Digital Timer
H5CX-@-N
Ultra-compact Timer Provides Advanced
Functions and Security Settings.
Basic Features
• Short body with depth of only 59 mm (for 24-VAC / 12 to 24-VDC Models with Screw Terminals). *1
• Character height of 12 mm for better readability (on models with 4 digits). • The present value display characters can be switched between red, green,
and orange. *2
Safety and Reliability
• Power supply circuit and input circuits are isolated for safety and reliability. *3
• New set value limit and output counter functions have been added.
Other Features
• Front Panel can be changed to white or light gray. *4
• Models with instantaneous contact output added to the series. *1. For 100 to 240 VAC Models with Screw Terminals 78 mm, Models with Sockets: 63.7 mm
(case dimension).
*2. The H5CX-A11, H5CX-L8 and H5CX-B Timers have only red characters. *3. Specifications: 100 to 240 VAC
*4. Replacement Front Panels sold separately.
Features
Basic Features
Ultra Short Body
The body depth has been greatly reduced. Helps in making thinner control panels. (Models with Screw Terminals)
Easier to Read
For better readability, the character height for the present value display is 12 mm (on models with 4 digits), the largest class in the industry. The wide viewing angle and brightness provide excellent visibility. The number of display segments has also been increased to make settings easier to understand, and the present value display can be switched between red, green and orange so that output status can be seen from a distance.
Note: The H5CX-A11 and H5CX-L8 Timers have only red characters.
The Easiest Operation
Operation is simplified by the Up/Down Keys for each digit on 4-digit models and Up Keys for each digit on 6-digit models.
Safety and Reliability
Isolated Power Supply and Input Circuits
*1Power supply circuit and input circuits are isolated for safety and reliability.
Previous non-isolated timers had wiring restrictions and could be damaged if wired incorrectly. The New H5CX removes these worries.
*1. New Models (H5CX-@-N) with 100 to 240-VAC specifications.
Set Value Limit
You can set an upper limit for the set value to prevent unexpected operation of output devices caused by setting mistakes.
Output Counter
The output counter counts the number of times the output turns ON (alarm display, count monitoring, count in increments of 1,000). This counter is useful in managing the service life of the Timer or the load.
Refer to “Safety Precautions” on page 41.
New models
Previous models24-VAC / 12 to 24-VDC Models with Screw Terminals: 59 mm 100 to 240-VAC / VDC Models with Screw Terminals: 78 mm *
Models with Sockets: 63.7 mm (case dimension)
* The shortest body for a timer with isolated power supply and input circuits and a maximum
ambient temperature of 55°C (according to OMRON investigation in June 2009).
Model with 4 Digits Model with 6 Digits
(Display example) 12 mm
(actual size)
10 mm
(actual size) Previous models New models
Easy to read from the top, bottom, and sides!
Model with 4 Digits Model with 6 Digits
–V +V Output terminal on PLC or other device AC power supply *2 H5CX Previous Input terminal 0-V terminal COM terminal Forget These Worries with the New H5CX Stabilized DC
power supply
*2. The AC power supply ground is on the commercial power supply side.
Worry-free operation is achieved with the New H5CX by restricting the time that can be set.
Other Features
Change the Front Panel Color
The Front Panel can be replaced with an optional Front Panel (order separately) with a different color to match the installation site. Select from black, white, and light gray.
Models with Instantaneous Contact Output
Models with instantaneous contact outputs have been added to the lineup for use with self-holding circuits and as auxiliary relays. These models are also convenient when replacing analog timers.
Universal NPN/PNP Input
DC 2-wire sensors can be connected for a wide range of input devices.
Waterproof, Dust-proof Structure (UL508 Type
4X and IP66)
Worry-free application is possible in locations subject to water. Note: When the Y92S-29 Waterproof Packing is used.
Key Protection
Select from any of seven protection patterns. Use the best one for the application.
New Modes
Modes, such as a stopwatch mode (Mode S), have been added. Select any of 15 modes.
Model Number Structure
Model Configuration
Black (standard)
White Light gray
You can replace the Front Panel.
H5CX Series
TypeStandard Type
H5CX-A Series
Economy Type
H5CX-L Series
Six-digit Type
H5CX-B Series
Model H5CX-A@-N H5CX-A11@-N H5CX-L8@-N H5CX-L8E@-N H5CX-B@-N
Function
Timer Yes Yes No
Twin timer Yes Yes No
Two-stage settings/
forecast output No No Yes
Operating modes Timer Mode: 11 modes
Twin Timer Mode: 4 modes
Timer Mode : 4 modes Twin Timer Mode : 2 modes
Timer Mode: 2 modes
Input NPN/PNP input NPN input None NPN/PNP input
External connections Screw terminal
block 11-pin socket 8-pin socket Screw terminal block
Present value display character color
Red, green, or
orange Red
Number of display digits 4 6
Instantaneous contacts None Provided None
Gate input Supported Not supported Supported
Model Number Legend
(Not all possible combinations of functions are available.)
H5CX-
@@@@@-N
– – – – –
1 2 3 4 5Ordering Information
List of Models
Note: 1. The functions that are provided depend on the model. Check detailed specifications before ordering. 2. Refer to page 33 and later for information on H5CX-B Timers (6-digit display).
Type Time specifications Operating modes External
connections Inputs Outputs Supply voltage Models
H5CX-A 0.001 to 9.999 s 0.01 to 99.99 s 0.1 to 999.9 s 1 to 9999 s 1 s to 99 min 59 s 0.1 to 999.9 min 1 to 9999 min 1 min to 99 h 59 min 0.1 to 999.9 h 1 to 9999 h Timer Mode A: Signal ON Delay I A-1: Signal ON Delay II A-2: Power ON Delay I A-3: Power ON Delay II b: Repeat cycle 1 b-1: Repeat cycle 2 d: Signal OFF Delay E: Interval F: Cumulative
Z: ON/OFF-duty-adjustable flicker S: Stopwatch
Twin Timer Mode toff: Flicker OFF Start 1 ton: Flicker ON Start 1 toff-1: Flicker OFF Start 2 ton-1: Flicker ON Start 2
Screw terminals Signal, Reset, Gate (NPN/ PNP inputs) Contact output (time-limit SPDT) 100 to 240 VAC H5CX-A-N 12 to 24 VDC/ 24 VAC H5CX-AD-N Transistor output (SPST) 100 to 240 VAC H5CX-AS-N 12 to 24 VDC/ 24 VAC H5CX-ASD-N 11-pin socket Contact output (time-limit SPDT) 100 to 240 VAC H5CX-A11-N 12 to 24 VDC/ 24 VAC H5CX-A11D-N Transistor output (SPST) 100 to 240 VAC H5CX-A11S-N 12 to 24 VDC/ 24 VAC H5CX-A11SD-N H5CX-L 8-pin socket Signal, Reset (NPN inputs) Contact output (time-limit SPDT) 100 to 240 VAC H5CX-L8-N 12 to 24 VDC/ 24 VAC H5CX-L8D-N Transistor output (SPST) 100 to 240 VAC H5CX-L8S-N 12 to 24 VDC/ 24 VAC H5CX-L8SD-N Timer Mode
A-2: Power ON Delay I b: Repeat cycle 1 E: Interval
Z: ON/OFF-duty-adjustable flicker Twin Timer Mode
toff: Flicker OFF Start 1 ton: Flicker ON Start 1
None Contact output (time-limit SPDT + instantaneous SPDT) Models with instantaneous contact outputs 100 to 240 VAC H5CX-L8E-N 12 to 24 VDC/ 24 VAC H5CX-L8ED-N H5CX-B 0.01 to 9999.99 s 1 s to 99 h 59 min 59 s 0.1 to 99999.9 min 0.1 to 99999.9 h A: Signal ON Delay I
F-1: Cumulative Screw terminals
Signal, Reset, Gate (NPN/ PNP inputs) Transistor output (DPST) 12 to 24 VDC H5CX-BWSD-N 4. Output type
* Can be used as a time-limit DPDT output.
5. Supply voltage
* The H5CX-BWSD-N is available only for 12 to 24 VDC. Symbol Meaning
None Contact output (time-limit SPDT) E Contact output (time-limit
SPDT + instantaneous SPDT) *
S Transistor output
Symbol Meaning
None 100 to 240 VAC 50/60 Hz D 12 to 24 VDC/24 VAC 50/60 Hz *
1. Type Classifier 2. External Connections 3. Settings
Symbol Meaning
A Standard type
B 6-digit type
L Economy type
Symbol Meaning
None Screw terminals
8 8-pin socket
11 11-pin socket
Symbol Meaning
None One stage
Accessories (Order Separately)
Front Panels (Replacement Parts)
Note: 1. You can change the color of the front panel when mounting the Timer. The Timer is shipped with a black (N1.5) Front Panel. 2. "TIMER" is printed on the front of Replacement Front Panels.
Soft Cover
Hard Cover
Flush Mounting Adapter
Waterproof Packing
Connection Sockets
Terminal Covers for P3G-08 and P3GA-11 Back-connecting Sockets
Models Color Applicable Timers Page Y92P-CXT4G Light gray (5Y7/1)
Four-digit models 12
Y92P-CXT4S White (5Y9.2 / 0.5)
Y92P-CXT4B Black (N1.5)
Models Remarks Page
Y92A-48F1 --- 12
Models Remarks Page
Y92A-48 --- 12
Models Remarks Page
Y92F-30 Included with models with terminal blocks.
12 Y92F-45
Use this Adapter to install the Timer in a cutout previously made for a DIN 72 x 72 mm device (panel cutout: 68 x 68 mm).
Models Remarks Page
Y92S-29 Included with models with terminal blocks. 12
Models Type Connectable Timers Remarks Page
P2CF-08 Front Connecting Socket H5CX-L8@ 13 P2CF-08-E Front Connecting Socket (Finger-safe Type)
Round crimp terminals cannot be used on Finger-safe Sockets. Use forked crimp terminals.
P2CF-11 Front Connecting Socket H5CX-A11@ P2CF-11-E Front Connecting Socket (Finger-safe Type)
Round crimp terminals cannot be used on Finger-safe Sockets. Use forked crimp terminals.
P3G-08
Back Connecting Socket
H5CX-L8@ A Y92A-48G Terminal Cover can be used with the Socket to create a finger-safe construction.
P3GA-11 H5CX-A11@
Models Remarks Page
• Switch the display color
* between red, green, and orange
to see the output status from a distance.
• Up/Down Keys for each digit enable easy operation.
• Cyclic control is easy with the Twin Timer and Variable
ON/OFF Duty modes.
* Not supported by the H5CX-A11@ or H5CX-L8@.
Specifications
Ratings
*1. Do not use the output from an inverter as the power supply. The ripple must be 20% maximum for DC power. *2. Inrush current will flow for a short time when the power supply is turned ON.
Inrush Current (Reference Values)
*3. The display is lit only when the power is ON. Nothing is displayed when power is OFF.
H5CX-A
@-N/-L@-N Digital Timers
Item Models H5CX-A@-N H5CX-A11@-N H5CX-L8@-N
Classification Standard Type Economy Type
Ratings Power supply voltage *1 • 100 to 240 VAC 50/60 Hz • 12 to 24 VDC/24 VAC 50/60 Hz Operating voltage
fluctuation range 85% to 110% of rated supply voltage (90% to 110% at 12 to 24 VDC)
Power consumption Approx. 6.2 VA at 100 to 240 VAC, Approx. 5.1 VA/2.4 W at 24 VAC/12 to 24 VDC *2
Mounting method Flush mounting Flush mounting, surface mounting, DIN track mounting
External connections Screw terminals 11-pin socket 8-pin socket
Degree of protection IEC IP66, UL508 Type 4X (indoors) for panel surface only and when Y92S-29 Waterproof Packing is used 4 digits
Digits
Time ranges 0.001 s to 9.999 s, 0.01 s to 99.99 s, 0.1 s to 999.9 s, 1 s to 9999 s, 1 s ti 99 min 59 s
0.1 m to 999.9 min, 1 min to 9999 min, 1 min to 99 h 59 min, 0.1 h to 999.9 h, 1 h to 9999 h
Timer mode Elapsed time (Up), remaining time (Down) (selectable)
Inputs
Input signals Signal, Reset, Gate
Signal, Reset
(no inputs on models with instantaneous contact outputs)
Input method
No-voltage Input ON impedance: 1 kΩ max. (Leakage current: 12 mA when 0 Ω) ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min. Voltage Input High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ) No-voltage input/voltage input (switchable)
No-voltage Input ON impedance: 1 kΩ max.
(Leakage current: 12 mA when 0 Ω) ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
Signal, reset, gate Minimum input signal width: 1 or 20 ms (selectable, same for all input)
Reset system Power reset (depending on output mode), external reset, manual reset, automatic reset (depending on output mode)
Power reset Minimum power-opening time: 0.5 s (except for A-3, b-1, F, ton-1, and toff-1 mode)
Reset voltage 10% max. of rated supply voltage
Sensor waiting time 250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Output
Output modes
A: Signal ON Delay I, A-1: Signal ON Delay II, A-2: Power ON Delay I, A-3: Power ON Delay II, b: Repeat Cycle 1, b-1: Repeat Cycle 2, d: Signal OFF Delay, E: Interval, F: Cumulative, Z: ON/OFF-duty-adjustable flicker, S: Stopwatch, toff: Flicker OFF Start 1, ton: Flicker ON Start 1, toff-1: Flicker OFF Start 2, ton-1: Flicker ON Start 2
Models with Instantaneous Contact Outputs
A-2: Power ON Delay I, b: Repeat Cycle 1, E: Interval, Z: ON/OFF-duty-adjustable flicker, toff: Flicker OFF Start 1, ton: Flicker ON Start 1
One-shot output
time 0.01 to 99.99 s
Control output
• Models with Contact Outputs
5 A at 250 VAC/30 VDC, resistive load (cos =1)
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value) • Transistor output: NPN open collector,
100 mA at 30 VDC max., residual voltage: 1.5 VDC max. (Approx. 1 V), Leakage current: 0.1 mA max.
Display method *3
7-segment, negative transmissive LCD; Present value: 12-mm-high characters,
(switchable between red, green, and orange) Set value: 6-mm-high characters,
green
7-segment, negative transmissive LCD; Present value: 12-mm-high characters, red Set value: 6-mm-high characters, green
Memory backup EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
Operating temperature range -10 to 55°C (-10 to 50°C if counters are mounted side by side) (with no icing or condensation)
Storage temperature range -25 to 70°C (with no icing or condensation)
Operating humidity range 25% to 85%
Case color Black (N1.5) (Optional Front Panels are available to change the Front Panel color to light gray or white.)
Attachments Waterproof packing, flush mounting
adapter, label for DIP switch settings Label for DIP switch settings
---Voltage Applied voltage Inrush current (peak value) Time
100 to 240 VAC 264 VAC 5.3 A 0.4 ms
12 to 24 VDC/24 VAC 26.4 VAC 6.4 A 1.4 ms
Characteristics
* Refer to Life-test Curve. Accuracy of operating time and setting error (including temperature and voltage influences)
Power-ON start: ±0.01% ±50 ms max. (See note 1.) Signal start: ±0.005%±0.03 ms max. (See note 1.)
Signal start for transistor output model: ±0.005%±3 ms max. (See note 1 and 2.)
If the set value is within the sensor waiting time at startup the control output of the H5CX will not turn ON until the sensor waiting time passes.
Note: 1. The values are based on the set value.
2. The value is applied for a minimum pulse width of 1 ms.
Insulation resistance
100 MΩ min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and between non-continuous contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between power supply and input circuits for H5CX-A11-N/-A11S-N
1,000 VAC, 50/60 Hz for 1 min between control output, power supply, and input circuits for H5CX-@SD-N
2,000 VAC, 50/60 Hz for 1 min between control output, power supply, and input circuits for other models
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage
3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC 1.5 kV for 24 VAC/12 to 24 VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/ 1 µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance
Destruction 10 to 55 Hz with 0.75-mm single amplitude each in three directions for
2 h each
Malfunction 10 to 55 Hz with 0.35-mm single amplitude each in three directions for
10 min each
Shock resistance
Destruction 300 m/s2 in three directions, three cycles
Malfunction 100 m/s2 in three directions, three cycles
Life expectancy
Mechanical 10,000,000 operations min. (under no load at 18,000 operations/h and
ambient temperature of 23°C)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800
operations/h and ambient temperature of 23°C) *
Weight Approx. 115 g (Timer only)
Life-test Curve (Reference
Values)
A maximum current of 0.15 A can be switched at 125 VDC (cosφ =1) and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected.
DC30V L/R=7ms AC250V/DC30V cosφ =1 AC250V cosφ =0.4 0 1 2 3 4 5 1,000 500 100 50 10 S w itching oper ations (× 10 4)
Applicable Standards
*1. The following safety standards apply to models with sockets (H5CX-A11@ or H5CX-L8@).
cUL (Listing): Applicable when an OMRON P2CF (-E) Socket is used. cUR (Recognition): Applicable when any other socket is used.
*2. Excluding the H5CX-ASD-N/-A11SD-N/-L8SD-N.
I/O Functions
For details, refer to the timing charts on page 20 and page 29.
*1. The H5CX-L8E@ does not have an input. *2. The H5CX-L@ does not have a gate input.
Response Delay Time When Resetting (Transistor Output)
The following table shows the delay from when the reset signal is input until the output is turned OFF.
(Reference value)
Approved safety standards
UL508/Listing, UL50 Type 4X for indoor use (enclosure rating), CSA C22.2 No. 14 *1,
conforms to EN61812-1 (Pollution degree 2/overvoltage category III) B300 PILOT DUTY
1/4 HP 120 VAC, 1/3 HP, 240 VAC, 5 A resistive load VDE0106/P100
CCC: Pollution degree 2, Overvoltage category II *2
EMC
(EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 2) 8 kV air discharge (level 3)
Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3); 10 V/m (Pulse-modulated, 900 MHz 5 MHz) (level 3) Immunity Conducted Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3); 1 kV I/O signal-line (level 4)
Immunity Surge: EN61000-4-5: 1 kV line to lines (power and output lines) (level 3); 2 kV line to ground (power and output lines) (level 3) Immunity Voltage Dip/Interruption: EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Inputs *1
Start signal Normally functions to start timing.
In modes A-2 and A-3, disable timing. In mode S, starts and stops timing.
Reset
• Resets present value. (In elapsed time mode, the present value returns to 0; in remaining time mode, the present value returns to the set value.)
• Count inputs are not accepted and control output turns OFF while reset input is ON. • Reset indicator is lit while reset input is ON.
Gate *2 Disables timing. (If a reset occurs while the gate input is ON, a reset will be performed.)
Outputs Control output (OUT) Outputs take place according to designated operating mode when timer reaches corresponding set value.
Minimum reset signal width Output delay time
1 ms 0.8 to 1.2 ms
Connections
Block Diagram
Note: Basic insulation is provided between the power supply circuit and the input circuits. However, basic insulation is not provided in the
H5CX-@D-N.
Terminal Arrangement
Confirm that the power supply meets specifications before use.
H5CX-A-N/-AD-N H5CX-AS-N/-ASD-N H5CX-A11-N/-A11D-N H5CX-A11S-N/-A11SD-N H5CX-L8-N/-L8D-N H5CX-L8S-N/-L8SD-N H5CX-L8E-N/-L8ED-N Output circuit (See note.) Internal control circuit Display circuit
Key switch circuit Input circuits Power supply circuit (Basic insulation) (Basic insulation) 6 7 8 9 0V 1 2 3 4 5 (-) (+) Contact output
Reset Signal Gate
Terminals 1 and 6 of the H5CX-AD-N are connected internally.
6 7 8 9
0V
1 2 3 4 5
(-) (+)
Transistor output
Reset Signal Gate
Terminals 1 and 6 of the H5CX-ASD-N are connected internally.
6 7 8 9 10 11 1 2 3 4 5 0V Reset Signal
Gate Internal circuit
Unused
Unused
Contact output
(-) (+)
Terminals 2 and 3 of the H5CX-A11D-N are connected internally. 6 7 8 9 10 11 1 2 3 4 5 0V Reset Signal
Gate Internal circuit
Unused
Unused
Transistor output
(-) (+)
Terminals 2 and 3 of the H5CX-A11SD-N are connected internally. 4 3 2 1 8 7 6 5 0V Signal Reset Internal circuit Contact output (-) (+)
Terminals 1 and 2 of the H5CX-L8D-N are connected internally.
4 3 2 1 8 7 6 5 0V Signal Reset Internal circuit Unused Transistor output (-) (+)
Terminals 1 and 2 of the H5CX-L8SD-N are connected internally.
Transistor Output
• The transistor output of
Input Circuits
Signal, Reset, and Gate Input
Input Connections
The inputs are no-voltage (closed or open) inputs or voltage inputs except for the H5CX-L8@. (The inputs of the H5CX-L8@ are no-voltage inputs only. The H5CX-L8E@ does not have an input.)
No-voltage Inputs (NPN Inputs)
Voltage Inputs (PNP Inputs)
The inputs of the H5CX-L8@ are no-voltage inputs only.
Voltage Input Signal Levels
Note: 1. The DC voltage must be 30 VDC max.
2. Input resistance: Approx. 4.7 kΩ
Open Collector
Voltage Output
Contact Input
DC Two-wire Sensor
No-contact Input (NPN Transistor)
No-contact Input (PNP Transistor)
Contact Input
High level (Input ON): 4.5 to 30 VDC Low level (Input OFF): 0 to 2 VDC
Internal circuit IN +14 V 1 kΩ Internal circuit IN Approx. 4.7 kΩ
No-voltage Inputs (NPN Inputs)
Voltage Inputs (PNP Inputs)
H5CX-A@ -H5CX-A11@ H5CX-L8@ 6 7 8 9 3 7 6 5 1 3 4 PLC or sensor
Note: Operate with transistor ON
0 V f
o
r inputs
Reset input Signal input Gate input
H5CX-A@ H5CX-A11@ H5CX-L8@ -6 7 8 9 3 7 6 5 1 3 4 Sensor
Note: Operate with transistor ON
0 V f
o
r inputs
Reset input Signal input Gate input
H5CX-A@ -H5CX-A11@ H5CX-L8@ 6 7 8 9 3 7 6 5 1 3 4
Note: Operate with relay ON
0 V f
or inputs
Reset input Signal input Gate input
H5CX-A@ -H5CX-A11@ H5CX-L8@ 6 7 8 9 3 7 6 5 1 3 4
Note: Operate with transistor ON
0 V f
or inputs
Reset input Signal input Gate input
Applicable Two-wire Sensor
• Leakage current: 1.5 mA max. • Switching capacity: 5 mA min. • Residual voltage: 3.0 VDC max. • Operating voltage: 10 VDC
No-voltage Input Signal Levels
Note: The DC voltage must be 30 VDC max.
No-contact input
Short-circuit level Transistor ON • Residual voltage: 3 V max. • Impedance when ON: 1 kΩ max.
(The leakage current is approx. 12 mA when the impedance is 0 Ω.)
Open level Transistor OFF • Impedance when OFF: 100 kΩ min.
Contact input Use contacts which can adequately switch 5 mA at 10 V
H5CX-A@ H5CX-A11@
6 7 8 9
3 7 6 5
Sensor
Note: Operate with transistor OFF
0 V f
o
r inputs
Reset input Signal input Gate input
H5CX-A@ H5CX-A11@
6 7 8 9
3 7 6 5
Sensor
Note: Operate with transistor ON
0 V f
o
r inputs
Reset input Signal input Gate input
H5CX-A@ H5CX-A11@
6 7 8 9
3 7 6 5
Note: Operate with relay ON
0 V f
or inputs
Nomenclature
Dimensions
(unit: mm)
Digital Timers
Digital Timers
OFF ON 12mm 6mm 1 3 2 8 9 5 4 6 7 10 11 12 13Display Section
1. Key Protect Indicator (orange)
2. Control Output Indicator (orange)
Front View
Note: There is no DIP switch on the
H5CX-L8@. Character Size
for Present Value Display
Character Size for Set Value Display
3. Reset Indicator
(orange)Operation Key
Switches
8. Mode Key
(Changes modes and setting items)
9. Reset Key
(Resets present value and output)
10. Up Keys 1 to 4
11. Down Keys 1 to 4
12. Key-protect Switch
13. DIP Switch
6. Set Value Display
(Sub-display)(Character height: 6 mm, green)
7. Set Value 1, 2 Indicator
(green)4. Present Value Display
(Main display)(Character height: 12 mm, red *)
* Characters on models with screw terminals (H5CX-A@) can be switched between red, green, and orange.
5. Time Unit Indicators
(Color is same as present value display.) (If the time range is 0 min, 0 h, 0.0 h, or 0 h 0 min, these indicators flash to indicate timing operation.) 1 2 3 4 5 6 7 8 OFF (Disabled) (Enabled)ON (Default setting) 78 6 44.8×44.8 48×48
H5CX-A-N/-AS-N (Flush Mounting Models)
Note: M3.5 terminal screw (effective length: 6 mm)
59 6
44.8×44.8 48×48
H5CX-AD-N/-ASD-N (Flush Mounting Models)
Note: M3.5 terminal screw (effective length: 6 mm)
H5CX-A11
@-N
(Flush Mounting/Surface Mounting Models)
Dimensions with Flush Mounting Adapter
58 48 7.5 76.5 (51) Y92S-29 (provided) Waterproof Packing Y92F-30 (provided) Flush Mounting Adapter PanelH5CX-A-N/-AS-N (Provided with Adapter and Waterproof Packing)
Panel CutoutsPanel cutouts areas shown below. (according to DIN43700).
Note: 1. The mounting panel thickness
should be 1 to 5 mm.
2. To allow easier operation, it is
recommended that Adapters be mounted so that the gap between sides with hooks is at least 15 mm (i.e., with the panel cutouts separated by at least 60 mm).
3. It is possible to mount Timers
side by side, but only in the direction without the hooks. (However, if Timers are mounted side by side, water resistance will be lost.)
Dimensions with Front
Connecting Socket
* These dimensions vary with the type of DIN track
(reference value). 60 min. 60 min. 45+0.6 0 45+0.6 0 15 min. A A=(48n-2.5)
With Y92A-48F1 attached. A={48n-2.5+(n-1)×4}
With Y92A-48 attached. A = (51n - 5.5)
n Units mounted side-by-side
+1 –0 +1 –0 +1 –0 103.2 100.9 H5CX -A11@-N
P2CF-11(-E) (order separately) Front Connecting Socket
*
H5CX -L8@-N
P2CF-08(-E) (order separately) Front Connecting Socket
92.3 90 * 58 48 7.5 57.5 (51) Y92S-29 (provided) Waterproof Packing Y92F-30 (provided) Flush Mounting Adapter Panel
H5CX-AD-N/-ASD-N (Provided with Adapter and Waterproof Packing)
58
48 7.5 89.9 (51)
Y92S-29 (order separately) Waterproof Packing
Y92F-30 (order separately) Flush Mounting Adapter
P3GA-11 (order separately) Back-connecting Socket Panel
H5CX-A11
@-N (Adapter and Waterproof Packing Ordered Separately)
H5CX-L8
@-N (Adapter and Waterproof Packing Ordered Separately)
58
48 7.5 84.8 (51)
Y92F-30 (order separately)
Flush Mounting Adapter P3G-08 (order separately) Back-connecting Socket Panel
Y92S-29 (order separately) Waterproof Packing
Accessories (Order Separately)
Front Panel (Replacement Part)
You can change the color of the front panel when mounting the Timer.
The Timer is shipped with a black (N1.5) Front Panel.
Protecting the Timer in Environments Subject to Oil
The Waterproof Packing will deteriorate, harden, and shrink depending on the application environment. To ensure maintaining the IP@6, UL Type 4X waterproof level, periodically replace the Waterproof Packing. The periodic replacement period will depend on the application environment. You must confirm the proper
replacement period. Use 1 year or less as a guideline. If the Waterproof Packing is not replaced periodically, the waterproof level will not be maintained.
It is not necessary to mount the Waterproof Packing if waterproof construction is not required.
Note:
Depending on the operating environment, the condition of resin products may deteriorate, and may shrink or become harder. Therefore, it is recommended that resin products are replaced regularly.
Y92P-CXT4S
Cover for Timer with 4 Digits White (5Y9.2/0.5)
Y92P-CXT4G
Cover for Timer with 4 Digits Light gray (5Y7/1)
Y92P-CXT4B
Cover for Timer with 4 Digits Black (N1.5)
Replacement Method
The Front Panel is attached to the Terminal with tabs in four locations. To remove the Front Panel, open the tabs and pull the Front Panel forward.
To attach the Front Panel, press it onto the Timer so that all four tabs lodge into the groves on the body of the Timer.
Tabs
Grooves
The H5CX's panel surface is water-resistive (IP@6, UL Type 4X) and so even if drops of water penetrate the gaps between the keys, there will be no adverse effect on internal circuits. If, however, there is a possibility of oil being present on the operator's hands, use the Soft Cover. The Soft Cover ensures protection equivalent to IP54 against oil. Do not, however, use the H5CX in locations where it would come in direct contact with oil.
Soft Cover
Y92A-48F1
Hard Cover
Y92A-48
Y92F-45
Use this Adapter to install the Timer in a cutout previously made for a DIN 72 x 72 mm device (panel cutout: 68 x 68 mm).
Flush Mounting Adapter
Y92F-30
Order the Flush Mounting Adapter separately if it is lost or damaged. Note: A Flush Mounting Adapter is included with models with screw terminals.
Waterproof Packing
Y92S-29
Note: The Waterproof Packing is included with models with screw terminals.Order the Waterproof Packing separately if it is lost or damaged. The Waterproof Packing can be used to achieve IP66 protection.
Connection Sockets
Front-connecting Sockets
Note: Round crimp terminals cannot be used on Finger-safe Sockets. Use forked crimp terminals.
Back-connecting Sockets
Note: A Y92A-48G Terminal Cover can be used with the Socket to create a finger-safe construction.
Model Dimensions Terminal arrangement
and internal connections
Mounting hole dimensions P2CF-08
(Top View)
Note: The Socket can
also be mounted to DIN track. P2CF-08-E
(Finger Safe Terminal)
P2CF-11
(Top View)
Note: The Socket can
also be mounted to DIN track. P2CF-11-E
(Finger Safe Terminal Type)
Model Dimensions Terminal arrangement
and internal connections P3G-08 (Bottom View) P3GA-11 (Bottom View) 4 70 max. Two, 4.5-dia. holes
Eight, M3.5 x 7.5 sems screws 7.8
20.3 max. 4.5 3 50 max. 35.4 6 5 4 3 7 8 1 2 40±0.2
Two, M4 or 4.5-dia. holes
1 2 7 8 4 3 6 5 P2CF-08-E 10A250VAC RESISTIVE 4 70 max. Two, 4.5-dia. holes
Eight, M3.5 x 7.5 set screws 7.8
21.5 max. 20.3 19 4.5 35.4 1.3 3 5 50 max. 40±0.2 4 70 max. 50 max.
Two, 4.5-dia. holes
Eleven, M3.5 x 7.5 sems screws 7.8
31.2 max. 4.5 3 35.4 8 7 6 5 10 11 1 2 9 3 4 40±0.2
Two, M4 or 4.5-dia. holes
10 11 1 2 7 8 6 5 3 4 9 P2CF-11-E 10A250VAC RESISTIVE 4 70 max. 50 max. 40±0.2
Two, 4.5-dia. holes
Eleven, M3.5 x 7.5 set screws 7.8
31.2 max. 30 4.5 35.4 1.2 3 5 27 dia 4.9 17 45 45 6 5 4 3 7 8 1 2 27 dia 4.5 16.3 6.2 25.6 45 45 8 7 6 4 3 9 5 10 11 1 2
Terminal Covers for P3G-08 and P3GA-11 Back-connecting Sockets
Note: The Terminal Cover can be used with a Back-mounting Socket (P3G-08 or P3GA-11) to create a finger-safe construction.
Optional Products for Track Mounting
Note: Order Spacers in increments of 10.
Model Dimensions Y92A-48G Y92A-48G UP P C 34 Twelve, 6.4 dia 47.7×47.7 48×48 27.6 24.6 16.5 47.4 1 35±0.3 7.3±0.15 27±0.15 4.5 15 25 10 25 25 10 25 15 (5) *
1,000 (500) * * The values shown in parentheses are for the PFP-50N.
Mounting Track
PFP-100N
PFP-50N
15 25 25 1,000 4.5 25 10 25 15 1 24 27 35±0.3 16 1.5 29.2 10Mounting Track
PFP-100N2
4.8 1.3 35.5 35.3 1.8 1 1.8 10 6.2 M4 spring washer 50 11.5 M4 x 8 pan head screw 10End Plate
PFP-M
5 16 12 44.3 34.8 16.5Spacer
PFP-S
Timer
Operating Procedures
Setting Procedure Guide
Settings for Timer Operation
*Use the following settings.
Settings for Twin Timer Operation
*Refer to page 25.
* It is not necessary to mount the Waterproof Packing if waterproof construction is not required.
Operating Procedures for Timer Function
After making DIP switch settings for basic operation, advanced functions can be added using the operation keys on the front panel. Refer to on page 16 for details.
Key-protect Switch 1 2 3 4 5 6 7 8 OFF ON Disabled Enabled ON OFF ON OFF ON OFF ON OFF ON OFF OFF ON ON OFF OFF ON ON OFF OFF OFF OFF ON ON ON Refer to the table on
the right.
Refer to the table on the right. DIP switch settings
Time range
Output modes Timer mode Input signal width
UP DOWN 20 ms 1 ms 0.001 s to 9.999 s 0.01 s to 99.99 s 0.1 s to 999.9 s 1 s to 9999 s 0 min 01 s to 99 min 59 s 0.1 min to 999.9 min 0 h 01 min to 99 h 59 min 0.1 h to 999.9 h OFF ON OFF ON OFF OFF ON ON
Mode A: Signal ON delay 1
(Timer resets when power comes ON.) Mode A-2: Power ON delay 1 (Timer resets when power comes ON.) Mode E: Interval
(Timer resets when power comes ON.) Mode F: Cumulative
(Timer does not reset when power comes ON.)
Note: All the pins are factory-set to OFF.
Be sure to turn ON pin 1 of the DIP switch.
Changes to DIP switch settings are enabled when the
power is turned ON.
(Set the DIP switch while the power is OFF.)
Step1
Step2
Settings for basic functions can be performed with just the DIP switch.
Note: There is no DIP switch on the H5CX-L8
@. Go to .
Be sure to set pin 1 to ON when using the DIP switch.
Item OFF ON Pin 2 Pin 3 Pin 4 Time range
1 2 3 4 5 6 7 8
Pin 6 Output mode
Pin 5
Timer
Run mode Power ON
Function setting mode
Set the time range using the keys.
Set the timer mode using the keys.
Set the output mode using the keys.
Set the input signal width using the keys.
Set the NPN/PNP mode using the keys.
Set the display color using the keys.
Set each digit for the output time using the corresponding keys. For details, refer to the Time Range List.
(If the output time is set to 0.00, is displayed.)
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
Display Set Value Time Range List
0.01 s to 99.99 s (default setting) 0.1 s to 999.9 s 1 s to 9999 s 0 min 01 s to 99 min 59 s 0.1 min to 999.9 min 1 min to 9999 min 0 h 01 min to 99 h 59 min 0.1 h to 999.9 h 1 h to 9999 h 0.001 s to 9.999 s
~
Time range Timer mode Output modes Output time Input signal NPN/PNP input s s h s (DOWN) (UP) (1ms) (20ms)(A-1) (A-2) (A-3) (b) (b-1) (d) (E) (F) (Z) (S)
(A)
(0.01s) (99.99s) (Output hold)
Note:Displayed for modes A, A-1, A-2, A-3, b, b-1 and S only.
Note:Only modes A-2, b, E, and Z can be selected for models with instantaneous contact outputs.
(PNP input) (NPN input)
Note:Only displayed for the H5CX-A@ and H5CX-A11@.
3 s min. *2 3 s min. *1
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting). If pin 1 of the DIP switch is set to ON, the setting items indicated in will not be displayed.
Step2
Settings that cannot be performed with the DIP switch are performed with the operation keys.
• Change to Function Setting Mode.
Note:Not displayed for models with instantaneous contact outputs.
F
u
nction setting mode
…… s
20ms
1ms
pnp
npn
down
up
z
a-1
a
a-2
99.99
0.01
hold
hold
a-3
b
b-1
d
e
f
s
Timer
*1 To previous page From previous page Output ON count alarm set value/ monitor value Key protect level Set value upper limit (KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7) Instantaneous output 1 (OUT1) ON count alarm set value Instantaneous output 2 (OUT2) ON count alarm set value (9999 x 1000 times) (0 x 1000 times) (9999 x 1000 times) (0 x 1000 times)Note: The monitor value is only displayed.
It cannot be set. Output ON count alarm set value Output ON count monitor value (9999 x 1000 times) (0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Note: The monitor value is only displayed.
It cannot be set. Instantaneous output 1 (OUT1) ON count monitor value Instantaneous output 2 (OUT2) ON count monitor value (9999) (1)
9999
0
9999
0
9999
0
9999
kp-2
kp-1
kp-3
kp-4
kp-5
kp-6
kp-7
1
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
F
u
nction setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys.
*1. Set each digit for the output time using the corresponding keys.
~
~
Timer
Explanation of Functions
Operating Procedures for Timer Function
Items marked with stars (
) can be set using the DIP switch.Time Range (
timr)
Set the range to be timed in the range 0.001 s to 9,999 h. Settings of type ---- h (9,999 h) and ---- min (9,999 min) cannot be made with the DIP switch. Use the operation keys if these settings are required.
Timer Mode (
timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode. In UP mode, the elapsed time is displayed, and in DOWN mode, the remaining time is displayed.
Output Mode (
outm)
Set the output mode.
The possible settings are A, A-1, A-2, A-3, b, b-1, d, E, F, Z and S. Only output modes A, A-2, E, and F can be set using the DIP switch. Use the operation keys if a different setting is required.
(For details on output mode operation, refer to "Timing Charts" on
page 20.)
Output Time (
otim)
When using one-shot output, set the output time for one-shot output (0.01 to 99.99 s).
One-shot output can be used only if the selected output mode is A, A-1, A-2, A-3, b, b-1 or S.
If the output time is set to 0.00,
hold
is displayed, and the output is held.Input Signal Width (
iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset, and gate inputs.
The same setting is used for all external inputs (signal, reset, and gate inputs).
If contacts are used for the input signal, set the input signal width to 20 ms.
Processing to eliminate chattering is performed for this setting.
NPN/PNP Input Mode (
imod)
Select either NPN input (no-voltage input) or PNP input (voltage input) as the input format.
Set an NPN input when using a 2-wire sensor.
For details on input connections, refer to "Input Connections" on
page 9.
Display Color (
colr)
(Terminal block model: H5CX-A
@ only)
Set the color used for the present value.
Key Protect Level (
kypt)
Set the key protect level.
Refer to “Key Protect Level” on page 36.
Instantaneous/Time-limit (
otmd)
Set the contact output to time-limit SPDT + instantaneous SPDT or time-limit SPDT operation.
Set Value Upper Limit (
sl-h)
Set the upper limit for the set value when it is set in Run Mode. The limit can be set to between 1 and 9999.
This setting does not apply to the ON duty in Z mode.
Output ON Count Alarm Set Value (
on-a)
Set the alarm value for the output ON count.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000 (9,999,000 times). Only the underlined values are set. The alarm will be disabled if 0 is set.
If the total ON count of the output exceeds the alarm set value,
e3
will be displayed on the Timer to indicate that the output ON count alarm value was exceeded. Refer to “Self-diagnostic Function” on page32 for information on the
e3
display.ON Count Alarm Set Values for Outputs 1 and 2 (OUT1
and OUT2) (
on1a and on2a)
Set the ON count alarm values for the outputs 1 and 2.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000 (9,999,000 times). Only the underlined values are set. The alarm will be disabled if 0 is set.
If the total ON count of instantaneous output 1 or 2 exceeds the alarm set value,
e3
will be displayed on the Timer to indicate that the output ON count alarm value was exceeded. Refer to “Self-diagnosticFunction” on page 32 for information on the
e3
display.Output ON Count Monitor Value (
on-c)
The monitor value is only displayed. It cannot be set. The output ON count will be 1,000 times the displayed value.
Output OFF Output ON
red
Red (fixed)grn
Green (fixed)org
Orange (fixed)r-g
Red Greeng-r
Green Redr-o
Red Orangeo-r
Orange Redg-o
Green OrangeTimer
Operation in Run Mode
Operating Procedures for Timer Function
Present Value and Set Value
These items are displayed when the power is turned ON. The present value is displayed in the main display and the set value is displayed in the sub-display.
The values displayed will be determined by the settings made for the time range and the timer mode in function setting mode.
Present Value and ON Duty Ratio (Output Mode = Z)
The present value is displayed in the main display and the ON duty ratio is displayed in the sub-display. Set the ON duty ratio used in ON/ OFF-duty-adjustable flicker mode (Z) as a percentage.The output accuracy will vary with the time range, even if the ON duty ratio setting is the same. Therefore, if fine output time adjustment is required, it is recommended that the time range for the cycle time is set as small as possible.
Examples: 1. When Time Range = - - - - s (9999 s)
Rounded off to the nearest integer (because of the time range setting) → ON time = 6 s
2. When Time Range = - -. - - s (99.99 s)
Rounded off to 2 decimal places (because of the time range setting) → ON time = 6.20 s
If a cycle time is set, cyclic control can be performed in ON/OFF-duty-adjustable flicker mode simply by changing the ON duty ratio.
Present Value and Cycle Time (Output Mode = Z)
The present value is displayed in the main display and the cycle time is displayed in the sub-display. Set the cycle time.
Present value Set value Present value ON duty ratio Present value Cycle time
Set each digit for the output time using the corresponding keys.
Note: H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Set each digit for the output time using the corresponding keys. (The keys for the 4th digit cannot be used.)
Set each digit for the output time using the corresponding keys. When Output Mode Z Is Selected
ON time = Cycle time x ON duty ratio (%) 100
20(s) x 31(%) = 6.2(s) 100
20.00(s) x 31(%) = 6.200(s) 100
Elapsed cycle time
ON duty set as a percentage Up/Down keys used for analog adjustment of the ON duty
ON duty (%) Cycle time Control output Open Close Opening/ closing valve ON duty Fully closed↔ Fully open 0%↔100%
Timer
Timing Charts
Operating Procedures for Timer Function
Models without Instantaneous Contact Outputs
The gate input is not included in the H5CX-L8@ models. Either one-shot output or sustained output can be selected. Mode A: Signal ON delay 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-1: Signal ON delay 2 (Timer resets when power comes ON.) Basic operation Detailed operation
Timing starts when the start signal goes ON, and resets when the start signal goes OFF.
While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-2: Power ON delay 1 (Timer resets when power comes ON.) Basic operation Detailed operation
Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input).
The control output is controlled using a sustained or one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-3: Power ON delay 2 (Timer does not reset when power comes ON.)
Power Output
*
Start signal input Timing Power Start signal Gate t t Reset Control output Set value 0 Set value UP DOWN 0 Timing diag ra m Power Output Start signal input Timing t 0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m Power Output Timing t 0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra mTimer
Mode b: Repeat cycle 1 (Timer resets when power comes ON.) Basic operation Detailed operation
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start).
While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output type).
Sustained Output
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. The control output is turned ON when time is up. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output type).
One-shot Output
Mode b-1: Repeat cycle 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start).
While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output type).
Sustained Output
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. The control output is turned ON when time is up. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output type). One-shot Output Power Output
*
Start signalinput Timing Timing Timing Timing
0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m Power Output
*
Start signalinput Timing Timing Timing Timing
t t 0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m Power Output
*
Start signalinput TimingTiming SustainedTimingTiming Timing
0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m Power Output
*
Start signalinput TimingTimingSustainedTimingTiming Timing
t t t t t 0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m
Timer
Mode d: Signal OFF delay (Timer resets when power comes ON.) Basic operation Detailed operation
* Start signal input is enabled during timing.
The control output is ON when the start signal is ON (except when the power is OFF or the reset is ON). The timer resets when the time is up.
Note: Output functions only during start signal input
when setting is 0.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is enabled during timing.
Timing starts when the start signal comes ON. The timer resets when the time is up.
While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Note: Output is disabled when the setting is 0.
Mode F: Cumulative (Timer does not reset when power comes ON.) Basic operation Detailed operation
Start signal enables timing (timing is stopped when the start signal is OFF or when the power is OFF). A sustained control output is used.
Note: Output is instantaneous when setting is 0.
When the H5CX is used with power start in mode F mode or F-1 (i.e., cumulative operation with output on hold), there will be a timer error (approximately 100 ms each time the H5CX is turned ON) due to the characteristics of the internal circuitry. Use the H5CX with signal start if timer accuracy is required.
Mode Z: ON/OFF-duty-adjustable flicker (Timer resets when power comes ON.) Basic operation Detailed operation
Output
*
Start signal input Timing Power 0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m Power Output*
Start signal input Timing 0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m Power Output Start signalinput Timing Sustained Timing 0 0 Power Start signal Gate Reset Control output Set value Set value UP DOWN Timing diag ra m Power Power
Timer
Models with Instantaneous Contact Outputs
Either one-shot output or sustained output can be selected.Note: H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode S: Stopwatch (Timer resets when power comes ON.)
Basic operation Detailed operation
The signal starts and stops timing.
The display is held and timing is continued if the reset or gate input is received during timing operation. The timer resets if the reset or gate input is received when the timing operation is stopped.
Note: Output is instantaneous when setting is 0.
Mode A-2: Power ON delay (Timer resets when power comes ON.) Basic operation Detailed operation
The Timer starts when the power comes ON or when the reset input goes OFF.
Note: Output is instantaneous when setting is 0.
Mode b: Repeat cycle 1 (Timer resets when power comes ON.) Basic operation Detailed operation
The Timer starts when the power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short. Set the value to at least 100 ms.
Power Start signal input Gate/Reset Display (for elapsed time) *
flashes * Timing RST 9999 Set time 0 Set time 0 UP DOWN Power Start signal Gate/Reset Timing diag ra m Output Time-limit output Power Timing Instantaneous output t-a Reset Key Time-limit contacts, NC Time-limit contacts, NO Instantaneous contacts, NC Instantaneous contacts, NO t t-a t-a Rt Rt t
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.) Power Instantaneous output Time-limit output Power
t (time) t (time) t (time) t (time)
t-a t t t t-a Rt t t t t-a t-a Rt t-a
Reset Key Time-limit contacts, NC One-shot Output Time-limit contacts, NO Time-limit contacts, NC Instantaneous contacts, NC Time-limit contacts, NO Instantaneous contacts, NO
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.) Power
Timer
Note: H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when the reset input goes OFF.
Note: Output is not instantaneous when setting is 0.
Mode Z: ON/OFF-duty adjustable flicker (Timer resets when power comes ON.) Basic operation Detailed operation
The Timer starts when the power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short. Set the value to at least 100 ms. Instantaneous output Time-limit output Power Timing t-a Reset Key Time-limit contacts, NC Time-limit contacts, NO Instantaneous contacts, NC Instantaneous contacts, NO t t-a t-a Rt Rt t
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.) Power
Timing (cycle time) Timing (cycle time)
Timing
(ON duty) (ON duty)Timing
Instantaneous output Time-limit output Power
t-a t t-a Rt t t-a Rt t-a
dty dty dty dty
t-a
t = Set time, dty = ON duty time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.) Reset Key Time-limit contacts, NC Time-limit contacts, NO Instantaneous contacts, NC Instantaneous contacts, NO Power
Twin Timer
Setting Procedure Guide
Operating Procedures for Twin Timer Function
After making DIP switch settings for basic operation, advanced functions can be added using the operation keys on the front panel. Refer to on page 26 for details.
Hold down for 1 s min.
Hold down for 1 s min.
Timer
Press the or Key to switch to a Twin Timer.
Twin timer Key-protect Switch Run mode Power ON Timer/twin timer selection mode 1 + 1 +
tim
1 2 3 4 5 6 7 8 OFF ONStep2
Settings for basic functions can be performed with just the DIP switch.
Note: There is no DIP switch on the H5CX-L8
@. Go to .
Step1
Switching to a Twin Timer
Disabled Enabled OFF
ON OFF ON OFF OFF ON ON Refer to the table on the right.
Refer to the table on the right. DIP switch settings
OFF time range
ON time range Output mode Timer mode Input signal width
UP DOWN
Flicker OFF start Flicker ON start
20 ms 1 ms 0.01 s to 99.99 s 0.1 s to 999.9 s 1 s to 9999 s 0 min 01 s to 99 min 59 s OFF ON OFF ON OFF OFF ON ON 0.01 s to 99.99 s 0.1 s to 999.9 s 1 s to 9999 s 0 min 01 s to 99 min 59 s Note: All the pins are factory-set to OFF.
Step3
Be sure to turn ON pin 1 on the DIP switch.
Changes to DIP switch settings are enabled when the power is turned ON.
(Perform DIP switch settings while the power is OFF.)
Item OFF ON Pin 2 Pin 3 OFF time range
ON time range Pin 5 Pin 4 1 2 3 4 5 6 7 8
Be sure to set pin 1 to ON when using the DIP switch.
twn
Twin Timer
To switch to twin timer operation, use the procedure given below. For details, refer to page 31.
Run mode Power ON
Function setting mode
(1 ms) (20 ms)
(PNP input) (NPN input)
Note: Displayed only for the H5CX-A@ and H5CX-A11@.
3 s min. *2 3 s min. *1
Step3
s s h s s s h s (DOWN) (UP) OFF time range ON time range Timer mode ON/OFF start mode Input signal width NPN/PNP input( ) ( ) ( ) ( )
Display Set Value Time Range List
0.01 s to 99.99 s (default setting) 0.1 s to 999.9 s 1 s to 9999 s 0 min 01 s to 99 min 59 s 0.1 min to 999.9 min 1 min to 9999 min 0 h 01 min to 99 h 59 min 0.1 h to 999.9 h 1 h to 9999 h 0.001 s to 9.999 s Flicker OFF start 1 Flicker On Start 1 Flicker OFF start 2 Flicker On Start 2
Note:Not displayed for models with instantaneous contact outputs.
Note:Only Flicker OFF Start 1 or Flicker ON Start 1 can be selected for the H5CX-L8E@.
20ms
up
down
1ms
pnp
npn
…… s …… stoff
ton
tof1
ton1
For details, refer to Time Range List.
For details, refer to Time Range List.
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting). If pin 1 of the DIP switch is set to ON, the setting items indicated in will not be displayed.
Settings that cannot be performed with the DIP switch are performed with the operation keys.
• Change to Function Setting Mode.
F
u
nction setting mode
Set the OFF time range using the keys.
Set the ON time range using the keys.
Set the timer mode using the keys.
Set the twin timer output mode using the keys.
Set the input signal width using the keys.
Set the NPN/PNP input mode using the keys.
Set the display color using the keys.
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
Twin Timer
~
~
~
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7) (9999 x 1000 times) (0 x 1000 times) (9999 x 1000 times) (0 x 1000 times) (9999 x 1000 times) (0 x 1000 times)Note: The monitor value is only displayed.
It cannot be set.
Note: The monitor value is only displayed.
It cannot be set.
Note: The monitor value is only displayed.
It cannot be set. To previous page From previous page F u
nction setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys. Set value
upper limit 1
Set the digits for the set value limit using the corresponding keys. Set value upper limit 2 Key protect level Output ON count alarm set value/ monitor value Output ON count alarm set value Output ON count monitor value Instantaneous output 1 (OUT1) ON count alarm set value Instantaneous output 2 (OUT2) ON count alarm set value Instantaneous output 1 (OUT1) ON count monitor value Instantaneous output 2 (OUT2) ON count monitor value
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
*1. Set the digits for the output ON alarm set value using the corresponding
keys. *1 (9999) (1)
9999
0
9999
0
9999
0
9999
kp-2
kp-1
kp-3
kp-4
kp-5
kp-6
kp-7
1
(9999) (1)9999
1
Twin Timer
Explanation of Functions
Operating Procedures for Twin Timer Function
Items marked with stars (
) can be set using the DIP switch.OFF Time Range (
oftr)
Set the time range for the OFF time in the range 0.000 s to 9,999 h. Only settings of type --.-- s (99.99 s), ---.- s (999.9 s), ---- s (9,999 s), and -- min -- s (99 min 59 s) can be made with the DIP switch. Use the operation keys if another type of setting is required.
ON Time Range (
ontr)
Set the time range for the ON time in the range 0.001 s to 9,999 h. Only settings of type --.-- s (99.99 s), ---.- s (999.9 s), ---- s (9,999 s), and -- min -- s (99 min 59 s) can be made with the DIP switch. Use the operation keys if another type of setting is required.
Timer Mode (
timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode. In UP mode, the elapsed time is displayed, and in DOWN mode, the remaining time is displayed.
ON/OFF Start Mode (
totm)
Set the output mode.
Set either flicker OFF start or flicker ON start. (For details on output mode operation, refer to "Timing Charts" on page 29.)
Input Signal Width (
iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset, and gate inputs.
The same setting is used for all external inputs (signal, reset, and gate inputs).
If contacts are used for the input signal, set the input signal width to 20 ms.
Processing to eliminate chattering is performed for this setting.
NPN/PNP Input Mode (
imod)
Select either NPN input (no-voltage input) or PNP input (voltage input) as the input format. Set an NPN input when using a 2-wire sensor. The same setting is used for all external inputs.
For details on input connections, refer to "Input Connections" on
page 9.
Display Color (
colr)
(Terminal black model: H5CX-A
@ only)
Set the color used for the present value.
Key Protect Level (
kypt)
Set the key protect level.
Refer to “Key Protect Level” on page 36.
Operation in Run Mode
Operating Procedures for Twin Timer Function
Output OFF Output ON
red
Red (fixed)grn
Green (fixed)org
Orange (fixed)r-g
Red Greeng-r
Green Redr-o
Red Orangeo-r
Orange Redg-o
Green Orangeo-g
Orange GreenPresent value OFF set time
Present value ON set time
Note: 1. The display will automatically show the OFF set time when the OFF time is being timed and the ON set time when the ON time is being timed.
Set the digits for the OFF set time using the corresponding keys.