• No results found

KNX Technical Reference Manual ABB i-bus KNX. ETS-App "KNX Bus Update"

N/A
N/A
Protected

Academic year: 2021

Share "KNX Technical Reference Manual ABB i-bus KNX. ETS-App "KNX Bus Update""

Copied!
6
0
0

Loading.... (view fulltext now)

Full text

(1)

Pos: 2 /DinA-4 -- Online/00_Titel/ETS-APP - KNX Bus Update - @ 42\mod_1433939906638_0.docx @ 367891 @ @ 1

1473-1-8756 │ 11.08.2015

KNX Technical Reference Manual

ABB i-bus

®

KNX

ETS-App "KNX Bus Update"

(2)

Table of contents

Pos: 4 /DinA-4 -- Online/00_IVZ/IVZ - 2-Überschriftenebenen @ 39\mod_1415276617885_15.docx @ 305452 @ @ 1 Table of contents

1

Product description ... 3

2

Download ... 3

3

Installation ... 3

4

App operation ... 4

4.1

User interface ... 4

4.2

"Options" window ... 5

(3)

Product description

Pos: 6 /DinA-4 -- Online/1 Überschrift/Produktbeschreibung @ 42\mod_1433941436895_15.docx @ 367908 @ 1 @ 1

1 Product

description

Pos: 7 /DinA-4 -- Online/Aufbau und Funktion/Einleitung/Einleitung -- ETS-App - KNX Bus Update - @ 42\mod_1433941855456_15.docx @ 367924 @ @ 1

The ETS app „KNX Bus Update“ serves for the updating of devices (and their firmware) directly

via the ETS (Engineering Tool Software).

The app works both with ETS 4 as well as ETS 5.

Pos: 8 /DinA-4 -- Online/1 Überschrift/Download @ 42\mod_1433941974171_15.docx @ 367940 @ @ 1

2 Download

Pos: 9 /DinA-4 -- Online/Inbetriebnahme/Download/Download -- ETS-App - KNX Bus Update - @ 42\mod_1433942115194_15.docx @ 367957 @ @ 1

1. Log yourself in at website "https://my.knx.org/shop".

2. Search for the app „KNX Bus Update“. in product category "ETS apps".

3. Place the app into the shopping trolley.

4. Enter your invoice data.

5. Open the "My products" section.

6. Add your own dongle ID.

7. Save the license file (.zip) on your PC.

Pos: 10 /DinA-4 -- Online/1 Überschrift/Installation @ 42\mod_1433942261116_15.docx @ 367973 @ 1 @ 1

3 Installation

Pos: 11 /DinA-4 -- Online/Inbetriebnahme/Installation/Installation -- ETS-App - KNX Bus Update - @ 42\mod_1433942343514_15.docx @ 367990 @ @ 1

1. Unzip the license file. Save it as app file type (.etsapp).

2. Open the ETS.

3. Select "Settings" -> "ETS apps".

4. Select "Licensing" -> "Add".

5. Select the unzipped license file.

6. Click on "Install" and select file type 'etsapp'.

(4)

App operation

Pos: 13 /DinA-4 -- Online/1 Überschrift/App-Bedienung @ 42\mod_1433942513975_15.docx @ 368006 @ 1 @ 1

4 App

operation

Pos: 14 /DinA-4 -- Online/1.1 Überschrift/Arbeitsoberfläche @ 42\mod_1433942920695_15.docx @ 368022 @ 2 @ 1

4.1 User

interface

Pos: 15 /DinA-4 -- Online/Bedienung/Betrieb -- Einrichtbetrieb (Setup) / Einstellungen/00_Übersicht -- Gerät / Display/Arbeitsfenster -- ETS-App - KNX Bus Update - @ 42\mod_1433943049160_15.docx @ 368038 @ @ 1

Fig. 1: User interface "KNX Bus Update"

[1] "Device type"

Select the device type to be updated. After the selection, all devices of this type will be listed in the project according to the topology.

[2] "Update to version"

Select the version of the update file you wish to use. The latest version is always listed here as standard. [3] "Update firmware"

Button to start the update process. [4] "Options"

This button offers the option of performing settings, see chapter 4.2 "Options" window on page 5. [5] "Import"

This button allows update files to be added manually. The update files can be downloaded from the manufacturer's site.

[6] "Reload"

Changes to the project (number of devices, topology) while the update app is open, must be actuated with this button to make the changes visible also in the app.

[7] In this section all areas / lines are displayed in which devices of the selected type are located. When a line is selected, all devices of the selected type in this line are displayed in the middle section (see item 8). [8] In this section all devices of a line which can be updated with the selected firmware are displayed. The

devices for the update can be selected by activating the checkbox. [9] "Select all"

All "relevant" devices of a line are selected for the update with a press of the button.

(5)

App operation

4.2 "Options"

window

Pos: 17 /DinA-4 -- Online/Bedienung/Betrieb -- Einrichtbetrieb (Setup) / Einstellungen/00_Übersicht -- Gerät / Display/Fenster Optionen -- ETS-App - KNX Bus Update - @ 42\mod_1434010285215_15.docx @ 368075 @ @ 1

Fig. 2: "Options" window

[1] "Force Update"

The firmware update is also carried out when there is the same or a later version on the device. [2] "Trying to resume aborted firmware updates"

If a device is to be updated with a new firmware whose update failed during a previous try (with the same version), the update is continued from the point it was aborted.

[3] "On start, check if new updates are available"

If the computer is connected with the Internet and this option is activated, at the start of the program it will be checked whether new update files are available on the update server. These files will then be

downloaded automatically. There is the additional option of downloading firmware files manually and to integrate them via the "Import" button.

[4] "Pauses, to reduce the bus load"

To prevent impairment of the KNX system during the update it may be necessary to reduce the bus load caused by the update. This is made possible with the enforcement of pauses between the update telegrams.

[5] "Maximum frame length"

The attempt to carry out the update communication with the maximum length supported by the device and the system interface to minimize the duration of the update, is standard procedure.

General information

The duration of the update can vary greatly depending on the KNX interface

used. Recommended interfaces are:

– 6149/21 in connection with 6120/12-101,

– 6186/USB,

– KNX.Net/IP

interface,

– Interfaces which support long frames.

The duration of the update can be greatly reduced with the use of an interface

with a long-frames function.

It is recommended to always carry out the update from the line in which the

devices are located, to prevent the influence on the duration of the update from

other system components such as line couplers.

(6)

Pos: 19 /DinA-4 -- Online/00_Rueckseite/Rueckseite -- BJE/ABB @ 39\mod_1415285579815_15.docx @ 305612 @ @ 1

A member of the ABB Group

Busch-Jaeger Elektro GmbH PO box 58505 Lüdenscheid Freisenbergstraße 2 58513 Lüdenscheid www.BUSCH-JAEGER.com [email protected]

Central sales service:

Tel.: +49 2351 956-1600 Fax: +49 2351 956-1700

Notice

We reserve the right to at all times make technical changes as well as changes to the contents of this document without prior notice. The detailed specifications agreed upon apply for orders. ABB accepts no responsibility for possible errors or incompleteness in this document. We reserve all rights to this

document and the topics and illustrations contained therein. The document and its contents, or extracts thereof, must not be reproduced, transmitted or reused by third parties without prior written consent by ABB

Copyright© 2015 Busch-Jaeger Elektro GmbH

All rights reserved

KNX Technical Reference Manu

al 14 73-1-87 56 | 11.0 8 .2015

References

Related documents

Conversely, the Beo6 remote control from Bang & Olufsen can transmit to an IR receiver from ABB/Busch-Jaeger to control corresponding control elements. In other words, you

ƒ The cover n of the Weather Sensor is locked on the right and left side of the lower edge o. ƒ Remove the cover n from the Weather Sensor

This communication object is enabled if in parameter window Parameter window Gx Group, page 51, the additional function Sequence is enabled. This communication object is used

Using the parameter Value object Switch on bus voltage recovery, it is also possible to define if the channel switches on (staircase lighting time times out normally) or off.. If

This parameter defines whether in the event of a fault in the 12 V DC auxiliary supply, the communication object Tamper alarm is triggered in addition to the change of communication

The assignment of the address of the ABB i-bus ® IP INTERFACE is carried out via the ETS and the programming button on the device.. The device features a programming button

Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board.. They are especially suitable for switching

“Slave valve heating” has the value “1” if the room thermostat issues the command for heating via the object “Control value heating” (“Control value cooling” ≥ switch