HEATING, VENTILATING, AND AIR CONDITIONING SYMBOLS

SUPPLY GRILLE OR REGISTER (SG, SR)

EXHAUST, RETURN, OR TRANSFER GRILLE OR REGISTER (EG, ER, RG, RR, TG, TR)

CEILING DIFFUSERS (CD)

CEILING EXHAUST, RETURN AND TRANSFER GRILLES AND REGISTERS (EG, ER, RG, RR, TG, TR)

MITERED ELBOW WITH TURNING VANES RADIUS ELBOW FIRE DAMPER FIRE/SMOKE DAMPER FS F FLEXIBLE CONNECTION (FC)

PHOTO NUMBER AND DIRECTION IDENTIFIER DOOR GRILLE

PROVIDE DOOR UNDERCUT CEILING ACCESS DOOR

POINT OF REMOVAL, DEMOLITION

POINT OF CONNECTION, RENOVATION

PRESSURE AND TEMPERATURE TEST PLUG AIR FLOW QUANTITY: 200 SCFM

VIBRATION ISOLATOR

WEATHER PROOF COMBINATION DISCONNECT AND MOTOR STARTER

COMBINATION DISCONNECT AND MOTOR STARTER

FLEXIBLE DUCTWORK (SINGLE LINE)

FLEXIBLE DUCTWORK (DOUBLE LINE) RECTANGULAR DUCT

DIMENSIONS IN INCHES

FIRST DIMENSION VISIBLE SIDE

1. 2. 3. 24x16 24/16 FLAT-OVAL DUCT DIMENSIONS IN INCHES

FIRST DIMENSION VISIBLE SIDE

1. 2. 3. ROUND DUCT DIMENSIONS IN INCHES 1. 2.

INTERNAL INSULATION/SOUND ATTENUATION AS SPECIFIED. DUCT DIMENSIONS SHOWN ARE NET INSIDE, TO INSIDE FACE OF LINER.

PROVIDE LINING WHERE SHOWN OR NOTED ON DWGS, AND AS DESCRIBED IN SPECIFICATIONS.

1. 2.

3.

1.

1.DEMOLITION - EXISTING DUCT/EQUIPMENT

TO BE REMOVED

EXISTING DUCT/EQUIPMENT TO REMAIN

EXISTING EQUIPMENT, RELOCATED

INDICATES DUCT MOUNTED CONTROL

DEVICE "X" SEE HVAC CONTROL SYMBOLS SUPPLY OR INTAKE DUCT UP

SUPPLY OR INTAKE DUCT DOWN X

R

24x16 24x16 DUCT INSPECTION DOOR

(HORIZONTAL OR VERTICAL)

INCLINED RISE (R) OR DROP (D) ARROW IN DIRECTION OF FLOW

45 DEG BRANCH CONNECTION WITH BALANCING DAMPER ECCENTRIC TRANSITION

CONCENTRIC TRANSITION

TRANSITION, FOT = FLAT ON TOP FOB = FLAT ON BOTTOM

FLEX DUCT AND SPIN-IN CONNECTION WITH INTEGRAL BALANCING DAMPER

AIR INTO OPENING AIR OUT OF OPENING

AIR OUTLET AND INLET IDENTIFICATION

HVAC EQUIPMENT IDENTIFICATION

EQUIPMENT NOMENCLATURE

CONTROL VALVES IDENTIFICATION

RETURN OR EXHAUST DUCT DOWN RETURN OR EXHAUST DUCT UP

FLOW DIRECTION VALVE SYMBOL FLOW DIRECTION ACTUATOR SYMBOL

SEQUENTIAL UNIT NUMBER BUILDING IDENTIFICATION AHU-L-1001 AIRFLOW IN CFM SPECIFICATION DESCRIPTION DIMENSIONS IN INCHES 22x22 EG-2 (250)

HVAC EQUIPMENT IDENTIFICATION

STEAM, LOW PRESSURE STEAM, HIGH PRESSURE STEAM, CONDENSATE CHILLED WATER, SUPPLY CHILLED WATER, RETURN

HEATING HOT WATER, SUPPLY HEATING HOT WATER, RETURN HVAC CONDENSATE DRAIN CONDENSER WATER, SUPPLY CONDENSER WATER, RETURN CWR CWS CD HHR HHS CHR CHS SC HPS LPS

PIPING IDENTIFICATION

FLEXIBLE (ELASTOMER) PIPE CONNECTION

PIPE ALIGNMENT GUIDE ANCHOR UNION ECCENTRIC REDUCER CONCENTRIC REDUCER LATERAL UP TEE DOWN TEE UP ELBOW DOWN ELBOW UP

STEEL BELLOWS EXPANSION JOINT GROOVED END ADAPTER FLANGE FLEXIBLE COUPLING

FLANGED JOINT

GROOVED END JOINT WELDED JOINT

EXISTING PIPE TO BE REMOVED ABANDONED

EXISTING PIPE TO BE NEW PIPE

EXISTING PIPE (SCREENED) SINGLE LINE DOUBLE LINE BALL CHECK SWING CHECK REGULATED SIDE PRESSURE CONTROL

AIR VENT (MANUAL) GATE BUTTERFLY GLOBE BALL SEATING PORT ECCENTRIC PLUG PLUG OR COCK

NEEDLE AIR VENT (AUTO)

PRESSURE RELIEF SHUT-OFF VALVE

BALANCING FITTING AND COMBINATION FLOWMETER, AND BALANCING FITTING COMBINATION FLOWMETER BALANCING FITTING

H H

T T TEMPERATURE SENSOR OR THERMOSTAT HUMIDITY SENSOR OR HUMIDISTAT

ENTHALPY SENSOR LIQUID FLOW SWITCH

DUCT MOUNTED AIRFLOW MONITORING STATION MOTOR CONTROL VALVE (2-WAY), (3-WAY) OCCUPANCY SENSOR

SWITCH

HVAC CONTROL PANEL (HCP)

VARIABLE/ADJUSTABLE FREQUENCY DRIVE AFD VFD S OS M M MS

MCC DIVISION 16 MOTOR CONTROL CENTER MOTOR STARTER

ELECTRIC MOTOR

LOW-LIMIT FREEZE THERMOSTAT FZ

M

CONDENSATE RETURN UNIT CHEMICAL FEEDER

CEILING FAN

CEILING DIFFUSER

CABINET CONVECTOR UNIT COOLING COIL

BOILER

BACKDRAFT DAMPER (GRAVITY) BALANCING DAMPER

AIR HANDLING UNIT AIR CONDITIONING UNIT

AIR COOLED CONDENSING UNIT ACCU

ACU

HVAC CONTROLS SYMBOLS

ABBREVIATIONS

AHU BD BDD BO CC CCU CD CF CMF

CEILING-MOUNTED AIR SUPPLY UNIT CRU

CSU

CU CONDENSING UNIT CABINET UNIT HEATER CUH

EA EXHAUST AIR

ELECTRIC DUCT HEATER EDH

ANALOG OUTPUT, INPUT: DATA POINT TO DDC DIGITAL OUTPUT, INPUT: DATA POINT TO DDC

FCU FD FC EUH ET ER EG EF EXHAUST FAN EXHAUST GRILLE EXHAUST REGISTER

DIAPHRAGM EXPANSION TANK ELECTRIC UNIT HEATER

FLEXIBLE CONNECTION, FAIL CLOSE FAN-COIL UNIT

FIRE DAMPER FAIL OPEN FINAL FILTER

FIBERGLASS REINFORCED PLASTIC FIRE SMOKE DAMPER

FINNED-TUBE BASEBOARD HEATER FREEZE STAT

HEATING COIL

HVAC CONTROL PANEL HOOD, EXHAUST HD HCP HC FZ FT FSD FRP FF FO CURRENT SENSOR

DIFFERENTIAL PRESSURE SENSOR OR SWITCH STATIC PRESSURE SENSOR

DUCT SMOKE DETECTOR AREA SMOKE DETECTOR MOTORIZED DAMPER

RELAY

SOLENOID VALVE

DIVISION 16 FIRE ALARM CONTROL PANEL LIQUID LINE PRESSURE SENSOR AND

SIGNAL TRANSMITTER

LIQUID FLOW INDICATING TRANSMITTER

FLOW CONTROL VALVE

TURBINE LIQUID FLOW METER

VENTURI FLOW METER OBD

OAI OA ML MD MB MAU LP IRH HX HWP HVU HTP HGS

HGR HOT GLYCOL RETURN HOT GLYCOL SUPPLY HEAT TRANSFER PACKAGE

HEATING AND VENTILATING UNIT HEATING WATER PUMP

HEAT EXCHANGER INFRARED HEATERS LOUVERED PENTHOUSE MAKEUP AIR UNIT MIXING BOX

MOTORIZED DAMPER MOTORIZED LOUVER ODOROUS AIR

OUTSIDE AIR INTAKE

OPPOSED-BLADE DAMPER (MANUAL) POSITIVE, NEGATIVE, NEUTRAL ROOM

PRESSURIZATION

FAN SPEED CONTROLLER

ALARM LIGHT AND HORN STATION

OIT OS OSA PA PCV PRESSURE-CONTROL VALVE PRESSURIZATION AIR OUTSIDE AIR OCCUPANCY SENSOR

OPERATOR INTERFACE TERMINAL

PREFILTER PREHEAT COIL

PACKAGED TERMINAL AIR CONDITIONING UNIT PTAC

PHC PF

PTS PITOT-TUBE TESTING STATION RETURN AIR RA RF RG RTU RL RR RETURN REGISTER

REFRIGERANT LIQUID PIPE RETURN GRILLE

RETURN FAN

REFRIGERANT SUCTION PIPE

SOUND ATTENUATOR, SUPPLY AIR SA RS SF SG SP SR SUPPLY REGISTER STATIC PRESSURE SUPPLY GRILLE SUPPLY FAN TRANSFER GRILLE TG UNIT HEATER

VEE-FILTER MIXING BOX

VARIABLE AIR VOLUME CEILING DIFFUSER WALL-MOUNTED AIR CONDITIONING UNIT WACU

VCD VFMB UH

THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS ON THIS SHEET MAY NOT APPEAR ON THE PLANS.

FOR ADDITIONAL ABBREVIATIONS OF OTHER DIVISIONS, SEE OTHER LEGENDS FOR PLUMBING, MECHANICAL, AND STRUCTURAL/ARCHITECTURAL. 1. 2. FCV FSC FIT PT FACP S R FI I SP DP CS FS F h

VALVE SYMBOLS

HVAC PIPING SYMBOLS

HVAC GENERAL NOTES

R (200) BALANCING DAMPER 24 DIA 24x16 AD N S SMOKE DAMPER UC WP MOTORIZED DAMPER M1 12x10 8x8 12x10 6x6 FOT

+

-B B F B F S.O. M ID BACKDRAFT DAMPER BDD

ACF AIR CIRCULATION FAN

ROOF TOP UNIT AIR CONDITIONER

M

+

-PLOT DATE: 2/5/2010 PLOT TIME:2:08:38 PM

FILE NAME 6c-00nH001d_319969.dgn

LEGEND

H-0.01

HVAC

GS YMF

BENSON EUGENE SMARR - PE64269

0 09/29/08 PERMIT LEVEL DRAWINGS

1 08/14/09 HCBD SUBMITTAL RB

RB

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(2)

1/8"=1’-0" 10-101 N 0 8 16 24 1/8"=1’-0"

SCALE FLOOR

1

2

3

4

5

6

7

1

2

3

4

5

6

7

B

C

B

C

LOWER FLOOR PLAN (SECTOR "A")

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

B

"

PLOT DATE: 2/5/2010 PLOT TIME:2:09:24 PM

FILE NAME 6c-10nH131d_319969.dgn

H-1.01

(SECTOR A)

TRANSFER STATION BUILDING

HVAC

YF YF GS 10-SF-17 10-SF-18 10-SF-19 10-SF-20 10-SF-21 10-ACF-1 10-ACF-8 10-ACF-2 10-ACF-3 10-ACF-10 NOTES:

PERMANENT WEST WALL OPENING. REFER TO ARCHITECTURAL DRAWINGS.

1 1 S S S S M M S S 10-ACF-9 2 H-5.03

ACF CONTROLLER (TYP)

BENSON EUGENE SMARR - PE64269

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

A

A

WALL MTD FAN (TYP OF 6) M M M

TUNNEL FLOOR PLAN

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

2 01/29/10 GS

3 02/01/10 GS

CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(3)

TF

YF GS

BENSON EUGENE SMARR - PE64269

1/8"=1’-0" N 0 8 16 24 1/8"=1’-0"

7

7

B

C

B

C

LOWER FLOOR PLAN (SECTOR "B")

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

A

"

8

9

10

11

12

8

9

10

11

12

PLOT DATE: 2/5/2010 PLOT TIME:2:09:30 PM

FILE NAME 6c-10nH132d_319969.dgn

H-1.02

(SECTOR B)

TRANSFER STATION BUILDING

HVAC

10-ACF-12 10-HCP-2 10-SF-23 10-SF-22 10-ACF-6 10-ACF-4 10-ACF-5 1 1 S S S S M M WALL MTD FAN (TYP OF 2) 2 H-5.03

ACF CONTROLLER (TYP)

NOTES:

PERMANENT EAST WALL OPENING, REFER TO ARCHITECTURAL DRAWINGS.

TRANSITION DUCT AS NECESSARY FOR FINAL CONNECTION TO UNIT.

2

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS. S 10-ACF-7 10-101

SCALE FLOOR

10-ACF-11 S 10-SF-24 M

A

A

13

13

14

14

RG-2 (100) 8x4 8x4 UP

TUNNEL FLOOR PLAN

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

01/29/10 2

02/01/10

3 CONTRACT DOCUMENTS

CHANGES TO PERMIT DRAWINGS GS GS

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(4)

C

A

A

C

1

2

3

4

5

6

7

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

B

"

1

2

3

4

5

6

7

MATCH LINE

SECTOR "C"

OPEN OPEN 10-202

CRANE

SERVICE AREA

10-201

TIPPING

FLOOR

1/8"=1’-0"

UPPER FLOOR PLAN (SECTOR "A")

N

0 8 16 24

1/8"=1’-0"

PLOT DATE: 2/5/2010 PLOT TIME:2:09:36 PM

FILE NAME 6c-10nH141d_319969.dgn

H-1.03

(SECTOR A)

GRADE FLOOR PLAN

TRANSFER STATION BUILDING

HVAC

SA YF GS 10-SF-14 10-SF-13 10-SF-12 10-SF-15 10-AC-2 M M M 1 2 2 WALL MTD FAN (TYP OF 3) 6 7 5 (BELOW) 4 T 10-AC-2 8 10-ACF-13 H-5.03 1 1 3 4 H-5.03 2 2 PLAN NOTES:

FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

5

SERVICE 10-AC-2 TWICE A YEAR. CHANGE RETURN GRILLE FILTER AS NEEDED.

5 H-5.03

(SIM)

6 CEILING DIFFUSER, TITUS MODEL TMSA-AA, 24x24, 400 CFM.

7

8 THERMOSTAT AND GRILLES SERVING OPERATOR BOOTH TO BE INSTALLED BY BOOTH MANUFACTURER.

ACF CONTROLLER (TYP)

BENSON EUGENE SMARR - PE64269

16x14 ALUMINUM RETURN DUCT 2 INCH DUCTBOARD INSULATION BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-2 RETURN OPENING. ELEVATION IS

APPROXIMATELY 29 FEET 10 INCHES ABOVE THE FLOOR MEASURED AT THE SOUTH WALL.

S

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

9

9 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE

WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST HUB DRAIN. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF HUB DRAINS. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO

0 09/29/08 PERMIT LEVEL DRAWINGS

10 PROVIDE FILTER AT UNIT RETURN AIR OPENING. PROVIDE ACCESS DOOR IN DUCTWORK FOR FILTER REPLACEMENT ACCESS.

RETURN GRILLE, TITUS MODEL 350FL, 24x14.

RB

1 08/14/09 HCBD SUBMITTAL RB

11

11

2 01/29/10 GS

16x14 ALUMINUM SUPPLY DUCT (SEAL CLASS A) WITH 2 INCH DUCTBOARD INSULATION. BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-2 SUPPLY OPENING. ELEVATION IS APPROXIMATELY 31 FEET 1 INCHES ABOVE

THE FLOOR MEASURED AT THE SOUTH WALL.

SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ACCESS TO

10-AC-2.

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

D R D D RD RD V V

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(5)

A

C

7

8

9

10

11

12

7

8

9

10

11

12

1/8"=1’-0"

UPPER FLOOR PLAN (SECTOR "B")

N 0 8 16 24 1/8"=1’-0"

A

C

MATCH LINE

SECTOR "D"

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

A

"

CRANE

SERVICE AREA

10-202 OPEN OPEN OPEN

TIPPING

FLOOR

10-201

PLOT DATE: 2/5/2010 PLOT TIME:2:09:42 PM

FILE NAME 6c-10nH142d_319969.dgn

H-1.04

(SECTOR B)

GRADE FLOOR PLAN

TRANSFER STATION BUILDING

HVAC

YF YF GS 10-AC-1 10-SF-10 10-SF-11 10-HCP-1 10-SF-9 M M M 2 2 1 T 7 8 6 10-ACF-15 10-ACF-14 5 4 (BELOW) 10-AC-1 1 H-5.03 1 3 4 2 H-5.03 2 PLAN NOTES:

FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

5

SERVICE 10-AC-1 TWICE A YEAR. CHANGE RETURN GRILLE FILTER AS NEEDED.

H-5.03 5

(SIM)

6 CEILING DIFFUSER, TITUS MODEL TMSA-AA, 24x24, 800 CFM.

7

8 THERMOSTAT AND GRILLES SERVING OPERATOR BOOTH TO BE

INSTALLED BY BOOTH MANUFACTURER. WALL MTD FAN

(TYP OF 3)

BENSON EUGENE SMARR - PE64269

16x14 ALUMINUM RETURN DUCT 2 INCH DUCTBOARD INSULATION BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-1 RETURN OPENING. ELEVATION IS

APPROXIMATELY 29 FEET 2 INCHES ABOVE THE FLOOR MEASURED AT THE SOUTH WALL.

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS. ACF CONTROLLER (TYP) 8x8 RG-2 (100) 8x4 10-EF-17 6 H-5.04 2 EXHAUST LOUVER REFER TO ARCH DWGS ACCESS DOOR AT CEILING 8x4

9 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE

WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST HUB DRAIN. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF HUB DRAINS. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO

11

0 09/29/08 PERMIT LEVEL DRAWINGS

10 PROVIDE FILTER AT UNIT RETURN AIR OPENING. PROVIDE ACCESS

DOOR IN DUCTWORK FOR FILTER REPLACEMENT ACCESS. RETURN GRILLE, TITUS MODEL 350FL, 24x14.

RB

1 08/14/09 HCBD SUBMITTAL RB

11 9

16x14 ALUMINUM SUPPLY DUCT (SEAL CLASS A) WITH 2 INCH DUCTBOARD INSULATION. BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-1 SUPPLY

OPENING. ELEVATION IS APPROXIMATELY 31 FEET 11 INCH ABOVE THE FLOOR MEASURED AT THE SOUTH WALL.

SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ACCESS TO 10-AC-1.

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

W 1 W 2 D D D D D D RD RD RD V V RD S S

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(6)

1

2

3

4

5

6

7

1

2

3

4

5

6

7

C

D

C

D

UPPER LEVEL FLOOR PLAN (SECTOR "C")

1/8"=1’-0"

MATCH LINE

SECTOR "A"

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

D

"

TIPPING

FLOOR

10-201 0 8 16 24 1/8"=1’-0" N

PLOT DATE: 2/5/2010 PLOT TIME:2:09:47 PM

FILE NAME 6c-10nH143d_319969.dgn

H-1.05

(SECTOR C)

GRADE FLOOR PLAN

TRANSFER STATION BUILDING

HVAC

SA

YF GS

10-EF-1 10-EF-2 10-EF-3 10-EF-4

10-EF-9 10-EF-10 10-EF-11 10-EF-12

10-SF-1 10-SF-16 10-SF-2 10-SF-3 90-AC-1 M M M WALL MTD FAN (TYP OF 5) M M 1 1 1 10-SF-15 ROOF MTD FAN (TYP OF 8) 3 H-5.03 3 1 1 H-5.03 1 1 3 H-5.03 2 2 PLAN NOTES:

FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

5 H-5.03

(SIM) SERVICE 90-AC-1 TWICE A YEAR.

BENSON EUGENE SMARR - PE64269

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

4 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE

WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST DRYWELL. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF DRYWELL. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO

4

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

RD RD W2 W1 W2 W1 V V

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(7)

C

D

MATCH LINE

SECTOR "A"

7

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

D

"

C

D

7

UPPER LEVEL FLOOR PLAN (SECTOR "D")

1/8"=1’-0" 0 8 16 24 1/8"=1’-0" N

TIPPING

FLOOR

10-201

8

9

10

11

12

PLOT DATE: 2/5/2010 PLOT TIME:2:09:52 PM

FILE NAME 6c-10nH144d_319969.dgn

H-1.06

(SECTOR D)

GRADE FLOOR PLAN

TRANSFER STATION BUILDING

HVAC

SA YF GS 10-SF-4 10-SF-5 10-SF-6 10-SF-7 10-EF-8 10-EF-7 10-EF-6 10-EF-5 10-EF-16 10-EF-15 10-EF-14 10-EF-13 10-SF-8 90-AC-2 3 M 1 1 M M 1 M 1 M WALL MTD FAN (TYP OF 5) ROOF MTD FAN (TYP OF 8) 3 H-5.03 1 H-5.03 1 3 2 H-5.03

2 FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

H-5.03 5

(SIM) SERVICE 90-AC-2 TWICE A YEAR.

PLAN NOTES:

FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL

BENSON EUGENE SMARR - PE64269

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

1

8X4

8x4 DN 4

3 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE

WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST DRYWELL. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF DRYWELLS. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

W2 RD RD RD W 1 W 2 W1 W2 W1

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(8)

30-101

WORK

AREA

30-106

TOILET

30-102

BREAK

AREA

30-105

FILE/

STORAGE

30-104

IT

CLO

FLOOR PLAN

1/4"=1’-0" 30-EF-1 N 16x16 16x14 1 0 X 1 4 1 0 X 1 4 10x10 RG-1 RG-1 8 CD-1 (185) TYP 4 RG-1 0 4 8 12 1/4"=1’-0" 30-HP-1 30-CU-1 30-AC-1 EXHAUST LOUVER, SEE ARCH DWGS 8 CD-1 (110) 8 CD-1 (115) 8 CD-1 (110) 8 CD-1 (110) 8 CD-1 (135) T T 9 H-5.04 7 H-5.04 (TYP) 8 H-5.04 16X16 6 H-5.04 H-5.04 10 PUMPED CONDENSATE TO DRAIN PIPING, SEE PLUMBING DWGS

PLOT DATE: 2/5/2010 PLOT TIME:2:09:58 PM

FILE NAME 6c-30nH141d_319969.dgn

H-3.01

FLOOR PLAN

SCALE HOUSE

HVAC

GS YMF BV GS 8x8 NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

BENSON EUGENE SMARR - PE 64269

REFRIGERANT PIPING, RUN IN CEILING SPACE WITH

INSULATION ON SUCTION LINE, REFER TO SPECIFICATIONS.

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

1

2

PLAN NOTES:

ALUMINUM DUCTWORK, SEAL CLASS A.

2

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

INSTALL 30-HP-1 ON ROOF WITH MINIMUM 60" CLEARANCE FROM CONDENSER FAN TO BOTTOM OF CANOPY. SEE DRAWING H-5.04. UNDERCUT DOOR 3/4".

3

3

3

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(9)

PLOT DATE: 2/5/2010 PLOT TIME:2:09:05 PM

FILE NAME 6c-00nH501d_319969.dgn

H-5.01

SCHEDULES

HVAC

BENSON EUGENE SMARR - PE64269

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(10)

HVAC CONTROL PANEL

OFF HAND AUTO OFF HAND AUTO

10-HCP-1

PILOT LIGHT LEGEND: R=RED A=AMBER G=GREEN OFF HAND AUTO OFF HAND AUTO 10-SF-1 10-EF-1 G G G G R R FAN FAIL R R FAN ON 10-SF-2 10-EF-2 OFF HAND AUTO G R 10-EF-3 OFF HAND AUTO G R 10-SF-3 OFF HAND AUTO G R 10-EF-4 OFF HAND AUTO G R 10-SF-4 OFF HAND AUTO G R 10-EF-5 OFF HAND AUTO G R 10-SF-5 OFF HAND AUTO G R 10-EF-9 OFF HAND AUTO G R 10-SF-9 OFF HAND AUTO G R 10-EF-10 OFF HAND AUTO G R 10-SF-10 OFF HAND AUTO G R 10-EF-11 OFF HAND AUTO G R 10-SF-11 OFF HAND AUTO G R 10-EF-12 OFF HAND AUTO G R 10-SF-12 OFF HAND AUTO G R OFF HAND AUTO G R

HVAC CONTROL PANEL

10-HCP-2

PILOT LIGHT LEGEND: R=RED A=AMBER G=GREEN OFF HAND AUTO G R 10-SF-17 OFF HAND AUTO G R 10-SF-18 OFF HAND AUTO G R 10-SF-19 OFF HAND AUTO G R 10-SF-20 OFF HAND AUTO G R 10-SF-21 OFF HAND AUTO G R 10-SF-22 OFF HAND AUTO G R 10-SF-23 OFF HAND AUTO G R 10-SF-24 NTS

10-HCP-2 OPERATOR INTERFACE

NTS

10-HCP-1 OPERATOR INTERFACE

FAN FAIL FAN ON FAN FAIL FAN ON GENERAL NOTE:

EACH CONTROL PANEL TO HAVE INTERNAL TIME CLOCK.

PLOT DATE: 2/5/2010 PLOT TIME:2:09:19 PM

FILE NAME 6c-00nH502d_319969.dgn

H-5.02

CONTROL PANELS

HVAC

OFF HAND AUTO G R 10-EF-6 OFF HAND AUTO G R 10-SF-6 OFF HAND AUTO G R 10-EF-7 OFF HAND AUTO G R 10-SF-7 OFF HAND AUTO G R 10-EF-8 OFF HAND AUTO G R 10-SF-8 OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R 10-EF-13 10-SF-13 10-EF-14 10-SF-14 10-EF-15 10-SF-15 10-EF-16 10-SF-16

BENSON EUGENE SMARR - PE 64269

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 RB

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS HCBD SUBMITTAL

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(11)

1’-6" 6"

2

1/2"=1’-0"

1

SUPPLY FAN

1/2"=1’-0" 5’x6’ LOUVER

(TYP 2 PER FAN)

SUPPLY FAN HOUSING 5’-0" 5’-0" 6 ’ -0 " CROSSED VERTICAL VERTICAL CROSSED 10 MOTORIZED DAMPER 55" ~ FLOOR 3/4" THREADED ROD UP TO STRUCTURE (TYP OF 4) 3/4" THREADED ROD UP TO STRUCTURE (TYP OF 4) MOTORIZED DAMPER 3/4" THREADED ROD

CROSS RODS AT MOTORIZED DAMPER FOR STABILITY

A

A

SECTION A-A

SEE ARCH FOR LOUVER ELEVATION ~23’-5" ON EAST WALL

SUPPLY/EXHAUST FAN

2"x2"x1/4" ANGLE-TYP BIRDSCREEN BIRDSCREEN 4

PLOT DATE: 2/5/2010 PLOT TIME:2:08:49 PM

FILE NAME 6c-00nH401d_319969.dgn

H-5.03

STANDARD DETAILS

HVAC

ALUMINUM 16 GAUGE SHEETMETAL PLENUM ALUMINUM 16 GAUGE SHEETMETAL PLENUM

BENSON EUGENE SMARR - PE 64269

LOUVER LOUVER

6"

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

2 01/29/10 GS

3 02/01/10 CONTRACT DOCUMENTS GS

CHANGES TO PERMIT DRAWINGS

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

EB0000072 AAC001992

ROOF-SEE ARCH. AND STRUCT. DRAWINGS

PRE-FAB NONCOMBUSTIBLE ROOF CURB

RUN POWER LEADS IN CORNER INSIDE CURB

DISCONNECT BY MANUFACTURER GRAVITY DAMPER

BAFFLE

3

UP-BLAST ROOF EXHAUSTER

NTS

MOTORIZED DAMPER

FIBERGLASS INSULATION

CONTINUOUS PRESSURE TREATED WOOD NAILER

ROOF STRUCTURE

4

ROOF CURB MTD EQUIPMENT HURRICANE RESTRAINT

NTS

STAINLESS STEEL, #10 TEC SCREWS 2 PER STRAP

PREFABRICATED METAL ROOF CURB WITH CANT

CURB MOUNTED EQUIPMENT

HURRICANE STRAP: 2" WIDE, 18 GAGE,

STAINLESS STEEL - ONE PER SIDE (4 TOTAL)

(2) STAINLESS STEEL #10 TEC SCREW, FASTEN TO STRUCTURE

A

A

DETAIL

NTS

5

WALL MTD AC UNIT

NTS DOUBLE DEFLECTION SUPPLY GRILLE SUPPLY AIR RETURN AIR INTERIOR RETURN GRILLE WALL FINISHED FLOOR CD, FULL SIZE CONNECTION TO UNIT

NOTE: SUPPLY AND RETURN GRILLE BY AC UNIT MANUFACTURER,

UNLESS SHOWN OTHERWISE ON PLANS. GRADE

UNIT CONDENSATE DRAIN & TRAP

EXTERIOR WALL MOUNT AC UNIT

SUPPORT UNIT PER MANUFACTURERS INSTALLATION INSTRUCTIONS

SEAL WEATHER TIGHT AROUND UNIT MOUNTING FLANGE SHEET METAL FLANGE AC UNIT

SEAL PERIMETER WITH CAULK, AIR TIGHT

GRILLE DUCT SLEEVE 10 H-5.04 TO DRY WELL, OR HUBDRAIN REFER TO PLUMBING DRAWINGS

(12)

PLOT DATE: 2/5/2010 PLOT TIME:2:09:00 PM

FILE NAME 6c-00nH402d_319969.dgn

H-5.04

STANDARD DETAILS

HVAC

BENSON EUGENE SMARR - PE64269

0 09/29/08 PERMIT LEVEL DRAWINGS RB

1 08/14/09 HCBD SUBMITTAL RB

2 01/29/10 GS

3 2/01/10 CONTRACT DRAWINGS GS

CHANGES TO PERMIT DRAWINGS

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL 3011 SW WILLISTON RD GAINESVILLE, FL 32608 EB0000072 AAC001992 REQUIRED STRUCTURE AS SUSPEND FROM VIBRATION ISOLATORS HANGER RODS WITH

EXHAUST FAN

CEILING GRILLE

FLEXIBLE CONNECTION

OR ROOF CAP. SEE PLANS FOR SIZE DUCT CONNECTION TO WALL CAP

6

CEILING MOUNTED EXHAUST FAN

NTS

DUCT COLLAR WITH LOCKING QUADRANT (W/2" STANDOFF) VOLUME DAMPER. CENTER TAPS IN VERTICAL HEIGHT OF DUCT. EXTERNALLY INSULATE

WITH 2" BLANKET INSULATION BUTTERFLY DAMPER

DO NOT COVER DAMPER HANDLE WITH INSULATION.

DIFFUSER

CEILING AVOID SHARP BEND IN

FLEXIBLE DUCTS. USE GENEROUS BENDS SO THAT FLEX DOES NOT CRIMP. BLANKET INSULATION

7

DIFFUSER INSTALLATION

NTS 3 6 " M IN

8

ROOFTOP HEATPUMP

NTS PROVIDE 6" SOUND ATTENUATION BLANKET IN ROOF CUB AREA

FOR SOUND ATTENUATION ROOF STRUCTURE

REFER TO ARCH DWGS FOR CONSTRUCTION TYPE

COIL SECTION

FILTER SECTION SUPPLY FAN

SECTION RETURN AIR

AND OSA MIXING SECTION

NOTES:

1. PROVIDE AIRTIGHT NON-HARDENING SILICONE CAULK SEAL AT ALL PENETRATIONS. OPENINGS IN DECK SHALL BE A MAXIMUM OF 1" LARGER THAN DUCT SIZE.

2. PROVIDE GASKET BETWEEN UNIT AND CURB. PROVIDE LAG BOLTS TO CURB THROUGH A/C TO WITHSTAND HURRICANE FORCE WINDS WHERE APPLICABLE.

3. PROVIDE TRAPPED CONDENSATE DRAIN LINE FULL SIZE OF UNIT CONNECTION TO ROOF MTD HUB DRAIN. PROVIDE SUPPORT FOR DRAIN AS NECESSARY TO ATTAIN MIN

OF 1/8" PER FOOT SLOPE.

4. PROVIDE MOTORIZED OUTSIDE AIR DAMPER WHERE INDICATED IN SPECIFICATIONS OR DRAWINGS. OTHERWISE PROVIDE MANUAL DAMPER.

RETURN AIR PLENUM WITH SOUND ELBOW

ROOF CURB, SEE

FOR HURRICANE RESTRAINT 4 H-5.03 SUPPLY DUCT TRANSITION AS REQ’D

TO SIZE SHOWN ON PLANS RAIN HOOD BOTTOM OF CANOPY 60" CLEAR,COMPLY WITH MFG INSTALLATION INSTRUCTIONS PI TCH RS R L AIR COOLED CONDENSING UNIT REFRIG. SERVICE/SHUT-OFF VALVE (TYP) (OMIT IF

INCLUDED WITH UNIT) FILTER DRYER (BI-FLOW TYPE FOR HEAT PUMP)

SHRAEDER ACCESS FITTING (TYPICAL) OMIT IF INCLUDED WITH UNIT.

SOLENOID VALVE (IF REQ’D BY MFG.)

SIGHT GLASS

(IF THERMAL EXPANSION VALVE IS USED)

THERMAL EXPANSION VALVE (IF

REQ’D BY MFG)

PROVIDE RISER TRAPS WHEN CONDENSING UNIT IS ABOVE EVAPORATOR

CONTRACTOR SHALL SUBMIT A REFRIGERANT PIPING DIAGRAM APPROVED

BY THE CONDENSING UNIT MANUFACTURER BEFORE PROCEEDING WITH

WORK. (REFER TO SPECIFICATIONS FOR REFRIGERANT PIPING

INSTALLATION REQUIREMENTS)

DELETE ANY VALVES OR MATERIALS THAT ARE FURNISHED WITH UNIT. REFRIGERANT PIPING SHALL BE SIZED PER MANUFACTURER OPTIMUM PERFORMANCE RATING. NOTES: 1. 2. 3. SCHRAEDER ACCESS FITTING (TYP) (OMIT IF INCLUDED WITH UNIT)

9

REFRIGERANT PIPING

NTS

PUMPED CONDENSATE DRAIN PIPE REFER TO SPECS & PLUMBING DRAWINGS

CONCRETE APRON

WALL MTD INDOOR UNIT

1-1/2" MIN

1.

HEIGHT EQUAL TO AIR HANDLER FAN STATIC

PRESSURE, 3 1/2 "(MIN) OPEN TEE PLUGGED TEE 2" REFER TO PIPING SCHEDULE OR SPECIFICATIONS FOR PIPE MATERIAL

PIPE SIZE EQUAL TO FULL SIZE OF UNIT CONNECTION. FLOOR DRAIN OR ROOF DRAIN EQUIPMENT PAD COOLING COIL FROM DRAIN PAN

EXTERNALLY INSULATE ALL CONDENSATE LINES.

(SEE PIPING SCHEDULE OR SPECIFICATIONS FOR INSULATION TYPE) NOTE:

10

CONDENSATE PIPING

NTS

2

D

1" MIN BAND CLAMP ATTACH TO

STRUCTURE PER SMACNA

RECOMMENDATIONS NUT WITH LOCK WASHER ATTACH TO STRUCTURE WITH BEAM CLAMPS OR MASONRY EXPANSION BOLTS KINDORF HANGER

WITH ALL THREAD ROD IN TRAPEZE CONFIGURATION ALL-THREAD ROD

STAINLESS STEEL

SHEET METAL SADDLE

LENGTH EQUALS DIAMETER OF DUCT

RIGID/FLEXIBLE ROUND DUCTWORK RECTANGULAR DUCTWORK

CAUSE DUCT SHAPE DEFORMATION.

HANGER SIZES SHALL BE IN ACCORDANCE WITH SMACNA, LATEST EDITION. SUPPORT SYSTEM MUST NOT DAMAGE DUCT, INSULATION, OR

SUPPORTS TO STRUCTURE.

DO NOT USE POWDER POWERED FASTENING SYSTEMS TO ATTACH

3. 2. 1. NOTES:

(13)

VALVE SYMBOLS

PLUMBING FIXTURE SCHEDULE

PLUMBING GENERAL NOTES

PIPING IDENTIFICATION

PLUMBING SYMBOLS

FIRE SPRINKLER SYMBOLS

DRAWING NOTES

ABBREVIATIONS

TEE CO

YCO-X

CLEANOUT, BUILDING EXTERIOR

Y = F - FLOOR CLEANOUT D - DECK CLEANOUT W - WALL CLEANOUT X - NO. IN SPECIFICATION HD-XY HUB DRAIN Y - T WITH TRAP

Y - P WITH PRIMED TRAP X - NO. IN SPECIFICATION FD-XY

FLOOR DRAIN

X - NO. IN SPECIFICATION Y - T WITH TRAP

Y -P WITH PRIMED TRAP RD-X

ROOF DRAIN

X = NO. IN SPECIFICATION

OVERFLOW ROOF DRAIN X = NO. IN SPECIFICATION OD-X

CLEANOUT PLUG (EXPOSED PIPING) CO

ELBOW DOWN ELBOW UP TEE DOWN

TEE DOWN WITH ELBOW ELBOW

TEE UP

THERMOMETER

PRESSURE GAUGE WITH COCK STRAINER HOSE VALVE REDUCER HOSE RACK GATE GLOBE BALL

PRESSURE RELIEF VALVE

BACKWATER CHECK VALVE CHECK VALVE

PRESSURE REGULATING VALVE

BACKFLOW PREVENTER

WALL FIRE DEPARTMENT CONNECTION

POST FIRE DEPARTMENT CONNECTION

FIRE ALARM BELL

SPECIFICATION DETAIL NUMBER ABOVE FINISHED FLOOR

AFF

DOWN DN

VTR VENT THRU ROOF

HV HOSE VALVE WC LAV EWH WATER CLOSET UR URINAL SINK

HAND HELD EYE/FACE WASH

SSK SK

LAVATORY

FA FIXED AIR GAP DRAIN

ON OVERFLOW NOZZLE SH SHOWER ABV ABOVE CL CENTERLINE CO CLEANOUT DT DILUTION TANK EL ELEVATION FD FLOOR DRAIN FDC FLR FLOOR HD HUB DRAIN IE INVERT ELEVATION LP LABORATORY FAUCET P PUMP SP SUMP PUMP

SSH SAFETY SHOWER/EYEWASH COMBINATION

SERVICE BASIN, OR SAMPLE SINK

WH WATER HEATER

15XXX

CONN CONNECTION

DEPT DEPARTMENT

RL RAIN LEADER

AAV AIR ADMITTANCE VALVE

MS MOP SINK

EWC ELECTRIC WATER COOLER

FIRE DEPARTMENT CONNECTION

WHA WATER HAMMER ARRESTER

TP TRAP PRIMER VALVE

ETP ELECTRONIC TRAP PRIMER

WF WASH FOUNTAIN

TMV THERMOSTATIC MIXING VALVE

EE EMERGENCY EYEWASH SANITARY DRAIN D ARD V ARV SANITARY VENT

ACID RESISTANT VENT ACID RESISTANT DRAIN

RD

W1 NG

HW

RECIRCULATING HOT WATER

RHW DEIONIZED WATER LABORATORY VACUUM VAC NATURAL GAS He N NITROUS OXIDE HELIUM NITROGEN

COLD WATER (POTABLE) HOT WATER (POTABLE) COMPRESSED AIR

H HYDROGEN GAS

CH2 ACETYLENE

AIR

NO

W2 COLD WATER (NON-POTABLE)

FS FIRE SPRINKLER

SPD SUMP PUMP DISCHARGE

ERW EMERGENCY RAINWATER PIPING

TW TEMPERED WATER (POTABLE)

DIW

PG PROPANE GAS

THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR

ABBREVIATIONS ON THIS SHEET MAY NOT APPEAR ON THE PLANS. FOR ADDITIONAL ABBREVIATIONS OF OTHER DIVISIONS, SEE

OTHER LEGENDS FOR HVAC, MECHANICAL, AND STRUCTURAL/ ARCHITECTURAL. 1. 2. ITEM WC-1 LAV-1 S-1 EWC-1

EE-1 EMERGENCY EYEWASH

SINK (KITCHEN) LAVATORY DESCRIPTION D ARD W1 HW W2 ADA COMPLIANT COMMENTS ADA COMPLIANT 2" -1 -1/2" 1/2" 1/2" 1/2" 1/2" -4" - 1" - -- -2" - 3/4" -

-1. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, VERIFY EXISTING PLUMBING PIPING SYSTEMS AND VERIFY NEW POINTS OF CONNECTION TO EXISTING PIPING PRIOR TO

PERFORMING WORK.

2.

4.

5.

ALL PIPE PENETRATIONS THROUGH FLOORS AND WALLS SHALL BE SLEEVED AND SEALED.

6.

7.

8.

9. PLUMBING VENTS THROUGH ROOF SHALL BE OFFSET AT ROOF TO PROVIDE MINIMUM DISTANCE OF 3’-6" FROM EXTERIOR WALL.

12.

13.

14.

COORDINATE FINAL LOCATIONS OF FLOOR AND HUB DRAINS THAT RECEIVE CONDENSATE DRAINAGE FROM HVAC EQUIPMENT.

15.

ALL PIPING LOCATED IN RETURN AIR PLENUM SPACES SHALL BE METAL.

16.

17.

INSULATE ABOVE GRADE DRAINAGE PIPING THAT RECEIVES CONDENSATE FROM AIR CONDITIONING UNITS.

CLEANOUT TO GRADE FITTINGS, WHERE SANITARY DRAIN EXITS THE BUILDING, SHALL ALLOW FOR RODDING BOTH WAYS.

PROVIDE CLEANOUTS IN ROOF DRAIN PIPING, ROOF OVERFLOW DRAIN PIPING AND SANITARY WASTE PIPING AS SHOWN ON THE DRAWINGS. FURNISH AND INSTALL ADDITIONAL CLEANOUTS AS REQUIRED BY CODE. 3.

ALL BURIED AND CONCRETE ENCASED COPPER PIPING SHALL BE INSTALLED WITH A PROTECTIVE SLEEVE, OR WRAP, FOR ITS ENTIRE LENGTH. SLEEVE, OR WRAP, SHALL BE FLEXIBLE POLYETHYLENE MANUFACTURED FOR CONTINUOUS PIPE COVER APPLICATION. EXTEND SLEEVE, OR WRAP, 2 INCHES ABOVE FINISHED FLOOR.

THE CONTRACTOR SHALL PROVIDE OFFSETS IN THE PIPING RUNS, IN ADDITION TO WHAT IS SHOWN ON THE DRAWINGS, WHERE

REQUIRED TO CLEAR EXISTING AND NEW; DUCT, STRUCTURE AND OTHER PIPING SYSTEMS.

ALL PIPES PASSING THROUGH FIRE RATED WALLS AND FLOORS SHALL BE INSTALLED TO MEET APPLICABLE UL SYSTEM REQUIREMENTS PERTAINING TO THE TYPE OF CONSTRUCTION. REFER TO ARCHITECTURAL DRAWINGS FOR WALLS WHICH ARE FIRE RATED.

FURNISH AND INSTALL WATER HAMMER ARRESTERS ON W1 AND HW PIPING IN RESTROOM AREAS. P.D.I. SIZE "C" MINIMUM.

PATCH ALL HOLES IN WALLS AND FLOORS LEFT AS A RESULT OF PLUMBING WORK.

PIPING ELEVATIONS SHOWN ARE APPROXIMATE, FIELD VERIFY PIPING ELEVATIONS PRIOR TO INSTALLATION.

11.

INSTALL TRAP PRIMER VALVES ON ALL FLOOR AND HUB DRAINS WITH "P" EXTENSION, SEE DETAIL 15200A. FLOOR AND HUB DRAINS WITH "T" EXTENSIONS SHALL HAVE DEEP SEAL TRAPS.

RAIN WATER DRAIN

-REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF PLUMBING FIXTURES, ROOF DRAINS, AND ROOF GUTTER OUTLETS.

PLOT DATE: 2/5/2010 PLOT TIME:2:10:02 PM

FILE NAME 6c-00nP001d_319969.dgn

P-0.01

ABBREVIATIONS

LEGEND AND

PLUMBING

ELECTRIC WATER COOLER 1/2"

WATER CLOSET - FLOOR MOUNTED FLUSH VALVE TYPE

EMERGENCY EYEWASH

FF FINISHED FLOOR

3" - 1/2" 1/2"

-MS-1 MOP SINK

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

BENSON EUGENE SMARR - PE 64269

09/29/08

0 PERMIT LEVEL DRAWINGS

SPECIFICATIONS:

a. FOR PLUMBING PIPING SCHEDULE SEE SECTION 15100. b. FOR PIPE SUPPORTS AND HANGERS SEE SECTION 15100

AND DETAILS REFERENCED ON THE DRAWINGS.

c. FOR PIPING INSULATION SEE SECTION 15255. d FOR PLUMBING PIPING SEE SECTION 15100. e. FOR VALVES SEE SECTION 15202.

f. FOR PLUMBING FIXTURES SEE SECTION 15410.

g. FOR PLUMBING EQUIPMENT SEE SECTION 15440.

h. FOR FIRE SPRINKLER SYSTEM SEE SECTION 13930.

08/14/09

1 HCBD SUBMITTAL RB

10. PROVIDE PIPE IDENTIFICATION FOR PLUMBING SYSTEMS. REFER TO SECTION 15100, PLUMBING PIPING SCHEDULE.

18. BV GS RB RB RB 01/29/10 2 RB 02/01/10 3 RB

CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(14)

1/8"=1’-0" 10-101 N 0 8 16 24 1/8"=1’-0"

SCALE FLOOR

1

2

3

4

5

6

7

1

2

3

4

5

6

7

A

B

A

B

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

B

"

PLOT DATE: 2/5/2010 PLOT TIME:2:10:08 PM

FILE NAME 6c-10nP131d_319969.dgn

P-1.01

(SECTOR A)

TRANSFER STATION BUILDING

PLUMBING

RB RB GS GENERAL NOTES: PLAN NOTES: 1. 1 2

AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM. 3 4 5 6 FLOOR EL 28.75

BASEMENT FLOOR PLAN (SECTOR "A")

4" D FROM FD-3T DRAINS ON THE GRADE FLOOR. 1 1/2"

CL EL 44.67

2. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400. 1 1 1 4 4 4 4" 8 15550 X S-1.23 1 1/2" HOSE REEL 3/4" HOSE REEL 5 3

BENSON EUGENE SMARR - PE64269

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

FCO-2 6" LEACHATE

5

P-5.03

TRENCH SUMP DRAINS REFER TO STRUCTURAL DRAWINGS (TYP)

6" GRATE EL 28.25 3" 6" 6" LEACHATE 4 6" LEACHATE 4" D 6" 6" FCO-2 4 15551 15551 2 1/2" 4" 5 1 1/2" HOSE REEL 3/4" HOSE REEL 3 2 2 2 4" D 3" CL EL 44.00 15551 15551 3" V UP TO GRADE FLOOR TRENCH SUMP GRATE EL 28.25 TYP OF 2 2 1/2" W2 CL EL 44.67 7 7 FIRE SPR RISER 15551 8 6 6 TO FIRE SPRINKLER SYSTEM 2" P-5.03 1 2" W1 CL EL 44.67

REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS. S-1.23 Y 6" IE 25.58 (AT SUMP) 6" IE 25.58 (AT SUMP) 6" IE 25.58 (AT SUMP) 15721 15721 8" RD FROM ABOVE (9659 SF) 8" ON-1

TERMINATE ROOF DRAIN LEADER THRU WALL 1’-0" ABOVE GRADE AND DISCHARGE ONTO SPLASH BLOCK. COORDINATE INVERT ELEVATION WITH CIVIL.

2 1/2" AND 2" V642 BACKFLOW PREVENTERS STACKED. 3316 6 3155 3155 6 PIPE ENCASEMENT (TYP) 6 6 IE 21.50 AT SUMP FCO-2 IE 21.90 3" IE 23.75 2" DOMESTIC FM 2" W1 AND 2 1/2" W2 UP CO IE 44.00 FC0-2 IE 25.00 IE 25.00 4" HDPE LEACHATE FM 2 IE 24.25 3" V UP TO GRADE FLOOR 6" IE 25.58 (AT SUMP) IE 22.37 AT SUMP DOMESTIC PUMP STATION WET WELL LEACHATE PUMP

STATION WET WELL LEACHATE

VALVE VAULT

CAST IN CONCRETE ALL BURIED LEACHATE DRAIN AND FM LINES, SANITARY DRAIN AND FM LINES.

3155 DOMESTIC PS VALVE VAULT 6" LEACHATE 8" TRENCH BOTTOM OUTLET

REFER TO UTILITY PLAN C-6.06 AND C-5.03 FOR CONTINUATION.

8" STORM DRAIN

IE 24.50

PIPE DN AND CAST INTO WALL AND FLOOR SLAB

IE 30.00

IE 30.33

PIPE DN AND CAST INTO WALL AND FLOOR SLAB EXTERIOR 3/4" V235 3’-0" ABOVE GRADE (FEED FROM W2) 3316 IE 22.20 4" W1 (CLDI) 4" W1 (CLDI) 6" FS (CLDI) 6" LEACHATE FROM TIPPING FLOOR

TUNNEL FLOOR PLAN

PERMIT LEVEL DRAWINGS

09/29/08 0 1 1/2" DN TO HOSE REELS 1 1/2" DN TO HOSE REELS

MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.

MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.

CL EL 45.92

BETWEEN BEAMS

1.

FIRE SPRINKLER NOTES:

ROUTE FIRE SPRINKLER MAIN ALONG NORTH AND/OR SOUTH WALL OF BASEMENT. RUN BRANCHES UP, THAT SERVE THE BASEMENT, AND BETWEEN STEEL BEAMS. PIPING SHALL NOT BE RUN BELOW THE BEAMS EXCEPT AT THE NORTH AND SOUTH WALLS.

08/14/09

1 HCBD SUBMITTAL RB

GS

9

9 4" FROM CANTILEVERED WALKWAY ABOVE, TERMINATE DRAIN

LEADER 1’-0" ABOVE GRADE AND DISCHARGE ONTO SPLASH BLOCK. RB 01/29/10 2 RB 02/01/10 3 RB

CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS D D V V W1 W1 W2 W2 D V V W2 W2

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(15)

1/8"=1’-0" 10-101 N 0 8 16 24 1/8"=1’-0"

SCALE FLOOR

7

7

A

B

A

B

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

A

"

8

9

10

11

12

8

9

10

11

12

PLOT DATE: 2/5/2010 PLOT TIME:2:10:15 PM

FILE NAME 6c-10nP132d_319969.dgn

P-1.02

(SECTOR B)

TRANSFER STATION BUILDING

PLUMBING

RB RB GS GENERAL NOTES: PLAN NOTES: 1. 1 2

AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM.

3

4

5

6 4" D FROM FD-3T DRAINS ON THE GRADE FLOOR.

1" W1 DOWN AND CONNECT TO PLUMBING FIXTURES AND WATER HEATER. REFER TO FIXTURE SCHEDULE ON

P-0.01 FOR STUBOUT SIZES.

7

8

BASEMENT FLOOR PLAN (SECTOR "B")

6 6

6

CO 4"

2. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400. 1 1 1 LAV-1 WC-1 3 P-5.03 3" FD-4P 15200A 4 9 9 10-10X

TOILET

15551 3 15550 15721 5 7

BENSON EUGENE SMARR - PE64269

NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

REFER TO DRAWING P-5.01 FOR TOILET RISER DIAGRAM.

10 TRENCH SUMP DRAIN REFER TO STRUCTURAL DRAWINGS.

10 10 SUMP GRATE EL 28.50 GRATE EL 28.25 TRENCH SUMP 1 1/2" HOSE REEL 1 1/2" 3/4" HOSE REEL 3/4" EE-1 4" 6 4" D DN 6 FCO-2 6" LEACHATE 15551 8" RD FROM ABOVE (11,553 SF) 2 1/2" W2 UP TO GRADE FLOOR 2" W1 UP TO GRADE FLOOR 15551 15551 15550 4" D 2 1/2" W2 CL EL 44.67 2" W1 CL EL 44.67 3" V UP TO GRADE FLOOR TRENCH SUMP 6" IE 25.58 1" W1 CL EL 46.25 2 1/2" W2 CL EL 46.25 15551 6" IE 25.58 IE 24.00 3" V UP 2 1/2" CL EL 44.67 3" V CL EL 44.00 15721 5 7 3/4" HOSE REEL 1 1/2" HOSE REEL 4" D IE 25.25 3" 4" D DN FROM GRADE FLOOR 10-WH-02 (UNDER LAV-1) FCO-2 8 8 8 4" D 6" LEACHATE 8" ON-1

REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS. 6" LEACHATE FCO-2 FCO-2 3" V UP 4" S-1.23 X Y S-1.23

TERMINATE ROOF DRAIN LEADER THRU WALL 1’-0" ABOVE GRADE AND DISCHARGE ONTO SPLASH BLOCK. COORDINATE INVERT ELEVATION WITH CIVIL.

CAST IN CONCRETE ALL BURIED LEACHATE DRAIN LINES AND SANITARY DRAIN LINES.

NOT USED 3155 3316 3316 PIPE ENCASEMENT (TYP) 8 8 FLOOR EL 28.75 3155 8" TRENCH SIDE OUTLET DRAIN IE 27.42

TUNNEL FLOOR PLAN

8" TRENCH SIDE DRAIN IE 27.17

12" TRENCH OUTLET TO MANHOLE

12" DRAIN IE 26.85

0 09/29/08 PERMIT LEVEL DRAWINGS

MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.

MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.

1 1/2" DN TO HOSE REELS V304 1 1/2" DN TO HOSE REELS V300 5’-0" AFF 1.

FIRE SPRINKLER NOTES:

ROUTE FIRE SPRINKLER MAIN ALONG NORTH AND/OR SOUTH WALL OF BASEMENT. RUN BRANCHES UP, THAT SERVE THE BASEMENT, AND BETWEEN STEEL BEAMS. PIPING SHALL NOT BE RUN BELOW THE BEAMS EXCEPT AT THE NORTH AND SOUTH WALLS.

1 08/14/09 HCBD SUBMITTAL RB

GS

11 MOUNT TRAP PRIMER EXPOSED IN CORNER.

11

RB

2 01/29/10 RB

3 02/01/10 RB

CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS D D D W 2 W1 W2 D D V D W2 W 1 W1 W2

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(16)

A

A

1

2

3

4

5

6

7

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

B

"

1

2

3

4

5

6

7

MATCH LINE

SECTOR "C"

OPEN OPEN OPEN 10-202

CRANE

SERVICE AREA

10-201

TIPPING

FLOOR

1/8"=1’-0"

GRADE FLOOR PLAN (SECTOR "A")

N

0 8 16 24

1/8"=1’-0"

PLOT DATE: 2/5/2010 PLOT TIME:2:10:21 PM

FILE NAME 6c-10nP141d_319969.dgn

P-1.03

(SECTOR A)

GRADE FLOOR PLAN

TRANSFER STATION BUILDING

PLUMBING

RB RB GS GENERAL NOTES: PLAN NOTES: 1. 1

REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS.

AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM. 2 15620 3 4 5 6 2. 7

6" ROOF GUTTER OUTLET. 1894 SF EACH.

8 9

10

HUB DRAIN FOR AC CONDENSATE.

10-20X

OPERATOR

BOOTH

3. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400.

ROUTE HYDRAULIC LINES FROM FLOOR MOUNTED OPERATOR CONTROL PANEL TO KNUCKLE BOOM CRANE ALONG BACK OF PUSH WALL.

FD-3T FD-3T 4" 4" 5 5 5 5 5

11 6" ROOF GUTTER OUTLET. 2083 SF EACH. 1 1 15721 EE-1 EYEWASH 3 11 6 6 6 6 6 1 1/2" HOSE REEL 4 10 15550 9 2 FLOOR EL 49.25 15410-1 CO (TYP) CO (TYP) 6" RD IE 76.00 6" RD IE 75.83 3" 15550 7

SLOPE 1/8" PER LF MINIMUM.

7 6" 3" V FROM BASEMENT 3" V FROM BASEMENT NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

BENSON EUGENE SMARR - PE 64269

4" FD-3T

4" FD-3T

4" DRAIN PIPING BELOW FLOOR BETWEEN STEEL BEAMS. SEE DETAIL 1 1/2" W2 CL EL 77.25 15551 3" VTR 15551 3/4" HOSE REEL 6" RD 15550 8" RD DN TO BASEMENT (9659 SF) 15550 15551 4" FD-3T

4" D FROM FD-3T AND 2" VENT UP.

7 6" RD IE 75.87 3" V CL EL 76.75 3" V CL EL 76.75 15551 3/4" W1 CL EL 77.25 1 1/2" W2 CL EL 77.25 15551 3 3 3 3

B

B

2" V 8 2" HD-1

0 09/29/08 PERMIT LEVEL DRAWINGS

MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED

FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.

MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.

1 1/2" DN TO

HOSE REELS

V300

5’-0" AFF

ALL FLOOR PIPE PENETRATIONS ABOVE THE BASEMENT FLOOR DRIVE THROUGH SHALL BE SLEEVED, REFER TO DETAIL 1 08/14/09 HCBD SUBMITTAL RB GS 4" DOWN 3" WALKWAY DRAIN 4" 4" 3" WALKWAY DRAIN 3" WALKWAY DRAIN 12 12 12 PIPING BELOW WALKWAY FCO-2 IE 47.90 IE 47.30

12 3" WALKWAY AREA DRAIN JR SMITH FIGURE 1470

OR APPROVED EQUAL BY WADE AND ZURN.

RB

PROVIDE FIRE SPRINKLERS IN THE CRANE OPERATORS BOOTH AND IN THE ROOM BELOW THE OPERATORS BOOTH.

2 01/29/10 RB

3 02/01/10 RB

CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS D R D D RD RD V V C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

(17)

A

7

8

9

10

11

12

7

8

9

10

11

12

1/8"=1’-0"

GRADE FLOOR PLAN (SECTOR "B")

N 0 8 16 24 1/8"=1’-0"

A

MATCH LINE

SECTOR "D"

M

A

T

C

H

L

IN

E

S

E

C

T

O

R

"

A

"

CRANE

SERVICE AREA

10-202 OPEN OPEN OPEN

TIPPING

FLOOR

10-201

PLOT DATE: 2/5/2010 PLOT TIME:2:10:28 PM

FILE NAME 6c-10nP142d_319969.dgn

PLAN NOTES:

AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM.

1" W1 DOWN AND CONNECT TO PLUMBING

FIXTURES AND WATER HEATER. REFER TO P-0.01 FOR STUBOUT SIZES.

6" ROOF GUTTER OUTLET. 1894 SF EACH.

1 2 3 4 5 6 7 8 9 10 GENERAL NOTES:

REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS.

15620

1.

2.

11

4" D FROM FD-3T, AND FLOOR CLEANOUT.

OPERATOR

BOOTH

10-20X

3. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400.

ROUTE HYDRAULIC LINES FROM FLOOR MOUNTED OPERATOR CONTROL PANEL TO KNUCKLE BOOM CRANE ALONG BACK OF PUSH WALL.

2 1/2" W2 FROM THE BASEMENT WITH V100 18" AFF 11 10-20X

TOILET

WC-1 LAV-1 10-WH-01 3" FD-1P (UNDER LAV-1) 3 P-5.03 15200A 12 12 15551 4" 4" 4" FCO-2

AAV AAV AAV

3 5

13 6" ROOF GUTTER OUTLET. 2083 SF EACH.

1 1 15721 15620 (TYP) 14 14 14 14 14 14 14 13 6 6 6 1 1/2" HOSE REEL 3/4" HOSE REEL 4 10 15551 15550 15551 2 9 9 FLOOR EL 49.25 CO (TYP) 6" RD IE 75.83

SLOPE 1/8" PER LF MINIMUM.

15 7 FLOOR EL 49.25 IE 46.85 2" W1 FROM THE BASEMENT WITH V304 18" AFF NOTE:

ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)

OF 1929, ADD 0.9 FEET TO THE SHOWN

ELEVATIONS.

8 MS-1

REFER TO DRAWING P-5.01 FOR TOILET RISER DIAGRAM.

ROUTE PIPING FROM WATER HEATER TO LAV-1 AND MS-1. ROUTE IN PLUMBING CHASE.

BENSON EUGENE SMARR - PE 64269

FCO-2 FCO-2 4" FD-3T 4" FD-3T 4" FD-3T 4" FD-3T 4" FD-3T 4" FD-3T 15550 15551 15551 3 6 3 5 5 1" 3/4" 2" IE 46.85 4" 4" 4" 4" 3/4" W1 CL EL 77.25 1 1/2" W2 CL EL 77.25 6" RD 2" V CL EL 76.75 3" V FROM BASEMENT

4" D DOWN FROM FD-3T AND 2" VENT UP.

FLOOR DRAIN PIPING BELOW FLOOR BETWEEN STEEL BEAMS. 2" V CL EL 76.75 15551 7 15550 8" RD DN TO BASEMENT (11,553 SF) 2 1/2" W2 CL EL 77.25 2" W1 CL EL 77.25 15551 3" 3" VTR 3/4" W1 15551 4" 2 1/2" 15551

B

B

15 HUB DRAIN FOR AC CONDENSATE.15410-1 15

3" VTR

2" HD-1

0 09/29/08 PERMIT LEVEL DRAWINGS

MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED

FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.

MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED

FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED. 1" DN WITH V304

5’-0" AFF

1 1/2 DN TO

HOSE REELS

ALL FLOOR PIPE PENETRATIONS ABOVE THE BASEMENT FLOOR DRIVE THROUGH SHALL BE SLEEVED, REFER TO DETAIL

14 14

14

1 08/14/09 HCBD SUBMITTAL

16 MOUNT TRAP PRIMER IN ACCESSIBLE PLUMBING CHASE. 16

17 4" WALKWAY AREA DRAIN, JR SMITH FIGURE 1470

OR APPROVED EQUAL BY WADE AND ZURN.

17 4" 4" IE 37.75 IE 37.25 TERMINATE AT FACE OF RETAINING WALL 18 18 ON-1

3" LANDING AREA DRAIN, PIPE IE IS AT LANDING ELEVATION.

PROVIDED FIRE SPRINKLERS IN THE CRANE OPERATORS BOOTH AND IN THE ROOM BELOW THE OPERATORS BOOTH.

2 01/29/10 3 02/01/10 RB RB RB RB

PLOT DATE: 2/5/2010 PLOT TIME:2:10:28 PM

FILE NAME 6c-10nP142d_319969.dgn

GS

BENSON EUGENE SMARR - PE 64269

GS RB

RB

PLUMBING

TRANSFER STATION BUILDING

GRADE FLOOR PLAN

(SECTOR B)

P-1.04

CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS W 1 W 2 D D D D D D RD RD RD V V RD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD

PIPE1STD PIPE1STD PIPE1STD

PIPE1STD PIPE1STD PIPE1STD PIPE1STD C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41

ENGINEERING ASSOCIATES, INC.

4921 Memorial Highway One Memorial Center, Suite 300

Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.

THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN

OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.

NORTHWEST SOLID WASTE

TRANSFER STATION EXPANSION

FOR

HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS

PROFESSIONAL SEAL

3011 SW WILLISTON RD GAINESVILLE, FL 32608

References

Related documents

The Florida master teacher initiative: Graduate education and professional development for early childhood educators [Research presentation]. Annual meeting of the Association

Install strainers immediately ahead of each expansion valve, solenoid valve, hot gas bypass valve, compressor suction valve, and as required to protect refrigerant piping

Rectisol Tall Towers platforms and replacement of corroded floor gratings & structure. Replacement/rectification of dislocated and damaged piping Headers supports, Hanger

The proposed guideline indicates the development and maintenance of an Urban Planning Area Utility Infrastructure Master Plan in which objectives and principles for urban

Surface of safes and blue second amendment digital safe to the money and if there was a hard plate each safe worth buying and the best by crediting the interruption.. corporate

The effects of “hard” water on calcium and magnesium ions is minimized by the addition of “builders”. The most common builders to be used is sodium trimetaphosphate. The phosphate

by

Using shotgun metagenomic sequencing, I compared the taxonomic composition and functional potential of sediment microbial communities in three adjacent floodplain wetland units