Addendum  Solicitation 

Name  Alterations at Guy B. Love Towers C20013  Addendum 

Number  4  Date  12/02/19  This addendum answers questions raised about this solicitation.  To aid in readability, the questions are  in black, the answers are in bolded blue, and the answers follow immediately below. 

Q1  In addendum #‐3 that you sent out, you listed a new HW SET #‐3 for the Entrance Doors, you didn’t list  a Deadbolt with an IC Core or  2 Peep‐Sites. Is this an oversite or didn’t you want to list them? 

For your information:  if you list spring hinges  you don’t need a closer.  Likewise if you list a  closer you  don’t need  spring hinges‐you only need one or the other. 

Please see the attached Revised Door Hardware specifications.  

Q2  As I’m not sure, please tell me are the wood doors field finished or factory finished? 

Refer to revised Flush Wood Door specifications from Addendum 1. 

Q3  In response to change in addenda 2 on the possible location of ADA units between the (2) buildings, will  the scope of work regarding striping of the parking areas need to change as well for ADA parking at  building B? 

KCDC is not adding additional ADA units as noted in the previous addendum. 

Q4  The exterior scope of work is calling for the replacement of all of the caulking at the existing control  joints, is this to include the caulking around the HVAC/PTAC units as well? 

The exterior caulking is described on drawing sheet A‐3.1.   There is no caulking around the existing 

PTAC units to remain.  The manufacturer’s installation instructions for PTAC unit replacement shall be 

followed.   

(2)

Page 3 of 5   

Revised  SECTION 08 71 00: DOOR HARDWARE  PART 1  GENERAL 

1.01 SECTION INCLUDES 

A. Hardware for wood and hollow metal doors. 

B. Lock cylinders for doors that hardware is specified in other sections. 

1.02 REFERENCE STANDARDS 

A. ADA Standards ‐ Americans with Disabilities Act (ADA) Standards for Accessible Design; 2010. 

B. BHMA A156.2 ‐ American National Standard for Bored and Preassembled Locks & Latches; 

2017. 

C. BHMA A156.5 ‐ American National Standard for Cylinders and Input Devices for Locks; 2014. 

D. BHMA A156.18 ‐ American National Standard for Materials and Finishes; 2016. 

E. DHI (KSN) ‐ Keying Systems and Nomenclature; 1989. 

F. ICC A117.1 ‐ Accessible and Usable Buildings and Facilities; 2017. 

1.03 SUBMITTALS 

A. See Section 01 30 00 ‐ Administrative Requirements, for submittal procedures. 

B. Product Data: Manufacturer's catalog literature for each type of hardware, marked to clearly  show products to be furnished for this project, and includes construction details, material  descriptions, finishes, and dimensions and profiles of individual components. 

C. Manufacturer's Installation Instructions: Indicate special procedures and perimeter conditions  requiring special attention. 

D. Warranty: Submit manufacturer's warranty and ensure that forms have been completed in  Owner's name and registered with manufacturer. 

E. Maintenance Materials and Tools: Furnish the following for Owner's use in maintenance of  project. 

1. See Section 01 60 00 ‐ Product Requirements, for additional provisions. 

1.04 QUALITY ASSURANCE 

A. Installer Qualifications: Company specializing in performing work of the type specified for  commercial door hardware with at least three years of documented experience. 

1.05 DELIVERY, STORAGE, AND HANDLING 

A. Package hardware items individually; label and identify each package with door opening code  to match door hardware schedule. 

1.06 WARRANTY 

A. Warranty against defects in material and workmanship for period indicated, from Date of  Substantial Completion. 

1. Locksets and Cylinders: Three years, minimum. 

 

 

 

 

(3)

Page 4 of 5   

PART 2  PRODUCTS  2.01 HINGES 

1).   Hinges: BHMA A156.1. 

    1.     Manufacturers: Subject to compliance with requirements, provide products by one of the following: 

      a.   Stanley Commercial Hardware; a division of Stanley Security Solutions. 

      b.   H. B. Ives: an Allegion company. 

      c.   Hager Companies. 

2.02 DOOR LOCKS AND LEVERS 

1). Manufacturers listed in the hardware specification are as follows: 

1. Locks and Deadbolts: 

a. Manufacturer:  Stanley or Pamex  NO SUBSTITUTION 

b. Substitutions:  Model numbers and performance criteria for door hardware 

manufactured by Stanley and Pamex are listed to establish a standard of quality for  design, function, materials, workmanship, and appearance.  Specific materials and  product manufacturer(s) are specified to maintain standard building finishes and  materials across multiple facilities for ease of maintenance. Therefore KCDC will not  entertain requests for substitute products for this item. 

A. Cylindrical Locks: Meet or exceeds ANSI/BHMA A156.2 Series 4000, Grade 2. Locksets shall  be capable of receiving 6 or 7 pin, Small Format Interchangeable Cores, (SFIC). Provide lock  sets and latch sets with 2‐3/4 inch backset unless otherwise determined from existing door  preparations. Provide cylindrical lock sets and latch sets model “AL” series “Jupiter” (JUP)  design levers manufactured by Stanley or Pamex. 

B. Deadbolts: Meet or exceeds ANSI/BHMA A156.5. Deadbolts shall be capable of receiving 6  or 7 pin SFIC cores. Provide deadbolt locks with 2‐3/4 inch backset unless otherwise  indicated or determined from existing door preparations. Provide deadbolt locks,  manufactured by Stanley or Pamex. 

2). Locks shall be master keyed into new SFIC master key system. Supply 4 keys per lock, 4 master  keys and 4 Control keys total. Unless otherwise indicated. 

3). Finish: Lock sets, latch sets and deadbolt locks hardware shall be satin nickel finish (619). 

4). Provide hardware and finishes used in any individual system from the same manufacturer; no exceptions. 

5).  Provide hardware sets as follows: 

      Hardware Set #1: each to have: 

      Existing hardware to remain except the following: 

        1  Lever Passage    Stanley QCL230E or 

                Pamex Cambridge FL363 

        1  Deadlock    Stanley QDB281 or 

                Pamex FD7PA 

 

 

(4)

Page 5 of 5   

      Hardware Set #2: each to have: 

        3  Butt Hinges    Stanley FBB179 4.5” x 4.5” 

        1  Lever Privacy    Stanley QCL240E or 

                Pamex FL361C 

        2  Hinge pin stops  Don‐Jo 1512 (top and middle hinges) 

        3  Silencers    Ives SR64 

   

      Hardware Set #3: each to have: 

        3  Spring Hinges    Hager 1250 – 4.5” x 4.5” 

        1  Butt Hinge    Hager BB1279 – 4.5” x 4.5” (Top Only)          1  Lever Passage    Stanley QCL230E or 

                Pamex Cambridge FL363 

        1  Kick Plate    Hager 190S 8” x 2” LDW 

        1   Door Stop    Hager 236W 

        1  Set Smoke Seal  NGP 5050 x head and jambs          2  Door Viewers w/flap  Hager 1759 

 

2.03 SURFACE CLOSERS 

A. Surface Closers: BHMA A 156.4; rack‐and‐pinion hydraulic type with adjustable sweep and latch speeds  controlled by key‐operated valves and forged‐steel main arm. Comply with manufacturer's written  recommendations for size of door closers depending on size of door, exposure to weather, and  anticipated frequency of use. Provide factory‐sized closers, adjustable to meet field conditions and  requirements for opening force. 

1. Manufacturers: Subject to compliance with requirements, provide products by one of the  following: 

a. Falcon; an Allegion company. 

b. Stanley Commercial Hardware; a division of Stanley Security Solutions. 

c. Hager Companies. 

2.04 MECHANICAL STOPS AND HOLDERS 

A. Wall‐ and Floor‐Mounted Stops: BHMA A156.16; polished cast brass, bronze, or aluminum base metal. 

1. Manufacturers: Subject to compliance with requirements, provide products by one of the  following: 

a.    Hager Companies. 

b.        H. B. Ives; an Allegion company. 

c.       Trimco. 

B. Hinge Pin Stops: Provide hinge pin stops, where floor or wall mounted stops are not feasible. Provide 

(5)

Page 6 of 5   

as scheduled. 

   

2.05 DOOR GASKETING 

A.

Door Gasketing: BHMA A156.22; air leakage not to exceed 0.50 cfm per foot of crack length for  gasketing other than for smoke control, as tested according to ASTM E 283; with resilient or flexible  seal strips that are easily replaceable and readily available from stocks maintained by manufacturer.

 

1. Manufacturers: Subject to compliance with requirements, provide products by one of the  following:

 

a. National Guard Products, Inc. 

b. Pemko Manufacturing Co. 

c. Reese Enterprises, Inc. 

d. Zero International, Inc. 

2.06 FINISHES 

A. Finishes: Provide door hardware of same finish, unless otherwise indicated. 

1. Primary Finish: Satin nickel (619). 

 

2.07 KEYING MACHINE 

A.  Provide a Key Punch Pro‐Lok by the lock and deadbolt manufacturer. 

PART 3  EXECUTION  3.01 EXAMINATION 

A. Verify that doors and frames are ready to receive this work; labeled, fire‐rated doors and  frames are properly installed, and dimensions are as indicated on shop drawings. 

3.02 INSTALLATION 

A. Install hardware in accordance with manufacturer's instructions and applicable codes. 

3.03 ADJUSTING 

A. Adjust hardware for smooth operation. 

3.04 CLEANING 

A. Clean finished hardware in accordance with manufacturer's written instructions after final  adjustments have been made. 

B. Clean adjacent surfaces soiled by hardware installation. 

3.05 PROTECTION 

A. Do not permit adjacent work to damage hardware or finish. 

 

END OF SECTION 

(6)

REF. REF.

REF.

REF.

REF. REF.

REF. REF.

REF.

REF. Washer DryerWasher Dryer

REF. REF. REF.

REF.

REF.

REF.

REF. REF.

Tower A Tower B

5

4 8 10

23

A0.1 6 ADJACENT BOUNDARY

CLEAR

132" MIN. 60" MIN.

EXISTING SIDEWALK

ACCESSIBLE SIGNAGE

18' - 0"

2

2

Tower A

VAN ACCESSIBLE SPACE

5' - 0" 8' - 0" 8' - 0" 5' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 5' - 0" 8' - 0"

5' - 0" 8' - 0" 8' - 0" 5' - 8 3/4"

V.I.F 7' - 1"

50'-0" TRAVEL DISTANCE 50'-0" TR

AVEL DISTANCE

23' - 3"

50'-0" TRAVEL DISTANCE

V.I.F18' -0"

V.I.F18' - 0" V.I.F18' -0"

EXHIBITING 2" CURB

EXISTING PLANTERS - TYPICAL

EXISTING SIDEWALK

EXISTING SIDEWALK

EXISTING PARKING LOT EXISTING PARKING LOT

EXISTING PARKING LOT

8' - 0"

V.I.F

5' - 0" 8' - 0"

VAN ACCESSIBLE SPACE

VAN ACCESSIBLE SPACE

8' - 0" 5' - 0" 8' - 0"

V.I.F.

21' - 0"

ALTERNATE ACCESSIBLE SPACE 1

IF EXISTING LOT SPACE WIDTH IS LESS THAN DIMENSIONED, THEN SUBSTITUTE THE INDICATED ACCESSIBLE PARKING SPACE WITH 'ALTERNATE ACCESSIBLE SPACE 1'

A0.1

5 TYP

A0.1

4 TYP

NO PARKING

8' - 0" 5' - 0"

NO PARKING

40"

46" 39"

34"

12"

18" MIN.60"

6"60" MIN. WITH VAN ACCESSIBLE SIGNAGE

INCLUDED AT VAN ACCESSIBLE PARKING ONLY TENNESSEE HANDICAP PARKING SIGN, TN-41

© 2019 STUDIO FOUR DESIGN, inc. This drawing, its design detail and invention is the property of Studio Four Design, inc. and shall not be reproduced or usedfor any other project in whole or in part without written consent. This drawing is an instrument of service only and shall be returned to the Architect upon request.

No. Descripton Date Project Phase:

Issue Date:

Revisions

Job Number:

Date: File:Drawn By:Checked By:

414 Clinch Ave. Knoxville, TN 37902 p 865 523-5001 f 865 523-5003 studiofourdesign.com

12/2/2019 9:41:02 AM C:\Revit Local Files\19089_Love_Central_kfirkins.rvt

A0.1

Construction Documents

11.07.2019

Architectural Site Plan

19089.00

AuthorChecker

KCDC - R enovati on at Guy B. Love Tower 1171 A rms trong Av e Knox vi lle, TN 37917

1" = 60'-0"

Site Plan

1

1/4" = 1'-0"

Enlarged Plan - Van Access Parking

2

1/8" = 1'-0"

Enlarged Site Plan - Accessible Parking Layout

6

Parking Matrix

3

ACCESSIBLE SPACES BY CODE PROVIDED

Total Accessible Spaces *13 (1/6 to be Van Accessible)

*2018 IBC_1106.2.3: 1 Access Space / 1 Access Unit

10 Car accessible spaces 3 Van accessible spaces ACCESSIBLE UNITS

Total Accessible Units 13

1" = 1'-0"

Handicap Striping Standard

5

1" = 1'-0"

Parking Signage Standard

4

2 Addendum 03 12.02.2019

2

2

(7)
(8)

PANEL: A (EXISTING) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: EX

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: EXISTING ENTRY: TOP AIC: EXISTING MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 20 2 LIVING RM HEAT 1,200.0 5,200.0 - - 4,000.0 RANGE 2 50 2

3 | | 1,200.0 - - 5,200.0 4,000.0 | | 4

5 20 2 BEDROOM HEAT 1,200.0 2,700.0 - - 1,500.0 WTR HEATER 2 20 6

7 | | 1,200.0 - - 2,700.0 1,500.0 | | 8

9 20 2 BEDROOM HEAT 1,200.0 2,400.0 - - 1,200.0 KITCHEN HEAT 2 20 10

11 | | 1,200.0 - - 2,400.0 1,200.0 | | 12

13 20 1 LIGHTS & HEAT BATH 1,000.0 1,800.0 - - 800.0 FRIDGE 1 20 14

15 20 1 LIGHTS 500.0 - - 1,000.0 500.0 KITCHEN RECEPT 1 20 16

17 20 1 RECEPT IN LIVING RM 900.0 1,440.0 - - 540.0 BEDROOM RECEPT 1 20 18

19 20 1 KITCHEN RECEPT 500.0 - - 1,040.0 540.0 BEDROOM RECEPT 1 20 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

23 SPACE 0.0 - - 0.0 0.0 SPACE 24

THIS PANEL TYPICAL OF 2 BEDROOM UNITS TOTAL 13,540.0 - 12,340.0 VA

TOTAL CONNECTED 25,880.0 VA

PANEL: C (EXISTING) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: EX

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: EXISTING ENTRY: TOP AIC: EXISTING MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 50 2 RANGE 4,000.0 5,500.0 - - 1,500.0 WATER HEATER 2 20 2

3 | | 4,000.0 - - 5,500.0 1,500.0 | | 4

5 20 2 BEDROOM HEAT 1,200.0 2,400.0 - - 1,200.0 LIVING RM HEATER 2 20 6

7 | | 1,200.0 - - 2,400.0 1,200.0 | | 8

9 20 1 LIVING RM RECEPT 900.0 1,700.0 - - 800.0 LIGHTS 1 20 10

11 20 1 KITCHEN RECEPT 500.0 - - 1,700.0 1,200.0 LIGHTS & HEATER 1 20 12

13 20 1 FRIDGE 800.0 1,300.0 - - 500.0 EXISTING LOAD 1 20 14

15 20 1 SPARE 0.0 - - 0.0 0.0 SPARE 1 20 16

17 SPACE 0.0 0.0 - - 0.0 SPACE 18

19 SPACE 0.0 - - 0.0 0.0 SPACE 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

23 SPACE 0.0 - - 0.0 0.0 SPACE 24

THIS PANEL TYPICAL OF 1 BEDROOM UNITS TOTAL 10,900.0 - 9,600.0 VA

TOTAL CONNECTED 20,500.0 VA

PANEL: D (EXISTING) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: EX

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: EXISTING ENTRY: TOP AIC: EXISTING MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 30 2 LIVING RM HEATER 1,200.0 5,200.0 - - 4,000.0 RANGE 2 50 2

3 | | 1,200.0 - - 5,200.0 4,000.0 | | 4

5 20 1 LIGHTS 800.0 2,300.0 - - 1,500.0 WATER HEATER 2 30 6

7 20 1 BATH LIGHTS & HEAT 1,200.0 - - 2,700.0 1,500.0 | | 8

9 20 1 LIVING & BED HEAT 1,200.0 2,000.0 - - 800.0 FRIDGE 1 20 10

11 20 1 SPARE 0.0 - - 500.0 500.0 KITCHEN RECEPT 1 20 12

13 20 1 EXISTING LOAD 1,200.0 2,100.0 - - 900.0 LIVING RM RECEPT 1 20 14

15 20 2 BEDROOM HEATER 1,200.0 - - 1,200.0 0.0 SPACE 16

17 | | 1,200.0 1,200.0 - - 0.0 SPACE 18

19 SPACE 0.0 - - 0.0 0.0 SPACE 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

THIS PANEL TYPICAL OF 0 BEDROOM UNITS TOTAL 12,800.0 - 9,600.0 VA

TOTAL CONNECTED 22,400.0 VA

PANEL: E (EXISTING) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: EX

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: EXISTING ENTRY: TOP AIC: EXISTING MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 50 2 RANGE 4,000.0 5,200.0 - - 1,200.0 LIVING RM HEAT 2 20 2

3 | | 4,000.0 - - 5,200.0 1,200.0 | | 4

5 20 2 WATER HEATER 1,500.0 2,700.0 - - 1,200.0 BEDROOM HEATER 2 20 6

7 | | 1,500.0 - - 2,700.0 1,200.0 | | 8

9 20 1 KITCHEN RECEPT 500.0 1,300.0 - - 800.0 LIGHTS 1 20 10

11 20 1 BEDROOM RECEPT 900.0 - - 1,700.0 800.0 LIGHTS 1 20 12

13 20 1 FRIDGE 800.0 800.0 - - 0.0 SPARE 1 20 14

15 20 1 LIVING RM RECEPT 900.0 - - 900.0 0.0 SPARE 1 20 16

17 SPACE 0.0 0.0 - - 0.0 SPACE 18

19 SPACE 0.0 - - 0.0 0.0 SPACE 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

THIS PANEL TYPICAL OF 1 BEDROOM UNITS

BEHIND ELEVATORS TOTAL 10,000.0 - 10,500.0 VA

TOTAL CONNECTED 20,500.0 VA

PANEL: A (NEW) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: CU

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: #2 ENTRY: TOP AIC: 10,000 MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 20 2 LIVING RM HEAT 1,200.0 5,200.0 - - 4,000.0 RANGE 2 50 2

3 | | 1,200.0 - - 5,200.0 4,000.0 | | 4

5 20 2 BEDROOM HEAT 1,200.0 2,700.0 - - 1,500.0 WTR HEATER 2 20 6

7 | | 1,200.0 - - 2,700.0 1,500.0 | | 8

9 20 2 BEDROOM HEAT 1,200.0 2,400.0 - - 1,200.0 KITCHEN HEAT 2 20 10

11 | | 1,200.0 - - 2,400.0 1,200.0 | | 12

13 20AF 1 LIGHTS & HEAT BATH 1,000.0 1,800.0 - - 800.0 FRIDGE 1 20AG 14

15 20AF 1 LIGHTS 500.0 - - 1,000.0 500.0 KITCHEN RECEPT 1 20AG 16

17 20AF 1 RECEPT IN LIVING RM 900.0 1,440.0 - - 540.0 BEDROOM RECEPT 1 20AF 18

19 20AG 1 KITCHEN RECEPT 500.0 - - 1,040.0 540.0 BEDROOM RECEPT 1 20AF 20

21 20AG 1 SPARE 0.0 0.0 - - 0.0 SPARE 1 20AF 22

23 SPACE 0.0 - - 180.0 180.0 BATHROOM RECEPT 1 20 24

THIS PANEL TYPICAL OF 2 BEDROOM UNITS;

PROVIDE 4" BY 14" CABINET, SIMILAR TO SQUARE

D QO. "LOAD CENTER" SERIES. TOTAL 13,540.0 - 12,520.0 VA

AF=AFCI TYPE; AG=AF/GF COMB.TYPE,

PROVIDE LOCK-ON DEVICE FOR SMOKE ALARM CKT. FIELD VERIFY WATER HEATER BREAKER RATING PER UNIT PRIOR TO ORDERING PANEL AS BREAKER SIZES VARY.

TOTAL CONNECTED 26,060.0 VA

PANEL: C (NEW) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: CU

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: #2 ENTRY: TOP AIC: 10,000 MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 50 2 RANGE 4,000.0 5,500.0 - - 1,500.0 WATER HEATER 2 20 2

3 | | 4,000.0 - - 5,500.0 1,500.0 | | 4

5 20 2 BEDROOM HEAT 1,200.0 2,400.0 - - 1,200.0 LIVING RM HEATER 2 20 6

7 | | 1,200.0 - - 2,400.0 1,200.0 | | 8

9 20AF 1 LIVING RM RECEPT 900.0 1,700.0 - - 800.0 LIGHTS 1 20AF 10

11 20AG 1 KITCHEN RECEPT 500.0 - - 1,700.0 1,200.0 LIGHTS & HEATER 1 20AF 12

13 20AG 1 FRIDGE 800.0 1,300.0 - - 500.0 EXISTING LOAD 1 20AF 14

15 20AG 1 KITCHEN RECEPT 500.0 - - 500.0 0.0 SPARE 1 20AF 16

17 20AG 1 SPARE 0.0 180.0 - - 180.0 BATHROOM RECEPT 1 20 18

19 SPACE 0.0 - - 0.0 0.0 SPACE 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

23 SPACE 0.0 - - 0.0 0.0 SPACE 24

THIS PANEL TYPICAL OF 1 BEDROOM UNITS;

PROVIDE 4" BY 14" CABINET, SIMILAR TO SQUARE

D QO. "LOAD CENTER" SERIES. TOTAL 11,080.0 - 10,100.0 VA

AF=AFCI TYPE; AG=AF/GF COMB.TYPE,

PROVIDE LOCK-ON DEVICE FOR SMOKE ALARM CKT. FIELD VERIFY WATER HEATER BREAKER RATING PER UNIT PRIOR TO ORDERING PANEL AS BREAKER SIZES VARY.

TOTAL CONNECTED 21,180.0 VA

PANEL: D (NEW) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: CU

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: #2 ENTRY: TOP AIC: 10,000 MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 20 2 LIVING RM HEATER 2,000.0 6,000.0 - - 4,000.0 RANGE 2 50 2

3 | | 2,000.0 - - 6,000.0 4,000.0 | | 4

5 20AF 1 LIGHTS 800.0 2,300.0 - - 1,500.0 WATER HEATER 2 30 6

7 20AF 1 BATH LIGHTS & HEAT 1,200.0 - - 2,700.0 1,500.0 | | 8

9 20AF 1 LIVING & BED HEAT 1,200.0 2,000.0 - - 800.0 FRIDGE 1 20AG 10

11 20AG 1 SPARE 0.0 - - 500.0 500.0 KITCHEN RECEPT 1 20AG 12

13 20AF 1 EXISTING LOAD 1,200.0 2,100.0 - - 900.0 LIVING RM RECEPT 1 20AF 14

15 20 1 BATHROOM RECEPT 180.0 - - 680.0 500.0 KITCHEN RECEPT 1 20AG 16

17 20 2 BEDROOM HEATER 1,200.0 1,200.0 - - 0.0 SPACE 18

19 | | 1,200.0 - - 1,200.0 0.0 SPACE 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

THIS PANEL TYPICAL OF 0 BEDROOM UNITS;

PROVIDE 4" BY 14" CABINET, SIMILAR TO SQUARE D QO. "LOAD CENTER" SERIES.

TOTAL 13,600.0 - 11,080.0 VA

AF=AFCI TYPE; AG=AF/GF COMB.TYPE,

PROVIDE LOCK-ON DEVICE FOR SMOKE ALARM CKT. FIELD VERIFY WATER HEATER BREAKER RATING PER UNIT PRIOR TO ORDERING PANEL AS BREAKER SIZES VARY.

TOTAL CONNECTED 24,680.0 VA

PANEL: E (NEW) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: CU

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: #2 ENTRY: TOP AIC: 10,000 MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 50 2 RANGE 4,000.0 5,200.0 - - 1,200.0 LIVING RM HEAT 2 20 2

3 | | 4,000.0 - - 5,200.0 1,200.0 | | 4

5 20 2 WATER HEATER 1,500.0 2,700.0 - - 1,200.0 BEDROOM HEATER 2 20 6

7 | | 1,500.0 - - 2,700.0 1,200.0 | | 8

9 20AG 1 KITCHEN RECEPT 500.0 1,300.0 - - 800.0 LIGHTS 1 20AF 10

11 20AF 1 BEDROOM RECEPT 900.0 - - 1,700.0 800.0 LIGHTS 1 20AF 12

13 20AG 1 FRIDGE 800.0 800.0 - - 0.0 SPARE 1 20AG 14

15 20AF 1 LIVING RM RECEPT 900.0 - - 900.0 0.0 SPARE 1 20AF 16

17 SPACE 0.0 180.0 - - 180.0 BATHROOM RECEPT 1 20 18

19 SPACE 0.0 - - 0.0 0.0 SPACE 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

THIS PANEL TYPICAL OF 1 BEDROOM UNITS BEHIND ELEVATORS; PROVIDE 4" BY 14"

CABINET, SIMILAR TO SQUARE D QO. "LOAD

CENTER" SERIES. TOTAL 10,180.0 - 10,500.0 VA

AF=AFCI TYPE; AG=AF/GF COMB.TYPE,

PROVIDE LOCK-ON DEVICE FOR SMOKE ALARM CKT. FIELD VERIFY WATER HEATER BREAKER RATING PER UNIT PRIOR TO ORDERING PANEL AS BREAKER SIZES VARY.

TOTAL CONNECTED 20,680.0 VA

PANEL: G VOLTAGE: 120/208 PHASE: 3 WIRE: 4 BUS: CU

BUS RATING: 60 AMP MAIN: NO-MLO ENCLOSURE: NEMA 1

LUGS/PHASE: #6 ENTRY: TOP AIC: 22,000 MOUNTING: SURFACE

# AMP POLE DESCRIPTION LOAD A B C LOAD DESCRIPTION POLE AMP #

1 30 2 JACKET HEATER 1,500.0 3,000.0 - - 1,500.0 DAY TANK PUMP 1 20 2

3 | | 1,500.0 - 1,500.0 - 0.0 SPACE 4

5 20 1 BATTERY CHARGER 1,000.0 - - 1,000.0 0.0 SPACE 6

7 SPACE 0.0 0.0 - - 0.0 SPACE 8

9 SPACE 0.0 - 0.0 - 0.0 SPACE 10

11 SPACE 0.0 - - 0.0 0.0 SPACE 12

13 SPACE 0.0 0.0 - - 0.0 SPACE 14

15 SPACE 0.0 - 0.0 - 0.0 SPACE 16

17 SPACE 0.0 - - 0.0 0.0 SPACE 18

19 SPACE 0.0 0.0 - - 0.0 SPACE 20

21 SPACE 0.0 - 0.0 - 0.0 SPACE 22

23 SPACE 0.0 - - 0.0 0.0 SPACE 24

25 SPACE 0.0 0.0 - - 0.0 SPACE 26

27 SPACE 0.0 - 0.0 - 0.0 SPACE 28

29 SPACE 0.0 - - 0.0 0.0 SPACE 30

TOTAL 3,000.0 1,500.0 1,000.0 VA

TOTAL CONNECTED 5,500.0 VA

PANEL: B (EXISTING) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: EX

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: EXISTING ENTRY: TOP AIC: EXISTING MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 30 2 KITCHEN HEAT 1,500.0 5,500.0 - - 4,000.0 RANGE 2 50 2

3 | | 1,500.0 - - 5,500.0 4,000.0 | | 4

5 20 2 BEDROOM HEAT 1,200.0 2,700.0 - - 1,500.0 WTR HEATER 2 20 6

7 | | 1,200.0 - - 2,700.0 1,500.0 | | 8

9 20 2 BEDROOM HEAT 1,200.0 2,400.0 - - 1,200.0 BEDROOM HEAT 2 20 10

11 | | 1,200.0 - - 2,400.0 1,200.0 | | 12

13 20 1 KITCHEN RECEPT 500.0 1,580.0 - - 1,080.0 BEDROOM RECEPT 1 20 14

15 20 1 LIGHTS 500.0 - - 1,000.0 500.0 KITCHEN RECEPT 1 20 16

17 20 1 LIGHTS 500.0 1,500.0 - - 1,000.0 BEDROOM RECEPT 1 20 18

19 20 1 FRIDGE 800.0 - - 1,800.0 1,000.0 KITCHEN & BED RECEPT 1 20 20

21 SPACE 0.0 0.0 - - 0.0 SPACE 22

23 SPACE 0.0 - - 0.0 0.0 SPACE 24

THIS PANEL TYPICAL OF 3 BEDROOM UNIT TOTAL 13,680.0 - 13,400.0 VA

TOTAL CONNECTED 27,080.0 VA

PANEL: B (NEW) VOLTAGE: 120/240 PHASE: 1 WIRE: 3 BUS: CU

BUS RATING: 100 AMP MAIN: YES - 100A/2P ENCLOSURE: NEMA 1

LUGS/PHASE: #2 ENTRY: TOP AIC: 10,000 MOUNTING: RECESSED

# AMP POLE DESCRIPTION LOAD A - B LOAD DESCRIPTION POLE AMP #

1 30 2 KITCHEN HEAT 1,500.0 5,500.0 - - 4,000.0 RANGE 2 50 2

3 | | 1,500.0 - - 5,500.0 4,000.0 | | 4

5 20 2 BEDROOM HEAT 1,200.0 2,700.0 - - 1,500.0 WTR HEATER 2 20 6

7 | | 1,200.0 - - 2,700.0 1,500.0 | | 8

9 20 2 BEDROOM HEAT 1,200.0 2,400.0 - - 1,200.0 BEDROOM HEAT 2 20 10

11 | | 1,200.0 - - 2,400.0 1,200.0 | | 12

13 20AG 1 KITCHEN RECEPT 500.0 1,580.0 - - 1,080.0 BEDROOM RECEPT 1 20AF 14

15 20AF 1 LIGHTS 500.0 - - 1,000.0 500.0 KITCHEN RECEPT 1 20AG 16

17 20AF 1 LIGHTS 500.0 1,500.0 - - 1,000.0 BEDROOM RECEPT 1 20AF 18

19 20AG 1 FRIDGE 800.0 - - 1,340.0 540.0 BEDROOM RECEPT 1 20AF 20

21 20AG 1 KITCHEN RECEPT 500.0 680.0 - - 180.0 BATHROOM RECEPT 1 20 22

23 20AF 1 SPARE 0.0 - - 0.0 0.0 SPARE 1 20 24

THIS PANEL TYPICAL OF 3 BEDROOM UNIT;

PROVIDE 4" BY 14" CABINET, SIMILAR TO SQUARE D QO. "LOAD CENTER" SERIES.

TOTAL 14,360.0 - 12,940.0 VA AF=AFCI TYPE; AG=AF/GF COMB.TYPE,

PROVIDE LOCK-ON DEVICE FOR SMOKE ALARM CKT.

TOTAL CONNECTED 27,300.0 VA

© 2019 STUDIO FOUR DESIGN, inc. This drawing, its design detail and invention is the property of Studio Four Design, inc. and shall not be reproduced or usedfor any other project in whole or in part without written consent. This drawing is an instrument of service only and shall be returned to the Architect upon request.

No. Descripton Date Project Phase:

Issue Date:

Revisions

Job Number:

Date: File:Drawn By:Checked By:

414 Clinch Ave. Knoxville, TN 37902 p 865 523-5001 f 865 523-5003 studiofourdesign.com

11/26/2019 5:19:13 PM C:\Users\jcleveland\Documents\SFD910-LOVE TOWERS-MEP-R18_jcleveland@facilitysystems.org.rvt

E0.2

Construction Documents

11/07/19

ELECTRICAL PANELBOARD SCHEDULES

19089.00

AuthorChecker

KCDC Guy B. Love Tower Renovation 1171 A rms trong A ve Knoxville , TN 3 7917

Renovation

1 ADDENDUM 3 12/02/19 1

1

(9)

FIRST FLOOR EXTERIOR INTERIOR

EXISTING PANELBOARD

"A"

120/240V 1⌀

SECOND FLOOR

NEW PANELBOARD

"A"

120/240V 1⌀

EXISTING PANELBOARD

"C"

120/240V 1⌀

NEW PANELBOARD

"C"

120/240V 1⌀

EXISTING PANELBOARD

"D"

120/240V 1⌀

NEW PANELBOARD

"D"

120/240V 1⌀

EXISTING PANELBOARD

"E"

120/240V 1⌀

NEW PANELBOARD

"E"

120/240V 1⌀

BASEMENT

EXISTING PANELBOARD

"A"

120/240V 1⌀

NEW PANELBOARD

"A"

120/240V 1⌀

EXISTING PANELBOARD

"C"

120/240V 1⌀

NEW PANELBOARD

"C"

120/240V 1⌀

EXISTING PANELBOARD

"D"

120/240V 1⌀

NEW PANELBOARD

"D"

120/240V 1⌀

EXISTING PANELBOARD

"E"

120/240V 1⌀

NEW PANELBOARD

"E"

120/240V 1⌀

EXISTING PANELBOARD

"A"

120/240V 1⌀

NEW PANELBOARD

"A"

120/240V 1⌀

EXISTING PANELBOARD

"C"

120/240V 1⌀

NEW PANELBOARD

"C"

120/240V 1⌀

EXISTING PANELBOARD

"D"

120/240V 1⌀

NEW PANELBOARD

"D"

120/240V 1⌀

EXISTING PANELBOARD

"E"

120/240V 1⌀

NEW PANELBOARD

"E"

120/240V 1⌀

EXISTING PANELBOARD

"A"

120/240V 1⌀

NEW PANELBOARD

"A"

120/240V 1⌀

EXISTING PANELBOARD

"C"

120/240V 1⌀

NEW PANELBOARD

"C"

120/240V 1⌀

EXISTING PANELBOARD

"D"

120/240V 1⌀

NEW PANELBOARD

"D"

120/240V 1⌀

EXISTING PANELBOARD

"E"

120/240V 1⌀

NEW PANELBOARD

"E"

120/240V 1⌀

EXISTING PANELBOARD

"A"

120/240V 1⌀

NEW PANELBOARD

"A"

120/240V 1⌀

EXISTING PANELBOARD

"C"

120/240V 1⌀

NEW PANELBOARD

"C"

120/240V 1⌀

EXISTING PANELBOARD

"D"

120/240V 1⌀

NEW PANELBOARD

"D"

120/240V 1⌀

EXISTING PANELBOARD

"E"

120/240V 1⌀

NEW PANELBOARD

"E"

120/240V 1⌀

EXISTING PANELBOARD

"A"

120/240V 1⌀

NEW PANELBOARD

"A"

120/240V 1⌀

EXISTING PANELBOARD

"C"

120/240V 1⌀

NEW PANELBOARD

"C"

120/240V 1⌀

EXISTING PANELBOARD

"D"

120/240V 1⌀

NEW PANELBOARD

"D"

120/240V 1⌀

EXISTING PANELBOARD

"E"

120/240V 1⌀

NEW PANELBOARD

"E"

120/240V 1⌀

EXISTING PANELBOARD

"A"

120/240V 1⌀

NEW PANELBOARD

"A"

120/240V 1⌀

EXISTING PANELBOARD

"C"

120/240V 1⌀

NEW PANELBOARD

"C"

120/240V 1⌀

EXISTING PANELBOARD

"D"

120/240V 1⌀

NEW PANELBOARD

"D"

120/240V 1⌀

EXISTING PANELBOARD

"E"

120/240V 1⌀

NEW PANELBOARD

"E"

120/240V 1⌀

THIRD FLOOR FOURTH FLOOR FIFTH FLOOR SIXTH FLOOR SEVENTH FLOOR

EXISTING 120/208V 3⌀, 4W UNIT - SUBSTATION/SWBD

TO REMAIN

2 2

2 2 2 2

2 2 2 2

2 2 2 2

2 2 2 2

2 2 2 2

2 2 2 2

3 , TYPICAL

4 , TYPICAL

1 , TYPICAL EXISTING TAP BOX TO

REMAIN IN CHASE, TYPICAL

REFERENCE NOTES:

1. EXISTING PANELBOARD CONVERTED TO PULLBOX, TYPICAL OF ALL APARTMENTS. SEE ENLARGED APARTMENT PLANS FOR MORE INFORMATION.

PROVIDE CUSTOM BLANK COVER; INSTALL INSULATED POLARIS TAPS TO EXTEND FEEDER; SET GROUND BAR.

2. EXISTING 3"C, 4#250MCM TO REMAIN.

3. EXISTING 1-1/4"C, 3#2 TO REMAIN, TYPICAL OF ALL APARTMENT PANEL TAPS.

4. 1-1/4"C, 3#2, 1#8G, TYPICAL OF ALL APARTMENT PANEL FEEDER EXTENSIONS TO NEW PANEL LOCATION.

5. EXISTING2-1/2"C; 4#3/0 TO REMAIN.

6. THIS WORK UNIQUE TO BUILDING A.

7. 1-1/4"C; 3#2, 1#6G.

8. EXISTING 1-1/4"C 3#2 TO BE REMOVED.

PARTIAL ELECTRICAL RISER DIAGRAM NOT TO SCALE

GENERAL NOTES:

1. THIS PARTIAL RISER DIAGRAM ONLY ILLUSTRATES EACH APARTMENT TYPE PER FLOOR. THIS DOES NOT REPRESENT TOTAL QUANTITY OF UNITS ON EACH FLOOR TO BE MODIFIED. THIS ILLUSTRATION IS TYPICAL OF BOTH BUILDING A & B. SEE OVERALL FLOOR PLANS FOR TOTAL QUANTITIES OF PANELS TO BE REPLACED.

EXISTING PANELBOARD

"B"

120/240V 1⌀

NEW PANELBOARD

"B"

120/240V 1⌀

EXISTING PANELBOARD

"M"

6 7

6 8 6 7

6 7

6

6 6

NEW 100A/2P 120/240V FUSED DISCONNECT

5 6

1

1

© 2019 STUDIO FOUR DESIGN, inc. This drawing, its design detail and invention is the property of Studio Four Design, inc. and shall not be reproduced or usedfor any other project in whole or in part without written consent. This drawing is an instrument of service only and shall be returned to the Architect upon request.

No. Descripton Date Project Phase:

Issue Date:

Revisions

Job Number:

Date: File:Drawn By:Checked By:

414 Clinch Ave. Knoxville, TN 37902 p 865 523-5001 f 865 523-5003 studiofourdesign.com

11/26/2019 5:19:17 PM C:\Users\jcleveland\Documents\SFD910-LOVE TOWERS-MEP-R18_jcleveland@facilitysystems.org.rvt

E0.3

Construction Documents

11/07/19

PARTIAL ELECTRICAL RISER DIAGRAM

19089.00

AuthorChecker

KCDC Guy B. Love Tower Renovation 1171 A rms trong A ve Knoxville , TN 3 7917

Renovation

1 ADDENDUM 3 12/02/19

(10)

REF. Washer DryerWasher Dryer

WH REF.

4

LOC LOC

IP MON

LOC

3 6

EXISTING DATA RACK LOCATION TO REMAIN Y

(EXISTING)

X (EXISTING)

7

BB BB-SUBPANEL

(EXISTING) (EXISTING)

3 E2.0

"TTB"

8

SOCIAL HALL

F "FACP"

RM

5

E2.0 1

M NEW 100A

DISCONNECT TO FEED PANEL "B", SEE RISER.

(EXISTING) 1

LOC

LOC

LOC LOC

LOC

LOC

IP

(TYPICAL) 1

5 2

Z (EXISTING) 3

E2.0 1

E2.0

2 E2.0

F"FACP"

RM

CMU Wall - New 1 Hour Fire Rated Wall

8" CMU WALL - TO MATCH EXISTING

© 2019 STUDIO FOUR DESIGN, inc. This drawing, its design detail and invention is the property of Studio Four Design, inc. and shall not be reproduced or usedfor any other project in whole or in part without written consent. This drawing is an instrument of service only and shall be returned to the Architect upon request.

No. Descripton Date Project Phase:

Issue Date:

Revisions

Job Number:

Date: File:Drawn By:Checked By:

414 Clinch Ave. Knoxville, TN 37902 p 865 523-5001 f 865 523-5003 studiofourdesign.com

11/26/2019 5:19:30 PM C:\Users\jcleveland\Documents\SFD910-LOVE TOWERS-MEP-R18_jcleveland@facilitysystems.org.rvt

E1.1

Construction Documents

11/07/19

FIRST FLOOR

ELECTRICAL PLANS

19089.00

AuthorChecker

KCDC Guy B. Love Tower Renovation 1171 A rms trong A ve Knoxville , TN 3 7917

Renovation

1/8" = 1'-0"

1 First Floor Electrical Plan - Building A

1/8" = 1'-0"

2 First Floor Electrical Plan - Building B

REFERENCE NOTES:

1. PROVIDE NEW SURFACE MOUNTED DUPLEX RECEPTACLE AT EACH LOCATOR LOCATION. PROVIDE 3/4"C; 2#12, 1#12G FROM LOCATOR RECEPTACLE TO APARTMENT PANELBOARD. PROVIDE NEW 20A/1 POLE BREAKER WITH LOCK- ON DEVICE IN CORRESPONDING PANELBOARD FOR LOCATOR POWER. ALL INDOOR CONDUIT TO BE SURFACE MOUNTED WIREMOLD WHERE CONDUIT CANNOT BE CONCEALED. PATCH CEILINGS/WALLS AS NECESSARY WHERE CONDUITS CAN BE CONCEALED.

2. PROVIDE CAT6 CABLE IN 3/4"C FROM EMERGENCY CALL SYSTEM HUB TO EXISTING NETWORK RACK IN BASEMENT MAINTENANCE SHOP. FIELD VERIFY EXACT DATA RACK LOCATION.

3. PROVIDE SURFACE MOUNTED DUPLEX RECEPTACLE BETWEEN HUB AND MONITOR. PROVIDE 3/4"C; 2#12, 1#12G FROM DUPLEX TO NEW 20A/1 POLE BREAKER IN "BB" SUBPANEL.

4. PROVIDE CAT6 CABLE IN 3/4"C FROM EMERGENCY CALL SYSTEM HUB TO EXISTING NETWORK RACK IN MAIN OFFICE. FIELD VERIFY EXACT DATA RACK LOCATION.

5. PROVIDE NEW SURFACE MOUNTED DUPLEX RECEPTACLE AT INDICATOR PANEL LOCATION. PROVIDE 3/4"C; 2#12, 1#12G FROM INDICATOR PANEL RECEPTACLE TO PANEL "Z". PROVIDE SPARE 20A/1 POLE BREAKER IN PANEL

"Z" WITH LOCK-ON DEVICE FOR INDICATOR PANEL POWER. ALL INDOOR CONDUIT TO BE SURFACE MOUNTED WIREMOLD WHERE CONDUIT CANNOT BE CONCEALED. PATCH CEILINGS/WALLS AS NECESSARY WHERE CONDUITS CAN BE CONCEALED.

6. PROVIDE NEW SURFACE MOUNTED DUPLEX RECEPTACLE AT EACH LOCATOR LOCATION. PROVIDE 3/4"C; 2#12, 1#12G FROM LOCATOR RECEPTACLE TO "BB"

SUBPANEL. PROVIDE NEW 20A/1 POLE BREAKER WITH LOCK-ON DEVICE IN CORRESPONDING PANELBOARD FOR LOCATOR POWER. ALL INDOOR CONDUIT TO BE SURFACE MOUNTED WIREMOLD WHERE CONDUIT CANNOT BE CONCEALED. PATCH CEILINGS/WALLS AS NECESSARY WHERE CONDUITS CAN BE CONCEALED.

7. PROVIDE NEW SURFACE MOUNTED DUPLEX RECEPTACLE AT LOCATOR LOCATION. PROVIDE 3/4"C; 2#12, 1#12G FROM LOCATOR RECEPTACLE TO "X"

PANEL. PROVIDE NEW 20A/1 POLE BREAKER WITH LOCK-ON DEVICE IN CORRESPONDING PANELBOARD FOR LOCATOR POWER.

8. EXISTING TTB TO REMAIN. LOCATION FOR NEW ADA UNIT TV RG6 TERMINATIONS.

1 ADDENDUM 3 12/02/19

(11)

REF.

WH

TV

SS

SS

REF.

WH

TV TV

SS

REF.

WH

TV

TV

SS

REF.

WH

TV

TV

SS

TV

TV TV

RM

SA

D

RP

6-20R RM

GF RM

RM

RM

RM

RM RM

RM

RM

RM RM

RM RM

RM

RM

S

S

RM GF

RM

S

PC PC

D 2

RM

RM

RM

D-15 1

RM

H RM 4

7

C

RM

SA

RP

SA

6-20R RM

6-20R RM

GF RM

RM RM

RM RM

RM

GF RM RM

RM RM

RM

RM

S SS S S

S

RM

RM

RM

RM

RM RM RM RM

33

H

PC PC

C

RM

RM RM

RM RM

RM

RM

2 1

C-18 BEDROOM

LIVING AREA

CLOSET

BATH KITCHEN

CLOSET

RM

4 7

SA

RV

A

RM RM RM

RM

RM

RM

RM RM

RM

RM

RM RM

RM

RM RM

RM RM

6-20R RM

6-20R RM

GF RM RM

S S

S S S

S

S

S

RM

RM

RM

RM

RM RM

RM

RM

RM

GF RM

RM

RM

H

SA

SA

SA

PC

PC PC

RP

3

RM RM RM

RM RM

RM RM

RM RM

1 A-24

6

4 5

6 7

E

6-20R

RM 6-20R

RM

RM RM

RM RM

RM RM

RM

RM

RM RM

RM RM

RM

RM RM

RM

RM RM

RM

RM

RM

RMGF

S

S S SS S

S

RM

SA

RV

H SA SA

E

PC

PC

RM

RM

RM

2

RM RM

RM

RM RM

1 E-18

RM

5

RM

4 7

CMU Wall - New 1 Hour Fire Rated Wall

8" CMU WALL - TO MATCH EXISTING 8

2

9

B B

6

6-20R RM

6-20R RM 6-20R

RM

GF RM

RM RM

RM

RM RM

RM

RM RM

H

RM

RM

1 B-22

S

3

S S S S

S

3

S

S

RM RM

RM

RM RM

RM

RM RM

RM RM RM RM RM

RM RM

RM RM RM

RM RM

RM RM RM

RM

RM RM

RM RM RM

RM RM RM

RM RM

RM RM

RM RM RM

RM

SA

RM

HS

RM

RM

© 2019 STUDIO FOUR DESIGN, inc. This drawing, its design detail and invention is the property of Studio Four Design, inc. and shall not be reproduced or usedfor any other project in whole or in part without written consent. This drawing is an instrument of service only and shall be returned to the Architect upon request.

No. Descripton Date Project Phase:

Issue Date:

Revisions

Job Number:

Date: File:Drawn By:Checked By:

414 Clinch Ave. Knoxville, TN 37902 p 865 523-5001 f 865 523-5003 studiofourdesign.com

11/26/2019 5:19:35 PM C:\Users\jcleveland\Documents\SFD910-LOVE TOWERS-MEP-R18_jcleveland@facilitysystems.org.rvt

E2.0

Construction Documents

11/07/19

TYPICAL ENLARGED ELECTRICAL FLOOR PLANS

19089.00

AuthorChecker

KCDC Guy B. Love Tower Renovation 1171 A rms trong A ve Knoxville , TN 3 7917

Renovation

1/4" = 1'-0"

1 Typical Enlarged Floor Plan - Type 0

1/4" = 1'-0"

2 Typical Enlarged Floor Plan - Type 1

1/4" = 1'-0"

3 Typical Enlarged Floor Plan - Type 2

REFERENCE NOTES:

1. 3/4"C; 2#12, 1#12G TO CORRESPONDING PANEL TO SEPERATE BATHROOM RECEPTACLE CIRCUIT FROM OTHER LOADS PER NEC CODE.

2. REMOVE EXISTING PANEL INTERIOR COMPONENTS AND PROVIDE BLANK COVER FOR PANEL. SPLICE AND EXTEND ALL WIRING FROM EXISTING PANEL LOCATION TO NEW PANEL LOCATION. REWIRE BRANCH CIRCUITS AS NECESSARY TO ELIMINATE SHARED NEUTRALS. ASSUME 3 CIRCUITS WITH SHARED NEUTRAL CKTS. PROVIDE NEW GROUND WIRES WHERE NOT PRESENT AND CONDUIT DOESN'T PROVIDE ADEQUATE GROUND PATH.

3. REPLACE EXISTING PANEL WITH NEW PANEL ROTATED 90° TO WHERE PANEL DOOR OPENS NORMALLY. REWIRE BRANCH CIRCUITS AS NECESSARY TO ELIMINATE SHARED NEUTRALS. ASSUME 3 CIRCUITS WITH SHARED NEUTRAL CKTS. PROVIDE NEW GROUND WIRES WHERE NOT PRESENT AND CONDUIT DOESN'T PROVIDE ADEQUATE GROUND PATH.

4. WATER HEATER CONNECTION TO REMAIN. DISCONNECT EXISTING WATER HEATER AND RECONNECT WATER HEATER UPON COMPLETION OF CABINET INSTALLATION.

5. CONNECT TO SAME UNSWITCHED LIGHTING CIRCUIT AS EXISTING SMOKE ALARM TO BE REMOVED.

6. AIR TRANSFER FAN TO REMAIN.

7. THE WORK SHOWN ON THIS ENLARGED PLAN IS TYPICAL FOR ALL UNITS OF THIS TYPE IN THE FACILITY.

8. EXISTING WATER HEATER CONNECTION TO REMAIN.

9. 3/4"C; 2#12, 1#12G TO B-21 TO SEPERATE KITCHEN LOADS FROM OTHER LOADS ON EXISTING PANEL "B" CKT. 20.

GENERAL NOTES:

1. ALL NEW CONDUITS WITHIN DWELLING UNITS TO BE SURFACE MOUNTED WIREMOLD WHERE CONDUIT CANNOT BE CONCEALED. PATCH

CEILINGS/WALLS AS NECESSARY WHERE CONDUITS CAN BE CONCEALED.

2. ENSURE ALL SMOKE ALARMS ARE CONNECTED TO UNSWITCHED CIRCUIT.

1/4" = 1'-0"

4 Typical Enlarged Foor Plan - 1 BR Behind Elevator

1 ADDENDUM 3 12/02/19

1/4" = 1'-0"

5 Enlarged Floor Plan - 3 BR

1

1

(12)

TV SS

REF. REF.

WH WH

SS S

TV

SS

SS

TV TV

REF.

WH

S

WH

SS

TV SS

TV TV S

RV

RV RV

RV RV RV

S

RV

RV

RV

RM

RM

RM

RM

RM RV RV

RV RV

H RV

RV

RP

1

6-20R

SA

RP

RM D

c

c

a

a

S

RVb

b

2

8 15cd

GF 15cd

RM

RM

RM RM

RM6-20R

GF GF

SA S

D

GF 16 RM 2,4 12

12

3

S

a

B

a

16

14

B

b

14 1,3

14 14

S

PC

b 10

D

c 15

c

PC

4 9

8

10

NEW CEILING MOUNTED HEATER

7 14

1

S

S SS SS

3a3a

RM

RM

RM

H

SA

RP RV RV

RV RV

RV RV

RV

RV

RV RM GF

RMGF

RM

RM

RM

RM

RM

RM RM

6-20R 6-20R

RM RM

RM RM

RM RM RM

1

RV

C

RP

c c

b

a

6

RM

b

8

15cd

15cd

SA

RM

RM RM

S

RM GF

RMGF

RM

RM

RM

RM

RM

RM RM

6-20R 6-20R

RM RM

RM RM

RM RM

PC

RM

GF

S

SS S

3a

3a

C

15 11 GF

11

6

a

1,3

13

15

9

9

6,8

9 b

RM

SA

9

14

14

5,7

14 14

PC

b 9

c

D

c 18

9

8

NEW CEILING MOUNTED HEATER

12

CMU Wall - New 1 Hour Fire Rated Wall

8" CMU WALL - TO MATCH EXISTING

© 2019 STUDIO FOUR DESIGN, inc. This drawing, its design detail and invention is the property of Studio Four Design, inc. and shall not be reproduced or usedfor any other project in whole or in part without written consent. This drawing is an instrument of service only and shall be returned to the Architect upon request.

No. Descripton Date Project Phase:

Issue Date:

Revisions

Job Number:

Date: File:Drawn By:Checked By:

414 Clinch Ave. Knoxville, TN 37902 p 865 523-5001 f 865 523-5003 studiofourdesign.com

11/26/2019 5:19:43 PM C:\Users\jcleveland\Documents\SFD910-LOVE TOWERS-MEP-R18_jcleveland@facilitysystems.org.rvt

E2.1

Construction Documents

11/07/19

ADA TYPE 0 & ADA TYPE 1 DEMO AND NEW

WORK ELECT. PLANS 19089.00

AuthorChecker

KCDC Guy B. Love Tower Renovation 1171 A rms trong A ve Knoxville , TN 3 7917

Renovation

1/4" = 1'-0"

1 ADA Type 0 - Electrical Demo Plan

1/4" = 1'-0"

2 ADA Type 0 - Electrical New Work Plan

1/4" = 1'-0"

3 ADA Type 1 - Electrical Demo Plan

1/4" = 1'-0"

4 ADA Type 1 - Electrical New Work Plan

GENERAL NOTES:

1. ALL NEW SPEAKER STROBES IN DWELLING UNIT BEDROOMS TO BE LOW FREQUENCY TYPE..

2. ALL NEW CONDUITS WITHIN DWELLING UNITS TO BE SURFACE MOUNTED WIREMOLD WHERE CONDUIT CANNOT BE CONCEALED. PATCH CEILINGS/WALLS AS NECESSARY WHERE CONDUITS CAN BE CONCEALED.

3. ALL WALL MOUNTED SMOKE ALARMS TO BE MOUNTED AT 8" BELOW CEILING TO CENTERLINE OF SMOKE ALARM.

4. REUSE EXISTING WIRE AND CONDUIT IN SAME LOCATION WHERE POSSIBLE AND IN GOOD CONDITION.

5. WIRING IN DWELLING UNITS NOT SHOWN ON PLANS FOR CLARITY.

PROVIDE BRANCH CIRCUIT WIRING TO CONNECT ALL DEVICES, FIXTURES, HVAC UNITS, ETC. TO CIRCUITS INDICATED ON DRAWINGS.

REFERENCE NOTES:

1. REMOVE EXISTING PANEL INTERIOR COMPONENTS AND PROVIDE BLANK COVER FOR PANEL. SPLICE AND EXTEND ALL WIRING FROM EXISTING PANEL LOCATION TO NEW PANEL LOCATION. REWIRE BRANCH CIRCUITS TO REMAIN AS NECESSARY TO ELIMINATE SHARED NEUTRALS. ASSUME THREE CIRCUITS WITH SHARED NEUTRALS. PROVIDE NEW GROUND WIRES WHERE NOT PRESENT AND CONDUIT DOESN'T PROVIDE ADEQUATE GROUND PATH.

2. WATER HEATER CONNECTION TO BE REMOVED.

3. SUPPLY NEW WATER HEATER CONNECTION AT THIS LOCATION. SUPPLY 3/4"C , 2#10, 1#10G BACK TO NEW PANEL LOCATION AND UTILIZE CKTS 6,8.

4. ALL LIGHTING IN THIS UNIT EXCEPT FOR BATHROOM TO BE SERVED BY CKT. 5 IN PANEL. BATHROOM LIGHTING TO BE SERVED BY CKT. 7.

5. NOT USED.

6. EXISTING WATER HEATER CONNECTION TO REMAIN. DISCONNECT EXISTING WATER HEATER AND RECONNECT UPON COMPLETION OF CABINETRY WORK.

7. ALL LIGHTING IN THIS UNIT EXCEPT FOR BATHROOM TO BE SERVED BY CKT. 10 IN PANEL. BATHROOM LIGHTING TO BE SERVED BY CKT. 12.

8. THE WORK SHOWN ON THIS ENLARGED PLAN IS TYPICAL FOR ALL UNITS OF THIS TYPE IN THE FACILITY.

9. PROVIDE 3#8, 1#10G, 3/4"C BACK TO PANEL FOR NEW RANGE RECEPTACLE.

10. PROVIDE 2#12, 1#12G, 3/4"C BACK TO PANEL FOR PTAC RECEPTACLE TO REMAIN.

1 ADDENDUM 3 12/02/19

References

Related documents

Last day for request for information May 28 Last Addendum issued for RFQ June 1 Statement of Qualifications Due June 8. Note: Please include Builder and Architect name and direct

By having Redirecting Locator Files in directories A, B, and C that point to the Locator File in directory D, you can ensure that the Gateway engine specified by the Locator File

Assuming that the leisure time physical activity behaviour of children relates to that of their parents [50], it is plausible to con- clude that the associations between

We will develop a method for joint optimization of the delivery policies for all service parts, such that we find an optimal balance between MSPD and the total inventory holding costs

If a range of service dates was entered in form locator 6, enter the number of units of service corresponding to each date of service in this field on the same lines where Revenue

9.2 Commercial General Liability - The minimum limits of insurance (inclusive of any amounts provided by an umbrella or excess policy) without exclusion for independent

Since a private managed wide network will not be in play will KCDC be acceptable to a centralized solution with teleworkers at the 15 remote sites or does each site require an

Retailing: Gross income from sales to consumers of prepared food, poured spirits, soft drinks, cigarettes and items of tangible personal property.. Wholesaling: Gross income from