Configurable Events for
APC Network Management Card
Table of Contents
Silcon DP300E Series ……… 3
Smart-UPS / Matrix ……… 7
Symmetra ……… 9
Symmetra 3-Phase ………13
Environmental Monitor ……… 21
Silcon DP300E Series
Event Event
Code Default Severity
System: Coldstart. 0x0001 Severe
System: Warmstart. 0x0002 Severe
System: SNMP configuration change. 0x0003 Warning
System: Detected an unauthorized user attempting to access the SNMP
interface. 0x0004 Informational
System: Detected an unauthorized user attempting to access the Console
interface. 0x0005 Warning
System: Detected an unauthorized user attempting to access the Web
interface. 0x0006 Warning
System: Network service started. 0x0007 None
System: Password changed. 0x0008 Warning
System: File transfer started. 0x000C None
System: File transfer started. 0x000D None
System: File transfer failed. 0x000F None
System: Console user logged in. 0x0014 None
System: Web user logged in. 0x0015 None
System: FTP user logged in. 0x0016 None
System: Console user logged out. 0x001E None
System: Web user logged out. 0x001F None
System: FTP user logged out. 0x0020 None
System: Reset to defaults. 0x0018 None
System: Initializing data in the file. 0x0019 None
System: Email information. 0x001A None
System: Trace information. 0x0024 None
System: Modem dial-out failed. 0x0025 Warning
System: RMS CLI user logged in. 0x0026 None
System: RMS CLI user logged out. 0x0027 None
System: Network service information. 0x002A None
System: Network service could not start. 0x002B None
System: Network service stopped. 0x002C None
UPS: Communications established. 0x1001 Informational
UPS: Communications lost. 0x1002 Severe
UPS: Sensed a load greater than 100 percent of rated capacity. 0x1003 Severe
UPS: Overload condition cleared. 0x1004 Informational
UPS: Passed internal self-test. 0x1005 Informational
UPS: Failed internal diagnostic self-test. 0x1006 Severe
UPS: Batteries discharged. 0x1007 Severe
UPS: Battery discharge condition cleared. 0x1008 Informational
UPS: Switched to battery backup power. 0x1009 Warning
UPS: Returned from battery backup power. 0x100A Informational
Silcon DP300E Series (continued)
Event Event
Code Default Severity
UPS: Enabled SmartBoost; low incoming line voltage. 0x100B Warning
UPS: Returned from SmartBoost. 0x100C Informational
UPS: Enabled SmartTrim; high incoming line voltage. 0x100D Warning
UPS: Returned from SmartTrim. 0x100E Informational
UPS: Battery power is low and will soon be exhausted. 0x100F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational
UPS: Turned on. 0x0113 Informational
UPS: Turned off. 0x0114 Warning
UPS: Entered sleep mode. 0x0115 Warning
UPS: Returned from sleep mode. 0x0116 Informational
UPS: Started reboot sequence. 0x0117 Warning
UPS: Batteries need immediate replacement. 0x0119 Severe
UPS: Bad battery condition cleared. 0x011A Informational
UPS: In bypass due to an internal fault. 0x011B Severe
UPS: In bypass due to user command via software or panel. 0x011C Warning
UPS: In bypass initiated by user. 0x011D Warning
UPS: Returned from bypass. 0x011E Informational
UPS: Base module bypass power supply failure. 0x011F Severe
UPS: Base module fan failure. 0x0120 Severe
UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe
UPS: Battery calibration test initiated. 0x0123 Informational
UPS: Battery calibration complete. 0x0124 Informational
UPS: Graceful shutdown in progress. 0x0125 Informational
UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning
UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational
UPS: Bad output voltage condition. 0x0128 Warning
UPS: Bad output voltage condition cleared. 0x0129 Informational
UPS: Battery charger failure. 0x012A Warning
UPS: Battery charger failure cleared. 0x012B Informational
UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational
UPS: No batteries installed. 0x012F Warning
UPS: No batteries installed cleared. 0x0130 Informational
UPS: Power Module failure. 0x0201 Severe
UPS: Power Module failure cleared 0x0202 Informational
UPS: Intelligence Module failure. 0x0203 Severe
UPS: Intelligence Module failure cleared. 0x0204 Informational UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational
UPS: Battery failure. 0x0207 Severe
Silcon DP300E Series (continued)
Event Event
Code Default Severity
UPS: Battery failure cleared. 0x0208 Informational
UPS: Load(kVA) alarm threshold violation. 0x0209 Severe
UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational
UPS: Redundancy lost. 0x020B Severe
UPS: Redundancy returned. 0x020C Informational
UPS: Redundancy below alarm threshold. 0x020D Severe
UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range cleared; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational
UPS: In bypass due to an internal fault 0x0215 Severe
UPS: In bypass due to an internal fault cleared. 0x0216 Informational
UPS: In bypass due to an overload. 0x0217 Severe
UPS: In bypass due to an overload cleared. 0x0218 Informational
UPS: In maintenance bypass. 0x0219 Severe
UPS: In maintenance bypass cleared. 0x021A Informational
UPS: Input circuit breaker tripped open. 0x021B Severe
UPS: Input circuit breaker tripped open cleared. 0x021C Informational
UPS: System level fan failure. 0x021D Severe
UPS: System level fan failure cleared. 0x021E Informational
UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational
UPS: No working Power Modules. 0x0223 Severe
UPS: No working Power Modules cleared. 0x0224 Informational
UPS: Load shutdown from bypass; input frequency or voltage outside
limits. 0x0225 Severe
UPS: Load shutdown from bypass cleared; input frequency or voltage
outside limits. 0x0226 Informational
UPS: Runtime below alarm threshold. 0x0227 Severe
UPS: Runtime below alarm threshold cleared. 0x0228 Informational
UPS: Extended Run Frame fault. 0x0229 Severe
UPS: Extended Run Frame fault cleared. 0x022A Informational
UPS: Output voltage out of range. 0x022B Severe
UPS: Output voltage out of range cleared. 0x022C Informational
UPS: Not synchronized fault 0x022D Severe
UPS: Not synchronized fault cleared. 0x022E Informational
Silcon DP300E Series (continued)
Event Event
Code Default Severity
UPS: No batteries installed. 0x022F Severe
UPS: No batteries installed cleared. 0x0230 Informational
UPS: Battery voltage high. 0x0231 Severe
UPS: Battery voltage high cleared. 0x0232 Informational
UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe
UPS: Non-specific fault cleared. 0x0234 Informational
UPS: Site wiring fault. 0x0235 Severe
UPS: Site wiring fault cleared. 0x0236 Informational
UPS: Backfeed protection relay open. 0x0237 Severe
UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register set cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0x0240 Informational
UPS: Number of batteries increased. 0x0241 Informational
UPS: Number of batteries decreased. 0x0242 Informational
UPS: Number of Power Modules increased. 0x0243 Informational
UPS: Number of Power Modules decreased. 0x0244 Informational
UPS: Intelligence Module inserted. 0x0245 Informational
UPS: Intelligence Module removed. 0x0246 Informational
UPS: Redundant Intelligence Module inserted. 0x0247 Informational UPS: Redundant Intelligence Module removed. 0x0248 Informational UPS: Number of Extended Run Frames increased. 0x0249 Informational UPS: Number of Extended Run Frames decreased. 0x024A Informational
Smart-UPS / Matrix
Event Event
Code Default Severity
System: Coldstart. 0x0001 Severe
System: Warmstart. 0x0002 Severe
System: SNMP configuration change. 0x0003 Warning
System: Detected an unauthorized user attempting to access the SNMP
interface. 0x0004 Informational
System: Detected an unauthorized user attempting to access the Console
interface. 0x0005 Warning
System: Detected an unauthorized user attempting to access the Web
interface. 0x0006 Warning
System: Network service started. 0x0007 None
System: Password changed. 0x0008 Warning
System: File transfer started. 0x000C None
System: File transfer started. 0x000D None
System: File transfer failed. 0x000F None
System: Console user logged in. 0x0014 None
System: Web user logged in. 0x0015 None
System: FTP user logged in. 0x0016 None
System: Console user logged out. 0x001E None
System: Web user logged out. 0x001F None
System: FTP user logged out. 0x0020 None
System: Reset to defaults. 0x0018 None
System: Initializing data in the file. 0x0019 None
System: Email information. 0x001A None
System: Trace information. 0x0024 None
System: Modem dial-out failed. 0x0025 Warning
System: RMS CLI user logged in. 0x0026 None
System: RMS CLI user logged out. 0x0027 None
System: Network service information. 0x002A None
System: Network service could not start. 0x002B None
System: Network service stopped. 0x002C None
UPS: Communication established. 0x0101 Informational
UPS: Communication lost. 0x0102 Severe
UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe
UPS: Overload condition cleared. 0x0104 Informational
UPS: Passed internal self-test. 0x0105 Informational
UPS: Failed internal diagnostic self-test. 0x0106 Severe
UPS: Batteries discharged. 0x0107 Severe
UPS: Batteries discharge condition cleared. 0x0108 Informational
UPS: Switched to battery backup power. 0x0109 Warning
UPS: Returned from battery backup power. 0x010A Informational
Smart-UPS / Matrix (continued)
Event Event
Code Default Severity
UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning
UPS: Returned from SmartBoost. 0x010C Informational
UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning
UPS: Returned from SmartTrim. 0x010E Informational
UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational
UPS: Turned on. 0x0113 Informational
UPS: Turned off. 0x0114 Warning
UPS: Entered sleep mode. 0x0115 Warning
UPS: Returned from sleep mode. 0x0116 Informational
UPS: Started reboot sequence. 0x0117 Warning
UPS: Batteries need immediate replacement. 0x0119 Severe
UPS: Bad battery condition cleared. 0x011A Informational
UPS: In bypass due to an internal fault. 0x011B Severe
UPS: In bypass due to user command via software or panel. 0x011C Warning
UPS: In bypass initiated by user. 0x011D Warning
UPS: Returned from bypass. 0x011E Informational
UPS: Base module bypass power supply failure. 0x011F Severe
UPS: Base module fan failure. 0x0120 Severe
UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe
UPS: Battery calibration test initiated. 0x0123 Informational
UPS: Battery calibration complete. 0x0124 Informational
UPS: Graceful shutdown in progress. 0x0125 Informational
UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning
UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational
UPS: Bad output voltage condition. 0x0128 Warning
UPS: Bad output voltage condition cleared. 0x0129 Informational
UPS: Battery charger failure. 0x012A Warning
UPS: Battery charger failure cleared. 0x012B Informational
UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational
UPS: No batteries installed. 0x012F Warning
UPS: No batteries installed cleared. 0x0130 Informational
UPS: Scheduled shutdown initiated. 0x0131 Informational
UPS: Scheduled shutdown failed. 0x0132 Warning
UPS: Scheduled shutdown deleted. 0x0133 Informational
Symmetra
Event Event
Code Default Severity
System: Coldstart. 0x0001 Severe
System: Warmstart. 0x0002 Severe
System: SNMP configuration change. 0x0003 Warning
System: Detected an unauthorized user attempting to access the SNMP
interface. 0x0004 Informational
System: Detected an unauthorized user attempting to access the Console
interface. 0x0005 Warning
System: Detected an unauthorized user attempting to access the Web
interface. 0x0006 Warning
System: Network service started. 0x0007 None
System: Password changed. 0x0008 Warning
System: File transfer started. 0x000C None
System: File transfer started. 0x000D None
System: File transfer failed. 0x000F None
System: Console user logged in. 0x0014 None
System: Web user logged in. 0x0015 None
System: FTP user logged in. 0x0016 None
System: Console user logged out. 0x001E None
System: Web user logged out. 0x001F None
System: FTP user logged out. 0x0020 None
System: Reset to defaults. 0x0018 None
System: Initializing data in the file. 0x0019 None
System: Email information. 0x001A None
System: Trace information. 0x0024 None
System: Modem dial-out failed. 0x0025 Warning
System: RMS CLI user logged in. 0x0026 None
System: RMS CLI user logged out. 0x0027 None
System: Network service information. 0x002A None
System: Network service could not start. 0x002B None
System: Network service stopped. 0x002C None
UPS: Communications established. 0x0101 Informational
UPS: Communications lost. 0x0102 Severe
UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe
UPS: Overload condition cleared. 0x0104 Informational
UPS: Passed internal self-test. 0x0105 Informational
UPS: Failed internal diagnostic self-test. 0x0106 Severe
UPS: Batteries discharged. 0x0107 Severe
UPS: Battery discharge condition cleared. 0x0108 Informational
UPS: Switched to battery backup power. 0x0109 Warning
UPS: Returned from battery backup power. 0x010A Informational
Symmetra (continued)
Event Event
Code Default Severity
UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning
UPS: Returned from SmartBoost. 0x010C Informational
UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning
UPS: Returned from SmartTrim. 0x010E Informational
UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational
UPS: Turned on. 0x0113 Informational
UPS: Turned off. 0x0114 Warning
UPS: Entered sleep mode. 0x0115 Warning
UPS: Returned from sleep mode. 0x0116 Informational
UPS: Started reboot sequence. 0x0117 Warning
UPS: Batteries need immediate replacement. 0x0119 Severe
UPS: Bad battery condition cleared. 0x011A Informational
UPS: In bypass due to an internal fault. 0x011B Severe
UPS: In bypass due to user command via software or panel. 0x011C Warning
UPS: In bypass initiated by user. 0x011D Warning
UPS: Returned from bypass. 0x011E Informational
UPS: Base module bypass power supply failure. 0x011F Severe
UPS: Base module fan failure. 0x0120 Severe
UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe
UPS: Battery calibration test initiated. 0x0123 Informational
UPS: Battery calibration complete. 0x0124 Informational
UPS: Graceful shutdown in progress. 0x0125 Informational
UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning
UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational
UPS: Bad output voltage condition. 0x0128 Warning
UPS: Bad output voltage condition cleared. 0x0128 Informational
UPS: Battery charger failure. 0x012A Warning
UPS: Battery charger failure cleared. 0x012B Informational
UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational
UPS: No batteries installed. 0x012F Warning
UPS: No batteries installed cleared. 0x0130 Informational
UPS: Scheduled shutdown initiated. 0x0131 Informational
UPS: Scheduled shutdown failed. 0x0132 Warning
UPS: Scheduled shutdown deleted. 0x0133 Informational
UPS: Power Module failure. 0x0201 Severe
UPS: Power Module failure cleared. 0x0202 Informational
UPS: Intelligence Module failure. 0x0203 Severe
UPS: Intelligence Module failure cleared. 0x0204 Informational
Symmetra (continued)
Event Event
Code Default Severity
UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational
UPS: Battery failure. 0x0207 Severe
UPS: Battery failure cleared. 0x0208 Informational
UPS: Load(kVA) alarm threshold violation. 0x0209 Severe
UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational
UPS: Redundancy lost. 0x020B Severe
UPS: Redundancy returned. 0x020C Informational
UPS: Redundancy below alarm threshold. 0x020D Severe
UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range cleared; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational
UPS: In bypass due to an internal fault. 0x0215 Severe
UPS: In bypass due to an internal fault cleared. 0x0216 Informational
UPS: In bypass due to an overload. 0x0217 Severe
UPS: In bypass due to an overload cleared. 0x0218 Informational
UPS: In maintenance bypass. 0x0219 Severe
UPS: In maintenance bypass cleared. 0x021A Informational
UPS: Input circuit breaker tripped open. 0x021B Severe
UPS: Input circuit breaker tripped open cleared. 0x021C Informational
UPS: System level fan failure. 0x021D Severe
UPS: System level fan failure cleared. 0x021E Informational
UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational
UPS: No working Power Modules. 0x0223 Severe
UPS: No working Power Modules cleared. 0x0224 Informational
UPS: Load shutdown from bypass; input frequency or voltage outside
limits. 0x0225 Severe
UPS: Load shutdown from bypass cleared; input frequency or voltage
outside limits. 0x0226 Informational
UPS: Runtime below alarm threshold. 0x0227 Severe
UPS: Runtime below alarm threshold cleared. 0x0228 Informational
UPS: Extended Run Frame fault. 0x0229 Severe
UPS: Extended Run Frame fault cleared. 0x022A Informational
UPS: Output voltage out of range. 0x022B Severe
Symmetra (continued)
Event Event
Code Default Severity
UPS: Output voltage out of range cleared. 0x022C Informational
UPS: Not synchronized fault. 0x022D Severe
UPS: Not synchronized fault cleared. 0x022E Informational
UPS: No batteries installed. 0x022F Severe
UPS: No batteries installed cleared. 0x0230 Informational
UPS: Battery voltage high. 0x0231 Severe
UPS: Battery voltage high cleared. 0x0232 Informational
UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe
UPS: Non-specific fault cleared. 0x0234 Informational
UPS: Site wiring fault. 0x0235 Severe
UPS: Site wiring fault cleared. 0x0236 Informational
UPS: Backfeed protection relay open. 0x0237 Severe
UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0X0240 Informational
UPS: Number of batteries increased. 0X0241 Informational
UPS: Number of batteries decreased. 0X0242 Informational
UPS: Number of Power Modules increased. 0X0243 Informational
UPS: Number of Power Modules decreased. 0X0244 Informational
UPS: Intelligence Module inserted. 0X0245 Informational
UPS: Intelligence Module removed. 0X0246 Informational
UPS: Redundant Intelligence Module inserted. 0X0247 Informational UPS: Redundant Intelligence Module removed. 0X0248 Informational UPS: Number of Extended Run Frames increased. 0X0249 Informational UPS: Number of Extended Run Frames decreased. 0X024A Informational
Symmetra 3-Phase
Event Event
Code Default Severity
System: Coldstart. 0x0001 Severe
System: Warmstart. 0x0002 Severe
System: SNMP configuration change. 0x0003 Warning
System: Detected an unauthorized user attempting to access the SNMP
interface. 0x0004 Informational
System: Detected an unauthorized user attempting to access the Console
interface. 0x0005 Warning
System: Detected an unauthorized user attempting to access the Web
interface. 0x0006 Warning
System: Network service started. 0x0007 None
System: Password changed. 0x0008 Warning
System: File transfer started. 0x000C None
System: File transfer started. 0x000D None
System: File transfer failed. 0x000F None
System: Console user logged in. 0x0014 None
System: Web user logged in. 0x0015 None
System: FTP user logged in. 0x0016 None
System: Console user logged out. 0x001E None
System: Web user logged out. 0x001F None
System: FTP user logged out. 0x0020 None
System: Reset to defaults. 0x0018 None
System: Initializing data in the file. 0x0019 None
System: Email information. 0x001A None
System: Trace information. 0x0024 None
System: Modem dial-out failed. 0x0025 Warning
System: RMS CLI user logged in. 0x0026 None
System: RMS CLI user logged out. 0x0027 None
System: Network service information. 0x002A None
System: Network service could not start. 0x002B None
System: Network service stopped. 0x002C None
UPS: Communications established. 0x0101 Informational
UPS: Communications lost. 0x0102 Severe
UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe
UPS: Overload condition cleared. 0x0104 Informational
UPS: Passed internal self-test. 0x0105 Informational
UPS: Failed internal diagnostic self-test. 0x0106 Severe
UPS: Batteries discharged. 0x0107 Severe
UPS: Battery discharge condition cleared. 0x0108 Informational
UPS: Switched to battery backup power. 0x0109 Warning
UPS: Returned from battery backup power. 0x010A Informational
Symmetra 3-Phase (continued)
Event Event
Code Default Severity
UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning
UPS: Returned from SmartBoost. 0x010C Informational
UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning
UPS: Returned from SmartTrim. 0x010E Informational
UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational
UPS: Turned on. 0x0113 Informational
UPS: Turned off. 0x0114 Warning
UPS: Entered sleep mode. 0x0115 Warning
UPS: Returned from sleep mode. 0x0116 Informational
UPS: Started reboot sequence. 0x0117 Warning
UPS: Batteries need immediate replacement. 0x0119 Severe
UPS: Bad battery condition cleared. 0x011A Informational
UPS: In bypass due to an internal fault. 0x011B Severe
UPS: In bypass due to user command via software or panel. 0x011C Warning
UPS: In bypass initiated by user. 0x011D Warning
UPS: Returned from bypass. 0x011E Informational
UPS: Base module bypass power supply failure. 0x011F Severe
UPS: Base module fan failure. 0x0120
UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe
UPS: Battery calibration test initiated. 0x0123 Informational
UPS: Battery calibration complete. 0x0124 Informational
UPS: Graceful shutdown in progress. 0x0125 Informational
UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning
UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational
UPS: Bad output voltage condition. 0x0128 Warning
UPS: Bad output voltage condition cleared. 0x0129 Informational
UPS: Battery charger failure. 0x012A Warning
UPS: Battery charger failure cleared. 0x012B Informational
UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational
UPS: No batteries installed. 0x012F Warning
UPS: No batteries installed cleared. 0x0130 Informational
UPS: Scheduled shutdown initiated. 0x0131 Warning
UPS: Scheduled shutdown failed. 0x0132 Informational
UPS: Scheduled shutdown deleted. 0x0133 Severe
UPS: Power Module failure. 0x0201 Severe
UPS: Power Module failure cleared. 0x0202 Informational
UPS: Intelligence Module failure. 0x0203 Severe
UPS: Intelligence Module failure cleared. 0x0204 Informational
Symmetra 3-Phase (continued)
Event Event
Code Default Severity
UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational
UPS: Battery failure. 0x0207 Severe
UPS: Battery failure cleared. 0x0208 Informational
UPS: Load(kVA) alarm threshold violation. 0x0209 Severe
UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational
UPS: Redundancy lost. 0x020B Severe
UPS: Redundancy returned. 0x020C Informational
UPS: Redundancy below alarm threshold. 0x020D Severe
UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational
UPS: In bypass due to an internal fault. 0x0215 Severe
UPS: In bypass due to an internal fault cleared. 0x0216 Informational
UPS: In bypass due to an overload. 0x0217 Severe
UPS: In bypass due to an overload cleared. 0x0218 Informational
UPS: In maintenance bypass. 0x0219 Severe
UPS: In maintenance bypass cleared. 0x021A Informational
UPS: Input circuit breaker tripped open. 0x021B Severe
UPS: Input circuit breaker tripped open cleared. 0x021C Informational
UPS: System level fan failure. 0x021D Severe
UPS: System level fan failure cleared. 0x021E Informational
UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational
UPS: No working Power Modules. 0x0223 Severe
UPS: No working Power Modules cleared. 0x0224 Informational
UPS: Load shutdown from bypass; input frequency or voltage outside
limits. 0x0225 Severe
UPS: Load shutdown from bypass cleared; input frequency or voltage
outside limits. 0x0226 Informational
UPS: Runtime below alarm threshold. 0x0227 Severe
UPS: Runtime below alarm threshold cleared. 0x0228 Informational
UPS: Extended Run Frame fault. 0x0229 Severe
UPS: Extended Run Frame fault cleared. 0x022A Informational
UPS: Output voltage out of range. 0x022B Severe
Symmetra 3-Phase (continued)
Event Event
Code Default Severity
UPS: Output voltage out of range cleared. 0x022C Informational
UPS: Not synchronized fault. 0x022D Severe
UPS: Not synchronized fault cleared. 0x022E Informational
UPS: No batteries installed. 0x022F Severe
UPS: No batteries installed cleared. 0x0230 Informational
UPS: Battery voltage high. 0x0231 Severe
UPS: Battery voltage high cleared. 0x0232 Informational
UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe
UPS: Non-specific fault cleared. 0x0234 Informational
UPS: Site wiring fault. 0x0235 Severe
UPS: Site wiring fault cleared. 0x0236 Informational
UPS: Backfeed protection relay open. 0x0237 Severe
UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0x0240 Informational
UPS: Number of batteries increased. 0x0241 Informational
UPS: Number of batteries decreased. 0x0242 Informational
UPS: Number of Power Modules increased. 0x0243 Informational
UPS: Number of Power Modules increased. 0x0244 Informational
UPS: Intelligence Module inserted. 0x0245 Informational
UPS: Intelligence Module removed. 0x0246 Informational
UPS: Redundant Intelligence Module inserted. 0x0247 Informational UPS: Redundant Intelligence Module removed. 0x0248 Informational UPS: Number of Extended Run Frames increased. 0x0249 Informational UPS: Number of Extended Run Frames decreased. 0x024A Informational UPS: Number of System Power Supplies increased. 0x024B Informational UPS: Number of System Power Supplies decreased. 0x024C Informational
UPS: External Switch Gear Q001 closed. 0x024D Informational
UPS: External Switch Gear Q001 opened. 0x024E Informational
UPS: External Switch Gear Q002 closed. 0x024F Informational
UPS: External Switch Gear Q002 opened. 0x0250 Informational
UPS: External Switch Gear Q003 closed. 0x0251 Informational
UPS: External Switch Gear Q003 opened. 0x0252 Informational
UPS: External Switch Gear Q004 closed. 0x0253 Informational
UPS: External Switch Gear Q004 opened. 0x0254 Informational
Symmetra 3-Phase (continued)
Event Event
Code Default Severity
UPS: External Switch Gear failure. 0x0A01 Severe
UPS: External Switch Gear failure cleared. 0x0A02 Informational UPS: External Transformer over temperature. 0x0A03 Severe UPS: External Transformer over temperature cleared. 0x0A04 Informational
UPS: External DC Circuit Breaker tripped. 0x0A05 Severe
UPS: External DC Circuit Breaker closed. 0x0A06 Informational
UPS: System Power Supply failure. 0x0A07 Severe
UPS: System Power Supply failure cleared. 0x0A08 Informational
UPS: Battery Monitor Card failure. 0x0A09 Severe
UPS: Battery Monitor Card failure cleared. 0x0A0A Informational
UPS: Battery Monitor Card removed. 0x0A0B Severe
UPS: Battery Monitor Card inserted. 0x0A0C Informational
UPS: XR Communication Card failure. 0x0A0D Severe
UPS: XR Communication Card failure cleared. 0x0A0E Informational
UPS: XR Communication Card removed. 0x0A0F Severe
UPS: XR Communication Card inserted. 0x0A10 Informational
UPS: External Switch Gear Monitoring Card failure. 0x0A11 Severe UPS: External Switch Gear Monitoring Card failure cleared. 0x0A12 Informational UPS: External Switch Gear Monitoring Card removed. 0x0A13 Severe UPS: External Switch Gear Monitoring Card inserted. 0x0A14 Informational
UPS: Internal DC Circuit Breaker tripped. 0x0A15 Severe
UPS: Internal DC Circuit Breaker closed. 0x0A16 Informational
UPS: Static Bypass Switch failure. 0x0A17 Severe
UPS: Static Bypass Switch failure cleared. 0x0A18 Informational
UPS: System EEProm removed. 0x0A19 Severe
UPS: System EEProm inserted. 0x0A1A Informational
UPS: System EEProm failure. 0x0A1B Severe
UPS: System EEProm failure cleared. 0x0A1C Informational
UPS: UPS is in forced bypassed. 0x0A1D Severe
UPS: UPS returned from forced bypassed. 0x0A1E Informational
UPS: Bit 15 of the second abnormal condition register set. 0x0A1F Severe UPS: Bit 15 of the second abnormal condition register cleared. 0x0A20 Informational UPS: Bit 16 of the second abnormal condition register set. 0x0A21 Severe UPS: Bit 16 of the second abnormal condition register cleared. 0x0A22 Informational UPS: Bit 17 of the second abnormal condition register set. 0x0A23 Severe UPS: Bit 17 of the second abnormal condition register cleared. 0x0A24 Informational UPS: Bit 18 of the second abnormal condition register set. 0x0A25 Severe UPS: Bit 18 of the second abnormal condition register cleared. 0x0A26 Informational UPS: Bit 19 of the second abnormal condition register set. 0x0A27 Severe UPS: Bit 19 of the second abnormal condition register cleared. 0x0A28 Informational UPS: Bit 20 of the second abnormal condition register set. 0x0A29 Severe
Symmetra 3-Phase (continued)
Event Event
Code Default Severity
UPS: Bit 20 of the second abnormal condition register cleared. 0x0A2A Informational UPS: Bit 21 of the second abnormal condition register set. 0x0A2B Severe UPS: Bit 21 of the second abnormal condition register cleared. 0x0A2C Informational UPS: Bit 22 of the second abnormal condition register set. 0x0A2D Severe UPS: Bit 22 of the second abnormal condition register cleared. 0x0A2E Informational UPS: Bit 23 of the second abnormal condition register set. 0x0A2F Severe UPS: Bit 23 of the second abnormal condition register cleared. 0x0A30 Informational UPS: Bit 24 of the second abnormal condition register set. 0x0A31 Severe UPS: Bit 24 of the second abnormal condition register cleared. 0x0A32 Informational UPS: Bit 25 of the second abnormal condition register set. 0x0A33 Severe UPS: Bit 25 of the second abnormal condition register cleared. 0x0A34 Informational UPS: Bit 26 of the second abnormal condition register set. 0x0A35 Severe UPS: Bit 26 of the second abnormal condition register cleared. 0x0A36 Informational UPS: Bit 27 of the second abnormal condition register set. 0x0A37 Severe UPS: Bit 27 of the second abnormal condition register cleared. 0x0A38 Informational UPS: Bit 28 of the second abnormal condition register set. 0x0A39 Severe UPS: Bit 28 of the second abnormal condition register cleared. 0x0A3A Informational UPS: Bit 29 of the second abnormal condition register set. 0x0A3B Severe UPS: Bit 29 of the second abnormal condition register cleared. 0x0A3C Informational UPS: Bit 30 of the second abnormal condition register set. 0x0A3D Severe UPS: Bit 30 of the second abnormal condition register cleared. 0x0A3E Informational UPS: Bit 31 of the second abnormal condition register set. 0x0A3F Severe UPS: Bit 31 of the second abnormal condition register cleared. 0x0A40 Informational UPS: Bit 32 of the second abnormal condition register set. 0x0A41 Severe UPS: Bit 32 of the second abnormal condition register cleared. 0x0A42 Informational UPS: Bit 33 of the second abnormal condition register set. 0x0A43 Severe UPS: Bit 33 of the second abnormal condition register cleared. 0x0A44 Informational UPS: Bit 34 of the second abnormal condition register set. 0x0A45 Severe UPS: Bit 34 of the second abnormal condition register cleared. 0x0A46 Informational UPS: Bit 35 of the second abnormal condition register set. 0x0A47 Severe UPS: Bit 35 of the second abnormal condition register cleared. 0x0A48 Informational UPS: Bit 36 of the second abnormal condition register set. 0x0A49 Severe UPS: Bit 36 of the second abnormal condition register cleared. 0x0A4A Informational UPS: Bit 37 of the second abnormal condition register set. 0x0A4B Severe UPS: Bit 37 of the second abnormal condition register cleared. 0x0A4C Informational UPS: Bit 38 of the second abnormal condition register set. 0x0A4D Severe UPS: Bit 38 of the second abnormal condition register cleared. 0x0A4E Informational UPS: Bit 39 of the second abnormal condition register set. 0x0A4F Severe UPS: Bit 39 of the second abnormal condition register cleared. 0x0A50 Informational UPS: Bit 40 of the second abnormal condition register set. 0x0A51 Severe UPS: Bit 40 of the second abnormal condition register cleared. 0x0A52 Informational
Symmetra 3-Phase (continued)
Event Event
Code Default Severity
UPS: Bit 41 of the second abnormal condition register set. 0x0A53 Severe UPS: Bit 41 of the second abnormal condition register cleared. 0x0A54 Informational UPS: Bit 42 of the second abnormal condition register set. 0x0A55 Severe UPS: Bit 42 of the second abnormal condition register cleared. 0x0A56 Informational UPS: Bit 43 of the second abnormal condition register set. 0x0A57 Severe UPS: Bit 43 of the second abnormal condition register cleared. 0x0A58 Informational UPS: Bit 44 of the second abnormal condition register set. 0x0A59 Severe UPS: Bit 44 of the second abnormal condition register cleared. 0x0A5A Informational UPS: Bit 45 of the second abnormal condition register set. 0x0A5B Severe UPS: Bit 45 of the second abnormal condition register cleared. 0x0A5C Informational UPS: Bit 46 of the second abnormal condition register set. 0x0A5D Severe UPS: Bit 46 of the second abnormal condition register cleared. 0x0A5E Informational UPS: Bit 47 of the second abnormal condition register set. 0x0A5F Severe UPS: Bit 47 of the second abnormal condition register cleared. 0x0A60 Informational UPS: Bit 48 of the second abnormal condition register set. 0x0A61 Severe UPS: Bit 48 of the second abnormal condition register cleared. 0x0A62 Informational UPS: Bit 49 of the second abnormal condition register set. 0x0A63 Severe UPS: Bit 49 of the second abnormal condition register cleared. 0x0A64 Informational UPS: Bit 50 of the second abnormal condition register set. 0x0A65 Severe UPS: Bit 50 of the second abnormal condition register cleared. 0x0A66 Informational UPS: Bit 51 of the second abnormal condition register set. 0x0A67 Severe UPS: Bit 51 of the second abnormal condition register cleared. 0x0A68 Informational UPS: Bit 52 of the second abnormal condition register set. 0x0A69 Severe UPS: Bit 52 of the second abnormal condition register cleared. 0x0A6A Informational UPS: Bit 53 of the second abnormal condition register set. 0x0A6B Severe UPS: Bit 53 of the second abnormal condition register cleared. 0x0A6C Informational UPS: Bit 54 of the second abnormal condition register set. 0x0A6D Severe UPS: Bit 54 of the second abnormal condition register cleared. 0x0A6E Informational UPS: Bit 55 of the second abnormal condition register set. 0x0A6F Severe UPS: Bit 55 of the second abnormal condition register cleared. 0x0A70 Informational UPS: Bit 56 of the second abnormal condition register set. 0x0A71 Severe UPS: Bit 56 of the second abnormal condition register cleared. 0x0A72 Informational UPS: Bit 57 of the second abnormal condition register set. 0x0A73 Severe UPS: Bit 57 of the second abnormal condition register cleared. 0x0A74 Informational UPS: Bit 58 of the second abnormal condition register set. 0x0A75 Severe UPS: Bit 58 of the second abnormal condition register cleared. 0x0A76 Informational UPS: Bit 59 of the second abnormal condition register set. 0x0A77 Severe UPS: Bit 59 of the second abnormal condition register cleared. 0x0A78 Informational UPS: Bit 60 of the second abnormal condition register set. 0x0A79 Severe UPS: Bit 60 of the second abnormal condition register cleared. 0x0A7A Informational UPS: Bit 61 of the second abnormal condition register set. 0x0A7B Severe
Symmetra 3-Phase (continued)
Event Event
Code Default Severity
UPS: Bit 61 of the second abnormal condition register cleared. 0x0A7C Informational UPS: Bit 62 of the second abnormal condition register set. 0x0A7D Severe UPS: Bit 62 of the second abnormal condition register cleared. 0x0A7E Informational UPS: Bit 63 of the second abnormal condition register set. 0x0A7F Severe UPS: Bit 63 of the second abnormal condition register cleared. 0x0A80 Informational
Environmental Monitor
Event Event
Code Default Severity
Environment: Contact 1 fault. 0x0301 Severe
Environment: Contact 1 fault cleared. 0x0302 Informational
Environment: Contact 2 fault. 0x0303 Severe
Environment: Contact 2 fault cleared. 0x0304 Informational
Environment: Contact 3 fault. 0x0305 Severe
Environment: Contact 3 fault cleared. 0x0306 Informational
Environment: Contact 4 fault. 0x0307 Severe
Environment: Contact 4 fault cleared. 0x0308 Informational
Environment: Low temperature threshold violation on probe 1. 0x0309 Severe Environment: Low temperature threshold violation on probe 1 cleared. 0x030A Informational Environment: High temperature threshold violation on probe 1. 0x030B Severe Environment: High temperature threshold violation on probe 1 cleared. 0x030C Informational Environment: Low humidity threshold violation on probe 1. 0x030D Severe Environment: Low humidity threshold violation on probe 1 cleared. 0x030E Informational Environment: High humidity threshold violation on probe 1. 0x030F Severe Environment: High humidity threshold violation on probe 1 cleared. 0x0310 Informational Environment: Low temperature threshold violation on probe 2. 0x0311 Severe Environment: Low temperature threshold violation on probe 2 cleared. 0x0312 Informational Environment: High temperature threshold violation on probe 2. 0x0313 Severe Environment: High temperature threshold violation on probe 2 cleared. 0x0314 Informational Environment: Low humidity threshold violation on probe 2. 0x0315 Severe Environment: Low humidity threshold violation on probe 2 cleared. 0x0316 Informational Environment: High humidity threshold violation on probe 2. 0x0317 Severe Environment: High humidity threshold violation on probe 2 cleared. 0x0318 Informational
Environment: Communications established. 0x0319 Informational
Environment: Communications lost. 0x031A Severe
Environment: Integrated contact fault. 0x031B Severe
Environment: Integrated contact fault cleared. 0x031C Informational Environment: Low temperature threshold violation on integrated probe. 0x031D Severe Environment: Low temperature threshold violation on integrated probe
cleared. 0x031E Informational
Environment: High temperature threshold violation on integrated probe. 0x031F Severe Environment: High temperature threshold violation on integrated probe
cleared.
0x0320 Informational
Environment: Low humidity threshold violation on integrated probe. 0x0321 Severe Environment: Low humidity threshold violation on integrated probe cleared. 0x0322 Informational Environment: High humidity threshold violation on integrated probe. 0x0323 Severe Environment: High humidity threshold violation on integrated probe cleared. 0x0324 Informational
Environment: Integrated relay output fault. 0x0325 Warning
Environment: Integrated relay output fault cleared. 0x0326 Warning