• No results found

Busbar Protection AREVA

N/A
N/A
Protected

Academic year: 2021

Share "Busbar Protection AREVA"

Copied!
44
0
0

Loading.... (view fulltext now)

Full text

(1)
(2)

Bus

Bus

bar

bar

P

P

rotectio

rotectio

n

n

p:/applics/Powerpoint Cabinet/Training Courses/APPS1 p:/applics/Powerpoint Cabinet/Training Courses/APPS1

Janu

January 200ary 20044

 A

 Allan

an Wi

Wix

xo

on

n

Se

(3)

Bus

Bus

bar

bar

P

P

rotectio

rotectio

n

n

p:/applics/Powerpoint Cabinet/Training Courses/APPS1 p:/applics/Powerpoint Cabinet/Training Courses/APPS1

Janu

January 200ary 20044

 A

 Allan

an Wi

Wix

xo

on

n

Se

(4)

W

W

ith

ith

out

out

Bus

Bus

bar P

bar P

rot

rot

e

e

cti

cti

on

on

(

(

1

1

)

)

The

There are are fewer fare fewer faults ults on buson bus bars than on other parts bars than on other parts of the powof the pow er system.er system.

No dislocation of s ystem due to aNo dislocation of system due to accidental operation of busbarccidental operation of busbar

protection. protection.

Slow f ault cSlow fault c lealearance.rance.

Bus

Bus bar faults bar faults at F1 at F1 and F2 and F2 are cleaare cleared by rred by r emote timemote tim e delayee delayedd protection on c

protection on c ircuits ircuits feefeeding ding the fathe faults:ults: Time Delayed Overcurrent or 

Time Delayed Overcurrent or  Time De

Time Delayed Distance Protectlayed Distance Protect ionion F F22 F

(5)

W

W

ith

ith

out

out

Bus

Bus

bar P

bar P

rot

rot

e

e

cti

cti

on

on

(

(

2

2

)

)

FaFast cst clearalearance by bnce by breakereakers at thrs at the busbe busbarsars

WheWhere busre busbars are sectionbars are section alised,alised,

P

Protection can limit rotection can limit the athe amount mount of of systemsystem disrupti

disrupti on for a busbar faon for a busbar faultult

BUSBAR BUSBAR ZONE ZONE F F22 F F11

(6)

Busbar Faults Are Usually Permanent

CAUSES :

Insulation failures

Circuit breaker failuresFalling debris

Isolators operated out side their ratingsSafety earths left connected

Current transfor mer failures

THEREFORE :

Circuit breakers should be tripp ed and lo cked out by bus bar protection

(7)

Busbar Protection must be:

RELIABLE

 Failur e could cause widespread damage to th e

substation  STABLE

 False trippi ng can cause widespread interruption of

supplies to custo mers  DISCRIMINATING

 Should trip the minimum number of breakers to clear

the fault  FAST

(8)

Methods of Providing Busbar Protection

Frame to Earth (Leakage) Protection

Differential Protection : High Impedance

Low Impedance

Directional Comparison (Blocking Schemes)

(9)
(10)

Frame Earth Protection Scheme

Only an earth fault s yst em

Involves measuring fault curr ent f rom s wi tchgear frame to earth

Switchg ear insul ated by standing on c oncrete plinth

Only one earthin g poi nt allowed on sw itchg ear 

C.T. mount ed on singl e earth cond uctor used to energise

instantaneous relay

(11)

Current Distribution for External Fault

Outgoing feeder  Switchgear frame Switchgear frame bonding bar  Generator  System earthing resistor  Earth bar  Frame-leakage current transformer  Earthing electrode resistance (< 1Ω) Frame insulation resistance to earth (> 10Ω) IF = I1 + I2 I1 + I2 I1 I2 I1

(12)
(13)

High Impedance Protection (1)

This is a versatile and reliable prot ection system

applied to many different Busbar configurations.

If CT requirements are met, scheme performance

may be predicted by calculation without heavy

current conjunctive tests.

(14)

High Impedance Protection (2)

Simple system to apply and extend.

High sensitivity f or

phase and earth faults . Extremely stable for external faults.

CT requirements: Equal ratios Class ‘X’

May require stabilising resistor s, RST.

May require non-linear resistor s (Metrosils).

RST

METROSIL 87

(15)

Effective Setting

Since in each zone of pro tecti on th ere are several CT’s in p arallel with the relay and each o ther, the combin ed CT magnetising c urrents w ill increase the primary

operating current (P.O.C).

P.O.C. = CT ratio (IR + INLR + nIM) where

:-IR = Relay setting current

IM = CT magnetising current (one CT at relay setting voltage)

n = Number of paralleled CT’s

INLR = Non linear resistor current at relay setting voltage

(16)

Primary Operating Current (P.O.C)

The value of primary operating current should be

around 30% of minimum fault current available.

This ensures suffi cient relay current during int ernal

fault conditions for high speed operation.

(17)

Through Fault Stability

Busbar protection stability li mit is based on

maximum through fault cur rent.

Generally this value is derived from the rating of

the associated sw itchgear irrespective of existing

fault level, since it can be expected that system

will develop up to limit of rating.

(18)

Check Feature

Usually provided by duplication of pri mary protection using second set of CTs on all cir cuits other than bus section and coup ler unit s. Check system forms one zone only, covering whole of b usbar systems and not discrimin ating between faults on various sections.

Check zone Zone A Zone B 87A 87A 87A

(19)
(20)

CT Wiring Supervision (1)

Open circu it connection s between CT’s and relay circu it result in unbalance currents which may operate the

protection.

Supervision is applied by a voltage relay acros s dif ferential relay circuit .

Supervision relay is time delayed, gives alarm and also short s out bu s w ires to protect differential relay cir cuit.

Typical effective setting is 25 prim ary amps or 10% of low est circ uit rating, whi chever is greater.

(21)

M3 SP M3 SP M2 SP SP SP M4 M3 M2 1

Z

V

Z

V

Z

V

V

relay

n

supervisio

the

operate

current to

 balance

-of 

-Out

V

setting

relay

n

supervisio

If 

)

// Z

// Z

// Z

(R 

V

relay

n

supervisio

 by

measured 

Voltage

+ + + = Ι = Ι =

CT Wiring Supervision (2)

I1 CT1 Super  vision relay V RST RR R Z M2 ZM3 ZM4 I1 I2 I3 I4

(22)

Differential Relay Circuit

 A B C N

Zone bus wires

95X 95X 95X

Bus wire short contacts

Supervision relay 95 Stabilising resistors 87 87 87 v v v Metrosil resistors

(23)

Current Transformer Wiring

Lead bur dens between various sets of CT’s must be kept low. Usually busw ires are run in clos ed ring between breaker contro l p anels.

Typical rou te is

:- CT’s to m arshalling k iosk

 Marshallin g kios k to isol ator auxili aries  Loop between marshallin g kio sks

Conducto r size

(24)

Effect of C.T. Location on

Busbar Protection Performance

Busbar  protection Circuit protection Circuit protection Busbar  protection Overlapping C.T.s Circuit protection Busbar  protection Interlocked overcurrent relay

 All C.T.s on line side of circuit breaker 

 All C.T.s on Busbar side of circuit breaker 

Interlocked overcurrent relay

(25)
(26)

Typical Double Busbar Arrangement

60MW Generators 75MVA 132/13.8kV Transformers 132kV

(27)

Zones of Protection for Double Bus Station

Zone G Zone H

Zone J

BC BC

BS

(28)

Isolator Auxiliary Switches

R M  A B C D a b c d r  m Buswires

 Auxiliary switches should : 1) Close before the isolator

closes

2) Open after the isolator opens

In order to maintain stability on switching.

(29)

Tripping Circuits

One tripping relay (device 96) is required for each

feeder breaker and 2 for each bus section or bus

coupler breakers. Both main and check relays

must be energised before tripping relays trip all

breakers associated with zone.

(30)

Typical Trip Relay Arrangement

Double Busbar System

In Out CSS - M1 CSS - M2 CSS - R 87M1 - 1 87M2 - 1 87R - 1 M1M2R a1 c1 b1 c2 D.C. Buswires 80T 96H2 96H1 96G 96F2 96F1 96E 96D2 96D1

-+

87CH - 1

(31)

Double Busbar with Transfer Facilities

Main Reserve / Transfer  By-pass Isolator  By-pass Isolator 

(32)

Triple Busbar 

Main Transfer  CB Transfer  Reserve Transfer  CB

(33)
(34)

1½ Breaker Bus Protection

87

(35)

Mesh Busbar 

T1 F1 F3 T4 T3 T2 F4 F2

(36)

Mesh Busbar Protection

T1 F1 F3 T4 T3 T2 F4 F2 87 R1 87R3 87 R4 87R2

(37)

Busbar Protection and Breaker Fail

Where breaker fail pro tection is appli ed to a syst em, back trip ping o f associated breakers is requir ed in the event of a breaker failu re.

Often, breaker fail protection is arranged in conjunc tion with busbar protection trip ping circui ts to initi ate tripping o f

breakers on a busbar zone associated with the failed breaker.

(38)
(39)

Low Impedance Busbar Protection

Fast

Modular scheme design allows r elays t o relate to each circuit and

function of the protection. This enables the user to easily un derstand the principles of application.

High sensitivity for phase and earth faults. Protection for each phase can be relatively independent.

Earlier schemes were less stable than high impedance schemes. Modern schemes incor porate saturation detectors and are extremely stable.

Duplicate measuring cir cuits are inclu ded. Current transformers can be :

of dif ferent ratio

of relatively small outp ut

shared w ith other pr otections

Current transform er secondary cir cuits are not sw itched.

Continuous sup ervision of CT circuits and constant monitoring of vital circuits are included.

(40)

Single Bus Protection

F1 F2 F3 F4 Z2 Z1 BS F M1 M2F BSM M3F M4F Z1 ZCK Z2 ZCK ZCK Z1 Z2

(41)

Double Bus Protection

Z1 BCM 1 Z3 Z2 Z4 BS BC1 BC2 F1 F2 F3 F4 BCM 2 FM 1 FM 2 FM3 FM 4 BSM Z1 Z3 ZCK Z2 Z4 ZCK Z1 Z3 ZCK Z2 Z4

(42)
(43)

Busbar Blocking Protection

IF1

Incomer 

O/C Relay

O/C Relay O/C Relay O/C Relay O/C Relay

BLOCK

(44)

Directional Comparison Busbar Protection

Bus zone protection and unit pr otection of feeders

Forward Forward Forward

F1 BS F2

F3 F4 F5 F6

DOC DOC DOC

OC OC

OC OC

References

Related documents