LM6000-

50/60 HZ

Gas Turbine Generator Set

Product Specification

GE Energy

1333 West Loop South

Houston, TX 77027

Telephone: 713-803-0900

THIS PRODUCT MANUAL IS SUBMITTED WITH THE UNDERSTANDING THAT THE INFORMATION CONTAINED HEREIN WILL BE KEPT CONFIDENTIAL AND NOT DISCLOSED TO OTHERS OR DUPLCIATED WITHOUT THE PRIOR CONSENT OF GE ENERGY DATA AND SPECIFICATIONS MAY BE UPDATED FROM TIME TO TIME WITHOUT NOTICE. DATE OF ISSUE-6/2008

(2)

LM6000 - 60Hz Classic 6/2008

TABLE OF CONTENTS Index I

Table of Contents

Tab

Introduction

LM6000 Introduction 1

Technical Data

Data Sheet 2

Codes and Standards 3

Performance

Typical Performance Specifications 4

Typical Performance Curves 5

Description of Equipment

Major Equipment 6

System Descriptions – Major Equipment 7

Optional Equipment 8

Mechanical Outlines 9

Generator, Exciter and Voltage Regulator 10

One-Line Diagram 11

Control System Description 12

Equipment and Services by Buyer 13

Reference Specifications 14

(3)

LM6000 - 60 Hz Classic 6/2008 Page 2 of 156

Tab

Services

Customer Drawings 16

Extended Scope Equipment and Services 17

Training 18

(4)

LM6000 - 60 Hz Classic 6/2008 Page 3 of 156

1.

LM6000 Introduction

1.1

Equipment Capabilities

GE is pleased to offer the LM6000 Aeroderivative Package. With the ability to deliver over 49 MW on a gross electrical basis, the LM6000 maintains the proven reliable technology with modern design enhancements to improve maintainability and reliability. Additional benefits of the LM60000 Package are the lower overall installed cost, shorten installation time, reduced customer interfaces and enhanced safety.

The Package features the GE LM6000 gas turbine and a matching electric generator. It is designed for simple-cycle, combined-cycle, and cogeneration installations. The LM6000 is built with rugged components for base-load utility service. It can also start and stop easily for “peaking” or “dispatched” applications. Additionally, quick dispatchability is available in simple-cycle applications with the 10-minute fast start feature.

Package Type (60 Hz) kW Btu/kWh KJ/kWh

LM6000 PC SPRINT® – Natural Gas and Water Injection

50,337 8457 8923

LM6000 PC – Natural Gas and Water Injection

LM6000 PC – Natural Gas and Steam Injection 43,882 43,854 8,511 7,879 8,980 8,312

Conditions: Power at generator terminals NOx = 25 ppm (SAC-Water)

59º F / 15 ºC, 60% RH 13.8kV, 0.85 pf

Losses: 0”/0” H2O Inlet/Exhaust

Fuel: Spec Gas (19,000 Btu / Lb, LHr) at 77º / 25ºC VIGV option included

1.1.2 Engine Heritage

The LM6000 gas turbine is derived from the GE commercial CF6-80C2 aircraft engine. This engine first entered aircraft service in 1985 and is used extensively in wide-body commercial airliners. More than 2000 “80C2” engines are either on order or in use today.

1.1.3 Simple Design

The LM6000 package is offered in a 50 Hz and 60 Hz design. This document covers the 60 Hz design.

The LM6000 is a 2-shaft gas turbine engine equipped with a low-pressure compressor, high-pressure compressor, combustor, high-high-pressure turbine, and low-high-pressure turbine.

(5)

LM6000 - 60 Hz Classic 6/2008 Page 4 of 156

1.1.4 Emissions Control

The table below shows the emission levels for each configuration at 15% O2 dry.

Product Offerings Fuel Combustor Diluent Power

Augmentation NOx Level

LM6000 SAC, 60 Hz Gas, Liquid or Dual Fuel

Single Annular

(SAC) Water None

25 ppm gas/ 42 ppm liquid LM6000 DLE, 60 Hz Gas Dry Low Emissions

(DLE) None None 15 ppm

LM6000 Emissions Abatement Configurations

1.1.5 Output Enhancements

Various options are available to improve the typical OUTPUT-MW profile of the LM6000 gas turbine. To improve high ambient temperature performance, either evaporative cooling or coils for mechanical chilling are available.= GE Energy will work with the customer to determine the applicability of of these enhancements to their particular case.

1.1.6 High Availability and Reliability

The LM6000 gas turbine generator set has a proven record of high availability and reliability. With more than 700 units installed since 1992, the LM6000 gas turbine generator set leads the industry in reliability greater than 99.7%* and availability above 98.6%*. Each gas turbine is factory tested to full speed and full load for performance and mechanical integrity. Every package is static tested to check each system of the package. Refer to section 1.2.1 for static testing summary.

Leveraging aircraft experience and design, the aeroderivative design approach incorporates features such as split castings, modular construction, individual replacement of internal and external parts, and GE’s “lease pool” engine program. The extensive use of high quality components common with its parent aircraft engine validates engine reliability and offers reduced parts cost.

Various inspections and hot section repairs can be performed on the gas turbine at site within the turbine enclosure. The “Hot Section”,HPT and combustor, can be removed/replaced in the field within seventy-two hours allowing for greater availability during planned maintenance. Greater availability is achieved by the on-condition maintenance program, which inspects and repairs only as necessary to desired operational condition.

(6)

LM6000 - 60 Hz Classic 6/2008 Page 5 of 156

1.1.7 Simple Cycle

Simple cycle aeroderivative gas turbines are typically used to support the grid by providing quick start (10 minutes to full power) and load following capability. High part-power efficiency, as shown in Figure 1.1, enhances load following and improves system-operating economics.

Figure 1.1: Part Power Efficiency

1.2

Factory and Service Capabilities

A full range of services are available for the LM6000:

1.2.1 Factory Static Testing

The standard factory test for the package is a 400-point static test to confirm:

• Temperature element output and wiring

• Transmitter range, output and wiring

• Solenoid operation

• Control valve torque motor, excitation and return signal

• Fire system continuity and device actuation

Basis of Performance: Amb 59ºF RH of 60% with 0” H20 inlet/exhaust losses at 0 ft. ASL, Fuel natural Gas (19,000 Btu / Lb), 60Hz, 13.8 kV, 0.85pf. Not for guarantee.

NOx Water, Steam and DLE are to 25 PPMVD Nox at 15% 02 25% 27% 29% 31% 33% 35% 37% 39% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100% % of Baseload E ff ic ie n c y , % SAC-Dry SAC-Water DLE

(7)

LM6000 - 60 Hz Classic 6/2008 Page 6 of 156

• System cleanliness

• Control system software loading and validation

1.2.2 Factory String Testing

Available as a factory option. Reference section 8.2.28 for more details on String Testing.

1.2.3 Drawings and Service Manuals

Drawings are supplied which allow a buyer to design foundations for the package and off-base auxiliary modules, make station layouts, order long lead buyer-supplied equipment and prepare an installation bid package or plan. The Operation and Maintenance Manuals are provided in CD form in the English language, using standard (U.S.) customary engineering units. The manuals include basic concepts in operating the power generating equipment, guides to troubleshooting, equipment schematics, and general arrangement and flow and instrument diagrams.

The copies of the Installation and Commissioning (I&C) manuals will also be provided.

1.2.4 Recommended Spare Parts

Supplied with the Operation and Maintenance Manual are lists of the recommended spare parts for the turbine, generator, exciter, unit controls and off-base accessories. Additionally, specialists are available to assist you with your parts planning and ordering activities.

1.2.5 Installation and Start-Up Services

Field service consultation for installation and startup is available as an option with the basic unit. This extended service can be supplemented with the full range of in-house product support services available with various GE divisions and GE Energy in Houston, including supervisory services for field assembly of the major equipment components, commissioning and initial operation. Refer to Section 17 for details. (do a find and replace where appropriate for “See Section” to Refer to)

1.2.6 Operation and Maintenance Training

The basic scope includes a Gas Turbine Familiarization Course in Cincinnati, Ohio and an Operator’s Training Course at the GE Energy Jacintoport facility. These courses include basic concepts of an aeroderivative gas turbine generator set plus the normal operating guidelines and maintenance practices. Additional training courses are available (i.e., for controls) at other GE Training Centers.

(8)

LM6000 - 60 Hz Classic 6/2008 Page 7 of 156

1.2.7 Field Verification of Performance

GE Energy will assist with field performance testing to demonstrate that the generator electrical output and heat rate achieve guaranteed levels.

1.2.8 Summary

In summary, the LM6000 is unique to the power generation industry. As the most trusted and reliable gas turbines in the world, we recommend the LM6000 as a standard 40-50 MW building block for utility and industrial applications.

(9)

LM6000 - 60 Hz Classic 6/2008 Page 8 of 156

2.

Data Sheets

This section provides additional data for a typical LM6000 gas turbine generator package (60 Hz), including: auxiliary power loads, optional auxiliary power loads, and shipping dimensions and weights.

2.1

LM6000 Auxiliary Power Loads (60 Hz)

Normal Operating Load Required for Black Start

Standard Electric Loads Qty

Aux

Rating Total Qty KW Total Qty kW

Turbine Vent Fans 2 125 hp 1 93 1 93

Generator Vent Fans 2 100 hp 1 75 1 75

Hydraulic Start Pump 1 200 hp 0 0 1 149

Generator Aux. L.O. Pump 1 7.5 hp 1 5.6 1 5.6

Generator Jacking Oil Pump 1 15 hp 0 0 1 11.2

Gas Turbine Lube Oil Heater 1 3 kW 0 0 1 3

Generator L.O. Heater 2 4 kW 0 0 2 8

Hyd. Starter L.O. Heater 1 3 kW 0 0 1 3

Generator Space Heater 1 4 kW 0 0 1 4

Turbine Air/Oil Separator 1 1 hp 1 0.75 1 0.75

Lighting & Low Voltage

Distribution System 1 45 kVA 1 45 1 45

Water Wash Supply Pump 1 2 hp 1 1.5 0 0

Hydraulic Starter Oil Heat

Exchanger Fan 1 3 hp 1 2.2 1 2.2

Turbine Water Wash Tank

Heaters 2 9 kW 2 0 2 0

(10)

LM6000 - 60 Hz Classic 6/2008 Page 9 of 156

2.2

Optional LM6000 Auxiliary Power Loads

Normal Operating Load Required for Black Start Optional Electrical Loads Qty hp Total Qty kW Total Qty kW

Auxiliary Skid Vent Fans 2 1 2 1.5 2 1.5

Liquid Fuel Pump 2 100 1 74.6 1 74.6

Water Inj. Pump - Gas Fuel 2 75 1 55.9 0 0

Water Inj. Pump - Liquid

Fuel 2 125 1 93.2 1 93.2

Evap Cooler Recirc. Pumps 2 5 2 7.46 2 7.46

Auxiliary Skid Heater 1 3 kW 3 1 3

Fuel Pump Skid Vent Fans 2 1 2 1.5 2 1.5

Gen. Vent Fans - TEWAC 2 25 1 18.6 1 18.6

Control House A/C 2 4.1 kW 1 4.1 2 8.2

Sprint Skid Pump 1 10 1 7.5 1 7.5

Liquid Fuel Pump Skid

Heater 1 3 kW 1 3 1 3

Turbine Enclosure Heaters 2 5 kW 0 5 2 5

Turbine Enclosure Heaters 2 10 kW 0 5 2 5

Generator Enclosure Heaters 2 5 kW 0 10 2 10

(11)

LM6000 - 60 Hz Classic 6/2008 Page 10 of 156

2.3

Preliminary Shipping Dimensions and Weights

for One (1) LM6000 Gas Turbine Generator Unit

GROSS WEIGHT LENGTH WIDTH HEIGHT VOLUME Description lbs kg in cm in cm in cm ft3 m3 Turbine Base 120,000 54,432.0 371.00 942.3 171.00 434.3 178.00 452.12 6535.0 185.03 Shear Lugs 1,020 462.7 45.00 114.3 25.00 63.5 17.00 43.18 11.1 0.31 H-Frame 2,085 945.8 174.00 442.0 35.00 88.9 36.00 91.44 126.9 3.59 Ruffneck heaters 1,050 476.3 67.00 170.2 36.00 91.4 67.00 170.18 93.5 2.65 CDP Purge 1,185 537.5 80.00 203.2 48.00 121.9 24.00 60.96 53.3 1.51 VBV Expansion Joint 695 315.3 90.00 228.6 32.00 81.3 24.00 60.96 40.0 1.13 Exhaust Flashing 725 328.9 62.00 157.5 62.00 157.5 17.00 43.18 37.8 1.07 Mechanical Shiploose 2,785 1,263.3 170.00 431.8 48.00 121.9 43.00 109.22 203.1 5.75 Alignment Tool 530 240.4 104.00 264.2 30.00 76.2 32.00 81.28 57.8 1.64 Turbine Lift Fixture 1,410 639.6 128.00 325.1 76.00 193.0 17.00 43.18 95.7 2.71 LM6000 Generator Base 68,000 30,844.8 337.00 856.0 171.00 434.3 178.00 452.12 5936.1 168.08 Brush Generator 176,000 79,833.6 301.00 764.5 159.00 403.9 130.00 330.20 3600.5 101.94 Generator Lube Oil Piping 1,420 644.1 212.00 538.5 32.00 81.3 21.00 53.34 82.4 2.33 Run down tanks 1,455 660.0 106.00 269.2 46.00 116.8 30.00 76.20 84.7 2.40 Generator transition throat 1,800 816.5 125.00 317.5 125.00 317.5 39.00 99.06 352.6 9.98 Generator exhaust hood 9,070 4,114.2 174.00 442.0 150.00 381.0 87.00 220.98 1314.1 37.21 Electrical Shiploose 1,105 501.2 96.00 243.8 48.00 121.9 38.00 96.52 101.3 2.87 Lucas Coupling 1,445 655.5 120.00 304.8 32.00 81.3 40.00 101.60 88.9 2.52 Roof Skid Transition 44,000 19,958.4 470.00 1193.8 172.00 436.9 149.00 378.46 6970.6 197.36 Raincap 1,320 598.8 82.00 208.3 82.00 208.3 54.00 137.16 210.1 5.95 Raincap 1,320 598.8 82.00 208.3 82.00 208.3 54.00 137.16 210.1 5.95 Ventilation Silencer 3,100 1,406.2 80.00 203.2 80.00 203.2 131.00 332.74 485.2 13.74

(12)

LM6000 - 60 Hz Classic 6/2008 Page 11 of 156

2.3

Preliminary Shipping Dimensions and Weights

for One (1) LM6000 Gas Turbine Generator Unit (Cont.)

GROSS WEIGHT LENGTH WIDTH HEIGHT VOLUME Description lbs kg in cm in cm in cm ft3 m3 Ventilation Silencer 3,100 1,406.2 80.00 203.2 80.00 203.2 131.00 332.74 485.2 13.74 VBV Duct 15,600 7,076.2 158.00 401.3 150.00 381.0 102.00 259.08 1399.0 39.61 VBV Silencer 19,800 8,981.3 172.00 436.9 146.00 370.8 82.00 208.28 1191.7 33.74 VBV Hood 6,460 2,930.3 140.00 355.6 102.00 259.1 108.00 274.32 892.5 25.27 Roof Skid Transition 1,710 775.7 148.00 375.9 73.00 185.4 34.00 86.36 212.6 6.02 Generator

Fan Exp Jpint 450 204.1 51.00 129.5 51.00 129.5 24.00 60.96 36.1 1.02

Demister 720 326.6 36.00 91.4 36.00 91.4 74.00 187.96 55.5 1.57 Plenum 24,400 11,067.8 394.00 1000.8 146.00 370.8 149.00 378.46 4960.1 140.44 LH Coil Module 43,500 19,731.6 400.00 1016.0 153.00 388.6 149.00 378.46 5277.1 149.42 RH Coil Module 43,500 19,731.6 400.00 1016.0 153.00 388.6 149.00 378.46 5277.1 149.42 Walkways & Handrails 3,640 1,651.1 152.00 386.1 60.00 152.4 44.00 111.76 232.2 6.58 Coil Module Parts 1,225 555.7 44.00 111.8 44.00 111.8 38.00 96.52 42.6 1.21 Support Structure & Ladder 5,620 2,549.2 312.00 792.5 81.00 205.7 62.00 157.48 906.8 25.67 Pre-Filter Doors (16) 2,010 911.7 129.00 327.7 56.00 142.2 52.00 132.08 217.4 6.16 Pre-Filter Doors (16) 1,940 880.0 129.00 327.7 56.00 142.2 52.00 132.08 217.4 6.16 Nuts & Bolts

Shiploose 1,750 793.8 48.00 121.9 48.00 121.9 36.00 91.44 48.0 1.36 Paint (1-5 gal) 130 59.0 24.00 61.0 18.00 45.7 23.00 58.42 5.8 0.16 Flex Hoses 260 117.9 64.00 162.6 19.00 48.3 14.00 35.56 9.9 0.28 Auxiliary Module 85,000 38,556.0 564.00 1432.6 168.00 426.7 168.00 426.72 9212.0 260.83 Lineside Cubicle 2,800 1,270.1 68.00 172.7 68.00 172.7 124.00 314.96 331.8 9.40 Neutral Cubicle 4,400 1,995.8 96.00 243.8 68.00 172.7 120.00 304.80 453.3 12.84 Acid 650 294.8 47.00 119.4 19.00 48.3 33.00 83.82 17.1 0.48

CO2 Cover &

Rack 3,180 1,442.4 110.00 279.4 45.00 114.3 115.00 292.10 329.4 9.33 CO2 Bottles 3,885 1,762.2 47.00 119.4 37.00 94.0 72.00 182.88 72.5 2.05 BUS Relay

(13)

LM6000 - 60 Hz Classic 6/2008 Page 12 of 156

2.3

Preliminary Shipping Dimensions and Weights

for One (1) LM6000 Gas Turbine Generator Unit (Cont.)

GROSS WEIGHT LENGTH WIDTH HEIGHT VOLUME Description lbs kg in cm in cm in cm ft3 m3 Lift pins 7,260 3,293.1 114.00 289.6 78.00 198.1 30.00 76.20 154.4 4.37 Air Filter spreader bar 4,650 2,109.2 440.00 1117.6 33.00 83.8 12.00 30.48 100.8 2.85 Main Unit Spreader bar 1,800 816.5 211.00 535.9 26.00 66.0 12.00 30.48 38.1 1.08 Generator spreader bar 1,400 635.0 133.00 337.8 26.00 66.0 12.00 30.48 24.0 0.68 Slings & Shackles 10,000 4,536.0 139.00 353.1 96.00 243.8 42.00 106.68 324.3 9.18 Additional Cable (3 rolls) 3,000 1,360.8 72.00 182.9 36.00 91.4 36.00 91.44 54.0 1.53 Vent(Anti icing system) 15,600 7,076.2 158.00 401.3 150.00 381.0 102.00 259.08 1399.0 39.61 Vent(Anti icing system) 15,600 7,076.2 158.00 401.3 150.00 381.0 102.00 259.08 1399.0 39.61 Ladders 1,250 567.0 339.00 861.1 59.00 149.9 48.00 121.92 555.6 15.73 Platforms 8,325 3,776.2 202.00 513.1 102.00 259.1 59.00 149.86 703.5 19.92 Nuts & Bolts

Shiploose 670 303.9 61.00 154.9 43.00 109.2 42.00 106.68 63.8 1.81 High Pressure

Demin Water

Filter 460 208.7 27.00 68.6 27.00 68.6 48.00 121.92 20.3 0.57

Fire 700 317.5 36.00 91.4 36.00 91.4 72.00 182.88 54.0 1.53

Misc Parts for

water system 50 22.7 48.00 121.9 24.00 61.0 55.00 139.70 36.7 1.04 Relay Panels 900.00 408.2 72.00 182.9 48.00 121.9 72.0 182.88 144.0 4.08 Switch Board 750.00 340.2 72.00 182.9 36.00 91.4 72.0 182.88 108.0 3.06 Switch Gear 5,000.0 2,268.0 77.00 195.6 106.00 269.2 116.0 294.64 547.9 15.51 Switch Gear 18360.0 8,328.1 181.00 459.7 106.00 269.2 116.0 294.64 1287.9 36.47 Switchgear Accessories 1,250.0 567.0 88.00 223.5 48.00 121.9 48.0 121.92 117.3 3.32 Switchgear Accessories 1,350.0 612.4 110.00 279.4 39.00 99.1 29.0 73.66 72.0 2.04 Switchgear Accessories 850.00 385.6 94.00 238.8 46.00 116.8 20.0 50.80 50.0 1.42 Switchgear Accessories 290.00 131.5 60.00 152.4 31.00 78.7 17.0 43.18 18.3 0.52

(14)

LM6000 - 60 Hz Classic 6/2008 Page 13 of 156

2.3

Preliminary Shipping Dimensions and Weights

for One (1) LM6000 Gas Turbine Generator Unit (Cont.)

GROSS WEIGHT LENGTH WIDTH HEIGHT VOLUME Description lbs kg in cm in cm in cm ft3 m3 Switchgear Accessories 475.00 215.5 96.00 243.8 50.00 127.0 50.0 127.00 138.9 3.93 Switchgear Accessories 1,600.0 725.8 125.00 317.5 95.00 241.3 60.0 152.40 412.3 11.67 Switchgear Accessories 90.00 40.8 25.00 63.5 15.00 38.1 15.0 38.10 3.3 0.09

Note: Some equipment listed in this table may not be applicable to specific projects. .

(15)

LM6000 - 60 Hz Classic 6/2008 Page 14 of 156

3.

Codes and Standards

3.1

Codes and Standards for Gas Turbine Generators

GE Energy considers the applicable sections of the following US and ISO Codes and Standards to be the most relevant standards for gas turbine equipment. Our designs and procedures are generally compliant with applicable sections of the following:

ANSI A58.1 Minimum Design Loads for Buildings and Other Structures ANSI B1.1 Unified Inch Screw Threads

ANSI B1.20.1 Pipe Threads

ANSI B16.5 Steel Pipe Flanges and Flanged Fittings

ANSI B16.9 Factory-Made Wrought Steel Butt Welding Fittings

ANSI B16.21 Non-Metallic Flat Gaskets for Pipe Flanges. (Spiral-wound gaskets per API 601 may be used, particularly in turbine compartment piping)

ANSI B31.1 Pressure Piping and Gas Turbine Piping Systems Comply ANSI B133.2 Basic Gas Turbine

ANSI B133.3 Gas Turbine Auxiliary Equipment.

ANSI B133.4 Gas Turbine Controls and Protection Systems ANSI B133.5 Gas Turbine Electrical Equipment

ANSI B133.8 Gas Turbine Installation Sound Emissions ANSI/NAFPA 12 Carbon Dioxide Extinguishing Systems ANSI/NFPA 70 National Electrical Code

(16)

LM6000 - 60 Hz Classic 6/2008 Page 15 of 156

3.1

Codes and Standards for Gas Turbine Generators (Cont)

ANSI IEEE C37.2 Electrical Power System Device Function Numbers ANSI C37.90a/

IEEE-472

Guide for Surge Withstand Capability (SWC) Tests ANSI C50.10 General Requirements for Synchronous Machines

ANSI C50.14 Requirements for Combustion Gas Turbine Driven Cylindrical Rotor Synchronous Generators

ANSI C57.94 American Standard, Guide for Installation and Maintenance of Dry Type Transformers

ANSI C83.16 Relays

ANSI/IEEE 100 IEEE Standard Dictionary of Electrical and Electronic Terms ANSI/NEMA MG1 Motors and Generators

ANSI/NEMA MG2 Safety Standard for Construction and Guide for Selection, Installation and Use of Electric Motor and Generators ANSI S1.2 Method for the Physical Measurement of Sound ANSI S1.4 Specification for Sound Level Meters

ANSI S1.13 Method for the Measurement of Sound Pressure Levels ANSI S6.1/

SAE/J184A

Qualifying a Sound Data Acquisition System

AGMA 421 Standard Practice for High Speed Helical and Herringbone Gear Units

IBC 2000 International Building Code

IEEE Std 421 IEEE Standard Criteria and Definitions for Excitation Systems for Synchronous Machines

EIA RS-232 Interface between Data Terminal Equipment and Data

(17)

LM6000 - 60 Hz Classic 6/2008 Page 16 of 156

Note: ATEX and CE Codes and Standards are applied when required.

EN 61010-1 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements

CAN/CSA 22.2 No. 1010.1-92 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements

ANSI/ISA S82.02.01 1999 Safety Standard for Electrical and Electronic Test, Measuring, Controlling, and Related Equipment – General Requirements

UL 796 Printed Circuit Boards ANSI IPC Guidelines

ANSI IPC/EIA Guidelines

EN 55081-2 General Emission Standard

EN 50082-2 Generic Immunity Industrial Environment EN 55011 Radiated and Conducted Emissions

IEC 61000-4-2 Electrostatic Discharge Susceptibility IEC 61000-4-3 Radiated RF Immunity

IEC 61000-4-4 Electrical Fast Transit Susceptibility IEC 61000-4-5 Surge Immunity

IEC 61000-4-6 Conducted RF Immunity

IEC61000-4-11Voltage Variation, Dips & Interruptions ANSI/IEEE C37.90.1 Surge

EN 61010-1 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements

(18)

LM6000 - 60 Hz Classic 6/2008 Page 17 of 156

The GE Gas Turbine Drafting Standards are based on the following Standards as appropriate to the gas turbine. Please note that in several instances, symbols, etc. have been devised for GE’s special needs (such as flow dividers and manifolds:

ANSI B46.1 Surface Texture

ANSI Y14.15 Electrical and Electronics Diagrams (On base

gas turbine and accessory base equipment)

ANSI Y14.17 Fluid Power Diagrams

ANSI Y14.36 Surface Texture Symbols

ANSI Y32.2/CSA Graphic Symbols for Electrical and

Electronics

299/IEEE 315 Diagrams

ANSI Y32.10 Graphical Symbols for Fluid Power Diagram

ANSI Y32.11 Graphical Symbols for Process Flow Diagram

ANSI Z32.2.3 Graphical Symbols for Pipe Fittings, Valves

& Piping

(19)

LM6000 - 60 Hz Classic 6/2008 Page 18 of 156

4.

Typical Performance Specifications

4.1

LM6000 ISO Performance Data

Simple Cycle Gas Turbine 60 Hz Applications

(Natural Gas)

Engine Fuel Configuration Power Heat Rate LHV kW BTU/kW-hr KJ/kW-hr

Single Annular Combustor Natural Gas 43,284 8,133 8,581

Single Annular Combustor Natural Gas and Water Injection

43,882 8,511 8,980

Single Annular Combustor Natural Gas and Steam Injection

43,854 7,879 8,312

Dry Low Emissions Natural Gas 42,300 8,315 8,773

Conditions:

Power at Generator Terminals

NOx =51 mg / Nm³ (SAC-Water, SAC-Steam, and DLE)

15°C, 60% RH 11.5 kV,PF: 0.85

Losses: 0/0mm H2O Inlet/Exhaust

Fuel: Spec Gas (44,194 kJ/kg, LHV) at 25ºC VIGV Included

Simple Cycle Gas Turbine 60 Hz Applications

(Liquid Fuel)

Engine Fuel Configuration Power Heat Rate LHV kW BTU/kW-hr KJ/kW-hr

Single Annular Combustor Liquid 41,784 8,253 8,708

Single Annular Combustor Liquid and Water Injection

43,053 8,631 9,106

Dry Low Emissions Liquid 40,179 8,421 8,885

Conditions:

Power at Generator Terminals NOx = 86 mg / Nm³ (SAC-Water)

15ºC, 60% RH 11.5 kV, PF: 0.85

Losses: 0/0mm H²O Inlet/Exhaust

Fuel: Spec (42,798 kJ/kg) Liquid with ≤ 0.1% Sulfur VIGV Included

(20)

LM6000 - 60 Hz Classic 6/2008 Page 19 of 156

Simple Cycle Gas Turbine 60 Hz Applications

(Natural Gas with SPRINT®)

Engine Fuel Configuration Power Heat Rate LHV KW BTU/kW-hr KJ/kW-hr

Single Annular Combustor Natural Gas 46,673 8,142 8,591

Single Annular Combustor Natural Gas and Water Injection

50,337 8, 8,980

Single Annular Combustor Natural Gas and Steam Injection

50,500 7,895 8,329

Dry Low Emissions Natural Gas 46,903 8,272 8.727

Conditions:

Power at Generator Terminals

NOx =25PPM (SAC-Water, SAC-Steam, and DLE)

15ºC, 60% RH 13.8 kV, 0.85 pf

Losses: 0/0mm H²O Inlet/Exhaust

Fuel: Spec Gas (44,194 kj/kg), LHV) at 25 ºC VIGV included

Simple Cycle Gas Turbine 60 Hz Applications

(Liquid with SPRINT®)

Engine Fuel Configuration Power Heat Rate LHV KW BTU/kW-hr KJ/kW-hr

Single Annular Combustor Liquid 41,769 8,291 8,748

Single Annular Combustor Liquid and Water 43,811 8,311 8,769

Conditions:

Power at Generator Terminals NOx = 86 mg / Nm³ (SAC-Water)

15ºC, 60% RH 11.5 kV, 0.85 pf

Losses: 0/0mm H²O Inlet/Exhaust

Fuel: Spec (42,798 kj/kg) Liquid with ≤ 0.1% Sulfur VIGV Included

4.2

Performance Data and Curves

Performance curves are included in Performance Curves Section 5. From these curves it is possible to determine performance at ambient temperatures, altitudes, and conditions differing from those listed in the performance specifications.

4.3

Guarantee Basis

Performance guarantees for power and efficiency are based on the condition and cleanliness of the gas turbine. If more than 200 fired hours have elapsed before conducting a

(21)

LM6000 - 60 Hz Classic 6/2008 Page 20 of 156

performance test, a GE Energy representative has the right to inspect the unit to ensure condition and cleanliness standards have been met. The guarantees are also based on a site test conducted in accordance with GE Energy’s standard practices and protocols as described in the Test Specifications. GE Energy reserves the right to have a representative present during the performance test.

(22)

LM6000 - 60 Hz Classic 6/2008 Page 21 of 156

5.

Performance Curves

5.1

Turbine Performance Curves

5.1.1 Turbine Curves –at 60 Hz/ 13.8 kV*

LM6000 performance at various ambient temperatures Figure 5-1

LM6000 with SPRINT performance at various ambient temperatures Figure 5-2

LM6000 heat rate at various ambient temperatures Figure 5-3

LM6000 with SPRINT® heat rate at various ambient temperatures Figure 5-4

LM6000 part power heat rate Figure 5-5

LM6000 with SPRINT® performance at various altitudes Figure 5-6

• LM6000 part power heat rate (LHV) Figure 5-7

• LM6000 with SPRINT part power heat rate (LHV) Figure 5-8

• LM6000 part power efficiency Figure 5-9

• LM6000 with SPRINT™ part power efficiency Figure 5-10

• LM6000 10-minute start cycle Figure 5-11

* Note - The performance curves may change slightly upon finalization of the product design and/or generator manufacturer selection.

(23)

LM6000 - 60 Hz Classic 6/2008 Page 22 of 156

Figure 5- 1: LM6000 performance at various ambient temperatures

Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 kJ/kg), 50Hz, 11.5kV, 0.85pf. Not for guarantee.

Nox Water and DLE are to 51 mg / Nm³.

Figure 5- 2: LM6000 with SPRINT performance at various ambient temperatures Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 kJ/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee.

Nox Water and DLE are to 51 mg / Nm³. 25000 30000 35000 40000 45000 50000 55000 -20 -10 0 10 20 30 40 Temperature, O C P o w e r a t G e n e ra to r T e rm in a l, k W SAC DRY Water DLE 25000 30000 35000 40000 45000 50000 55000 -20 -10 0 10 20 30 40 Temperature, O C P o w e r a t G e n e ra to r T e rm in a l, k W SAC DRY Water DLE

(24)

LM6000 - 60 Hz Classic 6/2008 Page 23 of 156 7400 7900 8400 8900 9400 9900 10400 -20 -10 0 10 20 30 40 Temperature, O C H e a t R a te , k J /k W -h r, L H V SAC DRY Water DLE 7400 7900 8400 8900 9400 9900 -20 -10 0 10 20 30 40 Temperature, O C H e a t R a te , k J /k W -h r, L H V SAC DRY W ater DLE

Figure 5- 4: LM6000 heat rate at various ambient temperatures Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee.

Nox Water and DLE are to 51 mg / Nm³.

Figure 5- 3: LM6000 with SPRINT heat rate at various ambient temperatures Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194

J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee. Nox Water and DLE are to 51 mg / Nm³.

(25)

LM6000 - 60 Hz Classic 6/2008 Page 24 of 156 34000 36000 38000 40000 42000 44000 46000 48000 50000 52000 0 200 400 600 800 1000 1200 1400 1600

Altitude, M eters above sea level

P o w e r a t G e n e ra to r T e rm in a l, k W S A C DRY W ater DLE 100% 105% 110% 115% 120% 125% 130% 135% 140% 50 60 70 80 90 100 % of Baseload H e a t R a te , % o f B a s e lo a d SAC DRY SAC W ater DLE

Figure 5- 5: LM6000 part power heat reate

Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee. Nox Water and DLE are to 51 mg / Nm³.

Figure 5- 6: LM6000 60Hz with SPRINT performance at various altitudes Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee.

(26)

LM6000 - 60 Hz Classic 6/2008 Page 25 of 156 100% 105% 110% 115% 120% 125% 130% 135% 140% 50 60 70 80 90 100 % of Baseload H e a t R a te , % o f B a s e lo a d SAC DRY SAC Water DLE 1 0 0 % 1 0 5 % 1 1 0 % 1 1 5 % 1 2 0 % 1 2 5 % 1 3 0 % 1 3 5 % 1 4 0 % 5 0 6 0 7 0 8 0 9 0 1 0 0 % o f B a s e lo a d H e a t R a te , % o f B a s e lo a d S A C D R Y S A C W a te r D L E

Figure 5- 8: LM6000 60Hz part power heat rate (LHV)

Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee.

Nox Water and DLE are to 51 mg / Nm³.

Figure 5- 7: LM6000 60Hz with SPRINT part power heat rate (LHV) Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee.

(27)

LM6000 - 60 Hz Classic 6/2008 Page 26 of 156 20% 25% 30% 35% 40% 45% 50% 50 55 60 65 70 75 80 85 90 95 100 % of Baseload E ff ic ie n c y , % SAC DRY SAC W ATER DLE 20% 25% 30% 35% 40% 45% 50% 50 55 60 65 70 75 80 85 90 95 100 % of Baseload E ff ic ie n c y , % SAC DRY SAC WATER DLE

Figure 5- 10: LM6000 60Hz part power efficiency

Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee.

Nox Water and DLE are to 51 mg / Nm³.

Figure 5- 9: LM6000 60Hz with SPRINT part power heat rate (LHV) Basis of Performance: RH of 60% with 0 mm H20 inlet exhaust losses at 0m ASL, Fuel: Natural Gas (44,194 J/kg), 60Hz, 11.5kV, 0.85pf. Not for guarantee.

(28)

LM6000 - 60 Hz Classic 6/2008 Page 27 of 156

10-Minute Simple Cycle Start Cycle for LM6000 with SPRINT®

(29)

LM6000 - 60 Hz Classic 6/2008 Page 28 of 156

6.

Major Equipment

6.1

LM6000 PC Gas Turbine

Base-mounted, simple cycle, two (2) spool gas turbine in a fully enclosed turbine compartment:

• Two-shaft configuration with direct drive output at (50 Hz) 3600 rpm… match apps for PC & PD

• Radial inlet

• Five stage low pressure compressor (LPC)

• Fourteen stage high pressure compressor (HPC) with horizontal split casing

• Combustor

• Thirty fuel nozzles and dual igniters (DLE is option)

• Two stage high pressure turbine (HPT)

• Five stage low pressure turbine (LPT)

• Borescope ports for diagnostic inspection

• Accessory drive gearbox for starter, lube & scavenge pumps

• Flexible dry type main load coupling and guard

6.1.1 Fuel Systems

• Natural gas fuel system

• Water Injection for NOx

• Liquid/Dual Fuel

6.1.2 Starting System

The hydraulic start system mounted on the auxiliary skid will include:

• 40 gallon / 151 l Reservoir tank (should the dimensions be included in the Greybook or contract)

• Hydraulic pump assembly

• LP return filter

• Case drain filter

• Heat exchanger

(30)

LM6000 - 60 Hz Classic 6/2008 Page 29 of 156

• High efficiency inlet filter system

• Silencing system

• Support structure, ladders, and platforms

6.1.4 Exhaust System

• Axial exhaust collector system

• Connection flange at the wall of the turbine enclosure

6.1.5 Lube Oil Systems

The synthetic lube oil system for the turbine will include:

• 304 stainless steel tank (150 gallons / 568 l) and piping mounted on turbine skid

• Valves with stainless steel trim

• Duplex filters (supply) mounted on turbine skid

• Duplex filters (scavenge) mounted on auxiliary module

• Duplex shell and tube coolers mounted on the auxiliary module

• Shaft-driven positive displacement supply

• Scavenge pump

6.1.6 Turbine Engine Compartment

• For weatherproofing, acoustics, ventilation and fire system

6.1.7 Fire Protection System – CO

2

• Gas detectors, optical flame detectors and thermal detectors

• Primary and secondary high pressure CO2 cylinders

• Automatic vent fan shutdown and damper closure

6.1.8 Compressor Cleaning and Water Washing

• On-line water wash system

• Off-line water wash system

• 100 gallon / 379 l - 304 stainless steel reservoir mounted on the auxiliary skid

• Motor-driven pressurizing pump

6.1.9 Base Scope Auxiliary Equipment Module

Base auxiliary equipment module is provided with the unit to integrate several functions. Auxiliary components and fuel system components can be equipped with optional enclosures. The following is included:

(31)

LM6000 - 60 Hz Classic 6/2008 Page 30 of 156

Auxiliary equipment

• Synthetic lube oil reservoir, duplex scavenge oil filter and duplex shell/tube oil-to-water heat exchangers

• Electro-hydraulic start system

• CO2 cylinders

• On-line/off-line water wash system (including instrument air filter)

Note: In the base configuration the TCP and 24 VDC battery systems are shipped separately to be installed by others.

6.2

Generator & Excitation

6.2.1

Totally Enclosed, Open – Ventilated, Brushless Excitation

• Stator winding with Class F insulation and Class B temperature rises

• Cylindrical forged steel rotor with Class F insulation and Class B temperature rises

• Open ventilated air cooling with unit mounted filters

• Strip heaters (to prevent condensation during periods of shutdown)

• Resistance temperature detectors (RTD)

• embedded in the stator windings

• in the air stream

• Displacement probes with internal proximeters for vibration monitoring

• Bearing metal and drain RTDs for temperature monitoring

• Rotating rectifier excitation system including: - Three-phase rotating armature

- Three-phase rotating rectifier - Exciter field

- GE EX2100 automatic digital voltage regulator located in the turbine control panel (TCP). - Provisions for a key phasor (add to options)

- Permanent magnet generator (PMG) for the excitation system

6.2.3 Generator Auxiliaries

• As viewed when looking at generator non-drive end:

- Instrument and control termination box (MGTB), right side

- Lineside termination cubicle (containing lightning arrestors and surge capacitors) left side (very this is standard)

(32)

LM6000 - 60 Hz Classic 6/2008 Page 31 of 156

6.3

Unit Controls

6.3.1 Turbine Control Panel

• Free standing, for indoor location: 9 ft – 6 inch W x 2 ft – 6 inch D x 7 ft -6 inch H / 289.6 cm W x 76.2 cm D x 228.6 cm H

Woodward Micronet Plus

Sequencing, control, protection, monitoring

Desktop display and keyboard for operator I/O

Metering readouts shown digitally on the display

Plant ethernet port to user’s DCS

• Protective relaying and metering

• Rack-mounted electronic voltage regulator

• Vibration monitoring system

• Fire monitoring system

• Generator controls

6.3.2 24V Control Battery and Redundant Charger

• Battery: 19 cells, 24 VDC, Ni-CAD type

• Charger: 230 V (service voltage), 150 amps

• 323 AH

6.3.3 24V Fire and Gas Battery and Charger

• Battery: 19 cells, 24 VDC, Ni-CAD type

• Charger: 120 V (service voltage), 25 amps

• 138 AH

6.3.4 125 V Battery and Charger (SAC)

• Battery: 45 cell blocks, 125 VDC, Ni-CAD type

• Charger: 230 V (service voltage), 3-ph, 50 amps

• 84 AH

6.3.5 125 V Battery and Charger (DLE)

• Battery: 45 cell blocks, 125 VDC, Ni-CAD type

• Charger: 230 V (service voltage), 3-ph, 50 amps

(33)

LM6000 - 60 Hz Classic 6/2008 Page 32 of 156

6.4

Drawings, Documentation and Training

In addition to the supply of the equipment, for each unit GE Energy will:

• Coordinate engineering, manufacturing, and shipping schedules to meet contractual requirements

For the site, Services include:

• Provide Buyer’s drawings and six (6) copies of the Operation and Maintenance Manuals in CD form

• Provide Installation and Commissioning Manual

• Provide field technical direction for performance tests per GE standard test procedures.

• Conduct a Gas Turbine Package Familiarization and Operator’s Training Course for customer personnel at the GE Energy Jacintoport facility. See Section 18 for further details.

6.5

Testing and Transportation

In addition to the supply of the equipment, for each unit GE Energy will:

• Conduct standard factory tests of the equipment and conform to carefully established quality assurance practices

• Static test the LM6000 gas turbine package before shipment from Houston utilizing contract unit controls

• Prepare the equipment for domestic shipment

• Deliver the equipment, ex-works factory Houston, Texas

Note: A recommended installation schedule will be prepared by GE, which will define the manpower loading, and classification of the supervisors provided, as well as the schedule of events. (BD to verify)

(34)

LM6000 - 60 Hz Classic 6/2008 Page 33 of 156

7. Mechanical Descriptions - Major Equipment

7.1

Turbine Engine

LM6000 Turbine Engine

The LM6000 is a 2-shaft gas turbine engine derived from the core of the CF6-80C2, GE's high thrust, high efficiency aircraft engine. More than eighteen hundred CF6-80C2s are in service and 2,000 or more are on order or option. The CF6-80C2 has logged more than 30,000,000 flight hours in the Boeing 747 and other wide-body aircraft, with a 99.88% dispatch reliability and commercial aviation's lowest shop visit rate. GE used this 30 million hour flight experience to create the LM6000. Both engines have a common design and share most major parts. The Low Pressure Turbine, High Pressure Compressor, High Pressure Turbine, and Combustor are virtually identical. This use of flight-proven parts, produced in high volume, contributes to the low initial cost and high operating efficiency of the LM6000.

(35)

LM6000 - 60 Hz Classic 6/2008 Page 34 of 156

7.1

Turbine Engine (Cont)

Major Engine Components:

• 5-stage low-pressure compressor (LPC)

• 14-stage variable geometry high pressure compressor (HPC)

• Annular combustor

• 2-stage air-cooled high pressure turbine (HPT)

• 5-stage low pressure turbine (LPT)

• Accessory Gear Box

The LM6000 has two concentric rotor shafts: The LPC and LPT are assembled on one shaft, forming the Low Pressure Rotor. The HPC and HPT are assembled on the other shaft, forming the High Pressure Rotor.

The LM6000 uses the Low Pressure Turbine (LPT) to power the output shaft. By eliminating the separate power turbine found in many other gas turbines, the LM6000 design simplifies the engine, improves fuel efficiency and permits direct-coupling to 3600 rpm generators for 60 Hz power generation. The LM6000 gas turbine drives the generator via a flexible dry type coupling connected to the front, or “cold,” end of the LPC shaft.

7.1.1 Turbine Cycle

• Filtered air enters the bellmouth and flows through guide vanes to the LPC

• LPC compresses air by 2.4:1 ratio

• Air flows from LPC through the front frame & bypass air collector to HPC

• Air enters HPC through Inlet Guide Vanes

• The HPC compresses air by 12:1 ratio

• 30 Fuel (SAC) nozzles or 75 fuel (DLE) nozzles mix air and fuel

• Air-Fuel mixture is ignited in Annular Combustor

• Hot combustion gases expand through HPT driving the HPC

• Hot combustion gasses expand further through LPT driving the LPC and load

• Flanged end of the LPC shaft drives the electric generator load.

(36)

LM6000 - 60 Hz Classic 6/2008 Page 35 of 156

7.1.2 Inlet and IGV Section

The turbine inlet straightens the air stream and directs it into the Low Pressure Compressor (LPC).

7.1.3 Low Pressure Compressor

The Low Pressure Compressor (LPC) is a 5-stage axial flow compressor with a 2.4:1 pressure ratio. It is derived from the CF6-50 flight engine. A horizontally split casing provides access to blades and vanes. Borescope ports permit flow path inspection.

7.1.4 Bypass Air Collector

The LM6000 matches the airflow between the Low Pressure (LP) and High Pressure Compressor (HPC) with 12 hydraulically actuated variable bypass valves mounted in the turbine front frame. During start-up and part-load operation these valves open partially and vent excess air to the bypass air collector. The bypass air collector also supports the accessory gearbox.

7.1.5 High Pressure Compressor

The LM6000 High Pressure Compressor (HPC) is a 14-stage unit. Variable stators in stages 1-5 ensure high efficiency throughout the starting and operating range. The stator geometry of stages 6 through 14 is fixed horizontally. This allows ready access to the stator vanes and rotor blades for inspection or replacement.

7.1.6 Combustion Section

7.1.6.1 Singular Annular Combustor (SAC)

Thirty nozzles feed fuel into the LM6000 annular combustor, providing a uniform heat profile to the High Pressure Turbine (HPT). This produces maximum output with low thermal stress. The swirler-cup dome design produces a lean thoroughly mixed, mixture in the primary zone of the combustor. This provides cleaner combustion and reduces NOX. Available nozzle designs allow natural gas, distillate or dual-fuel operation. The nozzles also permit NOX reduction with water injection (natural gas and distillate fuels) and steam injection (natural gas fuel only). The annular combustor design provides low pressure loss, low exit temperature and extended operating life. A Hastelloy X inner liner resists corrosion and extends combustor life.

(37)

LM6000 - 60 Hz Classic 6/2008 Page 36 of 156

The DLE system controls NOx emissions without the use of water or steam. GE Energy installs special combustors, manifolds, nozzles and metering to control flame temperature and reduce emissions of NOx, CO and unburned hydrocarbons. This DLE system reduces emissions over the entire power range, not just at high power settings.

The fuel system hardware supplied with the DLE gas turbine includes a base mounted gas manifold, hoses, staging valves, and a set of thirty fuel premixers. The LM6000 DLE gas turbine utilizes a lean premix combustion system designed for operation on natural gas fuel as well as dual fuel. Gas fuel is introduced into the combustor via 75 air/gas premixers packaged in 30 externally removable and replaceable modules. The premixers produce a very uniformly mixed, lean fuel/air mixture. The triple annular configuration enables the combustor to operate in premix mode across the entire power range, minimizing nitrogen oxide (NOx) emissions even at low power.

The head end or dome of the combustor supports 75 segmented heat shields that form the three annular burning zones in the combustor, known as the outer or A-dome, the pilot or B-dome, and the inner or C-dome. In addition to forming the three annular domes, the heat shields isolate the structural dome plate from the hot combustion gases. The heat shields are an investment-cast superalloy and are impingement and convection cooled. The combustion liners are front mounted with thermal barrier coating (TBC) and no film cooling.

Fuel to the gas turbine will be controlled based on control mode, fuel schedules, and the load condition. For normal start sequence (13 minutes), gradual load changes are preferred with at least 5-minute ramp from idle to maximum power. If a fast start (10 minutes) is required, the load may be ramped from idle to full load in 4 minutes as part of the start sequence provided in Operation. Normal load reduction transients should be no faster than 2-3 minutes from maximum power to synchronous idle.

7.1.7 High Pressure Turbine

The High Pressure Turbine (HPT) is a 2-stage, air-cooled turbine rotated by the hot gasses exiting the combustor. The HPT powers the High Pressure Compressor (HPC) to supply high-pressure air to the combustor. Turbine disks, blades and stator are air-cooled for efficiency. Blades are coated to resist erosion and corrosion.

7.1.8 Low Pressure Turbine

The 5-stage Low Pressure Turbine (LPT) receives the outlet flow from the HPT. The LPT drives the Low Pressure Compressor and the driven load (generator, compressor, etc.) through a shaft concentric to the HPT shaft.

(38)

LM6000 - 60 Hz Classic 6/2008 Page 37 of 156

The LM6000 gas turbine uses three frames to support the LP and HP rotors, the front frame, compressor rear frame and the turbine rear frame. This configuration produces excellent rotor stability and closely controlled blade tip clearance.

7.1.9.1

Front Frame

The LM6000 front frame is a major engine structure that provides sup-port for the LPC shaft and the forward end of the HPC shaft. The frame also forms an airflow path between the outlet of the LPC and the inlet of the HPC. The front engine mounts attach to the front frame. The front frame contains the engine “A” sump that incorporates the thrust and radial bearings to support the LPC rotor and a radial bearing which supports the forward end of the HPC rotor. Lubrication oil supply and scavenge lines for the “A” sump are routed inside the front frame struts. The accessory gearbox drive shaft is located in the “A” sump and extends out through the strut located at the six o’clock position.

Pads are contained on the frame outer case for mounting of the two High Pressure Compressor inlet temperature sensors.

7.1.9.2

Compressor Rear Frame

The compressor rear frame consists of an outer case, 10 struts and the “B-C” sump housing. The outer case supports the combustor and 30 fuel nozzles. The hub supports both the thrust bearing, the radial bearing and in turn, the mid-section of the HP rotor system.

7.1.9.3

Turbine Rear Frame

The turbine rear frame supports the rear engine mount and contains the D-E sump. The 14-strut rear frame guides and straightens the exhaust flow for lower pressure drop and greater efficiency.

7.1.10 Accessory Drive System

The hydraulic starter, lube and scavenge pump, variable geometry hydraulic pump, and other accessories are mounted on and driven by the accessory gearbox. The accessory gearbox is located below the front HPC casing at the six o'clock position on the LPC bleed air collector and is driven by the transfer gearbox through a short horizontal shaft. The transfer gearbox is driven by the high-pressure rotor system. The gearbox is supported from the LPC bleed air collector.

(39)

LM6000 - 60 Hz Classic 6/2008 Page 38 of 156

7.2

Auxiliary Equipment Module

The base auxiliary equipment module is provided with the unit and integrates several

functions. The auxiliary and fuel systems can be equipped with optional separate enclosures. The following is included as part of the standard auxiliary equipment module:

Auxiliary Module

• Synthetic lube oil system components including: reservoir, duplex oil filter and duplex shell/tube oil-to-coolant heat exchangers

• Electro-hydraulic start system components, including: electric starting motor, variable displacement hydraulic pump, reservoir, air/oil cooler, low pressure return filter, and case drain return filter

• On-line/off-line water wash system, including: reservoir, supply valves, solenoid valves, pump, electric tank heater, in-line water filter, and instrument air filter

7.3

Fire Protection CO

2

cylinders

• Optional sun shield

• Optional heated enclosure

7.4

Inlet Air System Multi-Stage Design

The GE Energy air inlet system is designed to protect the gas turbine, generator and equipment compartments from effects of air-borne dirt, contamination and foreign objects. It also provides a pre-engineered, modular design to minimize field assembly and eliminate field welding.

(40)

LM6000 - 60 Hz Classic 6/2008 Page 39 of 156

INLET VOLUTE DRAI N

VBV DRAIN

CO2 ACTU ATOR RESE T GENER ATOR EXHAUS T

~45000 SCFM [1274 SCMM] I AIR I I ROOM

STATOR TEMP SENSORS GENER ATOR I A B ~ 60 00 0 S C F M [1 69 9 S C M M ] INLET VOLUTE TURBINE ROOM A I B I

TURBINE ROOM EXHAUST

~60000 SCFM [1699 SCMM] I AIR I I HI LO LO HI I I I ATM ATM I MTTB MGTB SPARES STATOR I I I I II II II II I I I D R IF T E LI M IN A TO R D R IF T E LI M IN A TO R VENTIL ATION ~ 60 00 0 S C F M [1 69 9 S C M M ] TO ATM LH SECTION "A" AIR AIR I I TO ATM C A N IS T E R S C O M P O S IT E F IL T E R AIR COMBUSTION AIR ATMTO I I TO ATM TO ATM I SECTIONRH "B" I TO ATM C O M P O S IT E F IL T E R C A N IS T E R S AIR AIR I TO ATM ~ 45 00 0 S C F M [1 24 7 S C M M ] ~ 10 50 00 S C F M [2 97 3 S C M M ] COIL OPTIO N COIL OPTIO N I ALARM: IF ICING CONDITION EXIST I G U A R D F IL T E R G U A R D F IL T E R C O IL S E C T IO N C O IL S E C T IO N PDI 4106 4085TE PDT 4004 PDI 41044083TE 4005APDT PDT 4005B PDI 4107 TE 4086 PDI 4105 TE 4084 MT 4000A TE 4082A 4082B 4000B I I MT TE REL HUMIDITY SENSOR REL HUMIDITY SENSOR G-255-05 ~ 45 00 0 S C F M [1 27 4 S C M M ] MOT 4103A MOT4103B TE 4030 4031A1 TE 4102A1 PDT 4011A MOT 4017A 4054A1 MOT 4017B HE 4051 PDT 4007 PDT 4014 4054A2 4031A2 TE 4102A2 TE 4030 TE 4022 TE 4023 4023TE TE 4026 4026TE 4025TE 4025TE 4024TE 4024TE 4022TE 4021TE 4021TE PDT 4011B TE 4101C TE 4101A TE 4101B TE 4101D TE 4091 HE 4053 MOT 4122 MOT 4121 TC 4053 MOT 4120 MOT 4019 4001A2 4001A1 TE 4090 4090TE TE 4093 HE 4050 TE 4128 TE 4129 4127TE A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 TE TE TE TE TE TE A1 A2

(41)

LM6000 - 60 Hz Classic 6/2008 Page 40 of 156

7.4.1 Filtration Specification

The LM6000 static barrier filter removes more than 99.9% of all particles 5.0 micron and larger by utilizing a three-stage design.

Engine Combustion Air 230,000 scfm / 6,514 m3/min

Turbine Ventilation Air 60,000 scfm / 1,699 m3/min.

Generator Ventilation Air 45,000 scfm / 1,274 m3/min.

Total Typical Air Flow 355,000 scfm / 9,487 m3/min.

7.4.2 General Arrangement

The three-section inlet air filter mounts directly above the turbine enclosure, conserving space and providing compact, low-pressure loss ducting to the turbine inlet.

The filtered air is partitioned within the filter house assembly, providing combustion air for the gas turbine and ventilation air for the turbine and generator compartments.

The filter is designed for easy maintenance. A ladder and platform provides access to service doors on each filter section. Lighted internal walkways provide generous working room for replacement and maintenance of the filter elements.

(42)

LM6000 - 60 Hz Classic 6/2008 Page 41 of 156 AIR FILTER

Air Inlet Filter Assembly

7.4.3 Filter House Materials

7.4.4 Inlet Screens/Weatherhood

The weather hood provides a deflecting surface to prevent driving rain and snow from entering the filter house. In addition paper, leaves and wind-blown trash are blocked by the inlet screen. This structural component makes up the exterior face of the filter house and is manufactured from carbon steel.

The filter housing is constructed of 3/16 inch / 76 mm (verify units) steel plate. Protective paint is applied to the exterior and interior carbon steel surfaces.

Floors and drain pans downstream of the optional evaporative cooler media or optional inlet air chiller coils are stainless steel to resist corrosion.

(43)

LM6000 - 60 Hz Classic 6/2008 Page 42 of 156

7.4.5 Barrier Filter

7.4.6 Clean Air Plenum

7.4.7 Transition Ducts

Combustion air flows through a transition duct from the clean air plenum to the combustion air inlet silencer. Ventilation air flows through transition ducts to the turbine and generator compartment.

7.4.8 Inlet Silencer

The inlet silencer is a low-pressure-drop device located in the combustion air stream before the inlet volute. The silencer attenuates noise from the turbine and helps maintain the unit's low noise level.

7.4.9 Inlet Volute

The inlet volute is stainless steel weldment that directs the combustion air flowing down from the filter and turns it 90° to flow axially into the turbine inlet. Vanes within the volute smooth the airflow and present a balanced air stream to the turbine bellmouth.

The high-efficiency cylindrical barrier filter elements are mounted to the filter face of the inlet plenum and extend into the clean air plenum. The elements have extended surface area, large dirt holding capacity and low-pressure drop. Air flows through the elements from inside to outside keeping dirt safely trapped inside the element. The filter elements are designed specifically for gas turbine protection, and are particularly effective in filtering particles 5 microns or larger.

Air passes through the barrier filters and enters the clean air plenum. This fabricated structure is the center section of the inlet filter assembly and separates ventilation air from combustion air.

(44)

LM6000 - 60 Hz Classic 6/2008 Page 43 of 156

7.5

Package Enclosures

The package is equipped with a generator and a turbine enclosures plus an optional auxiliary module enclosure is available. The unit enclosures are designed for outdoor installation with wind loads up to 150 mph / 240 km/h and to reduce the average near field noise to 85 dB (A) at 3 ft. / 1.0 m from the enclosure and 5 ft. / 1.5m above grade. Each compartment is provided with access doors and AC lighting.

The turbine compartment contains an integral overhead bridge crane to facilitate engine removal.

Enclosure walls are a “sandwich” construction filled with insulation blankets of high temperature, sound attenuating material. The inner wall panel is fabricated from perforated 1.21 mm / 18-gauge stainless steel. The outer wall panel is 1.9 mm / 14-gauge cold rolled carbon steel, painted with abrasion resistant, exterior quality epoxy paint.

The turbine and generator compartment walls are supported by a structural steel framework that can withstand external wind loading and the internal pressure developed by the fire extinguishing system. External door hinges, latches and mounting hardware are stainless steel or chrome plated.

7.5.1 Enclosure Lighting

AC lighting for the interior of the gas turbine and generator compartments is provided.

7.5.2 Enclosure Ventilation System

The ventilation system removes heat from the turbine and generator compartments and removes combustible gases in the event of a fuel system failure. Both the turbine compartment and generator compartment are fully ventilated by redundant fans to improve reliability. Ventilation air is filtered to the same quality levels as the gas turbine combustion air.

(45)

LM6000 - 60 Hz Classic 6/2008 Page 44 of 156

(46)

LM6000 - 60 Hz Classic 6/2008 Page 45 of 156

7.5.2.1 Turbine Compartment Ventilation

Ventilation air enters the turbine compartment around the inlet collector. Dual 125 hp / 93 kW exhaust fans (1 running / 1 standby) create an induced-draft airflow of approximately 60,000 scfm / 1,699 m3.

7.5.2.2 Generator Compartment Ventilation

Filtered air is forced into the generator compartment by dual 100 hp / 75 kW forced draft fans (1 running / 1 stand-by) through ducts from the inlet air filter. The 45,000 scfm / 1,270 m3/min. airflow cools the generator and the generator compartment.

The ventilation fans produce a positive pressure in the generator compartment, providing additional isolation from the turbine compartment for gas leak protection purposes. This contributes to classification of the generator compartment as a non-hazardous area.

7.5.3 Noise Control

Lower noise limits can be provided with optional silencing equipment. Noise control will depend on the scope of the equipment supplied, the site plan, and project specific requirements.

7.5.4 Turbine Exhaust

The LM6000 exhausts air is extracted axially through a flange located at the end of the turbine enclosure. This provides low restrictions and a direct path into optional, or customer-supplied silencing or heat recovery equipment.

7.6

Baseplate

LM6000 generator sets are mounted on rugged I-beam baseplates to simplify shipping and installation.

The basic equipment is supplied with the support structures consisting of a two-piece skid assembly, which is sectioned between the gas turbine and the generator. The full depth, bolted section is designed to provide the full structural properties of the wide flange I-beams. Full depth crossmembers are utilized to provide a rigid design that meets the requirements of IBC 2006 and is therefore suitable for installation in earthquake areas. The baseplate support system is enhanced by the installation of a heavy-duty, welded superstructure which utilizes 6 inch x 6 inch x 3/8 inch wall structural tubing for wall columns and roof beams.

The LM6000 enclosure and air inlet silencer reduce the average near field noise to 85 dB (A) at 3 ft. / 1.0 m from the enclosure and 5 ft / 1.5 m above grade.

(47)

LM6000 - 60 Hz Classic 6/2008 Page 46 of 156

Tapered pins between the baseplates simplify field alignment and lifting spools are built into the baseplates providing a convenient structure for transportation.

7.7

Fuel System

The LM6000 gas turbine can be configured for gas, liquid or dual fuel operation. The basic gas fuel system is described below. Other configurations are available as options.

7.7.1 Gas Fuel System

The gas fuel system contains the following major components. They are mounted in the turbine compartment, adjacent to the engine.

• Fuel gas strainer

• Fuel gas flow meter

• Instrumentation

• Primary shutoff valve

• Fuel metering valve

• Secondary shutoff valve

• Fuel gas manifold

• Shipped loose manual shut-off valve

7.7.1.1

Gas Fuel Flow

Gas fuel must be supplied to the package baseplate connection at 675 +30/-20 psig / 4,053 – 4,962 kPag. Please see Section 14 for applicable fuel specification. Lower fuel supply pressure requirements for base load operation may be possible in certain circumstances. A customer supplied pressure regulator, pressure relief valve and GE supplied manually operated shut-off valve should be installed in the customer fuel supply system outside of main unit.

(48)

LM6000 - 60 Hz Classic 6/2008 Page 47 of 156 G-249-05 FCV 2001 SOV 2008 FT 2000 FE 2000 TE 2032A1 PT 2027B TE 2032A2 2028 PT FSV 2006 SOV 2006 FSV 2004 SOV 2004 PT 2027A FROM CDP PURGE SYSTEM A A E E G A S F U E L P U R G E M FC FO E 24 I

VENT TO SAFE ARE A

EDGE OF MAIN SKID

LC S 11 I MAIN SKID EDGE OF 10 I I G A S M A N IF OL D I 30 F U E L N O Z Z LE S T O TA L I FC FO CYL EXH IN S FC S EXH IN FO CYL I S E C O N D A R Y F U E L S U P P LY D D I LO I SET: 40 PSI 40 PSI SET: I I

VENT TO SAFE ARE A

INLET GAS FUEL

GAS FUEL GAS FUEL

I

Simplified Schematic – Gas Fuel System

7.7.1.2 Pressure and Temperature Monitoring

Pressure transmitters monitor the fuel supply pressure up stream and downstream of the fuel metering valve and forward the data to the fuel control and sequencer system. A platinum, dual element temperature RTD monitors fuel supply temperature and forwards the data to the fuel control and sequencer system.

7.7.1.3 Fuel Shutoff Valves and Safety Venting

Fuel shutoff valves manage gas flow to the combustor. Solenoid piloted fuel shutoff valves are quick-closure valve assemblies located upstream and downstream of the gas fuel metering valve. These fail-close valves are either fully open to allow fuel flow or fully closed to prevent fuel flow.

During startup, the shutoff valves are opened and fuel flow to the gas manifold is metered by the gas fuel metering valve. During shutdown, when the shutoff valves are closed, a solenoid-operated vent valve opens to vent the fuel supply line between shutoff valves to a safe area. A gas fuel drain valve opens during certain shutdown conditions to purge the gas manifold and the engine.

References

Related documents

There are 285 million visually impaired people worldwide are facing this challenge every day, including blind, partially blind or color blind persons, as well as elderly people

Virtual Sports Betting Secrets How to make a fortune betting on virtual football by using these revolutionary new betting systems A step-by-step blueprint for .... Emc Symmetrix

In a bid to give empirical evidence of poverty incidence and in- equalities among rural household in Southwest Nigeria, this study has assessed the gender differential

Some of the memorabilia is related to the educational institutions; Howard University, Wilberforce University, Oberlin College and Payne Theological Seminary, which Summers

Since the role played by tactical elements of the NBG is essential to the progress of the amphibious operation, plan for their employment concurrently with

Η βασιλεία (εξουσία του ενός) η αριστοκρατία (εξουσία των αρίστων) και η δηµοκρατία (εξουσία του συνόλου των πολιτών) είναι ορθά πολιτεύµατα,

1. The Fund cannot invest more than 5 per cent of its assets in transferable securities or money market instruments issued by a single entity. The Fund cannot invest more than 20

Foreign market access restrictions may lower the prices of exports, raise the prices of imports and have negative effects on the terms of trade, investment incentives and the growth