Internal Synchrocheck
Configuration
PCL
PCL
PCL
PCL
PACiS
PACiS
PACiS
PACiS Technical
Technical
Technical
Technical Training
Training
Training
Training Level
Level
Level
Level 2
2
2
2
CS&P
CS&P
CS&P
• Content
Prerequisites
Internal Synchrocheck Scheme
• Content
Prerequisites
Internal Synchrocheck Scheme
• Prerequisites
1) VOLTAGE ACQUISITION => CT/VT BOARD (TMU200 or TMU220) TMU200 => 4VT
TMU220 => 5VT => 1 synchrocheck on double busbars network.
• Content
Prerequisites
Internal Synchrocheck Scheme
VB
2π FB t
2π FL t
VL
• Voltages
VL1 VL2 VL3 VB1 VB2 VB3 ∆ϕ ∆ϕ∆ϕ ∆ϕ 2π.FB.t 2π.FL.t =2π.∆∆∆F.t (1st order development) ∆ Application ∆ ∆ ∆ ∆F small ∆ ∆ ∆ ∆V small VL1 VB1
Coupling Net Scheme ∆ϕ∆ϕ∆ϕ(t) from ∆∆ϕ ∆∆F∆
± ∆∆∆∆(∆ϕ∆ϕ∆ϕ)∆ϕ ∆ϕ ∆ϕ∆ϕ ∆ϕ = 2π.∆∆∆∆F.Ta VL1 VB1
Locking « Check » Scheme
∆ϕ ∆ϕ ∆ϕ
∆ϕ = Cte
Synchro Close Control NETWO RK B NETWO RK A VT VT 3 CB Closing conditions •Same frequency •Same amplitudes
•Same phases & zero-phase angle difference
4 Kinds of synchronisation closure
•Check synchronisation LOCK A, B already connected (Same Frequency)
•Power synchronisation COUPLING A, B split power system (independant)
•Generator synchronisation A generator, B Grid Drive Turbine/excitation
•Without synchronisation OVER-RIDE dead line/bar
• Application to 2 networks
C264
Internal Synchrocheck CT/VT calculations CB CLOSE ORDER NETWORK A INTERNAL SYNCHRO CHEK CT/VT CALCULATIONS NETWORK NETWORK NETWORK NETWORK A AA A NETWORK NETWORK NETWORK NETWORK B B BB LINELINELINELINE
Application to two networks
Voltage Thresholds Computation
Dead/Live Line&Bar (Vline and Vbusbar) settable thresholds
.Vline and not(Vbusbar) .not(Vline) and Vbusbar
.not(Vline) and not(Vbusbar) Settable Closing Override
Synchronise Scheme Closing Settable
Locking / Coupling Overriding Dead Side
Vline and Vbusbar TRUE if the measured voltage is above the threshold V>
Live threshold
not(Vline) and not(Vbusbar) TRUE if the measured voltage is below the threshold V<
Dead threshold
Voltage Thresholds Computation
Dead/Live Line&Bar (Vline and Vbusbar)
Dead None Live (Bypass)
• Live / Dead Bus / Line
Note : There is 5% of hysteresis on
voltage thresholds (See C264_FT).
Nominal V = 100V
If, during the T1, T2 delay time, one of the 2 criteria is lost, the timer is reinitialised and is launched again on reappearance of all the criteria.
➘ T1, T2 configurable delay
Vline and not(Vbusbar) voltage control (LL-DB)
Overriding Dead Side
Vline T2 0
& Closing authorization Not(Vbusbar)
Not(Vline )and Vbusbarvoltage control (DL-LB) T2 Not(Vline )and Not(Vbusbar)voltage control (DL-DB) T1
FOR CLOSING AUTHORISATION ➘ Presence of both voltages (LL-LB)
➘ ∆∆∆∆V is lower than a configurable threshold (%) ➘ Fline and Fbusbar are such Fmin<F<Fmax
➘ ∆∆∆∆F is lower than a configurable threshold (raw value)
➘ ∆ϕ∆ϕ∆ϕ∆ϕ voltages is lower than a configurable threshold (raw value in °) ➘ ∆∆∆∆(∆ϕ∆ϕ∆ϕ∆ϕ) anticipation (COUPLING)
Synchronise Scheme Closing
Settable
Locking or Coupling
• V
LINE
& V
BUSBAR
Voltage Control
2% on voltage delta threshold for locking and coupling 0,014 Hz on frequency delta threshold for locking
0,028 Hz on frequency delta threshold for coupling 0,01 Hz on frequencies thresholds
1°on phase delta threshold for locking.
➘ T1 configurable timer & Vline Vbusbar ∆ ∆∆ ∆F <Efreq ∆ ∆∆ ∆V < Evect
Fmin < Fbusbar < Fmax Fmin < Fline < Fmax
T1 0
Locking ∆ϕ∆ϕ∆ϕ < E∆ϕ phase
Locking close
Ta = anticipation time or response time of the CB
∆ ∆∆
∆(∆ϕ∆ϕ∆ϕ∆ϕ) is phase anticipation the acceptable mistake on ∆ϕ∆ϕ∆ϕ∆ϕ.
Coupling check ∆ϕ∆ϕ∆ϕ∆ϕ Close When ∆ϕ ∆ϕ ∆ϕ ∆ϕ = ∆∆∆∆F*360*Ta ± ∆∆∆(∆ϕ∆ ∆ϕ∆ϕ∆ϕ)
• Content
Prerequisites
Internal Synchrocheck Scheme
• Auto / Manual Internal SC (1)
1) INTERNAL MANUAL SYNCHROCHECK• Add / Configure an Internal SC (1)
1) Internal SC can be added at Bay Level.Built-in function : Internal auto CS Internal manu CS
2) Internal SC attributes : General Tab
Automatic Out Of Service : If Manual SC => Yes/No
• Add / Configure an Internal SC (2)
Deltas, VoltagesPresence / Absence Test Duration:
To declare Live/Dead 3) Internal SC attributes : General Tab (1)
For locking scheme :
∆ ∆∆
∆V, Fmin, Fmax,∆∆∆∆F,∆Φ∆Φ∆Φ∆Φ
For coupling scheme :
∆ ∆∆
• Add / Configure an Internal SC (3)
3) Internal SC attributes : General Tab (2)Thresholds :
detection of Live Line, Dead Line detection of Live Bus, Dead Bus % of nominal value
• Add / Configure an Internal SC (4)
3) Internal SC attributes : General Tab (3)Synchro Close =
Sync CB Close for automatic SC
Switch Ctrl DPC and SC On/off = ON for manual SC
coupling usage / locking usage / close authorisation in DL-LB, LL-DB, DL-DB / timer T1 for locking / coupling scheme to maintain conditions
Close =
Switch Ctrl DPC for automatic SC
Switch Ctrl DPC and SC On/off = OFF for manual
SC
locking usage (LB) / close authorisation in DL-LB, LL-DB, DL-DB / timer T1 for locking scheme to maintain conditions
Automatic Close = from AR
locking usage (LB) / close authorisation in DL-LB, LL-DB, DL-DB / timer T1 for locking scheme to maintain conditions
• Internal SC Sons & Relations (1)
1) Internal SC Relations=> 1 internal SC per C264
Relation “is synchrocheck of” target synchronised CB
Target CB Configuration
Add “Sync CB Close” under CB - same SBO/DE conf. as Switch Ctrl DPC
• Internal SC Sons & Relations (2)
1) Internal SC Basic ConfigurationClose Order SPS :
transient SPS set as soon as a synchronised closure is in progress
On/Off SPS : SC In/Out Service Possible Closing :
when locking conditions are OK, set after T1 timer
Dead Line Live Line Dead Bus Live Bus
• Internal SC Sons & Relations (3)
1) Internal SC Enhanced ConfigurationAccept forcing SPS : - not wired
- SPS datapoint, giving authorisation to force synchrocheck
- OI and GTW are clients of this SPS for synchrocheck forcing
CS Locked SPS : SC locked status
On/Off SPC or DPC :