HEATING, VENTILATING, AND AIR CONDITIONING SYMBOLS
SUPPLY GRILLE OR REGISTER (SG, SR)
EXHAUST, RETURN, OR TRANSFER GRILLE OR REGISTER (EG, ER, RG, RR, TG, TR)
CEILING DIFFUSERS (CD)
CEILING EXHAUST, RETURN AND TRANSFER GRILLES AND REGISTERS (EG, ER, RG, RR, TG, TR)
MITERED ELBOW WITH TURNING VANES RADIUS ELBOW FIRE DAMPER FIRE/SMOKE DAMPER FS F FLEXIBLE CONNECTION (FC)
PHOTO NUMBER AND DIRECTION IDENTIFIER DOOR GRILLE
PROVIDE DOOR UNDERCUT CEILING ACCESS DOOR
POINT OF REMOVAL, DEMOLITION
POINT OF CONNECTION, RENOVATION
PRESSURE AND TEMPERATURE TEST PLUG AIR FLOW QUANTITY: 200 SCFM
VIBRATION ISOLATOR
WEATHER PROOF COMBINATION DISCONNECT AND MOTOR STARTER
COMBINATION DISCONNECT AND MOTOR STARTER
FLEXIBLE DUCTWORK (SINGLE LINE)
FLEXIBLE DUCTWORK (DOUBLE LINE) RECTANGULAR DUCT
DIMENSIONS IN INCHES
FIRST DIMENSION VISIBLE SIDE
1. 2. 3. 24x16 24/16 FLAT-OVAL DUCT DIMENSIONS IN INCHES
FIRST DIMENSION VISIBLE SIDE
1. 2. 3. ROUND DUCT DIMENSIONS IN INCHES 1. 2.
INTERNAL INSULATION/SOUND ATTENUATION AS SPECIFIED. DUCT DIMENSIONS SHOWN ARE NET INSIDE, TO INSIDE FACE OF LINER.
PROVIDE LINING WHERE SHOWN OR NOTED ON DWGS, AND AS DESCRIBED IN SPECIFICATIONS.
1. 2.
3.
1.
1.DEMOLITION - EXISTING DUCT/EQUIPMENT
TO BE REMOVED
EXISTING DUCT/EQUIPMENT TO REMAIN
EXISTING EQUIPMENT, RELOCATED
INDICATES DUCT MOUNTED CONTROL
DEVICE "X" SEE HVAC CONTROL SYMBOLS SUPPLY OR INTAKE DUCT UP
SUPPLY OR INTAKE DUCT DOWN X
R
24x16 24x16 DUCT INSPECTION DOOR
(HORIZONTAL OR VERTICAL)
INCLINED RISE (R) OR DROP (D) ARROW IN DIRECTION OF FLOW
45 DEG BRANCH CONNECTION WITH BALANCING DAMPER ECCENTRIC TRANSITION
CONCENTRIC TRANSITION
TRANSITION, FOT = FLAT ON TOP FOB = FLAT ON BOTTOM
FLEX DUCT AND SPIN-IN CONNECTION WITH INTEGRAL BALANCING DAMPER
AIR INTO OPENING AIR OUT OF OPENING
AIR OUTLET AND INLET IDENTIFICATION
HVAC EQUIPMENT IDENTIFICATION
EQUIPMENT NOMENCLATURE
CONTROL VALVES IDENTIFICATION
RETURN OR EXHAUST DUCT DOWN RETURN OR EXHAUST DUCT UP
FLOW DIRECTION VALVE SYMBOL FLOW DIRECTION ACTUATOR SYMBOL
SEQUENTIAL UNIT NUMBER BUILDING IDENTIFICATION AHU-L-1001 AIRFLOW IN CFM SPECIFICATION DESCRIPTION DIMENSIONS IN INCHES 22x22 EG-2 (250)
HVAC EQUIPMENT IDENTIFICATION
STEAM, LOW PRESSURE STEAM, HIGH PRESSURE STEAM, CONDENSATE CHILLED WATER, SUPPLY CHILLED WATER, RETURN
HEATING HOT WATER, SUPPLY HEATING HOT WATER, RETURN HVAC CONDENSATE DRAIN CONDENSER WATER, SUPPLY CONDENSER WATER, RETURN CWR CWS CD HHR HHS CHR CHS SC HPS LPS
PIPING IDENTIFICATION
FLEXIBLE (ELASTOMER) PIPE CONNECTIONPIPE ALIGNMENT GUIDE ANCHOR UNION ECCENTRIC REDUCER CONCENTRIC REDUCER LATERAL UP TEE DOWN TEE UP ELBOW DOWN ELBOW UP
STEEL BELLOWS EXPANSION JOINT GROOVED END ADAPTER FLANGE FLEXIBLE COUPLING
FLANGED JOINT
GROOVED END JOINT WELDED JOINT
EXISTING PIPE TO BE REMOVED ABANDONED
EXISTING PIPE TO BE NEW PIPE
EXISTING PIPE (SCREENED) SINGLE LINE DOUBLE LINE BALL CHECK SWING CHECK REGULATED SIDE PRESSURE CONTROL
AIR VENT (MANUAL) GATE BUTTERFLY GLOBE BALL SEATING PORT ECCENTRIC PLUG PLUG OR COCK
NEEDLE AIR VENT (AUTO)
PRESSURE RELIEF SHUT-OFF VALVE
BALANCING FITTING AND COMBINATION FLOWMETER, AND BALANCING FITTING COMBINATION FLOWMETER BALANCING FITTING
H H
T T TEMPERATURE SENSOR OR THERMOSTAT HUMIDITY SENSOR OR HUMIDISTAT
ENTHALPY SENSOR LIQUID FLOW SWITCH
DUCT MOUNTED AIRFLOW MONITORING STATION MOTOR CONTROL VALVE (2-WAY), (3-WAY) OCCUPANCY SENSOR
SWITCH
HVAC CONTROL PANEL (HCP)
VARIABLE/ADJUSTABLE FREQUENCY DRIVE AFD VFD S OS M M MS
MCC DIVISION 16 MOTOR CONTROL CENTER MOTOR STARTER
ELECTRIC MOTOR
LOW-LIMIT FREEZE THERMOSTAT FZ
M
CONDENSATE RETURN UNIT CHEMICAL FEEDER
CEILING FAN
CEILING DIFFUSER
CABINET CONVECTOR UNIT COOLING COIL
BOILER
BACKDRAFT DAMPER (GRAVITY) BALANCING DAMPER
AIR HANDLING UNIT AIR CONDITIONING UNIT
AIR COOLED CONDENSING UNIT ACCU
ACU
HVAC CONTROLS SYMBOLS
ABBREVIATIONS
AHU BD BDD BO CC CCU CD CF CMF
CEILING-MOUNTED AIR SUPPLY UNIT CRU
CSU
CU CONDENSING UNIT CABINET UNIT HEATER CUH
EA EXHAUST AIR
ELECTRIC DUCT HEATER EDH
ANALOG OUTPUT, INPUT: DATA POINT TO DDC DIGITAL OUTPUT, INPUT: DATA POINT TO DDC
FCU FD FC EUH ET ER EG EF EXHAUST FAN EXHAUST GRILLE EXHAUST REGISTER
DIAPHRAGM EXPANSION TANK ELECTRIC UNIT HEATER
FLEXIBLE CONNECTION, FAIL CLOSE FAN-COIL UNIT
FIRE DAMPER FAIL OPEN FINAL FILTER
FIBERGLASS REINFORCED PLASTIC FIRE SMOKE DAMPER
FINNED-TUBE BASEBOARD HEATER FREEZE STAT
HEATING COIL
HVAC CONTROL PANEL HOOD, EXHAUST HD HCP HC FZ FT FSD FRP FF FO CURRENT SENSOR
DIFFERENTIAL PRESSURE SENSOR OR SWITCH STATIC PRESSURE SENSOR
DUCT SMOKE DETECTOR AREA SMOKE DETECTOR MOTORIZED DAMPER
RELAY
SOLENOID VALVE
DIVISION 16 FIRE ALARM CONTROL PANEL LIQUID LINE PRESSURE SENSOR AND
SIGNAL TRANSMITTER
LIQUID FLOW INDICATING TRANSMITTER
FLOW CONTROL VALVE
TURBINE LIQUID FLOW METER
VENTURI FLOW METER OBD
OAI OA ML MD MB MAU LP IRH HX HWP HVU HTP HGS
HGR HOT GLYCOL RETURN HOT GLYCOL SUPPLY HEAT TRANSFER PACKAGE
HEATING AND VENTILATING UNIT HEATING WATER PUMP
HEAT EXCHANGER INFRARED HEATERS LOUVERED PENTHOUSE MAKEUP AIR UNIT MIXING BOX
MOTORIZED DAMPER MOTORIZED LOUVER ODOROUS AIR
OUTSIDE AIR INTAKE
OPPOSED-BLADE DAMPER (MANUAL) POSITIVE, NEGATIVE, NEUTRAL ROOM
PRESSURIZATION
FAN SPEED CONTROLLER
ALARM LIGHT AND HORN STATION
OIT OS OSA PA PCV PRESSURE-CONTROL VALVE PRESSURIZATION AIR OUTSIDE AIR OCCUPANCY SENSOR
OPERATOR INTERFACE TERMINAL
PREFILTER PREHEAT COIL
PACKAGED TERMINAL AIR CONDITIONING UNIT PTAC
PHC PF
PTS PITOT-TUBE TESTING STATION RETURN AIR RA RF RG RTU RL RR RETURN REGISTER
REFRIGERANT LIQUID PIPE RETURN GRILLE
RETURN FAN
REFRIGERANT SUCTION PIPE
SOUND ATTENUATOR, SUPPLY AIR SA RS SF SG SP SR SUPPLY REGISTER STATIC PRESSURE SUPPLY GRILLE SUPPLY FAN TRANSFER GRILLE TG UNIT HEATER
VEE-FILTER MIXING BOX
VARIABLE AIR VOLUME CEILING DIFFUSER WALL-MOUNTED AIR CONDITIONING UNIT WACU
VCD VFMB UH
THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS ON THIS SHEET MAY NOT APPEAR ON THE PLANS.
FOR ADDITIONAL ABBREVIATIONS OF OTHER DIVISIONS, SEE OTHER LEGENDS FOR PLUMBING, MECHANICAL, AND STRUCTURAL/ARCHITECTURAL. 1. 2. FCV FSC FIT PT FACP S R FI I SP DP CS FS F h
VALVE SYMBOLS
HVAC PIPING SYMBOLS
HVAC GENERAL NOTES
R (200) BALANCING DAMPER 24 DIA 24x16 AD N S SMOKE DAMPER UC WP MOTORIZED DAMPER M1 12x10 8x8 12x10 6x6 FOT+
-B B F B F S.O. M ID BACKDRAFT DAMPER BDD
ACF AIR CIRCULATION FAN
ROOF TOP UNIT AIR CONDITIONER
M
+
-PLOT DATE: 2/5/2010 PLOT TIME:2:08:38 PM
FILE NAME 6c-00nH001d_319969.dgn
LEGEND
H-0.01
HVAC
GS YMFBENSON EUGENE SMARR - PE64269
0 09/29/08 PERMIT LEVEL DRAWINGS
1 08/14/09 HCBD SUBMITTAL RB
RB
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
1/8"=1’-0" 10-101 N 0 8 16 24 1/8"=1’-0"
SCALE FLOOR
1
2
3
4
5
6
7
1
2
3
4
5
6
7
B
C
B
C
LOWER FLOOR PLAN (SECTOR "A")
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
B
"
PLOT DATE: 2/5/2010 PLOT TIME:2:09:24 PM
FILE NAME 6c-10nH131d_319969.dgn
H-1.01
(SECTOR A)
TRANSFER STATION BUILDING
HVAC
YF YF GS 10-SF-17 10-SF-18 10-SF-19 10-SF-20 10-SF-21 10-ACF-1 10-ACF-8 10-ACF-2 10-ACF-3 10-ACF-10 NOTES:PERMANENT WEST WALL OPENING. REFER TO ARCHITECTURAL DRAWINGS.
1 1 S S S S M M S S 10-ACF-9 2 H-5.03
ACF CONTROLLER (TYP)
BENSON EUGENE SMARR - PE64269
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
A
A
WALL MTD FAN (TYP OF 6) M M MTUNNEL FLOOR PLAN
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
2 01/29/10 GS
3 02/01/10 GS
CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
TF
YF GS
BENSON EUGENE SMARR - PE64269
1/8"=1’-0" N 0 8 16 24 1/8"=1’-0"
7
7
B
C
B
C
LOWER FLOOR PLAN (SECTOR "B")
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
A
"
8
9
10
11
12
8
9
10
11
12
PLOT DATE: 2/5/2010 PLOT TIME:2:09:30 PM
FILE NAME 6c-10nH132d_319969.dgn
H-1.02
(SECTOR B)
TRANSFER STATION BUILDING
HVAC
10-ACF-12 10-HCP-2 10-SF-23 10-SF-22 10-ACF-6 10-ACF-4 10-ACF-5 1 1 S S S S M M WALL MTD FAN (TYP OF 2) 2 H-5.03ACF CONTROLLER (TYP)
NOTES:
PERMANENT EAST WALL OPENING, REFER TO ARCHITECTURAL DRAWINGS.
TRANSITION DUCT AS NECESSARY FOR FINAL CONNECTION TO UNIT.
2
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS. S 10-ACF-7 10-101
SCALE FLOOR
10-ACF-11 S 10-SF-24 MA
A
13
13
14
14
RG-2 (100) 8x4 8x4 UPTUNNEL FLOOR PLAN
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
01/29/10 2
02/01/10
3 CONTRACT DOCUMENTS
CHANGES TO PERMIT DRAWINGS GS GS
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
C
A
A
C
1
2
3
4
5
6
7
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
B
"
1
2
3
4
5
6
7
MATCH LINE
SECTOR "C"
OPEN OPEN 10-202CRANE
SERVICE AREA
10-201TIPPING
FLOOR
1/8"=1’-0"UPPER FLOOR PLAN (SECTOR "A")
N
0 8 16 24
1/8"=1’-0"
PLOT DATE: 2/5/2010 PLOT TIME:2:09:36 PM
FILE NAME 6c-10nH141d_319969.dgn
H-1.03
(SECTOR A)
GRADE FLOOR PLAN
TRANSFER STATION BUILDING
HVAC
SA YF GS 10-SF-14 10-SF-13 10-SF-12 10-SF-15 10-AC-2 M M M 1 2 2 WALL MTD FAN (TYP OF 3) 6 7 5 (BELOW) 4 T 10-AC-2 8 10-ACF-13 H-5.03 1 1 3 4 H-5.03 2 2 PLAN NOTES:FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
5
SERVICE 10-AC-2 TWICE A YEAR. CHANGE RETURN GRILLE FILTER AS NEEDED.
5 H-5.03
(SIM)
6 CEILING DIFFUSER, TITUS MODEL TMSA-AA, 24x24, 400 CFM.
7
8 THERMOSTAT AND GRILLES SERVING OPERATOR BOOTH TO BE INSTALLED BY BOOTH MANUFACTURER.
ACF CONTROLLER (TYP)
BENSON EUGENE SMARR - PE64269
16x14 ALUMINUM RETURN DUCT 2 INCH DUCTBOARD INSULATION BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-2 RETURN OPENING. ELEVATION IS
APPROXIMATELY 29 FEET 10 INCHES ABOVE THE FLOOR MEASURED AT THE SOUTH WALL.
S
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
9
9 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE
WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST HUB DRAIN. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF HUB DRAINS. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO
0 09/29/08 PERMIT LEVEL DRAWINGS
10 PROVIDE FILTER AT UNIT RETURN AIR OPENING. PROVIDE ACCESS DOOR IN DUCTWORK FOR FILTER REPLACEMENT ACCESS.
RETURN GRILLE, TITUS MODEL 350FL, 24x14.
RB
1 08/14/09 HCBD SUBMITTAL RB
11
11
2 01/29/10 GS
16x14 ALUMINUM SUPPLY DUCT (SEAL CLASS A) WITH 2 INCH DUCTBOARD INSULATION. BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-2 SUPPLY OPENING. ELEVATION IS APPROXIMATELY 31 FEET 1 INCHES ABOVE
THE FLOOR MEASURED AT THE SOUTH WALL.
SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ACCESS TO
10-AC-2.
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
D R D D RD RD V V
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
A
C
7
8
9
10
11
12
7
8
9
10
11
12
1/8"=1’-0"
UPPER FLOOR PLAN (SECTOR "B")
N 0 8 16 24 1/8"=1’-0"
A
C
MATCH LINE
SECTOR "D"
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
A
"
CRANE
SERVICE AREA
10-202 OPEN OPEN OPENTIPPING
FLOOR
10-201PLOT DATE: 2/5/2010 PLOT TIME:2:09:42 PM
FILE NAME 6c-10nH142d_319969.dgn
H-1.04
(SECTOR B)
GRADE FLOOR PLAN
TRANSFER STATION BUILDING
HVAC
YF YF GS 10-AC-1 10-SF-10 10-SF-11 10-HCP-1 10-SF-9 M M M 2 2 1 T 7 8 6 10-ACF-15 10-ACF-14 5 4 (BELOW) 10-AC-1 1 H-5.03 1 3 4 2 H-5.03 2 PLAN NOTES:FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
5
SERVICE 10-AC-1 TWICE A YEAR. CHANGE RETURN GRILLE FILTER AS NEEDED.
H-5.03 5
(SIM)
6 CEILING DIFFUSER, TITUS MODEL TMSA-AA, 24x24, 800 CFM.
7
8 THERMOSTAT AND GRILLES SERVING OPERATOR BOOTH TO BE
INSTALLED BY BOOTH MANUFACTURER. WALL MTD FAN
(TYP OF 3)
BENSON EUGENE SMARR - PE64269
16x14 ALUMINUM RETURN DUCT 2 INCH DUCTBOARD INSULATION BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-1 RETURN OPENING. ELEVATION IS
APPROXIMATELY 29 FEET 2 INCHES ABOVE THE FLOOR MEASURED AT THE SOUTH WALL.
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS. ACF CONTROLLER (TYP) 8x8 RG-2 (100) 8x4 10-EF-17 6 H-5.04 2 EXHAUST LOUVER REFER TO ARCH DWGS ACCESS DOOR AT CEILING 8x4
9 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE
WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST HUB DRAIN. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF HUB DRAINS. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO
11
0 09/29/08 PERMIT LEVEL DRAWINGS
10 PROVIDE FILTER AT UNIT RETURN AIR OPENING. PROVIDE ACCESS
DOOR IN DUCTWORK FOR FILTER REPLACEMENT ACCESS. RETURN GRILLE, TITUS MODEL 350FL, 24x14.
RB
1 08/14/09 HCBD SUBMITTAL RB
11 9
16x14 ALUMINUM SUPPLY DUCT (SEAL CLASS A) WITH 2 INCH DUCTBOARD INSULATION. BOD TO BE AT SAME ELEVATION AS BOTTOM OF 10-AC-1 SUPPLY
OPENING. ELEVATION IS APPROXIMATELY 31 FEET 11 INCH ABOVE THE FLOOR MEASURED AT THE SOUTH WALL.
SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ACCESS TO 10-AC-1.
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
W 1 W 2 D D D D D D RD RD RD V V RD S S
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
1
2
3
4
5
6
7
1
2
3
4
5
6
7
C
D
C
D
UPPER LEVEL FLOOR PLAN (SECTOR "C")
1/8"=1’-0"
MATCH LINE
SECTOR "A"
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
D
"
TIPPING
FLOOR
10-201 0 8 16 24 1/8"=1’-0" NPLOT DATE: 2/5/2010 PLOT TIME:2:09:47 PM
FILE NAME 6c-10nH143d_319969.dgn
H-1.05
(SECTOR C)
GRADE FLOOR PLAN
TRANSFER STATION BUILDING
HVAC
SAYF GS
10-EF-1 10-EF-2 10-EF-3 10-EF-4
10-EF-9 10-EF-10 10-EF-11 10-EF-12
10-SF-1 10-SF-16 10-SF-2 10-SF-3 90-AC-1 M M M WALL MTD FAN (TYP OF 5) M M 1 1 1 10-SF-15 ROOF MTD FAN (TYP OF 8) 3 H-5.03 3 1 1 H-5.03 1 1 3 H-5.03 2 2 PLAN NOTES:
FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
5 H-5.03
(SIM) SERVICE 90-AC-1 TWICE A YEAR.
BENSON EUGENE SMARR - PE64269
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
4 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE
WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST DRYWELL. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF DRYWELL. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO
4
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
RD RD W2 W1 W2 W1 V V
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
C
D
MATCH LINE
SECTOR "A"
7
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
D
"
C
D
7
UPPER LEVEL FLOOR PLAN (SECTOR "D")
1/8"=1’-0" 0 8 16 24 1/8"=1’-0" N
TIPPING
FLOOR
10-2018
9
10
11
12
PLOT DATE: 2/5/2010 PLOT TIME:2:09:52 PM
FILE NAME 6c-10nH144d_319969.dgn
H-1.06
(SECTOR D)
GRADE FLOOR PLAN
TRANSFER STATION BUILDING
HVAC
SA YF GS 10-SF-4 10-SF-5 10-SF-6 10-SF-7 10-EF-8 10-EF-7 10-EF-6 10-EF-5 10-EF-16 10-EF-15 10-EF-14 10-EF-13 10-SF-8 90-AC-2 3 M 1 1 M M 1 M 1 M WALL MTD FAN (TYP OF 5) ROOF MTD FAN (TYP OF 8) 3 H-5.03 1 H-5.03 1 3 2 H-5.032 FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
H-5.03 5
(SIM) SERVICE 90-AC-2 TWICE A YEAR.
PLAN NOTES:
FAN INTAKE PLENUM TO COVER TWO LOUVERS. SEE DETAIL
BENSON EUGENE SMARR - PE64269
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
1
8X4
8x4 DN 4
3 CONDENSATE DRAIN PIPING, FULL SIZE OF UNIT CONNECTION. PIPE
WITH TRAP AND SLOPE 1/8" PER FOOT TOWARDS NEAREST DRYWELL. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF DRYWELLS. PROVIDE WALL SLEEVES FOR ALL PIPING PENETRATING WALL. ALL VOIDS TO BE SEALED WATER TIGHT. REFER TO
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
W2 RD RD RD W 1 W 2 W1 W2 W1
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
30-101
WORK
AREA
30-106TOILET
30-102BREAK
AREA
30-105FILE/
STORAGE
30-104IT
CLO
FLOOR PLAN
1/4"=1’-0" 30-EF-1 N 16x16 16x14 1 0 X 1 4 1 0 X 1 4 10x10 RG-1 RG-1 8 CD-1 (185) TYP 4 RG-1 0 4 8 12 1/4"=1’-0" 30-HP-1 30-CU-1 30-AC-1 EXHAUST LOUVER, SEE ARCH DWGS 8 CD-1 (110) 8 CD-1 (115) 8 CD-1 (110) 8 CD-1 (110) 8 CD-1 (135) T T 9 H-5.04 7 H-5.04 (TYP) 8 H-5.04 16X16 6 H-5.04 H-5.04 10 PUMPED CONDENSATE TO DRAIN PIPING, SEE PLUMBING DWGSPLOT DATE: 2/5/2010 PLOT TIME:2:09:58 PM
FILE NAME 6c-30nH141d_319969.dgn
H-3.01
FLOOR PLAN
SCALE HOUSE
HVAC
GS YMF BV GS 8x8 NOTE:ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
BENSON EUGENE SMARR - PE 64269
REFRIGERANT PIPING, RUN IN CEILING SPACE WITH
INSULATION ON SUCTION LINE, REFER TO SPECIFICATIONS.
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
1
2
PLAN NOTES:
ALUMINUM DUCTWORK, SEAL CLASS A.
2
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
INSTALL 30-HP-1 ON ROOF WITH MINIMUM 60" CLEARANCE FROM CONDENSER FAN TO BOTTOM OF CANOPY. SEE DRAWING H-5.04. UNDERCUT DOOR 3/4".
3
3
3
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
PLOT DATE: 2/5/2010 PLOT TIME:2:09:05 PM
FILE NAME 6c-00nH501d_319969.dgn
H-5.01
SCHEDULES
HVAC
BENSON EUGENE SMARR - PE64269
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
HVAC CONTROL PANEL
OFF HAND AUTO OFF HAND AUTO10-HCP-1
PILOT LIGHT LEGEND: R=RED A=AMBER G=GREEN OFF HAND AUTO OFF HAND AUTO 10-SF-1 10-EF-1 G G G G R R FAN FAIL R R FAN ON 10-SF-2 10-EF-2 OFF HAND AUTO G R 10-EF-3 OFF HAND AUTO G R 10-SF-3 OFF HAND AUTO G R 10-EF-4 OFF HAND AUTO G R 10-SF-4 OFF HAND AUTO G R 10-EF-5 OFF HAND AUTO G R 10-SF-5 OFF HAND AUTO G R 10-EF-9 OFF HAND AUTO G R 10-SF-9 OFF HAND AUTO G R 10-EF-10 OFF HAND AUTO G R 10-SF-10 OFF HAND AUTO G R 10-EF-11 OFF HAND AUTO G R 10-SF-11 OFF HAND AUTO G R 10-EF-12 OFF HAND AUTO G R 10-SF-12 OFF HAND AUTO G R OFF HAND AUTO G R
HVAC CONTROL PANEL
10-HCP-2
PILOT LIGHT LEGEND: R=RED A=AMBER G=GREEN OFF HAND AUTO G R 10-SF-17 OFF HAND AUTO G R 10-SF-18 OFF HAND AUTO G R 10-SF-19 OFF HAND AUTO G R 10-SF-20 OFF HAND AUTO G R 10-SF-21 OFF HAND AUTO G R 10-SF-22 OFF HAND AUTO G R 10-SF-23 OFF HAND AUTO G R 10-SF-24 NTS
10-HCP-2 OPERATOR INTERFACE
NTS10-HCP-1 OPERATOR INTERFACE
FAN FAIL FAN ON FAN FAIL FAN ON GENERAL NOTE:EACH CONTROL PANEL TO HAVE INTERNAL TIME CLOCK.
PLOT DATE: 2/5/2010 PLOT TIME:2:09:19 PM
FILE NAME 6c-00nH502d_319969.dgn
H-5.02
CONTROL PANELS
HVAC
OFF HAND AUTO G R 10-EF-6 OFF HAND AUTO G R 10-SF-6 OFF HAND AUTO G R 10-EF-7 OFF HAND AUTO G R 10-SF-7 OFF HAND AUTO G R 10-EF-8 OFF HAND AUTO G R 10-SF-8 OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R OFF HAND AUTO G R 10-EF-13 10-SF-13 10-EF-14 10-SF-14 10-EF-15 10-SF-15 10-EF-16 10-SF-16BENSON EUGENE SMARR - PE 64269
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 RB
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS HCBD SUBMITTAL
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
1’-6" 6"
2
1/2"=1’-0"1
SUPPLY FAN
1/2"=1’-0" 5’x6’ LOUVER(TYP 2 PER FAN)
SUPPLY FAN HOUSING 5’-0" 5’-0" 6 ’ -0 " CROSSED VERTICAL VERTICAL CROSSED 10 MOTORIZED DAMPER 55" ~ FLOOR 3/4" THREADED ROD UP TO STRUCTURE (TYP OF 4) 3/4" THREADED ROD UP TO STRUCTURE (TYP OF 4) MOTORIZED DAMPER 3/4" THREADED ROD
CROSS RODS AT MOTORIZED DAMPER FOR STABILITY
A
A
SECTION A-A
SEE ARCH FOR LOUVER ELEVATION ~23’-5" ON EAST WALL
SUPPLY/EXHAUST FAN
2"x2"x1/4" ANGLE-TYP BIRDSCREEN BIRDSCREEN 4PLOT DATE: 2/5/2010 PLOT TIME:2:08:49 PM
FILE NAME 6c-00nH401d_319969.dgn
H-5.03
STANDARD DETAILS
HVAC
ALUMINUM 16 GAUGE SHEETMETAL PLENUM ALUMINUM 16 GAUGE SHEETMETAL PLENUMBENSON EUGENE SMARR - PE 64269
LOUVER LOUVER
6"
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
2 01/29/10 GS
3 02/01/10 CONTRACT DOCUMENTS GS
CHANGES TO PERMIT DRAWINGS
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
EB0000072 AAC001992
ROOF-SEE ARCH. AND STRUCT. DRAWINGS
PRE-FAB NONCOMBUSTIBLE ROOF CURB
RUN POWER LEADS IN CORNER INSIDE CURB
DISCONNECT BY MANUFACTURER GRAVITY DAMPER
BAFFLE
3
UP-BLAST ROOF EXHAUSTER
NTSMOTORIZED DAMPER
FIBERGLASS INSULATION
CONTINUOUS PRESSURE TREATED WOOD NAILER
ROOF STRUCTURE
4
ROOF CURB MTD EQUIPMENT HURRICANE RESTRAINT
NTS
STAINLESS STEEL, #10 TEC SCREWS 2 PER STRAP
PREFABRICATED METAL ROOF CURB WITH CANT
CURB MOUNTED EQUIPMENT
HURRICANE STRAP: 2" WIDE, 18 GAGE,
STAINLESS STEEL - ONE PER SIDE (4 TOTAL)
(2) STAINLESS STEEL #10 TEC SCREW, FASTEN TO STRUCTURE
A
A
DETAIL
NTS5
WALL MTD AC UNIT
NTS DOUBLE DEFLECTION SUPPLY GRILLE SUPPLY AIR RETURN AIR INTERIOR RETURN GRILLE WALL FINISHED FLOOR CD, FULL SIZE CONNECTION TO UNITNOTE: SUPPLY AND RETURN GRILLE BY AC UNIT MANUFACTURER,
UNLESS SHOWN OTHERWISE ON PLANS. GRADE
UNIT CONDENSATE DRAIN & TRAP
EXTERIOR WALL MOUNT AC UNIT
SUPPORT UNIT PER MANUFACTURERS INSTALLATION INSTRUCTIONS
SEAL WEATHER TIGHT AROUND UNIT MOUNTING FLANGE SHEET METAL FLANGE AC UNIT
SEAL PERIMETER WITH CAULK, AIR TIGHT
GRILLE DUCT SLEEVE 10 H-5.04 TO DRY WELL, OR HUBDRAIN REFER TO PLUMBING DRAWINGS
PLOT DATE: 2/5/2010 PLOT TIME:2:09:00 PM
FILE NAME 6c-00nH402d_319969.dgn
H-5.04
STANDARD DETAILS
HVAC
BENSON EUGENE SMARR - PE64269
0 09/29/08 PERMIT LEVEL DRAWINGS RB
1 08/14/09 HCBD SUBMITTAL RB
2 01/29/10 GS
3 2/01/10 CONTRACT DRAWINGS GS
CHANGES TO PERMIT DRAWINGS
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL 3011 SW WILLISTON RD GAINESVILLE, FL 32608 EB0000072 AAC001992 REQUIRED STRUCTURE AS SUSPEND FROM VIBRATION ISOLATORS HANGER RODS WITH
EXHAUST FAN
CEILING GRILLE
FLEXIBLE CONNECTION
OR ROOF CAP. SEE PLANS FOR SIZE DUCT CONNECTION TO WALL CAP
6
CEILING MOUNTED EXHAUST FAN
NTSDUCT COLLAR WITH LOCKING QUADRANT (W/2" STANDOFF) VOLUME DAMPER. CENTER TAPS IN VERTICAL HEIGHT OF DUCT. EXTERNALLY INSULATE
WITH 2" BLANKET INSULATION BUTTERFLY DAMPER
DO NOT COVER DAMPER HANDLE WITH INSULATION.
DIFFUSER
CEILING AVOID SHARP BEND IN
FLEXIBLE DUCTS. USE GENEROUS BENDS SO THAT FLEX DOES NOT CRIMP. BLANKET INSULATION
7
DIFFUSER INSTALLATION
NTS 3 6 " M IN8
ROOFTOP HEATPUMP
NTS PROVIDE 6" SOUND ATTENUATION BLANKET IN ROOF CUB AREAFOR SOUND ATTENUATION ROOF STRUCTURE
REFER TO ARCH DWGS FOR CONSTRUCTION TYPE
COIL SECTION
FILTER SECTION SUPPLY FAN
SECTION RETURN AIR
AND OSA MIXING SECTION
NOTES:
1. PROVIDE AIRTIGHT NON-HARDENING SILICONE CAULK SEAL AT ALL PENETRATIONS. OPENINGS IN DECK SHALL BE A MAXIMUM OF 1" LARGER THAN DUCT SIZE.
2. PROVIDE GASKET BETWEEN UNIT AND CURB. PROVIDE LAG BOLTS TO CURB THROUGH A/C TO WITHSTAND HURRICANE FORCE WINDS WHERE APPLICABLE.
3. PROVIDE TRAPPED CONDENSATE DRAIN LINE FULL SIZE OF UNIT CONNECTION TO ROOF MTD HUB DRAIN. PROVIDE SUPPORT FOR DRAIN AS NECESSARY TO ATTAIN MIN
OF 1/8" PER FOOT SLOPE.
4. PROVIDE MOTORIZED OUTSIDE AIR DAMPER WHERE INDICATED IN SPECIFICATIONS OR DRAWINGS. OTHERWISE PROVIDE MANUAL DAMPER.
RETURN AIR PLENUM WITH SOUND ELBOW
ROOF CURB, SEE
FOR HURRICANE RESTRAINT 4 H-5.03 SUPPLY DUCT TRANSITION AS REQ’D
TO SIZE SHOWN ON PLANS RAIN HOOD BOTTOM OF CANOPY 60" CLEAR,COMPLY WITH MFG INSTALLATION INSTRUCTIONS PI TCH RS R L AIR COOLED CONDENSING UNIT REFRIG. SERVICE/SHUT-OFF VALVE (TYP) (OMIT IF
INCLUDED WITH UNIT) FILTER DRYER (BI-FLOW TYPE FOR HEAT PUMP)
SHRAEDER ACCESS FITTING (TYPICAL) OMIT IF INCLUDED WITH UNIT.
SOLENOID VALVE (IF REQ’D BY MFG.)
SIGHT GLASS
(IF THERMAL EXPANSION VALVE IS USED)
THERMAL EXPANSION VALVE (IF
REQ’D BY MFG)
PROVIDE RISER TRAPS WHEN CONDENSING UNIT IS ABOVE EVAPORATOR
CONTRACTOR SHALL SUBMIT A REFRIGERANT PIPING DIAGRAM APPROVED
BY THE CONDENSING UNIT MANUFACTURER BEFORE PROCEEDING WITH
WORK. (REFER TO SPECIFICATIONS FOR REFRIGERANT PIPING
INSTALLATION REQUIREMENTS)
DELETE ANY VALVES OR MATERIALS THAT ARE FURNISHED WITH UNIT. REFRIGERANT PIPING SHALL BE SIZED PER MANUFACTURER OPTIMUM PERFORMANCE RATING. NOTES: 1. 2. 3. SCHRAEDER ACCESS FITTING (TYP) (OMIT IF INCLUDED WITH UNIT)
9
REFRIGERANT PIPING
NTSPUMPED CONDENSATE DRAIN PIPE REFER TO SPECS & PLUMBING DRAWINGS
CONCRETE APRON
WALL MTD INDOOR UNIT
1-1/2" MIN
1.
HEIGHT EQUAL TO AIR HANDLER FAN STATIC
PRESSURE, 3 1/2 "(MIN) OPEN TEE PLUGGED TEE 2" REFER TO PIPING SCHEDULE OR SPECIFICATIONS FOR PIPE MATERIAL
PIPE SIZE EQUAL TO FULL SIZE OF UNIT CONNECTION. FLOOR DRAIN OR ROOF DRAIN EQUIPMENT PAD COOLING COIL FROM DRAIN PAN
EXTERNALLY INSULATE ALL CONDENSATE LINES.
(SEE PIPING SCHEDULE OR SPECIFICATIONS FOR INSULATION TYPE) NOTE:
10
CONDENSATE PIPING
NTS
2
D
1" MIN BAND CLAMP ATTACH TO
STRUCTURE PER SMACNA
RECOMMENDATIONS NUT WITH LOCK WASHER ATTACH TO STRUCTURE WITH BEAM CLAMPS OR MASONRY EXPANSION BOLTS KINDORF HANGER
WITH ALL THREAD ROD IN TRAPEZE CONFIGURATION ALL-THREAD ROD
STAINLESS STEEL
SHEET METAL SADDLE
LENGTH EQUALS DIAMETER OF DUCT
RIGID/FLEXIBLE ROUND DUCTWORK RECTANGULAR DUCTWORK
CAUSE DUCT SHAPE DEFORMATION.
HANGER SIZES SHALL BE IN ACCORDANCE WITH SMACNA, LATEST EDITION. SUPPORT SYSTEM MUST NOT DAMAGE DUCT, INSULATION, OR
SUPPORTS TO STRUCTURE.
DO NOT USE POWDER POWERED FASTENING SYSTEMS TO ATTACH
3. 2. 1. NOTES:
VALVE SYMBOLS
PLUMBING FIXTURE SCHEDULE
PLUMBING GENERAL NOTES
PIPING IDENTIFICATION
PLUMBING SYMBOLS
FIRE SPRINKLER SYMBOLS
DRAWING NOTES
ABBREVIATIONS
TEE CO
YCO-X
CLEANOUT, BUILDING EXTERIOR
Y = F - FLOOR CLEANOUT D - DECK CLEANOUT W - WALL CLEANOUT X - NO. IN SPECIFICATION HD-XY HUB DRAIN Y - T WITH TRAP
Y - P WITH PRIMED TRAP X - NO. IN SPECIFICATION FD-XY
FLOOR DRAIN
X - NO. IN SPECIFICATION Y - T WITH TRAP
Y -P WITH PRIMED TRAP RD-X
ROOF DRAIN
X = NO. IN SPECIFICATION
OVERFLOW ROOF DRAIN X = NO. IN SPECIFICATION OD-X
CLEANOUT PLUG (EXPOSED PIPING) CO
ELBOW DOWN ELBOW UP TEE DOWN
TEE DOWN WITH ELBOW ELBOW
TEE UP
THERMOMETER
PRESSURE GAUGE WITH COCK STRAINER HOSE VALVE REDUCER HOSE RACK GATE GLOBE BALL
PRESSURE RELIEF VALVE
BACKWATER CHECK VALVE CHECK VALVE
PRESSURE REGULATING VALVE
BACKFLOW PREVENTER
WALL FIRE DEPARTMENT CONNECTION
POST FIRE DEPARTMENT CONNECTION
FIRE ALARM BELL
SPECIFICATION DETAIL NUMBER ABOVE FINISHED FLOOR
AFF
DOWN DN
VTR VENT THRU ROOF
HV HOSE VALVE WC LAV EWH WATER CLOSET UR URINAL SINK
HAND HELD EYE/FACE WASH
SSK SK
LAVATORY
FA FIXED AIR GAP DRAIN
ON OVERFLOW NOZZLE SH SHOWER ABV ABOVE CL CENTERLINE CO CLEANOUT DT DILUTION TANK EL ELEVATION FD FLOOR DRAIN FDC FLR FLOOR HD HUB DRAIN IE INVERT ELEVATION LP LABORATORY FAUCET P PUMP SP SUMP PUMP
SSH SAFETY SHOWER/EYEWASH COMBINATION
SERVICE BASIN, OR SAMPLE SINK
WH WATER HEATER
15XXX
CONN CONNECTION
DEPT DEPARTMENT
RL RAIN LEADER
AAV AIR ADMITTANCE VALVE
MS MOP SINK
EWC ELECTRIC WATER COOLER
FIRE DEPARTMENT CONNECTION
WHA WATER HAMMER ARRESTER
TP TRAP PRIMER VALVE
ETP ELECTRONIC TRAP PRIMER
WF WASH FOUNTAIN
TMV THERMOSTATIC MIXING VALVE
EE EMERGENCY EYEWASH SANITARY DRAIN D ARD V ARV SANITARY VENT
ACID RESISTANT VENT ACID RESISTANT DRAIN
RD
W1 NG
HW
RECIRCULATING HOT WATER
RHW DEIONIZED WATER LABORATORY VACUUM VAC NATURAL GAS He N NITROUS OXIDE HELIUM NITROGEN
COLD WATER (POTABLE) HOT WATER (POTABLE) COMPRESSED AIR
H HYDROGEN GAS
CH2 ACETYLENE
AIR
NO
W2 COLD WATER (NON-POTABLE)
FS FIRE SPRINKLER
SPD SUMP PUMP DISCHARGE
ERW EMERGENCY RAINWATER PIPING
TW TEMPERED WATER (POTABLE)
DIW
PG PROPANE GAS
THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR
ABBREVIATIONS ON THIS SHEET MAY NOT APPEAR ON THE PLANS. FOR ADDITIONAL ABBREVIATIONS OF OTHER DIVISIONS, SEE
OTHER LEGENDS FOR HVAC, MECHANICAL, AND STRUCTURAL/ ARCHITECTURAL. 1. 2. ITEM WC-1 LAV-1 S-1 EWC-1
EE-1 EMERGENCY EYEWASH
SINK (KITCHEN) LAVATORY DESCRIPTION D ARD W1 HW W2 ADA COMPLIANT COMMENTS ADA COMPLIANT 2" -1 -1/2" 1/2" 1/2" 1/2" 1/2" -4" - 1" - -- -2" - 3/4" -
-1. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, VERIFY EXISTING PLUMBING PIPING SYSTEMS AND VERIFY NEW POINTS OF CONNECTION TO EXISTING PIPING PRIOR TO
PERFORMING WORK.
2.
4.
5.
ALL PIPE PENETRATIONS THROUGH FLOORS AND WALLS SHALL BE SLEEVED AND SEALED.
6.
7.
8.
9. PLUMBING VENTS THROUGH ROOF SHALL BE OFFSET AT ROOF TO PROVIDE MINIMUM DISTANCE OF 3’-6" FROM EXTERIOR WALL.
12.
13.
14.
COORDINATE FINAL LOCATIONS OF FLOOR AND HUB DRAINS THAT RECEIVE CONDENSATE DRAINAGE FROM HVAC EQUIPMENT.
15.
ALL PIPING LOCATED IN RETURN AIR PLENUM SPACES SHALL BE METAL.
16.
17.
INSULATE ABOVE GRADE DRAINAGE PIPING THAT RECEIVES CONDENSATE FROM AIR CONDITIONING UNITS.
CLEANOUT TO GRADE FITTINGS, WHERE SANITARY DRAIN EXITS THE BUILDING, SHALL ALLOW FOR RODDING BOTH WAYS.
PROVIDE CLEANOUTS IN ROOF DRAIN PIPING, ROOF OVERFLOW DRAIN PIPING AND SANITARY WASTE PIPING AS SHOWN ON THE DRAWINGS. FURNISH AND INSTALL ADDITIONAL CLEANOUTS AS REQUIRED BY CODE. 3.
ALL BURIED AND CONCRETE ENCASED COPPER PIPING SHALL BE INSTALLED WITH A PROTECTIVE SLEEVE, OR WRAP, FOR ITS ENTIRE LENGTH. SLEEVE, OR WRAP, SHALL BE FLEXIBLE POLYETHYLENE MANUFACTURED FOR CONTINUOUS PIPE COVER APPLICATION. EXTEND SLEEVE, OR WRAP, 2 INCHES ABOVE FINISHED FLOOR.
THE CONTRACTOR SHALL PROVIDE OFFSETS IN THE PIPING RUNS, IN ADDITION TO WHAT IS SHOWN ON THE DRAWINGS, WHERE
REQUIRED TO CLEAR EXISTING AND NEW; DUCT, STRUCTURE AND OTHER PIPING SYSTEMS.
ALL PIPES PASSING THROUGH FIRE RATED WALLS AND FLOORS SHALL BE INSTALLED TO MEET APPLICABLE UL SYSTEM REQUIREMENTS PERTAINING TO THE TYPE OF CONSTRUCTION. REFER TO ARCHITECTURAL DRAWINGS FOR WALLS WHICH ARE FIRE RATED.
FURNISH AND INSTALL WATER HAMMER ARRESTERS ON W1 AND HW PIPING IN RESTROOM AREAS. P.D.I. SIZE "C" MINIMUM.
PATCH ALL HOLES IN WALLS AND FLOORS LEFT AS A RESULT OF PLUMBING WORK.
PIPING ELEVATIONS SHOWN ARE APPROXIMATE, FIELD VERIFY PIPING ELEVATIONS PRIOR TO INSTALLATION.
11.
INSTALL TRAP PRIMER VALVES ON ALL FLOOR AND HUB DRAINS WITH "P" EXTENSION, SEE DETAIL 15200A. FLOOR AND HUB DRAINS WITH "T" EXTENSIONS SHALL HAVE DEEP SEAL TRAPS.
RAIN WATER DRAIN
-REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF PLUMBING FIXTURES, ROOF DRAINS, AND ROOF GUTTER OUTLETS.
PLOT DATE: 2/5/2010 PLOT TIME:2:10:02 PM
FILE NAME 6c-00nP001d_319969.dgn
P-0.01
ABBREVIATIONS
LEGEND AND
PLUMBING
ELECTRIC WATER COOLER 1/2"
WATER CLOSET - FLOOR MOUNTED FLUSH VALVE TYPE
EMERGENCY EYEWASH
FF FINISHED FLOOR
3" - 1/2" 1/2"
-MS-1 MOP SINK
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
BENSON EUGENE SMARR - PE 64269
09/29/08
0 PERMIT LEVEL DRAWINGS
SPECIFICATIONS:
a. FOR PLUMBING PIPING SCHEDULE SEE SECTION 15100. b. FOR PIPE SUPPORTS AND HANGERS SEE SECTION 15100
AND DETAILS REFERENCED ON THE DRAWINGS.
c. FOR PIPING INSULATION SEE SECTION 15255. d FOR PLUMBING PIPING SEE SECTION 15100. e. FOR VALVES SEE SECTION 15202.
f. FOR PLUMBING FIXTURES SEE SECTION 15410.
g. FOR PLUMBING EQUIPMENT SEE SECTION 15440.
h. FOR FIRE SPRINKLER SYSTEM SEE SECTION 13930.
08/14/09
1 HCBD SUBMITTAL RB
10. PROVIDE PIPE IDENTIFICATION FOR PLUMBING SYSTEMS. REFER TO SECTION 15100, PLUMBING PIPING SCHEDULE.
18. BV GS RB RB RB 01/29/10 2 RB 02/01/10 3 RB
CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
1/8"=1’-0" 10-101 N 0 8 16 24 1/8"=1’-0"
SCALE FLOOR
1
2
3
4
5
6
7
1
2
3
4
5
6
7
A
B
A
B
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
B
"
PLOT DATE: 2/5/2010 PLOT TIME:2:10:08 PM
FILE NAME 6c-10nP131d_319969.dgn
P-1.01
(SECTOR A)
TRANSFER STATION BUILDING
PLUMBING
RB RB GS GENERAL NOTES: PLAN NOTES: 1. 1 2AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM. 3 4 5 6 FLOOR EL 28.75
BASEMENT FLOOR PLAN (SECTOR "A")
4" D FROM FD-3T DRAINS ON THE GRADE FLOOR. 1 1/2"
CL EL 44.67
2. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400. 1 1 1 4 4 4 4" 8 15550 X S-1.23 1 1/2" HOSE REEL 3/4" HOSE REEL 5 3
BENSON EUGENE SMARR - PE64269
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
FCO-2 6" LEACHATE
5
P-5.03
TRENCH SUMP DRAINS REFER TO STRUCTURAL DRAWINGS (TYP)
6" GRATE EL 28.25 3" 6" 6" LEACHATE 4 6" LEACHATE 4" D 6" 6" FCO-2 4 15551 15551 2 1/2" 4" 5 1 1/2" HOSE REEL 3/4" HOSE REEL 3 2 2 2 4" D 3" CL EL 44.00 15551 15551 3" V UP TO GRADE FLOOR TRENCH SUMP GRATE EL 28.25 TYP OF 2 2 1/2" W2 CL EL 44.67 7 7 FIRE SPR RISER 15551 8 6 6 TO FIRE SPRINKLER SYSTEM 2" P-5.03 1 2" W1 CL EL 44.67
REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS. S-1.23 Y 6" IE 25.58 (AT SUMP) 6" IE 25.58 (AT SUMP) 6" IE 25.58 (AT SUMP) 15721 15721 8" RD FROM ABOVE (9659 SF) 8" ON-1
TERMINATE ROOF DRAIN LEADER THRU WALL 1’-0" ABOVE GRADE AND DISCHARGE ONTO SPLASH BLOCK. COORDINATE INVERT ELEVATION WITH CIVIL.
2 1/2" AND 2" V642 BACKFLOW PREVENTERS STACKED. 3316 6 3155 3155 6 PIPE ENCASEMENT (TYP) 6 6 IE 21.50 AT SUMP FCO-2 IE 21.90 3" IE 23.75 2" DOMESTIC FM 2" W1 AND 2 1/2" W2 UP CO IE 44.00 FC0-2 IE 25.00 IE 25.00 4" HDPE LEACHATE FM 2 IE 24.25 3" V UP TO GRADE FLOOR 6" IE 25.58 (AT SUMP) IE 22.37 AT SUMP DOMESTIC PUMP STATION WET WELL LEACHATE PUMP
STATION WET WELL LEACHATE
VALVE VAULT
CAST IN CONCRETE ALL BURIED LEACHATE DRAIN AND FM LINES, SANITARY DRAIN AND FM LINES.
3155 DOMESTIC PS VALVE VAULT 6" LEACHATE 8" TRENCH BOTTOM OUTLET
REFER TO UTILITY PLAN C-6.06 AND C-5.03 FOR CONTINUATION.
8" STORM DRAIN
IE 24.50
PIPE DN AND CAST INTO WALL AND FLOOR SLAB
IE 30.00
IE 30.33
PIPE DN AND CAST INTO WALL AND FLOOR SLAB EXTERIOR 3/4" V235 3’-0" ABOVE GRADE (FEED FROM W2) 3316 IE 22.20 4" W1 (CLDI) 4" W1 (CLDI) 6" FS (CLDI) 6" LEACHATE FROM TIPPING FLOOR
TUNNEL FLOOR PLAN
PERMIT LEVEL DRAWINGS
09/29/08 0 1 1/2" DN TO HOSE REELS 1 1/2" DN TO HOSE REELS
MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.
MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.
CL EL 45.92
BETWEEN BEAMS
1.
FIRE SPRINKLER NOTES:
ROUTE FIRE SPRINKLER MAIN ALONG NORTH AND/OR SOUTH WALL OF BASEMENT. RUN BRANCHES UP, THAT SERVE THE BASEMENT, AND BETWEEN STEEL BEAMS. PIPING SHALL NOT BE RUN BELOW THE BEAMS EXCEPT AT THE NORTH AND SOUTH WALLS.
08/14/09
1 HCBD SUBMITTAL RB
GS
9
9 4" FROM CANTILEVERED WALKWAY ABOVE, TERMINATE DRAIN
LEADER 1’-0" ABOVE GRADE AND DISCHARGE ONTO SPLASH BLOCK. RB 01/29/10 2 RB 02/01/10 3 RB
CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS D D V V W1 W1 W2 W2 D V V W2 W2
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
1/8"=1’-0" 10-101 N 0 8 16 24 1/8"=1’-0"
SCALE FLOOR
7
7
A
B
A
B
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
A
"
8
9
10
11
12
8
9
10
11
12
PLOT DATE: 2/5/2010 PLOT TIME:2:10:15 PM
FILE NAME 6c-10nP132d_319969.dgn
P-1.02
(SECTOR B)
TRANSFER STATION BUILDING
PLUMBING
RB RB GS GENERAL NOTES: PLAN NOTES: 1. 1 2AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM.
3
4
5
6 4" D FROM FD-3T DRAINS ON THE GRADE FLOOR.
1" W1 DOWN AND CONNECT TO PLUMBING FIXTURES AND WATER HEATER. REFER TO FIXTURE SCHEDULE ON
P-0.01 FOR STUBOUT SIZES.
7
8
BASEMENT FLOOR PLAN (SECTOR "B")
6 6
6
CO 4"
2. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400. 1 1 1 LAV-1 WC-1 3 P-5.03 3" FD-4P 15200A 4 9 9 10-10X
TOILET
15551 3 15550 15721 5 7BENSON EUGENE SMARR - PE64269
NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
REFER TO DRAWING P-5.01 FOR TOILET RISER DIAGRAM.
10 TRENCH SUMP DRAIN REFER TO STRUCTURAL DRAWINGS.
10 10 SUMP GRATE EL 28.50 GRATE EL 28.25 TRENCH SUMP 1 1/2" HOSE REEL 1 1/2" 3/4" HOSE REEL 3/4" EE-1 4" 6 4" D DN 6 FCO-2 6" LEACHATE 15551 8" RD FROM ABOVE (11,553 SF) 2 1/2" W2 UP TO GRADE FLOOR 2" W1 UP TO GRADE FLOOR 15551 15551 15550 4" D 2 1/2" W2 CL EL 44.67 2" W1 CL EL 44.67 3" V UP TO GRADE FLOOR TRENCH SUMP 6" IE 25.58 1" W1 CL EL 46.25 2 1/2" W2 CL EL 46.25 15551 6" IE 25.58 IE 24.00 3" V UP 2 1/2" CL EL 44.67 3" V CL EL 44.00 15721 5 7 3/4" HOSE REEL 1 1/2" HOSE REEL 4" D IE 25.25 3" 4" D DN FROM GRADE FLOOR 10-WH-02 (UNDER LAV-1) FCO-2 8 8 8 4" D 6" LEACHATE 8" ON-1
REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS. 6" LEACHATE FCO-2 FCO-2 3" V UP 4" S-1.23 X Y S-1.23
TERMINATE ROOF DRAIN LEADER THRU WALL 1’-0" ABOVE GRADE AND DISCHARGE ONTO SPLASH BLOCK. COORDINATE INVERT ELEVATION WITH CIVIL.
CAST IN CONCRETE ALL BURIED LEACHATE DRAIN LINES AND SANITARY DRAIN LINES.
NOT USED 3155 3316 3316 PIPE ENCASEMENT (TYP) 8 8 FLOOR EL 28.75 3155 8" TRENCH SIDE OUTLET DRAIN IE 27.42
TUNNEL FLOOR PLAN
8" TRENCH SIDE DRAIN IE 27.17
12" TRENCH OUTLET TO MANHOLE
12" DRAIN IE 26.85
0 09/29/08 PERMIT LEVEL DRAWINGS
MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.
MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.
1 1/2" DN TO HOSE REELS V304 1 1/2" DN TO HOSE REELS V300 5’-0" AFF 1.
FIRE SPRINKLER NOTES:
ROUTE FIRE SPRINKLER MAIN ALONG NORTH AND/OR SOUTH WALL OF BASEMENT. RUN BRANCHES UP, THAT SERVE THE BASEMENT, AND BETWEEN STEEL BEAMS. PIPING SHALL NOT BE RUN BELOW THE BEAMS EXCEPT AT THE NORTH AND SOUTH WALLS.
1 08/14/09 HCBD SUBMITTAL RB
GS
11 MOUNT TRAP PRIMER EXPOSED IN CORNER.
11
RB
2 01/29/10 RB
3 02/01/10 RB
CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS D D D W 2 W1 W2 D D V D W2 W 1 W1 W2
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
A
A
1
2
3
4
5
6
7
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
B
"
1
2
3
4
5
6
7
MATCH LINE
SECTOR "C"
OPEN OPEN OPEN 10-202CRANE
SERVICE AREA
10-201TIPPING
FLOOR
1/8"=1’-0"GRADE FLOOR PLAN (SECTOR "A")
N
0 8 16 24
1/8"=1’-0"
PLOT DATE: 2/5/2010 PLOT TIME:2:10:21 PM
FILE NAME 6c-10nP141d_319969.dgn
P-1.03
(SECTOR A)
GRADE FLOOR PLAN
TRANSFER STATION BUILDING
PLUMBING
RB RB GS GENERAL NOTES: PLAN NOTES: 1. 1REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS.
AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM. 2 15620 3 4 5 6 2. 7
6" ROOF GUTTER OUTLET. 1894 SF EACH.
8 9
10
HUB DRAIN FOR AC CONDENSATE.
10-20X
OPERATOR
BOOTH
3. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400.
ROUTE HYDRAULIC LINES FROM FLOOR MOUNTED OPERATOR CONTROL PANEL TO KNUCKLE BOOM CRANE ALONG BACK OF PUSH WALL.
FD-3T FD-3T 4" 4" 5 5 5 5 5
11 6" ROOF GUTTER OUTLET. 2083 SF EACH. 1 1 15721 EE-1 EYEWASH 3 11 6 6 6 6 6 1 1/2" HOSE REEL 4 10 15550 9 2 FLOOR EL 49.25 15410-1 CO (TYP) CO (TYP) 6" RD IE 76.00 6" RD IE 75.83 3" 15550 7
SLOPE 1/8" PER LF MINIMUM.
7 6" 3" V FROM BASEMENT 3" V FROM BASEMENT NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
BENSON EUGENE SMARR - PE 64269
4" FD-3T
4" FD-3T
4" DRAIN PIPING BELOW FLOOR BETWEEN STEEL BEAMS. SEE DETAIL 1 1/2" W2 CL EL 77.25 15551 3" VTR 15551 3/4" HOSE REEL 6" RD 15550 8" RD DN TO BASEMENT (9659 SF) 15550 15551 4" FD-3T
4" D FROM FD-3T AND 2" VENT UP.
7 6" RD IE 75.87 3" V CL EL 76.75 3" V CL EL 76.75 15551 3/4" W1 CL EL 77.25 1 1/2" W2 CL EL 77.25 15551 3 3 3 3
B
B
2" V 8 2" HD-10 09/29/08 PERMIT LEVEL DRAWINGS
MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED
FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.
MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.
1 1/2" DN TO
HOSE REELS
V300
5’-0" AFF
ALL FLOOR PIPE PENETRATIONS ABOVE THE BASEMENT FLOOR DRIVE THROUGH SHALL BE SLEEVED, REFER TO DETAIL 1 08/14/09 HCBD SUBMITTAL RB GS 4" DOWN 3" WALKWAY DRAIN 4" 4" 3" WALKWAY DRAIN 3" WALKWAY DRAIN 12 12 12 PIPING BELOW WALKWAY FCO-2 IE 47.90 IE 47.30
12 3" WALKWAY AREA DRAIN JR SMITH FIGURE 1470
OR APPROVED EQUAL BY WADE AND ZURN.
RB
PROVIDE FIRE SPRINKLERS IN THE CRANE OPERATORS BOOTH AND IN THE ROOM BELOW THE OPERATORS BOOTH.
2 01/29/10 RB
3 02/01/10 RB
CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS D R D D RD RD V V C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608
A
7
8
9
10
11
12
7
8
9
10
11
12
1/8"=1’-0"
GRADE FLOOR PLAN (SECTOR "B")
N 0 8 16 24 1/8"=1’-0"
A
MATCH LINE
SECTOR "D"
M
A
T
C
H
L
IN
E
S
E
C
T
O
R
"
A
"
CRANE
SERVICE AREA
10-202 OPEN OPEN OPENTIPPING
FLOOR
10-201PLOT DATE: 2/5/2010 PLOT TIME:2:10:28 PM
FILE NAME 6c-10nP142d_319969.dgn
PLAN NOTES:
AREA BOUNDARY OF THE WET PIPE FIRE SPRINKLER SYSTEM.
1" W1 DOWN AND CONNECT TO PLUMBING
FIXTURES AND WATER HEATER. REFER TO P-0.01 FOR STUBOUT SIZES.
6" ROOF GUTTER OUTLET. 1894 SF EACH.
1 2 3 4 5 6 7 8 9 10 GENERAL NOTES:
REFER TO PLUMBING LEGEND DRAWING P-0.01 FOR PLUMBING GENERAL NOTES AND ADDITIONAL REQUIREMENTS.
15620
1.
2.
11
4" D FROM FD-3T, AND FLOOR CLEANOUT.
OPERATOR
BOOTH
10-20X
3. PROVIDE NONPOTABLE WATER SIGN AT ALL W2 HOSE VALVE LOCATIONS. REFER TO SPECIFICATION SECTION 10400.
ROUTE HYDRAULIC LINES FROM FLOOR MOUNTED OPERATOR CONTROL PANEL TO KNUCKLE BOOM CRANE ALONG BACK OF PUSH WALL.
2 1/2" W2 FROM THE BASEMENT WITH V100 18" AFF 11 10-20X
TOILET
WC-1 LAV-1 10-WH-01 3" FD-1P (UNDER LAV-1) 3 P-5.03 15200A 12 12 15551 4" 4" 4" FCO-2AAV AAV AAV
3 5
13 6" ROOF GUTTER OUTLET. 2083 SF EACH.
1 1 15721 15620 (TYP) 14 14 14 14 14 14 14 13 6 6 6 1 1/2" HOSE REEL 3/4" HOSE REEL 4 10 15551 15550 15551 2 9 9 FLOOR EL 49.25 CO (TYP) 6" RD IE 75.83
SLOPE 1/8" PER LF MINIMUM.
15 7 FLOOR EL 49.25 IE 46.85 2" W1 FROM THE BASEMENT WITH V304 18" AFF NOTE:
ALL ELEVATIONS SHOWN ARE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM (NAVD) OF 1988. TO CONVERT TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD)
OF 1929, ADD 0.9 FEET TO THE SHOWN
ELEVATIONS.
8 MS-1
REFER TO DRAWING P-5.01 FOR TOILET RISER DIAGRAM.
ROUTE PIPING FROM WATER HEATER TO LAV-1 AND MS-1. ROUTE IN PLUMBING CHASE.
BENSON EUGENE SMARR - PE 64269
FCO-2 FCO-2 4" FD-3T 4" FD-3T 4" FD-3T 4" FD-3T 4" FD-3T 4" FD-3T 15550 15551 15551 3 6 3 5 5 1" 3/4" 2" IE 46.85 4" 4" 4" 4" 3/4" W1 CL EL 77.25 1 1/2" W2 CL EL 77.25 6" RD 2" V CL EL 76.75 3" V FROM BASEMENT
4" D DOWN FROM FD-3T AND 2" VENT UP.
FLOOR DRAIN PIPING BELOW FLOOR BETWEEN STEEL BEAMS. 2" V CL EL 76.75 15551 7 15550 8" RD DN TO BASEMENT (11,553 SF) 2 1/2" W2 CL EL 77.25 2" W1 CL EL 77.25 15551 3" 3" VTR 3/4" W1 15551 4" 2 1/2" 15551
B
B
15 HUB DRAIN FOR AC CONDENSATE.15410-1 15
3" VTR
2" HD-1
0 09/29/08 PERMIT LEVEL DRAWINGS
MOUNT 1 1/2" HOSE REEL 4’-0" ABOVE FINISHED
FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED.
MOUNT 3/4" HOSE REEL 4’-0" ABOVE FINISHED
FLOOR. PROVIDE HOSE, FITTINGS AND ADAPTERS REQUIRED. 1" DN WITH V304
5’-0" AFF
1 1/2 DN TO
HOSE REELS
ALL FLOOR PIPE PENETRATIONS ABOVE THE BASEMENT FLOOR DRIVE THROUGH SHALL BE SLEEVED, REFER TO DETAIL
14 14
14
1 08/14/09 HCBD SUBMITTAL
16 MOUNT TRAP PRIMER IN ACCESSIBLE PLUMBING CHASE. 16
17 4" WALKWAY AREA DRAIN, JR SMITH FIGURE 1470
OR APPROVED EQUAL BY WADE AND ZURN.
17 4" 4" IE 37.75 IE 37.25 TERMINATE AT FACE OF RETAINING WALL 18 18 ON-1
3" LANDING AREA DRAIN, PIPE IE IS AT LANDING ELEVATION.
PROVIDED FIRE SPRINKLERS IN THE CRANE OPERATORS BOOTH AND IN THE ROOM BELOW THE OPERATORS BOOTH.
2 01/29/10 3 02/01/10 RB RB RB RB
PLOT DATE: 2/5/2010 PLOT TIME:2:10:28 PM
FILE NAME 6c-10nP142d_319969.dgn
GS
BENSON EUGENE SMARR - PE 64269
GS RB
RB
PLUMBING
TRANSFER STATION BUILDING
GRADE FLOOR PLAN
(SECTOR B)
P-1.04
CHANGES TO PERMIT DRAWINGS CONTRACT DOCUMENTS W 1 W 2 D D D D D D RD RD RD V V RD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD PIPE1STD
PIPE1STD PIPE1STD PIPE1STD
PIPE1STD PIPE1STD PIPE1STD PIPE1STD C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41 C12x7.41
ENGINEERING ASSOCIATES, INC.
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone 813 880-8881 Fax 813 880-8882 www.kingengineering.com Engineering License #2610 DESIGNED DRAWN CHECKED Q.C.
THE SIGNATURE OF THE QUALITY CONTROL OFFICER IN THIS SPACE INDICATES THAT ALL REQUIRED PERMITS HAVE BEEN
OBTAINED AND THAT CONSTRUCTION IS AUTHORIZED TO COMMENCE. C O P Y R IG H T 2 0 0 6 K IN G E N G IN E E R IN G A S S O C IA T E S , IN C . D R A W IN G S A N D C O N C E P T S M A Y N O T B E U S E D O R R E P R O D U C E D W IT H O U T W R IT T E N P E R M IS S IO N C O N S E N T I S H E R E B Y G R A N T E D S P E C IF IC A L L Y T O G O V E R N M E N T A L A G E N C IE S T O R E P R O D U C E T H IS D O C U M E N T I N C O M P L IA N C E W IT H F .S . C H A P T E R 1 1 9 . -APP’D BY DESCRIPTION DATE NO. AUGUST 2006 SCALE: AS SHOWN 5171-407-001 JOB NO. DATE: SHEET NO.
NORTHWEST SOLID WASTE
TRANSFER STATION EXPANSION
FOR
HILLSBOROUGH COUNTY BOARD OF COUNTY COMMISSIONERS
PROFESSIONAL SEAL
3011 SW WILLISTON RD GAINESVILLE, FL 32608