White Paper

Gigabit Passive Optical Networks

Passive Optical LAN Solutions (POLS)

Theory, Design, and Installation Considerations

Sean McCloud, RCDD

(2)

Table of Contents

Abstract 3

Standards 3

Understanding Passive Optical LANs and GPON 4

GPON Components 5

System Overview 7

Installation Options 8

POLS Safety Issues 12

Testing 12

Troubleshooting 14

(3)

Abstract

Today’s diverse and ever-changing technology applications require options for the distribution of information in commercial, public, and governmental markets. Gigabit Passive Optical Networks (GPON) provide a solution that minimizes the physical footprint, increases distance and bandwidth, reduces latency, and improves physical and network security.

Other potential benefits include:

• Adherence to green and sustainability initiatives – LEED® and STEP

• Reduced costs for moves, adds, and changes • Lower price per port on passive components

• Pre-terminated systems are easy to install and reduce labor and installation errors

Standards

The implementation of Passive Optical LAN Solutions was adopted by ANSI/TIA in August of 2012 under ANSI/TIA 568-C.0-2 General Cabling Addendum 2, General Updates.

Other applicable standards include:

• ANSI/TIA 526-7 Method A.1 Measurement of Optical Power Loss of Installed Single-mode Fiber Cable Plants • ANSI/TIA 568-C.0 Generic Telecommunications Cabling for Customer Premises

• ANSI/TIA 568-C.1 Commercial Building Telecommunications Cabling Standard • ANSI/TIA 568-C.2 Commercial Building Telecommunications Cabling Standard,

Balanced Twisted-Pair Cabling Components • ANSI/TIA 568-C.3 Optical Fiber Cabling Standard

• ANSI/TIA 569-C Commercial Building Standard for Telecommunications Pathways and Spaces • ANSI/TIA 606-B Administration Standard for Commercial Telecommunications

• ANSI/TIA 607-A Commercial Building Grounding (Earthing) and Bonding • ITU-T G.984 addresses PON systems (BPON, EPON, GPON)

• ITU/Telcordia GR-1209 CORE Generic Requirements for Passive Optical Components • ITU/Telcordia GR-1221 CORE Fiber Optic reliability

(4)

Understanding Passive Optical LANs and GPON

Network Architecture

While there are many applications for GPON, this paper will address Fiber-to-the-Desktop (FTTD) deployment often used in commercial, educational, and governmental office environments. The most commonly used POLS follow the ITU-T G.984 GPON Class B+ standard. In this application, GPON is distributed via single-mode, simplex optical fiber connectors, and passive optical splitter(s) typically using Angled Polish Connectors (APC) to provide precision terminations that minimize the impact of insertion and return loss. There are four major components to this GPON system: the Optical Line Terminal (OLT), the transport media (cabling and components), the fiber optic splitter, and the Optical Network Terminal (ONT). These components are identified in the following line diagram.

ONT Core Switch 1550nm Tx (Video) 1.24Gbps 1310nm Rv 1490nm Tx 2.48Gbps 1550nm Tx (Video) 1x32 Splitter Device OLT ONT ONT ONT ONT ONT ONT ONT ONT ONT ONT ONT Device Device Device Device Device Source IP Data

Voice Over Internet Protocol IP Video

RF Video

OLT (Optical Line Terminal)

Acts as the central aggregator and is typically located in the data center or main equipment room

Passive Optical Splitter

Passively splits the signal from the OLT over one fiber to as many as 32 fibers each connecting to an ONT

ONT (Optical Network Terminal)

Active device that converts the fiber optic signal and converges voice, data, and video signals as necessary to connected user devices

Building Automated Systems

Video Data VoiP Wireless Security

(5)

GPON Components

Optical Line Terminal (OLT)

The OLT is an active Ethernet aggregation device typically located in the Main Equipment Room or Data Center of a facility. An OLT converts the aggregated fiber optically transmitted signals to an electrical signals and presents them to a core Ethernet switch. The OLT replaces multiple layer 2 switches at distribution points (ERs, TRs, and TEs). Backbone cabling or horizontal cabling connects to the OLT distributing signal through optical splitters, which are connected to the Optical Network Terminal at each work area outlet.

Transport Media – Structured Cabling Systems

GPON uses the passive, physical cabling infrastructure to transmit a signal. This includes copper and fiber optic patch cords, enclosures, adapter plates, connectors, splitters, backbone and horizontal cable faceplates, and pathway support materials. All transport media components should be factored into the channel loss budget when verifying the systems performance.

Passive Optical Splitter

Part of the transport media, the splitter enables multiple devices to be serviced from a single inbound fiber. The passive optical splitter uses a series of silicon dioxide waveguides to split a fiber from one to two strands. The amount of outputs in the splitter determines the number of splits that occur. Approximately -3dB of loss occurs at each split, as shown here.

For this 1x8 splitter example, a perfectly terminated and performing splitter would have a -9 dB loss per output.

Optical Network Terminal (ONT)

The ONT is a device typically located near the work area outlet. The ONT provides conversion of GPON signals from optical to electrical for delivery to the end device. ONTs also provide AES encryption via a security key. The ONT typically has multiple Ethernet ports for connection to IP devices such as CPUs, phones, wireless access points, cameras, or other video components.

PON Equipment Vendor Options:

• Some ONTs support Power over Ethernet (WAPs, VoIP phones, etc.) IEEE802.3af, at • Some ONTs support copper horizontal distances (100m)

• Redundancy for fiber facility and/or added equipment redundancy • Remote powering and/or battery reserve at ONT

Silicon Dioxide Waveguides > 3dB loss in both directions at each 2x split 1310nm RV 1490nm Tx 1x8 Splitter

(6)

Link vs. Channel Attenuation (as defined by ANSI/TIA-568-C.0-2-2012)

Link attenuation only includes cable, connectors, and splices (excludes active devices and splitters)

Channel attenuation includes all passive components (cable, connectors, patch cords, splices, couplers, and splitters) Transport media consists of:

1. Pre-terminated (recommended) or field terminated: • Multi-fiber backbone cable assemblies • Simplex backbone cable assemblies • Simplex horizontal cable assemblies 2. Fiber Optic Splitters (typically 1x16 or 1x32)

• Can have redundant input capabilities (2x16 or 2x32) 3. Simplex fiber optic patch cords

4. Fiber optic connectors and couplers – Angled Polish Connector (APC)

• Typically the SC/APC connector is used, but LC connector and UPC solutions are available 5. Copper patch cords (Category 6 or better recommended)

The ITU-T G.984 standard determines the minimum and maximum channel attenuation allowed over a maximum distance. ITU-T G.984 GPON Class B+ values are as follows:

Nominal Wavelength (nm), Wavelength Range {nm}

1270

{1260-1280} {1260-1360}1310 {1480-1500}1490 {1575-1580}1577

Application Upstream Downstream

GPON Class B (ITU-T G.984)

Min. Channel Attenuation, dB 10 10

Max. Channel Attenuation, dB 25 25

Max. Supported Distance 20,000m (65,620 ft)

GPON Class B+ (ITU-T G.984)

Min. Channel Attenuation, dB 13 13

Max. Channel Attenuation, dB 28 28

Max. Supported Distance 20,000m (65,620 ft)

GPON Class C (ITU-T G.984)

Min. Channel Attenuation, dB 15 15

Max. Channel Attenuation, dB 30 30

Max. Supported Distance 20,000m (65,620 ft)

GPON Class C+ (ITU-T G.984)

Min. Channel Attenuation, dB 17 17

Max. Channel Attenuation, dB 32 32

Max. Supported Distance 60,000m (196,850 ft)

Notes: The channel attenuation is the sum of all link attenuations and attenuation values for all passive components including splitters,

(7)

System Overview Using Leviton Components

Wireless Access Point (WAP)

Structured Media® and Zone enclosures:

in-ceiling, wall-mount or below-floor consolidation points for plenum and non-plenum spaces to reduce the need for a TR

SM drop cables complete connection from the passive splitter to the work area

Pre-terminated trunk cabling speeds

deployment Opt-X fiber enclosures: in entrance

facility or TR consolidation point for traditional distribution footprint Secure and armored fiber

patch cords available

QuickPort® wallplates

and fiber connectors ONT with copper or fiber patch cords makes

the final connection to the user devices

(8)

Installation Options

Star/Hierarchical Star Topology

1. Follows traditional hierarchical star topology and uses common horizontal distribution methods from an Equipment Room (ER)/ localized Telecommunications Room (TR)

2. Uses existing TR located in a dedicated floor space on every floor 3. Requires longer horizontal cable runs and less backbone fiber 4. Allows interconnect or cross-connect methods at the ER/TR location

5. Allows easy access for IT personnel for any required maintenance, much of which is centralized away from office spaces

ER/TR

TR

Optical Line Terminal

or

Aggregator Switch

Fiber Optic Enclosure

WAO Device Optical Network Terminal (ONT) 1x32 PON C assette

Fiber Optic Adapter Plate

Device

ISP Backbone from ER

Pre-terminated trunks or field terminated fiber

Inbound Fiber

Field or pre-terminated fiber

Work Area Outlet

Single-gang angled faceplate

Outbound Leg

1 of 32 Shown

Horizontal Cabling to Workstation

Field or pre-terminated fiber

Fiber Patch Cord

(9)

In this example of the traditional hierarchical star topology method, 1x32 splitters are located in the

Telecommunications Room. Simplex, single-mode cables are installed from the Telecommunications Room to the Telecommunications Outlet. WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS OPEN OFFICE OFFICE OPEN OFFICE OFFICE BREAK ROOM STORAGE RECEPTION OFFICE CONFERENCE ROOM

CONFERENCE ROOM CONFERENCE ROOM TRAINING ROOM COPY ROOM RESTROOM RESTROOM JANITORIAL ELECTRICAL OFFICE OFFICE OFFICE OFFICE OFFICE AP AP AP AP AP AP 1 2 3 4 5 6 1 5 4 8 9 13 12 16 17 21 20 24 25 29 28 32 INP UT-1 INP UT-2 1 2 3 4 5 6 1 5 4 8 9 13 12 16 17 21 20 24 25 29 28 32 INP UT-1 INP UT-2 1 2 3 4 5 6 1 5 4 8 9 13 12 16 17 21 20 24 25 29 28 32 INP UT-1 INP UT-2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 Legend

Horizontal Cable Pathway

(1) GPON OS2 SM Port (AP)

AP

(1) OS2 SM Fiber Port (UON) (2) OS2 SM Fiber Ports (UON)

Fiber Optic Enclosure

in the Telecommunications Room (Typical)

TELECOM ROOM

(10)

Fiber Optic Enclosure ER WAO Optical Network Terminal (ONT) TR

Fiber Optic Enclosure

Fiber Optic Adapter Plate

CP

Zone Enclosure 1x32 PON Splitter

Optical Line Terminal or Aggregator Switch Fiber Optic A dapter Plate Fiber Optic A dapter Plate Fiber Optic A dapter Plate

Fiber Optic Adapter Plate

Device Device

Backbone Cabling from Main Equipment Room to Telecommunications Room

1RU enclosure serves up to 36 PON consolidation points

Work Area Outlet

Single-gang angled faceplate

Inbound Leg

Horizontal fiber from TR

Horizontal Cabling to Workstation

Field or pre-terminated fiber

Fiber Patch Cord

Copper Patch Cord Outbound Leg

1 of 32 Shown

Zone Distribution Topology

1. Allowed per ANSI/TIA standards. Requires additional design considerations from hierarchical star 2. Uses telecom enclosures located:

• Under raised floors; • On or in wall;

• Mounted in an open ceiling space; or • In or above a reflected ceiling

3. Requires longer backbone cabling and shorter horizontal fiber runs (less fiber cabling)

4. Uses enclosures which may be an added expense in existing environments or a lower-cost alternative in new environments (as opposed to needing a TR)

5. Allows interconnect or cross-connect at the enclosure location. Provides modularity and scalability 6. Allows easy access for IT personnel for any required maintenance, and minimizes the impact

(11)

In this example of the zone distribution topology method, simplex, single-mode cables are installed from the Telecommunications Room to the Zone Consolidation Point. 1x32 splitters are located at each consolidation point to allow for adequate redundancy and future expansion. Horizontal cables are installed from the feeding consolidation point to each telecommunications outlet.

WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS WS OFFICE OPEN OFFICE OFFICE

BREAK ROOM STORAGE

RECEPTION OFFICE CONFERENCE ROOM OFFICE OFFICE OFFICE OFFICE OFFICE

CONFERENCE ROOM CONFERENCE ROOM TRAINING ROOM COPY ROOM TELECOM ROOM RESTROOMS RESTROOMS JANITORIAL ELECTRICAL OPEN OFFICE AP AP AP AP AP AP Zone 6 Zone 11 Zone 12 Zone 7 Zone 8 Zone 13 Zone 14 Zone 9 Zone 15 Zone 10 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Legend

Consolidation Point Zone Boundary GPON OS2 SM Consolidation Point (32-PORT UON)

(1) GPON OS2 SM Port (AP)

AP

(1) OS2 SM Port (UON) (2) OS2 SM Ports (UON)

1 5 4 8 9 13 12 16 17 21 20 24 25 29 28 32 INPUT-1 INPUT-2 1 2 3 4 5 6 1 2 3 4 5 6 6 5 4 3 2 1

Connectivity in the Consolidation Point Enclosure

Fiber Optic Enclosure

in the Telecommunications Room (Typical)

1 2 3 4 5 6 1 2 3 4 5 6

(12)

POLS Safety Issues

Working with, installing, and servicing fiber optic components requires special care, materials, and consideration. While LED and VCSEL laser sources operate at relatively low power levels, systems using fiber amplification (CATV and video links at 1550nm or Telco DWDM) can be damaging to the eyes. The correct and safe approach to take is to always verify the link is inactive and never look directly into the end of a fiber connector or port.

Testing

General Testing Guidelines

POLS are tested the same way as traditionally installed fiber optic cabling. All cabling should be tested to ANSI or IEC standards, as applicable. It is essential to use reference-grade cords and proper inspection and cleaning practices for accurate and successful results.

For more information regarding testing methods and cleaning practices, visit Leviton’s series of Application Notes at: http://www.leviton.com/appnotes

Channel Optical Budget

Determining an attenuation budget prior to installation of the system is critical to verifying the system will function properly as designed. The budget is calculated to factor in the maximum loss allowed from each component of the fiber channel.

• Required to determine a budget: • Length of the cable used • Properties of the cable used • Type of fiber

• Physical topology of the cable plant • Specifications of the equipment to be used • Need for future changes or damage allowances The chart to the right is an example of a Link Budget Calculation and the evaluation against actual loss data. The maximum loss allowed for the channel per GPON Class B+ (ITU-T G.984) is -28dB.

Channel Link Budget Sample

400ft (0.122km) Total Length

Item Qty Loss (dB) Total Loss (dB)

Total Channel Link

Distance (km) 0.122 -1 -0.122

Total Fiber Splices 0 -0.3 0

Total Mated Fiber Pairs 7 -0.75 -5.25

Passive Fiber Splitter

(1x32) 1 -16.7 -16.7

Total Estimated Channel Link Loss (dB) -22.072

Actual Channel Link Attenuation

Item Qty Loss (dB) Total Loss (dB)

Total Channel Link

Distance (km) 0.122 -0.035 -0.00427

Total Fiber Splices 0 -0.3 0

Total Mated Fiber Pairs 7 -0.32 -2.24

Passive Fiber Splitter

(1x32) 1 -16.05 -16.05

Total Channel Link Loss (dB) -18.29427 Total Estimated Channel Link Loss (dB) 3.77773 Total Estimated Channel Link Loss (dB) 9.70573 Notes: 0.5dB/km loss allowance for outside plant fiber, 1.0dB/

km loss allowance for inside plant fiber, 0.3dB allowance for splices, 0.75dB allowance for mated pair connectors, splitter loss provided by manufacturer, includes the loss of all patch cords

(13)

Tier 1 Testing

Tier 1 testing is required per ANSI/TIA and IEC standards. It is achieved by performing a visual inspection of the end face of all connectors, documenting the length via cable markings or testing apparatus, verifying polarity (if applicable), and using an optical power source and optical meter. The optical meter measures the end-to-end loss (attenuation in dB) of the link.

The recommended method is ANSI/TIA 526-7 method A.1, One Reference Jumper method. Testing needs to be performed unidirectionally or bi-directionally at the appropriate wavelengths (1490nm for the downstream and 1310 upstream). As most optical test sets operate at 1550, this wavelength is typically acceptable as a substitute for the 1490 wavelength as the difference in loss will be small. A PON power meter is capable of the specific wavelengths in use: 1310 upstream, 1490 downstream, and 1550nm (used for video BPON [Broadband PON] if applicable).

Tier 2 Testing

Tier 2 testing is achieved by using an Optical Time Domain Reflectometer (OTDR). An OTDR sends pulses of light into an optical fiber and measures the strength of the power returned to the instrument as a function of time. The OTDR creates a graphical output (trace/picture) depicting the fiber link under test. The OTDR has the capability to measure the length of the fiber and estimate the loss between any two points along the fiber link.

Tier 2 testing is not required by ANSI/TIA standards and is not a substitute for Tier 1 certification. Tier 2 may be requested by the end user to provide added test detail and a historical benchmark for each individual link performance. OTDR testing is also valuable in determining cable attenuation and fault points during troubleshooting.

(14)

Troubleshooting

While there are often several components in the channel, troubleshooting a POLS system is relatively easy. The scenarios below address the probable fault points:

PON Troubleshooting Scenario 1: Simple PON - only one customer is affected

When only one user cannot receive service, three potential faults are probable:

• Fault in the distribution fiber between the work area outlet and the closest splitter • Fault in the ONT equipment

• Fault in the horizontal wiring

PON Troubleshooting Scenario 2: Multiple PON users affected from the same splitter

When all customers connected to the same splitter cannot receive service, but others connected to the same OLT can, the cause may be because of one of the following:

• Fault at the splitter

• Fault in the fiber link between the OLT and splitter

PON Troubleshooting Scenario 3: All customers are affected (at the OLT level)

Whether or not the PON is cascaded, all customers dependent on the same OLT may be affected. If all customers are affected, the cause may be from of the following:

• Fault at the splitter closest to the OLT

• Fault in the feeder fiber/cable of the fiber network • Fault in the OLT equipment

(15)

Telecommunications Room Optical Line Terminal (OLT)

Passive Splitter Circuit from Service Provider TR Horizontal Cabling Device Optical Network Terminal (ONT) Device SCENARIO 3:

• Fault from the service provider or other active component prior to the circuit reaching the OLT • Fault in the distribution fiber link between the OLT and splitter • Fault in the feeder fiber/cable of the fiber network

• Fault in the OLT equipment

SCENARIO 2:

• Fault at the splitter • Fault in the distribution fiber link between the OLT and splitter

SCENARIO 1:

• Fault in the horizontal fiber between the work area outlet and the splitter • Fault in the ONT equipment • Fault in the fiber connector or patch cords • Fault in the copper patch cord to the device

ISP Backbone from ER

Qty: 1 singlemode fiber

Telecommunications Room or Consolidation Point Enclosure Singlemode Fiber

Qty: 1 to each Optical Network Terminal (ONT)

Work Area Outlet

Faceplate, surface mount box, etc.

Fiber Patch Cord Copper Patch Cord

Troubleshooting Schematic:

Conclusion

POLS and GPON, while still a relatively new concept as a method for commercial structured FTTD cabling systems, are becoming more common due to flexibility, reduced physical footprint, improved physical and network security, and potential and realized cost savings. While not for every user or scenario, a carefully designed and properly commissioned POLS system will provide a scalable, bandwidth-rich and secure solution.

(16)

All Other International Inquiries E [email protected]

We invent the industry’s best technologies. We build them to last. And we stand behind every product and every installation – delivering guaranteed performance and unbeatable service and support – throughout the life of your structured cabling system. Add in the peace of mind that comes from working with a stable, century-old supplier and you get far and away the highest return on investment in the industry.

High-performance connectivity backed by the

industry’s best service and support

THE SMART CHOICE FOR

A BETTER NETWORK

Leviton International Offices

Asia / Pacific T +1.631.812.6228 E [email protected] India / SAARC T +971.4.886.4722 E [email protected] Caribbean T +1.954.593.1896 E [email protected] Mexico T +52.55.5082.1040 E [email protected] Canada T +1.514.954.1840 E [email protected] Latin America T +52.55.5082.1040 E [email protected] China T +852.2774.9876 E [email protected]

Middle East & Africa

T +971.4.886.4722 E [email protected] Colombia T +57.1.743.6045 E [email protected] South Korea T +82.2.3273.9963 E [email protected] Europe T +33.6.8869.1380 E [email protected] Leviton Network Solutions Division Headquarters

leviton.com/networksolutions

2222-222nd Street S.E., Bothell, WA 98021 USA Inside Sales T 800.722.2082 E [email protected] Technical Support T 800.824.3005 / +1.425.486.2222 E [email protected]

International Inside Sales

T +1.425.486.2222 E [email protected]

Leviton Corporate Headquarters leviton.com

201 N. Service Road, Melville, NY 11747 USA Customer Service

T 800.323.8920 / +1.631.812.6000 E [email protected]

References

Related documents

The primary technical objective of this project was to provide a low-cost CubeSat for a demonstration mis- sion that demonstrates three-axis fine attitude control

Today’s medical advancements have allowed for an increasing number of children to survive cancer and return to the regular school environment (Canter & Roberts, 2012). It has

The risk assessment process should be used to identify the need for inspection checklists and monitoring records and Facility Managers are responsible for ensuring that all

These trees would be suitable for planting adjacent to overhead power lines... Tree-Trimming Contractor List. This list of tree contractors is merely a compilation of businesses

It is necessary to consider security usability as part of vulnerability analysis and risk assessment in order to properly manage current and emerging risks. We have described a set

1 0 G b E 1 0 G b E Desktop 1..N OS OS Delta Personal vDisk ESXi Host Nutanix CVM Read Cache SATA SSD SATA HDD PCIe SSD ILM READ IO READ/WRITE IO ESXi Host Nutanix CVM Read Cache

In my comprehensive review of the literature, I addressed the practice question of: what are the components of a structured theory supported evidence-based mentorship program

FIL NOIR/JAUNE = NÉGATIF DE LA BATTERIE ALIMENTATION AVEC DÉMARREUR FIL ROUGE/VERT = POSITIF DE LA BATTERIE FIL NOIR/JAUNE = NÉGATIF DE LA BATTERIE FIL NOIR = NÉGATIF DU MOTEUR FIL