART 1 ‐ GENERAL 1.1 SUMMARY A. Section Includes: 1. Interior gypsum board. 2. Tile backing panels. 3. Non‐load bearing metal stud framing. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product. PART 2 ‐ PRODUCTS 2.1 PERFORMANCE REQUIREMENTS
A. Fire‐Resistance‐Rated Assemblies: For fire‐resistance‐rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 119 by an independent testing agency.
B. STC‐Rated Assemblies: For STC‐rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 90 and classified according to ASTM E 413 by an independent testing agency.
2.2 INTERIOR GYPSUM BOARD
A. Manufacturers: Subject to compliance with requirements, provide products by the following: 1. CertainTeed Corp. 2. Georgia‐Pacific Gypsum LLC. 3. Lafarge North America Inc. 4. National Gypsum Company. 5. USG Corporation.
1. Core: 5/8 inch (15.9 mm), Type X. 2. Long Edges: Tapered.
3. Mold Resistance: ASTM D 3273, score of 10 as rated according to ASTM D 3274.
2.3 TILE BACKING PANELS
A. Cementitious Backer Units: ANSI A118.9 and ASTM C 1288 or 1325, with manufacturer's standard edges.
1. Products: Subject to compliance with requirements, [provide the following] [provide one of the following] [available products that may be incorporated into the Work include, but are not limited to, the following]: a. CertainTeed Corp.; FiberCement BackerBoard. b. James Hardie Building Products, Inc.; Hardiebacker. c. National Gypsum Company, Permabase Cement Board. d. USG Corporation; DUROCK Cement Board. 2. Thickness: 5/8 inch. 3. Mold Resistance: ASTM D 3273, score of 10 as rated according to ASTM D 3274. 2.4 TRIM ACCESSORIES A. Interior Trim: ASTM C 1047.
1. Material: Galvanized or aluminum‐coated steel sheet, rolled zinc, plastic, or paper‐ faced galvanized steel sheet.
B. General: Comply with ASTM C 475/C 475M. C. Joint Tape:
1. Interior Gypsum Board: Paper.
2. Tile Backing Panels: As recommended by panel manufacturer.
D. Joint Compound for Interior Gypsum Board: For each coat use formulation that is compatible with other compounds applied on previous or for successive coats.
2.5 AUXILIARY MATERIALS
A. Steel Drill Screws: ASTM C 1002, unless otherwise indicated.
GYPSUM BOARD 092900 ‐ 3 C. Acoustical Joint Sealant: ASTM C 834. Product effectively reduces airborne sound transmission through perimeter joints and openings as demonstrated by testing according to ASTM E 90. D. Thermal Insulation: As specified in Section 072100 "Thermal Insulation." E. Vapor Retarder: As specified in Section 072100 "Thermal Insulation." 2.6 METAL STUD FRAMING SYSTEMS A. Steel Studs and Runners: ASTM C 645. 1. Minimum Base‐Metal Thickness: 0.027 inch 2. Depth: As indicated on Drawings
B. Slip‐Type Head Joints: Where indicated, provide one of the following in thickness not less than indicated for studs and in width to accommodate depth of studs:
1. Single Long‐Leg Runner System: ASTM C 645 top runner with 2‐inch‐ (51‐mm‐) deep flanges, installed with studs friction fit into top runner and with continuous bridging located within 12 inches (305 mm) of the top of studs to provide lateral bracing. 2. Double‐Runner System: ASTM C 645 top runners, inside runner with 2‐inch‐ (51‐mm‐)
deep flanges and fastened to studs, and outer runner sized to friction fit inside runner.
3. Deflection Track: Steel sheet top runner manufactured to prevent cracking of finishes due to deflection of structure above.
a. Products: Subject to compliance with requirements, provide one of the following 1) Dietrich Metal Framing; SLP‐TRK Slotted Deflection Track. 2) MBA Building Supplies; FlatSteel Deflection Track 3) Steel Network Inc. (The); VertiClip SLD Series. 4) Superior Metal Trim; Superior Flex Track System (SFT). 5) Telling Industries; Vertical Slip Track.
C. Firestop Tracks: Manufactured to allow partition heads to expand and contract with movement of the structure while maintaining continuity of fire‐resistance‐rated assembly indicated; in thickness not less than indicated for studs and in width to accommodate depth of studs.
1. Products: Subject to compliance with requirements, [provide the following] [provide one of the following] [available products that may be incorporated into the Work include, but are not limited to, the following]:
b. Grace Construction Products; FlameSafe FlowTrak System. c. Metal‐Lite, Inc.; The System. D. Hat‐Shaped, Rigid Furring Channels: ASTM C 645. 1. Minimum Base‐Metal Thickness: 0.033 inch 2. Depth: 1‐1/2 inches. 2.7 SUSPENSION SYSTEMS
A. Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.062‐inch‐ (1.59‐mm‐) diameter wire, or double strand of 0.048‐inch‐ (1.21‐mm‐) diameter wire.
B. Hanger Attachments to Concrete:
1. Anchors: Capable of sustaining a load equal to 5 times that imposed as determined by ASTM E 488.
2. Powder‐Actuated Fasteners: Capable of sustaining, a load equal to 10 times that imposed as determined by ASTM E 1190. C. Wire Hangers: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.16 inch (4.12 mm) in diameter. D. Carrying Channels: Cold‐rolled, commercial‐steel sheet with a base‐metal thickness of 0.053 inch (1.34 mm) and minimum 1/2‐inch‐ (13‐mm‐) wide flanges. E. Furring Channels (Furring Members):
1. Cold‐Rolled Channels: 0.053‐inch (1.34‐mm) uncoated‐steel thickness, with minimum 1/2‐inch‐ (13‐mm‐) wide flanges, 3/4 inch (19 mm) deep.
2. Steel Studs and Runners: ASTM C 645.[ Use either steel studs and runners or dimpled steel studs and runners of equivalent minimum base‐metal thickness.]
3. Hat‐Shaped, Rigid Furring Channels: ASTM C 645, 7/8 inch (22 mm) deep.
4. Resilient Furring Channels: 1/2‐inch‐ (13‐mm‐) deep members designed to reduce sound transmission.
2.8 AUXILIARY MATERIALS
GYPSUM BOARD 092900 ‐ 5 PART 3 ‐ EXECUTION
3.1 APPLYING AND FINISHING PANELS A. Comply with ASTM C 840.
B. Examine panels before installation. Reject panels that are wet, moisture damaged, and mold damaged.
C. Isolate perimeter of gypsum board applied to non‐load‐bearing partitions at structural abutments, except floors. Provide 1/4‐ to 1/2‐inch‐ (6.4‐ to 12.7‐mm‐) wide spaces at these locations and trim edges with edge trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces with acoustical sealant. D. Install trim with back flanges intended for fasteners, attach to framing with same fasteners used for panels. Otherwise, attach trim according to manufacturer's written instructions. 1. Control Joints: Install control joints according to ASTM C 840 and in specific locations approved by Architect for visual effect. E. Prefill open joints and damaged surface areas. F. Apply joint tape over gypsum board joints, except for trim products specifically indicated as not intended to receive tape.
G. Gypsum Board Finish Levels: Finish panels to levels indicated below and according to ASTM C 840:
1. Level 2: Panels that are substrate for tile.
2. Level 4: At panel surfaces that will be exposed to view.
a. Primer and its application to surfaces are specified in Section 099123 "Interior Painting."
3. Gypsum Veneer Plaster Assemblies: Also comply with requirements in ASTM C 844 that apply to framing installation. 4. Gypsum Board Assemblies: Also comply with requirements in ASTM C 840 that apply to framing installation. B. Install supplementary framing, and blocking to support fixtures, equipment services, heavy trim, grab bars, toilet accessories, furnishings, or similar construction. C. Install bracing at terminations in assemblies.
D. Do not bridge building control and expansion joints with non‐load‐bearing steel framing members. Frame both sides of joints independently.
3.3 INSTALLING FRAMED ASSEMBLIES
A. Install framing system components according to spacings indicated, but not greater than spacings required by referenced installation standards for assembly types.
B. Where studs are installed directly against exterior masonry walls or dissimilar metals at exterior walls, install isolation strip between studs and exterior wall.
C. Install studs so flanges within framing system point in same direction.
D. Install tracks (runners) at floors and overhead supports. Extend framing full height to structural supports or substrates above suspended ceilings, except where partitions are indicated to terminate at suspended ceilings. Continue framing around ducts penetrating partitions above ceiling.
1. Slip‐Type Head Joints: Where framing extends to overhead structural supports, install to produce joints at tops of framing systems that prevent axial loading of finished assemblies.
2. Door Openings: Screw vertical studs at jambs to jamb anchor clips on door frames; install runner track section (for cripple studs) at head and secure to jamb studs. a. Install two studs at each jamb unless otherwise indicated.
b. Install cripple studs at head adjacent to each jamb stud, with a minimum 1/2‐ inch (13‐mm) clearance from jamb stud to allow for installation of control joint in finished assembly.
c. Extend jamb studs through suspended ceilings and attach to underside of overhead structure.
GYPSUM BOARD 092900 ‐ 7 4. Fire‐Resistance‐Rated Partitions: Install framing to comply with fire‐resistance‐rated assembly indicated and support closures and to make partitions continuous from floor to underside of solid structure.
a. Firestop Track: Where indicated, install to maintain continuity of fire‐resistance‐ rated assembly indicated.
5. Sound‐Rated Partitions: Install framing to comply with sound‐rated assembly indicated.
6. Curved Partitions:
a. Bend track to uniform curve and locate straight lengths so they are tangent to arcs.
b. Begin and end each arc with a stud, and space intermediate studs equally along arcs. On straight lengths of no fewer than two studs at ends of arcs, place studs 6 inches (150 mm) o.c.
E. Direct Furring:
1. Screw to wood framing.
2. Attach to concrete or masonry with stub nails, screws designed for masonry attachment, or powder‐driven fasteners spaced 24 inches (610 mm) o.c. F. Z‐Furring Members: 1. Erect insulation vertically and hold in place with Z‐furring members spaced [24 inches (610 mm)] [600 mm] o.c. 2. Except at exterior corners, securely attach narrow flanges of furring members to wall with concrete stub nails, screws designed for masonry attachment, or powder‐driven fasteners spaced 24 inches (610 mm) o.c. 3. At exterior corners, attach wide flange of furring members to wall with short flange extending beyond corner; on adjacent wall surface, screw‐attach short flange of furring channel to web of attached channel. At interior corners, space second member no more than 12 inches (305 mm) from corner and cut insulation to fit. G. Installation Tolerance: Install each framing member so fastening surfaces vary not more
than 1/8 inch (3 mm) from the plane formed by faces of adjacent framing.
3.4 INSTALLING SUSPENSION SYSTEMS
A. Install suspension system components according to spacings indicated, but not greater than spacings required by referenced installation standards for assembly types.
C. Suspend hangers from building structure as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structural or suspension system. a. Splay hangers only where required to miss obstructions and offset resulting
horizontal forces by bracing, countersplaying, or other equally effective means. 2. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with locations of hangers, install supplemental suspension members and hangers in the form of trapezes or equivalent devices.
3. Do not attach hangers to steel roof deck.
CERAMIC TILING 093013 - 1 SECTION 093013 - CERAMIC TILING
1.1 SUMMARY
A. Section Includes: 1. Quarry tile.
2. Porcelain wall and floor tile. 3. Tile backing panels at flooring. 4. Waterproof membrane. 5. Metal edge strips. 1.2 ACTION SUBMITTALS
A. Product Data: For each type of product. B. Samples:
1. Each type and composition of tile and for each color and finish required.
2. Assembled samples mounted on a rigid panel, with grouted joints, for each type and composition of tile and for each color and finish required.
1.3 INFORMATIONAL SUBMITTALS A. Qualification Data: For Installer. 1.4 EXTRA MATERIALS / ATTIC STOCK
A. Furnish extra materials that match and are from same production runs as products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Tile and Trim Units: Furnish quantity of full-size units equal to 3 percent of amount installed for each type, composition, color, pattern, and size indicated.
PART 2 - PRODUCTS
2.1 PRODUCTS, GENERAL
B. ANSI Standards for Tile Installation Materials: Provide materials complying with ANSI A108.02, ANSI standards referenced in other Part 2 articles, ANSI standards referenced by TCNA installation methods specified in tile installation schedules, and other requirements specified.
2.2 TILE PRODUCTS
A. Ceramic Tile Type [T-3]: Unglazed square-edged quarry tile.
1. Manufacturers: Subject to compliance with requirements, provide products by the following:
a. Dal-Tile Corporation. 2. Product: Quarry Textures. 3. Face Size: 8 by 8 inches. 4. Thickness: 1/2 inch.
5. Wearing Surface: Nonabrasive, smooth.
6. Dynamic Coefficient of Friction: Not less than 0.42.
7. Tile Color and Pattern: As selected by Architect from manufacturer's full range. 8. Grout Color: As selected by Architect from manufacturer's full range.
9. Trim Units: Coordinated with sizes and coursing of adjoining flat tile where applicable and matching characteristics of adjoining flat tile. Provide shapes as follows, selected from manufacturer's standard shapes:
a. Base: Coved with surface bullnose top edge, face size 8 by 5 inches. B. Ceramic Tile Type [T-1 and T-2]: Porcelain wall and floor tile.
1. Manufacturers: Subject to compliance with requirements, provide products by the following:
a. Dal-Tile Corporation. 2. Product: Veranda Solids
3. Face Size: 6-1/2 inches X 20 inches (nominal) 4. Thickness: 3/8 inch.
5. Dynamic Coefficient of Friction: Not less than 0.60.
6. Tile Color, Glaze, and Pattern: As indicated on Drawings; different colors for wall and floor tile.
7. Grout Color: As selected by Architect from manufacturer's full range.
CERAMIC TILING 093013 - 3
2.3 THRESHOLDS
A. General: Fabricate to sizes and profiles indicated or required to provide transition between adjacent floor finishes.
1. Bevel edges at 1:2 slope, with lower edge of bevel aligned with or up to 1/16 inch (1.5 mm) above adjacent floor surface. Finish bevel to match top surface of threshold. Limit height of threshold to 1/2 inch (12.7 mm) or less above adjacent floor surface.
2.4 TILE BACKING PANELS
A. Cementitious Backer Units (at wall tile): See Section 092900 – Gypsum Board. B. Fiber-Cement Backer Board (at floor tile): ASTM C 1288.
1. Products: Subject to compliance with requirements, provide the following: a. James Hardie Building Products, Inc.; Hardiebacker 1/4"
2. Thickness: 1/4 inch.
2.5 WATERPROOF MEMBRANE
A. General: Manufacturer's standard product[, selected from the following,] that complies with ANSI A118.10 and is recommended by the manufacturer for the application indicated. Include reinforcement and accessories recommended by manufacturer.
B. Fabric-Reinforced, Modified-Bituminous Sheet: Self-adhering, SBS-modified-bituminous sheet with fabric reinforcement facing; 0.040-inch (1 -mm) nominal thickness.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Boiardi Products Corporation, a QEP company; Elastiment 340 Sound Control Sheet Membrane Waterproofing and Anti-Fracture/Crack Suppression System. b. National Applied Construction Products, Inc.; Strataflex.
2.6 SETTING MATERIALS
A. Latex-Portland Cement Mortar (Thinset): ANSI A118.4.
1. Manufacturers: Subject to compliance with requirements, provide products by the following:
c. Bostik, Inc.
d. Custom Building Products. e. Laticrete International, Inc. f. MAPEI Corporation.
g. TEC; H. B. Fuller Construction Products Inc.
2. Provide prepackaged, dry-mortar mix combined with liquid-latex additive at Project site.
3. For wall applications, provide non-sagging mortar. 2.7 GROUT MATERIALS
A. Water-Cleanable Epoxy Grout: ANSI A118.3.
1. Manufacturers: Subject to compliance with requirements, provide products by the following:
a. Bostik, Inc.
b. Custom Building Products. c. Laticrete International, Inc. d. MAPEI Corporation.
e. TEC; H. B. Fuller Construction Products Inc. 2.8 MISCELLANEOUS MATERIALS
A. Trowelable Underlayments and Patching Compounds: Latex-modified, portland cement-based formulation provided or approved by manufacturer of tile-setting materials for installations indicated.
B. Metal Edge Strips: Angle or L-shape, height to match tile and setting-bed thickness, metallic or combination of metal and PVC or neoprene base, designed specifically for flooring applications; stainless-steel, ASTM A 666, 300 Series exposed-edge material.
1. Manufacturers: Subject to compliance with requirements, [provide products by the following:
a. Schluter Systems L.P.
C. Grout Sealer: Manufacturer's standard product for sealing grout joints and that does not change color or appearance of grout.
1. Products: Subject to compliance with requirements, provide one of the following: a. Custom Building Products; Surfaceguard Sealer.
CERAMIC TILING 093013 - 5 PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions where tile will be installed, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
1. Verify that substrates for setting tile are firm; dry; clean; free of coatings that are incompatible with tile-setting materials, including curing compounds and other substances that contain soap, wax, oil, or silicone; and comply with flatness tolerances required by ANSI A108.01 for installations indicated.
2. Verify that substrates for tile floors installed with thinset mortar comply with surface finish requirements for installations indicated.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Fill cracks, holes, and depressions in concrete substrates for tile floors installed with thinset mortar with trowelable leveling and patching compound specifically recommended by tile-setting material manufacturer.
B. Where indicated, prepare substrates to receive waterproofing by applying a reinforced mortar bed that complies with ANSI A108.1A and is sloped 1/4 inch per foot (1:50) toward drains.
C. Blending: For tile exhibiting color variations, verify that tile has been factory blended and packaged so tile units taken from one package show same range of colors as those taken from other packages and match approved Samples. If not factory blended, either return to manufacturer or blend tiles at Project site before installing.
3.3 CERAMIC TILE INSTALLATION
A. Comply with TCNA's "Handbook for Ceramic, Glass, and Stone Tile Installation" for TCNA installation methods specified in tile installation schedules. Comply with parts of the ANSI A108 series "Specifications for Installation of Ceramic Tile" that are referenced in TCNA installation methods, specified in tile installation schedules, and apply to types of setting and grouting materials used.
1. For the following installations, follow procedures in the ANSI A108 series of tile installation standards for providing 95 percent mortar coverage:
B. Extend tile work into recesses and under or behind equipment and fixtures to form complete covering without interruptions unless otherwise indicated. Terminate work neatly at obstructions, edges, and corners without disrupting pattern or joint alignments.
C. Accurately form intersections and returns. Perform cutting and drilling of tile without marring visible surfaces. Carefully grind cut edges of tile abutting trim, finish, or built-in items for straight aligned joints. Fit tile closely to electrical outlets, piping, fixtures, and other penetrations so plates, collars, or covers overlap tile.
D. Provide manufacturer's standard trim shapes where necessary to eliminate exposed tile edges.
E. Where accent tile differs in thickness from field tile, vary setting bed thickness so that tiles are flush.
F. Jointing Pattern: Lay tile in grid pattern unless otherwise indicated on elevation drawings. Lay out tile work and center tile fields in both directions in each space or on each wall area. Lay out tile work to minimize the use of pieces that are less than half of a tile. Provide uniform joint widths unless otherwise indicated.
G. Joint Widths: Unless otherwise indicated, install tile with the following joint widths: 1. Quarry Tile: 3/8 inch.
2. Porcelain Tile: 3/16 inch.
H. Lay out tile wainscots to dimensions indicated or to next full tile beyond dimensions indicated.
I. Expansion Joints: Provide expansion joints and other sealant-filled joints, including control, contraction, and isolation joints, where indicated. Form joints during installation of setting materials, mortar beds, and tile. Do not saw-cut joints after installing tiles.
1. Where joints occur in concrete substrates, locate joints in tile surfaces directly above them.
J. Metal Edge Strips: Install at locations indicated or where exposed edge of tile flooring meets carpet, wood, or other flooring that finishes flush with or below top of tile and no threshold is indicated.
K. Grout Sealer: Apply grout sealer to grout joints in tile floors according to grout-sealer manufacturer's written instructions. As soon as grout sealer has penetrated grout joints, remove excess sealer and sealer from tile faces by wiping with soft cloth.
ACOUSTICAL TILE CEILINGS 095123 - 1 SECTION 095123 - ACOUSTICAL TILE CEILINGS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes acoustical tiles and concealed suspension systems for ceilings. 1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples: For each exposed product and for each color and texture specified. 1.3 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.4 EXTRA MATERIALS/ATTIC STOCK
A. Provide at least ten extra tiles of each type and size specified. PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Seismic Performance: Acoustical ceiling shall withstand the effects of earthquake motions determined according to ASCE/SEI 7.
B. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials. 2. Smoke-Developed Index: 450 or less.
2.2 ACOUSTICAL TILE CEILINGS, GENERAL
A. Acoustical Tile Standard: Comply with ASTM E 1264.
C. Attachment Devices: Size for five times the design load indicated in ASTM C 635, Table 1, "Direct Hung," unless otherwise indicated. Comply with seismic design requirements. 2.3 ACOUSTICAL TILES, GENERAL (ACT-1)
A. Manufacturers: Subject to compliance with requirements, provide products by the following”
1. Armstrong World Industries, Inc; Dune 1776. B. Color: White.
C. Edge/Joint Detail: Angled tegular. D. Thickness: 5/8 inch.
E. Modular Size: As indicated on Drawings. 2.4 ACOUSTICAL TILES, RESTROOMS (ACT-2)
A. Manufacturers: Subject to compliance with requirements, provide products by the following”
1. Armstrong World Industries, Inc; Optima Health Zone 3214. B. Color: White.
C. Surface: Vinyl faced, cleanable. D. Edge/Joint Detail: Angled tegular. E. Modular Size: As indicated on Drawings. 2.5 METAL SUSPENSION SYSTEM (CG-1)
A. Manufacturers: Subject to compliance with requirements, provide products by the following:
1. Armstrong World Industries, Inc; Prelude XL, 15/16” exposed tee profile. B. Structural Classification: Intermediate duty system.
ACOUSTICAL TILE CEILINGS 095123 - 3 metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.
PART 3 - EXECUTION 3.1 INSTALLATION
A. Install acoustical tile ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."
B. Measure each ceiling area and establish layout of acoustical tiles to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width tiles at borders, and comply with layout shown on reflected ceiling plans.
RESILIENT BASE AND ACCESSORIES 096513 - 1 SECTION 096513 - RESILIENT BASE AND ACCESSORIES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes: 1. Resilient base.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product. B. LEED Submittals:
1. Product Data for Credit IEQ 4.1: For adhesives, documentation including printed statement of VOC content.
2. Laboratory Test Reports for Credit IEQ 4.1: For adhesives, documentation indicating that products comply with the testing and product requirements of the California Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."
3. Product Data for Credit IEQ 4.3: For adhesives, documentation including printed statement of VOC content.
4. Product Data for Credit IEQ 4.3: For resilient stair accessories, documentation from an independent testing agency indicating compliance with the FloorScore standard. 5. Laboratory Test Reports for Credit IEQ 4.3: For resilient stair accessories,
documentation indicating that products comply with the testing and product requirements of the California Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."
C. Samples: For each exposed product and for each color and texture specified, not less than 12 inches (300 mm) long.
1.3 EXTRA MATERIALS/ATTIC STOCK
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. FloorScore Compliance: Resilient [base] [and] [stair accessories] shall comply with requirements of FloorScore certification.
B. Low-Emitting Materials: Flooring system shall comply with the testing and product requirements of the California Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."
2.2 THERMOPLASTIC-RUBBER BASE <Insert drawing designation>
A. Manufacturers: Subject to compliance with requirements, [provide products by the following:
1. Johnsonite, Inc.
B. Product Standard: ASTM F 1861, Type TS (rubber, vulcanized thermoset), Group I (solid, homogeneous).
1. Style and Location:
a. Style B, Cove: Provide in areas with resilient flooring.
C. Thickness: 0.125 inch (3.2 mm). D. Height: 4 inches.
E. Lengths: Coils in manufacturer's standard length. F. Outside Corners: Job formed.
G. Inside Corners: Job formed. H. Colors: As scheduled. 2.3 INSTALLATION MATERIALS
RESILIENT BASE AND ACCESSORIES 096513 - 3 C. Floor Polish: Provide protective, liquid floor-polish products recommended by resilient
stair-tread manufacturer. PART 3 - EXECUTION
3.1 PREPARATION
A. Prepare substrates according to manufacturer's written instructions to ensure adhesion of resilient products.
B. Concrete Substrates for Resilient Stair Accessories: Prepare horizontal surfaces according to ASTM F 710.
1. Verify that substrates are dry and free of curing compounds, sealers, and hardeners. 2. Remove substrate coatings and other substances that are incompatible with
adhesives and that contain soap, wax, oil, or silicone, using mechanical methods recommended by manufacturer. Do not use solvents.
3. Alkalinity and Adhesion Testing: Perform tests recommended by manufacturer. Proceed with installation only after substrate alkalinity falls within range on pH scale recommended by manufacturer in writing, but not less than 5 or more than [9] [10] <Insert number> pH.
4. Moisture Testing: Proceed with installation only after substrates pass testing according to manufacturer's written recommendations, but not less stringent than the following:
a. Perform anhydrous calcium chloride test according to ASTM F 1869. Proceed with installation only after substrates have maximum moisture-vapor-emission rate of [3 lb of water/1000 sq. ft. (1.36 kg of water/92.9 sq. m)] <Insert rate> in 24 hours.
b. Perform relative humidity test using in situ probes according to ASTM F 2170. Proceed with installation only after substrates have maximum [75] <Insert number> percent relative humidity level.
C. Fill cracks, holes, and depressions in substrates with trowelable leveling and patching compound; remove bumps and ridges to produce a uniform and smooth substrate.
D. Do not install resilient products until they are the same temperature as the space where they are to be installed.
3.2 RESILIENT BASE INSTALLATION
A. Comply with manufacturer's written instructions for installing resilient base.
B. Apply resilient base to walls, columns, pilasters, casework and cabinets in toe spaces, and other permanent fixtures in rooms and areas where base is required.
C. Install resilient base in lengths as long as practical without gaps at seams and with tops of adjacent pieces aligned.
D. Tightly adhere resilient base to substrate throughout length of each piece, with base in continuous contact with horizontal and vertical substrates.
E. Do not stretch resilient base during installation.
F. On masonry surfaces or other similar irregular substrates, fill voids along top edge of resilient base with manufacturer's recommended adhesive filler material.
G. Preformed Corners: Install preformed corners before installing straight pieces. H. Job-Formed Corners:
1. Outside Corners: Use straight pieces of maximum lengths possible and form with returns not less than 3 inches in length.
a. Form without producing discoloration (whitening) at bends.
2. Inside Corners: Use straight pieces of maximum lengths possible and form with returns not less than 3 inches in length.
a. Miter or cope corners to minimize open joints. 3.3 CLEANING AND PROTECTION
A. Comply with manufacturer's written instructions for cleaning and protecting resilient products.
B. Floor Polish: Remove soil, visible adhesive, and surface blemishes from resilient stair treads before applying liquid floor polish.
1. Apply two coat(s).
RESILIENT TILE FLOORING 096519 - 1 SECTION 096519 - RESILIENT TILE FLOORING
1.1 SUMMARY
A. Section Includes: 1. Luxury vinyl tile. 2. Rubber floor tile.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: For each type of floor tile. Include floor tile layouts, edges, columns, doorways, enclosing partitions, built-in furniture, cabinets, and cutouts.
1. Show details of special patterns.
C. Samples: Full-size units of each color and pattern of floor tile required. 1.3 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.4 WARRANTIES
A. Provide manufacturer’s standard ten-year commercial wear warranty on all installed products.
1.5 EXTRA MATERIALS / ATTIC STOCK
A. Provide at least twenty vinyl flooring tiles and ten rubber tiles for the Owner’s attic stock. PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
2.2 LUXURY VINYL TILE (VT-1)
A. Products: Subject to compliance with requirements, provide the following: 1. Shaw Contract Group: 0188V, Uncommon Ground 6.
B. Wearing Surface: Textured. C. Thickness: 1/8 inch thick.
D. Size: 6 inches x 36 inches, nominal. 1. Colors and Patterns: As scheduled. 2.3 RUBBER FLOOR TILE (RB-1)
A. Products: Subject to compliance with requirements, provide the following: 1. Johnsonite; A Tarkett Company; Cityscape (The Gardens Collection) B. Tile Standard: ASTM F 1344.
C. Wearing Surface: Textured. D. Thickness: 0.080 inch thick. E. Size: 24 by 24 inches.
F. Colors and Patterns: As scheduled. 2.4 INSTALLATION MATERIALS
A. Trowelable Leveling and Patching Compounds: Latex-modified, portland cement based or blended hydraulic-cement-based formulation provided or approved by floor tile manufacturer for applications indicated.
B. Adhesives: Water-resistant type recommended by floor tile and adhesive manufacturers to suit floor tile and substrate conditions indicated.
RESILIENT TILE FLOORING 096519 - 3 PART 3 - EXECUTION
3.1 PREPARATION
A. Prepare substrates according to floor tile manufacturer's written instructions to ensure adhesion of resilient products.
B. Concrete Substrates: Prepare according to ASTM F 710.
1. Verify that substrates are dry and free of curing compounds, sealers, and hardeners. 2. Remove substrate coatings and other substances that are incompatible with
adhesives and that contain soap, wax, oil, or silicone, using mechanical methods recommended by floor tile manufacturer. Do not use solvents.
3. Alkalinity and Adhesion Testing: Perform tests recommended by floor tile manufacturer. Proceed with installation only after substrate alkalinity falls within range on pH scale recommended by manufacturer in writing, but not less than 5 or more than 9 pH.
4. Moisture Testing: Proceed with installation only after substrates pass testing according to floor tile manufacturer's written recommendations, but not less stringent than the following:
a. Perform anhydrous calcium chloride test according to ASTM F 1869. Proceed with installation only after substrates have maximum moisture-vapor-emission rate of 3 lb of water/1000 sq. ft. (1.36 kg of water/92.9 sq. m) in 24 hours. C. Fill cracks, holes, and depressions in substrates with trowelable leveling and patching
compound; remove bumps and ridges to produce a uniform and smooth substrate.
D. Do not install floor tiles until they are the same temperature as the space where they are to be installed.
E. Immediately before installation, sweep and vacuum clean substrates to be covered by resilient floor tile.
3.2 FLOOR TILE INSTALLATION
A. Comply with manufacturer's written instructions for installing floor tile.
B. Lay out floor tiles from center marks established with principal walls, discounting minor offsets, so tiles at opposite edges of room are of equal width. Adjust as necessary to avoid using cut widths that equal less than one-half tile at perimeter.
C. Match floor tiles for color and pattern by selecting tiles from cartons in the same sequence as manufactured and packaged, if so numbered. Discard broken, cracked, chipped, or deformed tiles.
D. Scribe, cut, and fit floor tiles to butt neatly and tightly to vertical surfaces and permanent fixtures including built-in furniture, cabinets, pipes, outlets, and door frames.
E. Extend floor tiles into toe spaces, door reveals, closets, and similar openings. Extend floor tiles to center of door openings.
F. Maintain reference markers, holes, and openings that are in place or marked for future cutting by repeating on floor tiles as marked on substrates. Use chalk or other nonpermanent marking device.
G. Install floor tiles on covers for telephone and electrical ducts, building expansion-joint covers, and similar items in finished floor areas. Maintain overall continuity of color and pattern between pieces of tile installed on covers and adjoining tiles. Tightly adhere tile edges to substrates that abut covers and to cover perimeters.
H. Adhere floor tiles to flooring substrates using a full spread of adhesive applied to substrate to produce a completed installation without open cracks, voids, raising and puckering at joints, telegraphing of adhesive spreader marks, and other surface imperfections.
3.3 CLEANING AND PROTECTION
A. Comply with manufacturer's written instructions for cleaning and protecting floor tile. B. Floor Polish: Remove soil, adhesive, and blemishes from floor tile surfaces before applying
liquid floor polish. 1. Apply two coats.
SHEET CARPETING 096816 - 1 SECTION 096816 - SHEET CARPETING
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes broadloom carpeting and installation accessories. 1.2 ACTION SUBMITTALS
A. Product Data: For each type of product. B. Shop Drawings: Show the following:
1. Columns, doorways, enclosing walls or partitions, built-in cabinets, and locations where cutouts are required in carpet.
2. Carpet type, color, and dye lot. 3. Seam locations, types, and methods. 4. Pile direction.
C. Samples: For each exposed product and for each color and texture specified.
1.3 INFORMATIONAL SUBMITTALS A. Product test reports.
B. Warrant: Sample of special warranty. 1.4 CLOSEOUT SUBMITTALS
A. Maintenance data. 1.5 QUALITY ASSURANCE
A. Installer Qualifications: An experienced Installer who is certified by the International Certified Floorcovering Installers Association at the Commercial IIcertification level.
1.6 DELIVERY, STORAGE, AND HANDLING A. Comply with CRI 104.
1.7 FIELD CONDITIONS
A. Comply with CRI 104 for temperature, humidity, and ventilation limitations. 1.8 EXTRA MATERIALS / ATTIC STOCK
A. Provide a minimum of five square yards of each color/pattern of carpet specified to the Owner as attic stock upon Substantial Completion.
B. WARRANTY
C. Special Warranty for Carpet: Manufacturer agrees to repair or replace components of carpet installation that fail in materials or workmanship within specified warranty period. 1. Warranty does not include deterioration or failure of carpet due to unusual traffic,
failure of substrate, vandalism, or abuse.
2. Failures include, but are not limited to, more than 10 percent loss of face fiber, edge raveling, snags, runs, loss of tuft bind strength, excess static discharge, and delamination.
3. Warranty Period: Lifetime. PART 2 - PRODUCTS
2.1 BROADLOOM CARPET (C-1):
A. Products: Subject to compliance with requirements, provide the following: 1. Shaw Contract Group; Tribute 60710.
B. Color and Pattern: Refined Jade 10300.
C. Fiber Content: Manufacturer’s “Eco Solution Q” nylon. D. Construction: Multi-level pattern cut/loop.
SHEET CARPETING 096816 - 3 H. Backing: Manufacturer’s EcoWorx Performance Broadloom.
I. Applied Soil-Resistance Treatment: SSP Shaw Soil Protection. 2.2 INSTALLATION ACCESSORIES
A. Trowelable Leveling and Patching Compounds: Latex-modified, hydraulic-cement-based formulation provided or recommended by carpet[ cushion] manufacturer.
B. Adhesives: Water-resistant, mildew-resistant, nonstaining type to suit products and subfloor conditions indicated, that complies with flammability requirements for installed carpet and is recommended or provided by carpet manufacturer.
C. Tackless Carpet Stripping: Water-resistant plywood, in strips as required to match cushion thickness and that comply with CRI 104, Section 12.2.
D. Seam Adhesive: Hot-melt adhesive tape or similar product recommended by carpet manufacturer for sealing and taping seams and butting cut edges at backing to form secure seams and to prevent pile loss at seams.
PART 3 - EXECUTION 3.1 INSTALLATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for maximum moisture content, alkalinity range, installation tolerances, and other conditions affecting carpet performance. Examine carpet for type, color, pattern, and potential defects.
B. Concrete Subfloors: Verify that concrete slabs comply with ASTM F 710.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
D. Preparation: Comply with CRI 104, Section 7.3, "Site Conditions; Floor Preparation," and with carpet manufacturer's written installation instructions for preparing substrates. E. Installation: Comply with CRI 104 and carpet manufacturer's written installation
instructions for the following:
1. Double-Glue-Down Installation: Comply with CRI 104, Section 10, "Double-Glue-Down Installation."
G. Do not bridge building expansion joints with carpet.
H. Cut and fit carpet to butt tightly to vertical surfaces, permanent fixtures, and built-in furniture including cabinets, pipes, outlets, edgings, thresholds, and nosings. Bind or seal cut edges as recommended by carpet manufacturer.
I. Extend carpet into toe spaces, door reveals, closets, open-bottomed obstructions, removable flanges, alcoves, and similar openings.
J. Maintain reference markers, holes, and openings that are in place or marked for future cutting by repeating on finish flooring as marked on subfloor. Use nonpermanent, nonstaining marking device.
K. Install pattern parallel to walls and borders to comply with CRI 104, Section 15, "Patterned Carpet Installations" and with carpet manufacturer's written recommendations.
L. Perform the following operations immediately after installing carpet:
1. Remove excess adhesive, seam sealer, and other surface blemishes using cleaner recommended by carpet manufacturer.
2. Remove yarns that protrude from carpet surface.
3. Vacuum carpet using commercial machine with face-beater element.
M. Protect installed carpet to comply with CRI 104, Section 16, "Protecting Indoor Installations."
STONE WALL FACING 097513 - 1 SECTION 097513 - STONE WALL FACING
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes anchored stone paneling for the following interior applications: 1. Wall paneling.
1.2 ACTION SUBMITTALS
A. Product Data: For each manufactured product.
B. Shop Drawings: Show fabrication and installation details for stone paneling system, including dimensions and profiles of stone units.
C. Samples:
1. For each stone type indicated. Include two or more Samples in each set and show the full range of variations in appearance characteristics in completed Work.
2. For each color of grout required.
PART 2 - PRODUCTS 2.1 STONE, GENERAL
A. Product:
1. Daltile: Eastern Sand (Stacked Stone Natural Cleft Ungauged) S319. a. Size: 7” high x 16” long; thickness varies between ¾” and 1-1/4”. 2.2 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design stone paneling system.
B. General: Design stone anchors and anchoring systems according to ASTM C 1242.
2.3 SETTING MATERIALS
A. Portland Cement: ASTM C 150, Type I or Type II.
1. Low-Alkali Cement: Not more than 0.60 percent total alkali when tested according to ASTM C 114.
B. Hydrated Lime: ASTM C 207, Type S. C. Aggregate: ASTM C 144.
D. Water: Potable.
2.4 GROUT
A. Grout Colors: Match stone.
B. Water-Cleanable Epoxy Grout: ANSI A118.3, packaged, chemical-resistant, water-cleanable, tile-setting and -grouting epoxy.
2.5 STONE ACCESSORIES
A. Temporary Setting Shims: Rigid plastic shims, nonstaining to stone, sized to suit joint thickness.
B. Setting Shims for Direct-Mount Anchoring Systems: Strips of resilient plastic or neoprene, nonstaining to stone, of thickness needed to prevent point loading of stone on anchors and of depths to suit anchors without intruding into required depths of pointing materials. C. Cleaner: Stone cleaner specifically formulated for stone types, finishes, and applications
indicated, as recommended by stone producer. Do not use cleaning compounds containing acids, caustics, harsh fillers, or abrasives.
D. Stone Sealer: Colorless, stain-resistant sealer that does not affect color or physical properties of stone surfaces, as recommended by stone producer for application indicated. E. Spotting Plaster: Stiff mix of molding plaster and water.
STONE WALL FACING 097513 - 3 PART 3 - EXECUTION
3.1 SETTING STONE, GENERAL
A. Do necessary field cutting as stone is set. Use power saws with diamond blades to cut stone. Cut lines straight and true, with edges eased slightly to prevent snipping.
B. Contiguous Work: Provide reveals and openings as required to accommodate contiguous work.
C. Set stone to comply with requirements indicated. Install anchors, supports, fasteners, and other attachments indicated or necessary to secure stone in place. Shim and adjust anchors, supports, and accessories to set stone accurately in locations indicated, with edges and faces aligned according to established relationships and indicated tolerances. 3.2 CONSTRUCTION TOLERANCES
A. Variation from Plumb: For vertical lines and surfaces, do not exceed 1/8 inch in 96 inches (3 mm in 2400 mm), 1/4 inch (6 mm) maximum.
B. Variation from Level: For lintels, sills, chair rails, horizontal bands, horizontal grooves, and other conspicuous lines, do not exceed 1/8 inch in 10 feet (3 mm in 3 m), 1/4 inch in 20 feet (6 mm in 6 m), 3/8 inch (10 mm) maximum.
C. Variation in Joint Width: Do not vary from average joint width more than plus or minus 1/16 inch (1.5 mm) or one-fourth of nominal joint width, whichever is less.
D. Variation in Plane between Adjacent Stone Units (Lipping): Do not exceed 1/32-inch (0.8-mm) difference between planes of adjacent units.
3.3 GROUTING JOINTS
A. Grout stone to comply with ANSI A108.10.
1. Use sanded grout mixture for joints wider than 1/8 inch (3 mm). 2. Use unsanded grout mixture for joints 1/8 inch (3 mm) and narrower. B. Remove temporary shims before grouting.
3.4 ADJUSTING AND CLEANING
A. In-Progress Cleaning: Clean stone paneling as work progresses. Remove adhesive, grout, mortar, and sealant smears immediately.
B. Clean stone paneling no fewer than six days after completion of grouting and pointing, using clean water and soft rags or stiff-bristle fiber brushes. Do not use wire brushes, acid-type cleaning agents, cleaning compounds with caustic or harsh fillers, or other materials or methods that could damage stone.
C. Sealer Application: Apply stone sealer to comply with stone producer's and sealer manufacturer's written instructions and recommendations.
PAINTING 099100 - 1 SECTION 099100 - PAINTING
1.1 SUMMARY
A. Section includes surface preparation and the application of paint systems on interior and exterior substrates.
1.2 DEFINITIONS
A. Gloss Level 1: Not more than 5 units at 60 degrees and 10 units at 85 degrees, according to ASTM D 523.
B. Gloss Level 2: Not more than 10 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523.
C. Gloss Level 3: 10 to 25 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523.
D. Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to ASTM D 523.
E. Gloss Level 5: 35 to 70 units at 60 degrees, according to ASTM D 523. F. Gloss Level 6: 70 to 85 units at 60 degrees, according to ASTM D 523. G. Gloss Level 7: More than 85 units at 60 degrees, according to ASTM D 523. 1.3 ACTION SUBMITTALS
A. Product Data: For each type of product. Include preparation requirements and application instructions.
B. LEED Submittals:
1. Product Data for Credit EQ 4.2: For paints and coatings, including printed statement of VOC content.
2. Laboratory Test Reports for Credit EQ 4: For paints and coatings, documentation indicating that they meet the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."
D. Product List: For each product indicated. Include printout of current "MPI Approved Products List" for each product category specified in Part 2, with the proposed product highlighted.
1.4 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials, from the same product run,] that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Paint: [5] <Insert number> percent, but not less than [1 gal. (3.8 L)] <Insert number> of each material and color applied.
1.5 QUALITY ASSURANCE
A. Mockups: Apply mockups of each paint system indicated and each color and finish selected to verify preliminary selections made under Sample submittals and to demonstrate aesthetic effects and set quality standards for materials and execution.
1. Architect will select one surface to represent surfaces and conditions for application of each paint system specified in Part 3.
a. Vertical and Horizontal Surfaces: Provide samples of at least 100 sq. ft. (9 sq. m).
b. Other Items: Architect will designate items or areas required. 2. Final approval of color selections will be based on mockups.
a. If preliminary color selections are not approved, apply additional mockups of additional colors selected by Architect at no added cost to Owner.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Products: Subject to compliance with requirements, [provide product] [provide one of the products] [available products that may be incorporated into the Work include, but are not limited to products] listed in other Part 2 articles for the paint category indicated.
PAINTING 099100 - 3 B. Material Compatibility:
1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience.
2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated.
C. VOC Content: Products shall comply with VOC limits of authorities having jurisdiction[ and, for interior paints and coatings applied at Project site, the following VOC limits, exclusive of colorants added to a tint base, when calculated according to 40 CFR 59, Subpart D (EPA Method 24)].
1. Flat Paints and Coatings: 50 g/L. 2. Nonflat Paints and Coatings: 150 g/L. 3. Dry-Fog Coatings: 400 g/L.
4. Primers, Sealers, and Undercoaters: 200 g/L.
5. Anticorrosive and Antirust Paints Applied to Ferrous Metals: 250 g/L. 6. Zinc-Rich Industrial Maintenance Primers: 340 g/L.
7. Pretreatment Wash Primers: 420 g/L. 8. Floor Coatings: 100 g/L.
9. Shellacs, Clear: 730 g/L. 10. Shellacs, Pigmented: 550 g/L.
D. Low-Emitting Materials: Interior paints and coatings shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."
E. Colors: As indicated in a color schedule. 2.3 PRIMERS/SEALERS
A. Primer Sealer, Latex, Interior: 1. Sherwin-Williams, Harmony. B. Primer Sealer, Latex, Exterior:
1. Sherwin-Williams, Duration. 2.4 METAL PRIMERS
2.5 WATER-BASED PAINTS A. Latex, Interior, Flat:
1. Sherwin-Williams, Harmony. B. Latex, Interior, Eggshell:
1. Sherwin-Williams, Harmony. C. Latex, Interior, Satin:
1. Sherwin-Williams, Harmony. D. Latex, Exterior, Satin:
1. Sherwin-Williams, Duration. 2.6 SOLVENT-BASED PAINTS
A. Alkyd, Interior, Semi-Gloss:
1. Sherwin-Williams, Alkyd DTM Enamel. 2.7 EPOXY PAINTS
A. Interior, Satin:
1. Sherwin-Williams, Water-Based Catalyzed Epoxy (for use at restroom walls and ceiling above bar)
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work.
B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows:
PAINTING 099100 - 5 C. Verify suitability of substrates, including surface conditions and compatibility with existing
finishes and primers.
D. Proceed with coating application only after unsatisfactory conditions have been corrected. 1. Application of coating indicates acceptance of surfaces and conditions.
3.2 PREPARATION
A. Comply with manufacturer's written instructions and recommendations in "MPI Manual" applicable to substrates indicated.
B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting.
1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection if any.
C. Clean substrates of substances that could impair bond of paints, including dust, dirt, oil, grease, and incompatible paints and encapsulants.
1. Remove incompatible primers and reprime substrate with compatible primers or apply tie coat as required to produce paint systems indicated.
3.3 APPLICATION
A. Apply paints according to manufacturer's written instructions and to recommendations in "MPI Manual."
B. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.
3.4 CLEANING AND PROTECTION
A. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition.
3.5 INTERIOR PAINTING SCHEDULE A. Steel Substrates:
1. Alkyd System:
a. Prime Coat: Primer, alkyd, anti-corrosive, for metal. b. Intermediate Coat: Alkyd, interior, matching topcoat. c. Topcoat: Alkyd, interior, semi-gloss.
B. Galvanized-Metal Substrates:
1. Latex over Waterborne Primer System:
a. Prime Coat: Primer, galvanized, water based.
b. Intermediate Coat: Latex, interior, matching topcoat. c. Topcoat: Latex, interior, semi-gloss
C. Gypsum Board:
1. Latex System:
a. Prime Coat: Primer sealer, latex, interior. b. Prime Coat: Latex, interior, matching topcoat. c. Intermediate Coat: Latex, interior, matching topcoat. d. Topcoat: Latex, interior, flat.
e. Topcoat: Latex, interior, eggshell. f. Topcoat: Latex, interior, satin.
2. See Finish Schedule for finish and sheen requirements per color. 3.6 EXTERIOR PAINTING SCHEDULE
A. Metal Substrates:
1. One coat DTM alkyd primer. 2. Two coats DTM alkyd enamel. B. Wood Substrates: