Home Inspection Report

Prepared by

APG Home Inspections

Adrian Guertin, PMP, CMI, CCHI

www.apghomeinspections.ca

48 Harcourt Avenue

(2)

Furnace Make: Keeprite AC Make: Payne

Amperage: 200 amps Inspection Component Summary:

Age: 5 years

Unit Age: 5 years

Tons 2.5 tons

Water Meter Location: Basement SW

Age of Home: 70+ Report # INS090402

Panel: Cuttler-Hammer

Age of Hot Water Tank 5 years Insulation R Value:

R50+/-Foundation Type Poured Concrete/Cinder locks

Refrigerator Stove Dishwasher Dryer HW Tank Washer Furnace AC Circuit Type: Breakers

Branch Wiring: Copper

Location: Basement

Inspection Address 48 Harcourt Avenue

Backwater Valve Exists

✔ Storm Crocks Still Connected

Microwave

Copper Distribution

Synthetic Distribution (100%) SyntheticAluminum Core (Kitec - PE-AL-PE)

Galvanized Plumbing Synthetic Drainage

✔ Copper Drainage Cast Iron Drainage

Galvanized Drainage Roof Covering Type Architectural shingles and flat torched membrane

Possible ZURN Brass F1807 Fittings - Further Inspection Recommended Customer Name Date 2020-09-04 City Toronto Postal Code Phone # email HRV Other Other Other Other Other Other Other Other Other Other

Appliances Over 10 Years Old are Excluded from Warranty and Should be Considered AS IS. You should Test All Appliances on Closing Day and Contact Your Lawyer Should They Not Function Properly or Have Been Damaged

(3)

Executive/Narrative Summary

Major Concerns Minor Concerns

Good Overall Condition

Fiberglass loose fill Approximately 15"+/- Approximate R value 50 Sheathing dry - Ventilation good

Attic and Insulation Observations

Tested HVAC in heat / cool modes Units operated successfully Newer HW tank with mixing valve

Service units annually - change filter every 3-4 months

HVAC System Observations

200 amp service

Cuttler-Hammer breaker panel Copper branch wiring Good overall condition

Electrical Observations

Newer architectural shingles

Torched membrane at front, side and on garage Good overall condition

Roofing Observations

Potential Hazards Exist Substantial Concerns

N/A

Masonry/Chimney Observations

Plumbing/Washroom Observations

Panel Cuttler-Hammer Amperage 200 amps Circuit Breakers

Age 5 years Size 2.5 tons

AC Make Payne

Furnace Make: Keeprite Age: 5 years Type: Forced air high efficiency 60k BTU's

Insulation: Fiberglass loose fill Estimated R Value:

R50+/-Copper Distribution

Synthetic Distribution (100%) Synthetic Aluminum Core (Kitec - PE-AL-PE) Galvanized Plumbing Synthetic Drainage

✔ Copper Drainage Cast Iron Drainage Galvanized Drainage

Pressure and drainage good No evidence of leaks

Taps and faucets operated successfully GFCI and exhaust fans operational

(4)

House observed to be in excellent condition Old critter trap can be removed

Louver on West side of house should be replaced Good overall condition

Miscellaneous Defects, Repairs and Hazards

All units tested were functional Good overall condition

Window Observations Good condition No damages observed Siding Observations Executive/Narrative Summary Basement dry

No evidence of water penetration No structural deficiencies

No evidence of any wood destroying insects or rodents

Observed Condition of Basement

No damages observed Restricted view due to grade Good overall condition

Observed Condition of Exterior Foundation

Good overall condition

Observed Condition of Landscape and Grading

Clean dryer vent

Replace transition hose to metal - flex or rigid Clean gutters seasonally

Recommendations

Good condition

Exterior Deck

None observed

(5)

N/A

Exposed Delta Wrap

Window Well Re-Grading Required Step or Vertical Cracks Visible

Tree Root Obstructions Possible due to Size/Proximity Walkout/Basement Access with Drain s/b Clear of Obstructions Neighbouring Grading may Drain onto Property

Parging Damages Foundation Type: Poured Concrete/Cinder locks

Grading Requires Adjustment/Repairs

Extension Cord Wiring of Opener (recommend outlet install) Garage Door Damages Exist

** It is Code to Have a Fire Rated Door to Garage with an Auto-Closure Mechanism to Prevent Fire Spread and CO Penetration Fire-Rated/Auto-Closure Door Missing/Non-Functional Auto-Closure Improper or Non-Functional Fire Door

Drywall Damages Exist - S/B Repaired

Good condition Detached unit

Observed Condition of Chimney(s)

Exterior

Garage

1- Missing louver on West side of house - S/B replaced 2- Overhead (Drop) service - secured

3- Garage roof - good condition

Grade Infringes on Weeper Holes at Sill Plate

Basement Windows Should Have Wells Installed

Gas Line to House < 1" Gas Line to House 1" +

✔ No damages observed

Restricted view due to grade Good overall condition

(6)

Exterior

Roof Accessed in Compliance with 2015 Working at Heights Legislation (< 3 Meters Access)

Multi-layer Shingles: Not Recommended Evidence of Critter Penetration Vent Stacks Too Short - S/B Extended Ice Damming

Tree Overhang S/B Monitored

Newer architectural shingles

Torched membrane at front, side and on garage Good overall condition

Re-engineer Roof Drainage

Improper Mixture of Roof Venting Exists

High Failure Risk Moderate Failure Risk

Low Failure Risk Further Evaluation/Inspection/Repairs Required

Covering Type Architectural shingles and flat torched membrane Inspected by Accessed

Possible Leak Points Identified

Observed Condition of Roof/Shingles

Cross Venting Exists Roof vents

✔ ✔ Soffit vents Ridge Vent Turbine vent Gable vents

Metal valleys ✔ Asphalt valleys Good condition

✔ Poor condition Unable to inspect

Flashings Valleys Vents

N/A

Visible/Proper

✔ Improper None Observed

Exhaust Vents

(7)

Fascia/Soffit Damages Visible

Exterior

Siding Damages/Deficiencies Exist - Further Inspection Recommended

Good condition No damages observed

Potentially Unsafe Decking (Missing Handrails, Rotting Deck, Unstable) - REPAIRS REQUIRED *see below*

Hot Tub < 4 Feet From Foundation; Recommend Verifying Local (Municipal Code) Regulations Hornets/Wasp/Insect Infestation etc... Visible Around House - Recommend Removal (Pest Control)

Good condition

Missing or Damaged Elbow/Splash Blocks Repairs Required to Gutters and Downspouts (Slope and Secure)

Possible Weeping System Damages/Failure Due to Age/Root Obstructions Downspout Elbows Require Repointing to Drain away from Foundation

Grade, Slope or Concrete Repairs Required on Front Porch (Uneven Treads and Risers etc...)

Good condition

Exterior Deck

Good overall condition

Grading Deficiencies

Combined Sewer/Storm

Separate Sewer/Storm

Storm Crocks Still Connected Septic

Siding: EIFS - Exterior insulated finishing system

General Drainage, Gutters and Downspouts

Neighbouring Grading may Drain onto Property

Extend Downspouts Away From House Damages Observed to Gutters/Downspouts-Repairs Recommended

Gutters are Clogged - Require Cleaning

Ensure all gutters and downspouts drain minimum 2 feet from house. Maintain a positive grade away from house. Ensure minimum 5 degree slope away from foundations. Maintain and inspect grading and drainage often. Storm crocks should capped and sealed and all downspouts empty well away from house.

Improper Build/Fastening Further Inspection Required Rotting/Unstable - Damaged Trip Hazards Exist

Landscape and Grade Repairs Highly Recommended Around House - Should Slope Minimum 5 Degrees Away from House and 1st 24" Moisture Dissipating

Negative Grading / Possible Water Penetration Points (pooling) Too Much Mulch/Greenery Along Foundation

(8)

Sub-Panels Exist

Ungrounded Outlets Observed

Breakers other than Panel Manufacturer Exist Reversed Polarity on Existing Outlets Detected

Double Tapping Exists at Panel Location Basement

Service Upgrade Recommended (Panel or Amperage) Knockouts/Grommets Missing -At Panel

Overfusing at Panel Exists Further Evaluation/Inspection Required (ESA Inspection)

Fuse to Breaker Upgrade Recommended Electrical Deficiencies Observed: Recommend Electrical Inspection/Repairs by Licensed Electrician

200 amp service

Cuttler-Hammer breaker panel Copper branch wiring Good overall condition

High Failure Risk Moderate Failure Risk

Low Failure Risk

Further Evaluation/Inspection/Repairs Required

Amperage Location

Obsolete Panel Type (Pushmatic, Stablock Pioneer or Pacific, Sylvania etc...)

Branch Wiring: Copper

Observed Electrical/Wiring Details

Interior Components

Panel Cuttler-Hammer

Amperage 200 amps

(9)

Washroom Ventilation All/Function HRV Some GFCI

Electrical Faulty Recommend GFCI

Recommend Installation of Ventilation Fans

Grandfathered (Window Vented Washrooms) - Pre-1994

Caulked Toilet Base (not recommended)

Exhaust or Light Installed in Shower or Above Bath (Verify Model Specs)

Older Plumbing Should be Assessed by Plumber and Should be Scoped if Necessary (Where Cast Iron/Clay Pipes Exist-High Recommendation)

Slow Draining/Clogs Exist Backwater Valve Exists

Further Evaluation/Inspection/Repairs Required

Recommend Septic Inspection Sanitary Supply

City

✔ Septic

Lead Feed Line Cistern

City

✔ Well Potability Tests Required Well Inspection Recommended

Cross Connections:

Electrical is Grounded

Observed Drain Pipe Material (If Visible) Unknown

Video Inspection of Sewage/Waste Drains Recommended (Sewage Drains are Considered Hidden Components and not in Scope of Inspection)

In Older Homes, A Sewer Drain Scope Can Assess the Condition of Older Street Drains and Can Detect Potential Problems that May Occur

Most Regions Offer Excellent Rebates for Installation of Flood Prevention Devices: Contact Your Region for Details

Tested

Meter Location: Basement SW Pressure: Good

Drainage: Good

Copper Distribution

Synthetic Distribution (100%) Synthetic Aluminum Core (Kitec - PE-AL-PE) Galvanized Plumbing Synthetic Drainage

✔ Copper Drainage Cast Iron Drainage Galvanized Drainage

Interior

Operates

✔ Faulty

Sump Pump Does Not Drain Above Grade/EXT. Check Valve (Backwater Valve) Present Sump Pump Discharge Pipe Not Properly Braced Check Valve Leaks

It is recommended to contact your insurance carrier to inform them of galvanized, lead, cast iron or aluminum core plumbing as rates and coverage may vary from carrier to carrier...

Flood Prevention Program

None Toronto ✔ Halton Hamilton Wentworth Niagara Region Peel Region None Located Other

Possible ZURN Brass F1807 Fittings - Further Inspection Recommended

Pressure and drainage good No evidence of leaks

Taps and faucets operated successfully GFCI and exhaust fans operational

Faucets/Fixtures Functional Faulty Repairs Needed

Main water shut off Storm water sump pump Backwater valve access Exterior Shut Offs Located

Exterior Taps are Frost Free/Self Winterizing

(10)

Mould/Mildew in Cold Cellar

Wood Framing S/B Removed From Cold Room

Missing or Blocked Venting in Cold Room

Interior

High Moisture/Water Penetration Visible

N/A

Living Space

Some Doors Require Adjustment/Repairs

Damages or Possible Concealed Damages Consistent with Fire or Smoke Damages

Damages or Possible Concealed Damages Consistent with Potential "Grow House" Operation

Basement dry

No evidence of water penetration No structural deficiencies

No evidence of any wood destroying insects or rodents

Basement

1- Attic sheathing DRY

2- Humidifier exists - never operate when AC running 3- Dryer hose should be replaced to metal - flex or rigid

Water Staining Visible: None

Structural Concerns: None

Waterproofing System: Exterior waterproofing and sump pump

(11)

Recommend Upgrading Insulation Insulation: Fiberglass loose fill

Sheathing: Planks/plywood

Suspected Black Mould

Interior

Damaged/Displaced Insulation/Critter Penetration Possible

Further Evaluation/Inspection Required

Estimated R Value:

R50+/-Fiberglass loose fill Approximately 15"+/- Approximate R value 50 Sheathing dry - Ventilation good

Improperly Vented Exhaust Fan Tubes in Attic

Restricted View of Attic

Depth:

14-15"+/-Observed Attic Conditions: Insp. Method: From attic hatch

Unable to Determine Venting Attic Venting Good

✔ Poor Attic Venting

Attic Hatch Missing Insulation/Weather Stripping

(12)

Storms Representative # Opened

Windows

Cracks/Broken Panes Found

Some Sanding/Painting Required Some Thermal Seals Breached Suspected Black Mould Rotting Visible on Frames or Brick Mold

Window Desc.: Thermal LO E windows

Upgrading of Windows Due to Failure, Amount of Repairs Repairs or Energy Efficiency is Highly Recommended

All units tested were functional Good overall condition

Interior Horizontal Step Vertical Cracks Exist Cracks Exist Cracks Exist Monitor Monitor Monitor

Moisture Visible Not Visible Floor Drains Efflorescence Visible ✔ Visible Not Visible Not Visible ✔ Clear ✔ Obstructed

Physical Obstructions Restricting View: Unable to Inspect Evidence of Previous Water Damage Present

Normal

Moisture Levels 0-15% Over 30% High

✔ 15%-30%

Normal Levels Levels 0-15% - Over 30% May Indicate Current/Previous Water Penetration Problems West

Walls Covered North South East

Monitor

V Cracks Exist

Previous Damages/Leaks Disclosed

Thermal Imaging/Infra-Red Camera Used on Exterior Walls

✔ Manual Moisture Readings Taken on Exterior Walls

Basement dry

No evidence of water penetration

Due to Weather, House Size, Accessibility; Not All Windows Can Be Opened - Only a Representative Number are Operated During Inspection Stripped Gears / Damaged Locks

Further Evaluation/Inspection/Repairs Required

** Basements, especially finished, may not display water problems unless conditions are present or happened recently. A home

inspection is limited to a visible non-instrusive inspection and finished areas are considered out of scope. The inspector disclaims any responsibility for future damages which may occur due to finished walls/physical obstructions...**

Window Sills Have Deteriorating Caulking/Mortar/Bricks - Joints Should Be Caulked - Brick Sills Should be Waterproofed

Missing or Damaged Screens Thermal Imaging:

(13)

Interior

Kitchen

GFCI Visible in Kitchen

Adequate Smoke Detection

✔ Additional / Newer Smoke Detectors Required Recommend Carbon Monoxide Detectors *Regulations on external exhaust for any range (gas/electric) are governed by the manufacturers recommendations

Hazardous Materials

Laundry Room

Replace Dryer Vent Transition Hose to Metal - Flex or Rigid

Secondary Lint Trap Should be Installed Dryer Vent Should be Professionally Cleaned

Recommend Metal-Braided Water Lines

Operated VIA Switch Pilot Not Lit - Recommend HVAC Inspection Fireplace - Main

Operated VIA Switch Pilot Not Lit - Recommend HVAC Inspection Fireplace - 2nd

Fireplace - 3rd Operated VIA Switch Pilot Not Lit - Recommend HVAC Inspection

** Installation and Fitness for Use of Fireplaces are Out of Scope of the Home Inspection - Pilots not Lit Cannot be lit by Inspector ** *It is highly recommended, when possible, to properly exhaust overhead vents to exterior

Microwave/Exhaust < 24" of Clearance; Consult Manufacturer Specs to Determine Proper Recommended Clearance

Dryer 40 Amp Fused - Recommend 30 Amp Max

Service on Fireplace (s) Recommended (Annually)

Good condition

Internal Kitchen Exhaust (filter) External Kitchen Exhaust No Kitchen Exhaust or N/A

Rot Under Faucet (Leaks)

Description of Abatement Required Quantity Unit Price Amount

** Gas Fireplaces Should Have Screens to Prevent Accidental Contact

As of October 15th, 2014, Carbon Monoxide Detectors are Mandatory in Ontario

W/B Fireplace - S/B WETT Inspected W/B Fireplace - S/B WETT Inspected W/B Fireplace - S/B WETT Inspected Flexible Dryer Vents Can Not be Installed in a Finished Area - Non Accessible

Plumbing Good condition

Electrical Good condition

Cabinetry Good condition

Counter-Tops Good condition

Material Location/Type: None observed

Good condition Good condition

Visual Condition of Appliances in Kitchen

Visual Condition of Appliances (Washer and Dryer)

(14)

Filter Requires Cleaning/Replacing

Hot Water

Approx. Age 5 years

Make: Keeprite Age: 5 years

Additional Combustion Ventilation Required in Furnace Room Duct Work Requires Cleaning

Filter 16x25x1

Capacity 50 gallon

Duct Repairs Recommended HVAC Service Recommended

Oil Tank SN HRV

Unit Failure Possible

Upgrade/Replacement of Water Tank Recommended after 10 years

Approx. Age HVAC Inspection Recommended (Due to Age)

Unit Age 5 years

Size 2.5 tons A/C Condensor

Make Payne

Unable to Test AC Due to Weather

Tested HVAC in heat / cool modes Units operated successfully Newer HW tank with mixing valve

Service units annually - change filter every 3-4 months

High Failure Risk Moderate Failure Risk

Low Failure Risk Further Evaluation/Inspection/Service/Repairs Required

Finished Basements or Enclosed Areas Should Have External Combustion Air

Pressure Relief Valve/Sleeve Missing ✔ Thermostatic Mixing Valve Type: Forced air high efficiency 60k BTU's

There are absolutely no warranties expressed, written or assumed on any HVAC components. Inspection is "AS IS" at inspection time Units Over 10 Yrs Old are not included in 90 Day Warranty...

Interior - HVAC

Humidification System Exists

Operable By: Unable to Test Furnace Due to Weather

References

Related documents

‘natural’ environment around the house, an older, underlying landscape was erased, and once the new house was completed an older medieval hall, Gawthorpe Hall, was

Landscape and Grade Repairs Highly Recommended Around House - Should Slope Minimum 5 Degrees Away from House and 1st 24&#34; Moisture

• The heating equipment appears to be functioning as intended and all components appear in satisfactory condition at the time of this inspection.. • The return air temperature

Sump Pump: An automatic pump that drains accumulated weeping tile water in the sump pit to the surface and away from the house, thereby relieving water build-up around

The west grading should be set up to direct water to flow south and north (diverting away from the house) as much as possible.. Nevertheless, some dampness and wall efflorescence

After sweet potatoes are cured, the temperature in the storage house should be brought down below 60 degrees, but not lower than 55 degrees, as rapidly as possible-preferably

For all these reasons, we propose a new sustainable traffic aware duty-cycle adaptation algorithm (STADA) that fits the constraints of multi-hop energy harvesting wireless

The activities of the household, markets, businesses, government, financial institutions as economic systems has a great impact on the global economy because they