Configurable Events for

APC Network Management Card

(2)

Table of Contents

Silcon DP300E Series ……… 3

Smart-UPS / Matrix ……… 7

Symmetra ……… 9

Symmetra 3-Phase ………13

Environmental Monitor ……… 21

(3)

Silcon DP300E Series

Event Event

Code Default Severity

System: Coldstart. 0x0001 Severe

System: Warmstart. 0x0002 Severe

System: SNMP configuration change. 0x0003 Warning

System: Detected an unauthorized user attempting to access the SNMP

interface. 0x0004 Informational

System: Detected an unauthorized user attempting to access the Console

interface. 0x0005 Warning

System: Detected an unauthorized user attempting to access the Web

interface. 0x0006 Warning

System: Network service started. 0x0007 None

System: Password changed. 0x0008 Warning

System: File transfer started. 0x000C None

System: File transfer started. 0x000D None

System: File transfer failed. 0x000F None

System: Console user logged in. 0x0014 None

System: Web user logged in. 0x0015 None

System: FTP user logged in. 0x0016 None

System: Console user logged out. 0x001E None

System: Web user logged out. 0x001F None

System: FTP user logged out. 0x0020 None

System: Reset to defaults. 0x0018 None

System: Initializing data in the file. 0x0019 None

System: Email information. 0x001A None

System: Trace information. 0x0024 None

System: Modem dial-out failed. 0x0025 Warning

System: RMS CLI user logged in. 0x0026 None

System: RMS CLI user logged out. 0x0027 None

System: Network service information. 0x002A None

System: Network service could not start. 0x002B None

System: Network service stopped. 0x002C None

UPS: Communications established. 0x1001 Informational

UPS: Communications lost. 0x1002 Severe

UPS: Sensed a load greater than 100 percent of rated capacity. 0x1003 Severe

UPS: Overload condition cleared. 0x1004 Informational

UPS: Passed internal self-test. 0x1005 Informational

UPS: Failed internal diagnostic self-test. 0x1006 Severe

UPS: Batteries discharged. 0x1007 Severe

UPS: Battery discharge condition cleared. 0x1008 Informational

UPS: Switched to battery backup power. 0x1009 Warning

UPS: Returned from battery backup power. 0x100A Informational

(4)

Silcon DP300E Series (continued)

Event Event

Code Default Severity

UPS: Enabled SmartBoost; low incoming line voltage. 0x100B Warning

UPS: Returned from SmartBoost. 0x100C Informational

UPS: Enabled SmartTrim; high incoming line voltage. 0x100D Warning

UPS: Returned from SmartTrim. 0x100E Informational

UPS: Battery power is low and will soon be exhausted. 0x100F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational

UPS: Turned on. 0x0113 Informational

UPS: Turned off. 0x0114 Warning

UPS: Entered sleep mode. 0x0115 Warning

UPS: Returned from sleep mode. 0x0116 Informational

UPS: Started reboot sequence. 0x0117 Warning

UPS: Batteries need immediate replacement. 0x0119 Severe

UPS: Bad battery condition cleared. 0x011A Informational

UPS: In bypass due to an internal fault. 0x011B Severe

UPS: In bypass due to user command via software or panel. 0x011C Warning

UPS: In bypass initiated by user. 0x011D Warning

UPS: Returned from bypass. 0x011E Informational

UPS: Base module bypass power supply failure. 0x011F Severe

UPS: Base module fan failure. 0x0120 Severe

UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe

UPS: Battery calibration test initiated. 0x0123 Informational

UPS: Battery calibration complete. 0x0124 Informational

UPS: Graceful shutdown in progress. 0x0125 Informational

UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning

UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational

UPS: Bad output voltage condition. 0x0128 Warning

UPS: Bad output voltage condition cleared. 0x0129 Informational

UPS: Battery charger failure. 0x012A Warning

UPS: Battery charger failure cleared. 0x012B Informational

UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational

UPS: No batteries installed. 0x012F Warning

UPS: No batteries installed cleared. 0x0130 Informational

UPS: Power Module failure. 0x0201 Severe

UPS: Power Module failure cleared 0x0202 Informational

UPS: Intelligence Module failure. 0x0203 Severe

UPS: Intelligence Module failure cleared. 0x0204 Informational UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational

UPS: Battery failure. 0x0207 Severe

(5)

Silcon DP300E Series (continued)

Event Event

Code Default Severity

UPS: Battery failure cleared. 0x0208 Informational

UPS: Load(kVA) alarm threshold violation. 0x0209 Severe

UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational

UPS: Redundancy lost. 0x020B Severe

UPS: Redundancy returned. 0x020C Informational

UPS: Redundancy below alarm threshold. 0x020D Severe

UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range cleared; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational

UPS: In bypass due to an internal fault 0x0215 Severe

UPS: In bypass due to an internal fault cleared. 0x0216 Informational

UPS: In bypass due to an overload. 0x0217 Severe

UPS: In bypass due to an overload cleared. 0x0218 Informational

UPS: In maintenance bypass. 0x0219 Severe

UPS: In maintenance bypass cleared. 0x021A Informational

UPS: Input circuit breaker tripped open. 0x021B Severe

UPS: Input circuit breaker tripped open cleared. 0x021C Informational

UPS: System level fan failure. 0x021D Severe

UPS: System level fan failure cleared. 0x021E Informational

UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational

UPS: No working Power Modules. 0x0223 Severe

UPS: No working Power Modules cleared. 0x0224 Informational

UPS: Load shutdown from bypass; input frequency or voltage outside

limits. 0x0225 Severe

UPS: Load shutdown from bypass cleared; input frequency or voltage

outside limits. 0x0226 Informational

UPS: Runtime below alarm threshold. 0x0227 Severe

UPS: Runtime below alarm threshold cleared. 0x0228 Informational

UPS: Extended Run Frame fault. 0x0229 Severe

UPS: Extended Run Frame fault cleared. 0x022A Informational

UPS: Output voltage out of range. 0x022B Severe

UPS: Output voltage out of range cleared. 0x022C Informational

UPS: Not synchronized fault 0x022D Severe

UPS: Not synchronized fault cleared. 0x022E Informational

(6)

Silcon DP300E Series (continued)

Event Event

Code Default Severity

UPS: No batteries installed. 0x022F Severe

UPS: No batteries installed cleared. 0x0230 Informational

UPS: Battery voltage high. 0x0231 Severe

UPS: Battery voltage high cleared. 0x0232 Informational

UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe

UPS: Non-specific fault cleared. 0x0234 Informational

UPS: Site wiring fault. 0x0235 Severe

UPS: Site wiring fault cleared. 0x0236 Informational

UPS: Backfeed protection relay open. 0x0237 Severe

UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register set cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0x0240 Informational

UPS: Number of batteries increased. 0x0241 Informational

UPS: Number of batteries decreased. 0x0242 Informational

UPS: Number of Power Modules increased. 0x0243 Informational

UPS: Number of Power Modules decreased. 0x0244 Informational

UPS: Intelligence Module inserted. 0x0245 Informational

UPS: Intelligence Module removed. 0x0246 Informational

UPS: Redundant Intelligence Module inserted. 0x0247 Informational UPS: Redundant Intelligence Module removed. 0x0248 Informational UPS: Number of Extended Run Frames increased. 0x0249 Informational UPS: Number of Extended Run Frames decreased. 0x024A Informational

(7)

Smart-UPS / Matrix

Event Event

Code Default Severity

System: Coldstart. 0x0001 Severe

System: Warmstart. 0x0002 Severe

System: SNMP configuration change. 0x0003 Warning

System: Detected an unauthorized user attempting to access the SNMP

interface. 0x0004 Informational

System: Detected an unauthorized user attempting to access the Console

interface. 0x0005 Warning

System: Detected an unauthorized user attempting to access the Web

interface. 0x0006 Warning

System: Network service started. 0x0007 None

System: Password changed. 0x0008 Warning

System: File transfer started. 0x000C None

System: File transfer started. 0x000D None

System: File transfer failed. 0x000F None

System: Console user logged in. 0x0014 None

System: Web user logged in. 0x0015 None

System: FTP user logged in. 0x0016 None

System: Console user logged out. 0x001E None

System: Web user logged out. 0x001F None

System: FTP user logged out. 0x0020 None

System: Reset to defaults. 0x0018 None

System: Initializing data in the file. 0x0019 None

System: Email information. 0x001A None

System: Trace information. 0x0024 None

System: Modem dial-out failed. 0x0025 Warning

System: RMS CLI user logged in. 0x0026 None

System: RMS CLI user logged out. 0x0027 None

System: Network service information. 0x002A None

System: Network service could not start. 0x002B None

System: Network service stopped. 0x002C None

UPS: Communication established. 0x0101 Informational

UPS: Communication lost. 0x0102 Severe

UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe

UPS: Overload condition cleared. 0x0104 Informational

UPS: Passed internal self-test. 0x0105 Informational

UPS: Failed internal diagnostic self-test. 0x0106 Severe

UPS: Batteries discharged. 0x0107 Severe

UPS: Batteries discharge condition cleared. 0x0108 Informational

UPS: Switched to battery backup power. 0x0109 Warning

UPS: Returned from battery backup power. 0x010A Informational

(8)

Smart-UPS / Matrix (continued)

Event Event

Code Default Severity

UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning

UPS: Returned from SmartBoost. 0x010C Informational

UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning

UPS: Returned from SmartTrim. 0x010E Informational

UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational

UPS: Turned on. 0x0113 Informational

UPS: Turned off. 0x0114 Warning

UPS: Entered sleep mode. 0x0115 Warning

UPS: Returned from sleep mode. 0x0116 Informational

UPS: Started reboot sequence. 0x0117 Warning

UPS: Batteries need immediate replacement. 0x0119 Severe

UPS: Bad battery condition cleared. 0x011A Informational

UPS: In bypass due to an internal fault. 0x011B Severe

UPS: In bypass due to user command via software or panel. 0x011C Warning

UPS: In bypass initiated by user. 0x011D Warning

UPS: Returned from bypass. 0x011E Informational

UPS: Base module bypass power supply failure. 0x011F Severe

UPS: Base module fan failure. 0x0120 Severe

UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe

UPS: Battery calibration test initiated. 0x0123 Informational

UPS: Battery calibration complete. 0x0124 Informational

UPS: Graceful shutdown in progress. 0x0125 Informational

UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning

UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational

UPS: Bad output voltage condition. 0x0128 Warning

UPS: Bad output voltage condition cleared. 0x0129 Informational

UPS: Battery charger failure. 0x012A Warning

UPS: Battery charger failure cleared. 0x012B Informational

UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational

UPS: No batteries installed. 0x012F Warning

UPS: No batteries installed cleared. 0x0130 Informational

UPS: Scheduled shutdown initiated. 0x0131 Informational

UPS: Scheduled shutdown failed. 0x0132 Warning

UPS: Scheduled shutdown deleted. 0x0133 Informational

(9)

Symmetra

Event Event

Code Default Severity

System: Coldstart. 0x0001 Severe

System: Warmstart. 0x0002 Severe

System: SNMP configuration change. 0x0003 Warning

System: Detected an unauthorized user attempting to access the SNMP

interface. 0x0004 Informational

System: Detected an unauthorized user attempting to access the Console

interface. 0x0005 Warning

System: Detected an unauthorized user attempting to access the Web

interface. 0x0006 Warning

System: Network service started. 0x0007 None

System: Password changed. 0x0008 Warning

System: File transfer started. 0x000C None

System: File transfer started. 0x000D None

System: File transfer failed. 0x000F None

System: Console user logged in. 0x0014 None

System: Web user logged in. 0x0015 None

System: FTP user logged in. 0x0016 None

System: Console user logged out. 0x001E None

System: Web user logged out. 0x001F None

System: FTP user logged out. 0x0020 None

System: Reset to defaults. 0x0018 None

System: Initializing data in the file. 0x0019 None

System: Email information. 0x001A None

System: Trace information. 0x0024 None

System: Modem dial-out failed. 0x0025 Warning

System: RMS CLI user logged in. 0x0026 None

System: RMS CLI user logged out. 0x0027 None

System: Network service information. 0x002A None

System: Network service could not start. 0x002B None

System: Network service stopped. 0x002C None

UPS: Communications established. 0x0101 Informational

UPS: Communications lost. 0x0102 Severe

UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe

UPS: Overload condition cleared. 0x0104 Informational

UPS: Passed internal self-test. 0x0105 Informational

UPS: Failed internal diagnostic self-test. 0x0106 Severe

UPS: Batteries discharged. 0x0107 Severe

UPS: Battery discharge condition cleared. 0x0108 Informational

UPS: Switched to battery backup power. 0x0109 Warning

UPS: Returned from battery backup power. 0x010A Informational

(10)

Symmetra (continued)

Event Event

Code Default Severity

UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning

UPS: Returned from SmartBoost. 0x010C Informational

UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning

UPS: Returned from SmartTrim. 0x010E Informational

UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational

UPS: Turned on. 0x0113 Informational

UPS: Turned off. 0x0114 Warning

UPS: Entered sleep mode. 0x0115 Warning

UPS: Returned from sleep mode. 0x0116 Informational

UPS: Started reboot sequence. 0x0117 Warning

UPS: Batteries need immediate replacement. 0x0119 Severe

UPS: Bad battery condition cleared. 0x011A Informational

UPS: In bypass due to an internal fault. 0x011B Severe

UPS: In bypass due to user command via software or panel. 0x011C Warning

UPS: In bypass initiated by user. 0x011D Warning

UPS: Returned from bypass. 0x011E Informational

UPS: Base module bypass power supply failure. 0x011F Severe

UPS: Base module fan failure. 0x0120 Severe

UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe

UPS: Battery calibration test initiated. 0x0123 Informational

UPS: Battery calibration complete. 0x0124 Informational

UPS: Graceful shutdown in progress. 0x0125 Informational

UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning

UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational

UPS: Bad output voltage condition. 0x0128 Warning

UPS: Bad output voltage condition cleared. 0x0128 Informational

UPS: Battery charger failure. 0x012A Warning

UPS: Battery charger failure cleared. 0x012B Informational

UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational

UPS: No batteries installed. 0x012F Warning

UPS: No batteries installed cleared. 0x0130 Informational

UPS: Scheduled shutdown initiated. 0x0131 Informational

UPS: Scheduled shutdown failed. 0x0132 Warning

UPS: Scheduled shutdown deleted. 0x0133 Informational

UPS: Power Module failure. 0x0201 Severe

UPS: Power Module failure cleared. 0x0202 Informational

UPS: Intelligence Module failure. 0x0203 Severe

UPS: Intelligence Module failure cleared. 0x0204 Informational

(11)

Symmetra (continued)

Event Event

Code Default Severity

UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational

UPS: Battery failure. 0x0207 Severe

UPS: Battery failure cleared. 0x0208 Informational

UPS: Load(kVA) alarm threshold violation. 0x0209 Severe

UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational

UPS: Redundancy lost. 0x020B Severe

UPS: Redundancy returned. 0x020C Informational

UPS: Redundancy below alarm threshold. 0x020D Severe

UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range cleared; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational

UPS: In bypass due to an internal fault. 0x0215 Severe

UPS: In bypass due to an internal fault cleared. 0x0216 Informational

UPS: In bypass due to an overload. 0x0217 Severe

UPS: In bypass due to an overload cleared. 0x0218 Informational

UPS: In maintenance bypass. 0x0219 Severe

UPS: In maintenance bypass cleared. 0x021A Informational

UPS: Input circuit breaker tripped open. 0x021B Severe

UPS: Input circuit breaker tripped open cleared. 0x021C Informational

UPS: System level fan failure. 0x021D Severe

UPS: System level fan failure cleared. 0x021E Informational

UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational

UPS: No working Power Modules. 0x0223 Severe

UPS: No working Power Modules cleared. 0x0224 Informational

UPS: Load shutdown from bypass; input frequency or voltage outside

limits. 0x0225 Severe

UPS: Load shutdown from bypass cleared; input frequency or voltage

outside limits. 0x0226 Informational

UPS: Runtime below alarm threshold. 0x0227 Severe

UPS: Runtime below alarm threshold cleared. 0x0228 Informational

UPS: Extended Run Frame fault. 0x0229 Severe

UPS: Extended Run Frame fault cleared. 0x022A Informational

UPS: Output voltage out of range. 0x022B Severe

(12)

Symmetra (continued)

Event Event

Code Default Severity

UPS: Output voltage out of range cleared. 0x022C Informational

UPS: Not synchronized fault. 0x022D Severe

UPS: Not synchronized fault cleared. 0x022E Informational

UPS: No batteries installed. 0x022F Severe

UPS: No batteries installed cleared. 0x0230 Informational

UPS: Battery voltage high. 0x0231 Severe

UPS: Battery voltage high cleared. 0x0232 Informational

UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe

UPS: Non-specific fault cleared. 0x0234 Informational

UPS: Site wiring fault. 0x0235 Severe

UPS: Site wiring fault cleared. 0x0236 Informational

UPS: Backfeed protection relay open. 0x0237 Severe

UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0X0240 Informational

UPS: Number of batteries increased. 0X0241 Informational

UPS: Number of batteries decreased. 0X0242 Informational

UPS: Number of Power Modules increased. 0X0243 Informational

UPS: Number of Power Modules decreased. 0X0244 Informational

UPS: Intelligence Module inserted. 0X0245 Informational

UPS: Intelligence Module removed. 0X0246 Informational

UPS: Redundant Intelligence Module inserted. 0X0247 Informational UPS: Redundant Intelligence Module removed. 0X0248 Informational UPS: Number of Extended Run Frames increased. 0X0249 Informational UPS: Number of Extended Run Frames decreased. 0X024A Informational

(13)

Symmetra 3-Phase

Event Event

Code Default Severity

System: Coldstart. 0x0001 Severe

System: Warmstart. 0x0002 Severe

System: SNMP configuration change. 0x0003 Warning

System: Detected an unauthorized user attempting to access the SNMP

interface. 0x0004 Informational

System: Detected an unauthorized user attempting to access the Console

interface. 0x0005 Warning

System: Detected an unauthorized user attempting to access the Web

interface. 0x0006 Warning

System: Network service started. 0x0007 None

System: Password changed. 0x0008 Warning

System: File transfer started. 0x000C None

System: File transfer started. 0x000D None

System: File transfer failed. 0x000F None

System: Console user logged in. 0x0014 None

System: Web user logged in. 0x0015 None

System: FTP user logged in. 0x0016 None

System: Console user logged out. 0x001E None

System: Web user logged out. 0x001F None

System: FTP user logged out. 0x0020 None

System: Reset to defaults. 0x0018 None

System: Initializing data in the file. 0x0019 None

System: Email information. 0x001A None

System: Trace information. 0x0024 None

System: Modem dial-out failed. 0x0025 Warning

System: RMS CLI user logged in. 0x0026 None

System: RMS CLI user logged out. 0x0027 None

System: Network service information. 0x002A None

System: Network service could not start. 0x002B None

System: Network service stopped. 0x002C None

UPS: Communications established. 0x0101 Informational

UPS: Communications lost. 0x0102 Severe

UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe

UPS: Overload condition cleared. 0x0104 Informational

UPS: Passed internal self-test. 0x0105 Informational

UPS: Failed internal diagnostic self-test. 0x0106 Severe

UPS: Batteries discharged. 0x0107 Severe

UPS: Battery discharge condition cleared. 0x0108 Informational

UPS: Switched to battery backup power. 0x0109 Warning

UPS: Returned from battery backup power. 0x010A Informational

(14)

Symmetra 3-Phase (continued)

Event Event

Code Default Severity

UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning

UPS: Returned from SmartBoost. 0x010C Informational

UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning

UPS: Returned from SmartTrim. 0x010E Informational

UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational

UPS: Turned on. 0x0113 Informational

UPS: Turned off. 0x0114 Warning

UPS: Entered sleep mode. 0x0115 Warning

UPS: Returned from sleep mode. 0x0116 Informational

UPS: Started reboot sequence. 0x0117 Warning

UPS: Batteries need immediate replacement. 0x0119 Severe

UPS: Bad battery condition cleared. 0x011A Informational

UPS: In bypass due to an internal fault. 0x011B Severe

UPS: In bypass due to user command via software or panel. 0x011C Warning

UPS: In bypass initiated by user. 0x011D Warning

UPS: Returned from bypass. 0x011E Informational

UPS: Base module bypass power supply failure. 0x011F Severe

UPS: Base module fan failure. 0x0120

UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe

UPS: Battery calibration test initiated. 0x0123 Informational

UPS: Battery calibration complete. 0x0124 Informational

UPS: Graceful shutdown in progress. 0x0125 Informational

UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning

UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational

UPS: Bad output voltage condition. 0x0128 Warning

UPS: Bad output voltage condition cleared. 0x0129 Informational

UPS: Battery charger failure. 0x012A Warning

UPS: Battery charger failure cleared. 0x012B Informational

UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational

UPS: No batteries installed. 0x012F Warning

UPS: No batteries installed cleared. 0x0130 Informational

UPS: Scheduled shutdown initiated. 0x0131 Warning

UPS: Scheduled shutdown failed. 0x0132 Informational

UPS: Scheduled shutdown deleted. 0x0133 Severe

UPS: Power Module failure. 0x0201 Severe

UPS: Power Module failure cleared. 0x0202 Informational

UPS: Intelligence Module failure. 0x0203 Severe

UPS: Intelligence Module failure cleared. 0x0204 Informational

(15)

Symmetra 3-Phase (continued)

Event Event

Code Default Severity

UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational

UPS: Battery failure. 0x0207 Severe

UPS: Battery failure cleared. 0x0208 Informational

UPS: Load(kVA) alarm threshold violation. 0x0209 Severe

UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational

UPS: Redundancy lost. 0x020B Severe

UPS: Redundancy returned. 0x020C Informational

UPS: Redundancy below alarm threshold. 0x020D Severe

UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational

UPS: In bypass due to an internal fault. 0x0215 Severe

UPS: In bypass due to an internal fault cleared. 0x0216 Informational

UPS: In bypass due to an overload. 0x0217 Severe

UPS: In bypass due to an overload cleared. 0x0218 Informational

UPS: In maintenance bypass. 0x0219 Severe

UPS: In maintenance bypass cleared. 0x021A Informational

UPS: Input circuit breaker tripped open. 0x021B Severe

UPS: Input circuit breaker tripped open cleared. 0x021C Informational

UPS: System level fan failure. 0x021D Severe

UPS: System level fan failure cleared. 0x021E Informational

UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational

UPS: No working Power Modules. 0x0223 Severe

UPS: No working Power Modules cleared. 0x0224 Informational

UPS: Load shutdown from bypass; input frequency or voltage outside

limits. 0x0225 Severe

UPS: Load shutdown from bypass cleared; input frequency or voltage

outside limits. 0x0226 Informational

UPS: Runtime below alarm threshold. 0x0227 Severe

UPS: Runtime below alarm threshold cleared. 0x0228 Informational

UPS: Extended Run Frame fault. 0x0229 Severe

UPS: Extended Run Frame fault cleared. 0x022A Informational

UPS: Output voltage out of range. 0x022B Severe

(16)

Symmetra 3-Phase (continued)

Event Event

Code Default Severity

UPS: Output voltage out of range cleared. 0x022C Informational

UPS: Not synchronized fault. 0x022D Severe

UPS: Not synchronized fault cleared. 0x022E Informational

UPS: No batteries installed. 0x022F Severe

UPS: No batteries installed cleared. 0x0230 Informational

UPS: Battery voltage high. 0x0231 Severe

UPS: Battery voltage high cleared. 0x0232 Informational

UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe

UPS: Non-specific fault cleared. 0x0234 Informational

UPS: Site wiring fault. 0x0235 Severe

UPS: Site wiring fault cleared. 0x0236 Informational

UPS: Backfeed protection relay open. 0x0237 Severe

UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0x0240 Informational

UPS: Number of batteries increased. 0x0241 Informational

UPS: Number of batteries decreased. 0x0242 Informational

UPS: Number of Power Modules increased. 0x0243 Informational

UPS: Number of Power Modules increased. 0x0244 Informational

UPS: Intelligence Module inserted. 0x0245 Informational

UPS: Intelligence Module removed. 0x0246 Informational

UPS: Redundant Intelligence Module inserted. 0x0247 Informational UPS: Redundant Intelligence Module removed. 0x0248 Informational UPS: Number of Extended Run Frames increased. 0x0249 Informational UPS: Number of Extended Run Frames decreased. 0x024A Informational UPS: Number of System Power Supplies increased. 0x024B Informational UPS: Number of System Power Supplies decreased. 0x024C Informational

UPS: External Switch Gear Q001 closed. 0x024D Informational

UPS: External Switch Gear Q001 opened. 0x024E Informational

UPS: External Switch Gear Q002 closed. 0x024F Informational

UPS: External Switch Gear Q002 opened. 0x0250 Informational

UPS: External Switch Gear Q003 closed. 0x0251 Informational

UPS: External Switch Gear Q003 opened. 0x0252 Informational

UPS: External Switch Gear Q004 closed. 0x0253 Informational

UPS: External Switch Gear Q004 opened. 0x0254 Informational

(17)

Symmetra 3-Phase (continued)

Event Event

Code Default Severity

UPS: External Switch Gear failure. 0x0A01 Severe

UPS: External Switch Gear failure cleared. 0x0A02 Informational UPS: External Transformer over temperature. 0x0A03 Severe UPS: External Transformer over temperature cleared. 0x0A04 Informational

UPS: External DC Circuit Breaker tripped. 0x0A05 Severe

UPS: External DC Circuit Breaker closed. 0x0A06 Informational

UPS: System Power Supply failure. 0x0A07 Severe

UPS: System Power Supply failure cleared. 0x0A08 Informational

UPS: Battery Monitor Card failure. 0x0A09 Severe

UPS: Battery Monitor Card failure cleared. 0x0A0A Informational

UPS: Battery Monitor Card removed. 0x0A0B Severe

UPS: Battery Monitor Card inserted. 0x0A0C Informational

UPS: XR Communication Card failure. 0x0A0D Severe

UPS: XR Communication Card failure cleared. 0x0A0E Informational

UPS: XR Communication Card removed. 0x0A0F Severe

UPS: XR Communication Card inserted. 0x0A10 Informational

UPS: External Switch Gear Monitoring Card failure. 0x0A11 Severe UPS: External Switch Gear Monitoring Card failure cleared. 0x0A12 Informational UPS: External Switch Gear Monitoring Card removed. 0x0A13 Severe UPS: External Switch Gear Monitoring Card inserted. 0x0A14 Informational

UPS: Internal DC Circuit Breaker tripped. 0x0A15 Severe

UPS: Internal DC Circuit Breaker closed. 0x0A16 Informational

UPS: Static Bypass Switch failure. 0x0A17 Severe

UPS: Static Bypass Switch failure cleared. 0x0A18 Informational

UPS: System EEProm removed. 0x0A19 Severe

UPS: System EEProm inserted. 0x0A1A Informational

UPS: System EEProm failure. 0x0A1B Severe

UPS: System EEProm failure cleared. 0x0A1C Informational

UPS: UPS is in forced bypassed. 0x0A1D Severe

UPS: UPS returned from forced bypassed. 0x0A1E Informational

UPS: Bit 15 of the second abnormal condition register set. 0x0A1F Severe UPS: Bit 15 of the second abnormal condition register cleared. 0x0A20 Informational UPS: Bit 16 of the second abnormal condition register set. 0x0A21 Severe UPS: Bit 16 of the second abnormal condition register cleared. 0x0A22 Informational UPS: Bit 17 of the second abnormal condition register set. 0x0A23 Severe UPS: Bit 17 of the second abnormal condition register cleared. 0x0A24 Informational UPS: Bit 18 of the second abnormal condition register set. 0x0A25 Severe UPS: Bit 18 of the second abnormal condition register cleared. 0x0A26 Informational UPS: Bit 19 of the second abnormal condition register set. 0x0A27 Severe UPS: Bit 19 of the second abnormal condition register cleared. 0x0A28 Informational UPS: Bit 20 of the second abnormal condition register set. 0x0A29 Severe

(18)

Symmetra 3-Phase (continued)

Event Event

Code Default Severity

UPS: Bit 20 of the second abnormal condition register cleared. 0x0A2A Informational UPS: Bit 21 of the second abnormal condition register set. 0x0A2B Severe UPS: Bit 21 of the second abnormal condition register cleared. 0x0A2C Informational UPS: Bit 22 of the second abnormal condition register set. 0x0A2D Severe UPS: Bit 22 of the second abnormal condition register cleared. 0x0A2E Informational UPS: Bit 23 of the second abnormal condition register set. 0x0A2F Severe UPS: Bit 23 of the second abnormal condition register cleared. 0x0A30 Informational UPS: Bit 24 of the second abnormal condition register set. 0x0A31 Severe UPS: Bit 24 of the second abnormal condition register cleared. 0x0A32 Informational UPS: Bit 25 of the second abnormal condition register set. 0x0A33 Severe UPS: Bit 25 of the second abnormal condition register cleared. 0x0A34 Informational UPS: Bit 26 of the second abnormal condition register set. 0x0A35 Severe UPS: Bit 26 of the second abnormal condition register cleared. 0x0A36 Informational UPS: Bit 27 of the second abnormal condition register set. 0x0A37 Severe UPS: Bit 27 of the second abnormal condition register cleared. 0x0A38 Informational UPS: Bit 28 of the second abnormal condition register set. 0x0A39 Severe UPS: Bit 28 of the second abnormal condition register cleared. 0x0A3A Informational UPS: Bit 29 of the second abnormal condition register set. 0x0A3B Severe UPS: Bit 29 of the second abnormal condition register cleared. 0x0A3C Informational UPS: Bit 30 of the second abnormal condition register set. 0x0A3D Severe UPS: Bit 30 of the second abnormal condition register cleared. 0x0A3E Informational UPS: Bit 31 of the second abnormal condition register set. 0x0A3F Severe UPS: Bit 31 of the second abnormal condition register cleared. 0x0A40 Informational UPS: Bit 32 of the second abnormal condition register set. 0x0A41 Severe UPS: Bit 32 of the second abnormal condition register cleared. 0x0A42 Informational UPS: Bit 33 of the second abnormal condition register set. 0x0A43 Severe UPS: Bit 33 of the second abnormal condition register cleared. 0x0A44 Informational UPS: Bit 34 of the second abnormal condition register set. 0x0A45 Severe UPS: Bit 34 of the second abnormal condition register cleared. 0x0A46 Informational UPS: Bit 35 of the second abnormal condition register set. 0x0A47 Severe UPS: Bit 35 of the second abnormal condition register cleared. 0x0A48 Informational UPS: Bit 36 of the second abnormal condition register set. 0x0A49 Severe UPS: Bit 36 of the second abnormal condition register cleared. 0x0A4A Informational UPS: Bit 37 of the second abnormal condition register set. 0x0A4B Severe UPS: Bit 37 of the second abnormal condition register cleared. 0x0A4C Informational UPS: Bit 38 of the second abnormal condition register set. 0x0A4D Severe UPS: Bit 38 of the second abnormal condition register cleared. 0x0A4E Informational UPS: Bit 39 of the second abnormal condition register set. 0x0A4F Severe UPS: Bit 39 of the second abnormal condition register cleared. 0x0A50 Informational UPS: Bit 40 of the second abnormal condition register set. 0x0A51 Severe UPS: Bit 40 of the second abnormal condition register cleared. 0x0A52 Informational

(19)

Symmetra 3-Phase (continued)

Event Event

Code Default Severity

UPS: Bit 41 of the second abnormal condition register set. 0x0A53 Severe UPS: Bit 41 of the second abnormal condition register cleared. 0x0A54 Informational UPS: Bit 42 of the second abnormal condition register set. 0x0A55 Severe UPS: Bit 42 of the second abnormal condition register cleared. 0x0A56 Informational UPS: Bit 43 of the second abnormal condition register set. 0x0A57 Severe UPS: Bit 43 of the second abnormal condition register cleared. 0x0A58 Informational UPS: Bit 44 of the second abnormal condition register set. 0x0A59 Severe UPS: Bit 44 of the second abnormal condition register cleared. 0x0A5A Informational UPS: Bit 45 of the second abnormal condition register set. 0x0A5B Severe UPS: Bit 45 of the second abnormal condition register cleared. 0x0A5C Informational UPS: Bit 46 of the second abnormal condition register set. 0x0A5D Severe UPS: Bit 46 of the second abnormal condition register cleared. 0x0A5E Informational UPS: Bit 47 of the second abnormal condition register set. 0x0A5F Severe UPS: Bit 47 of the second abnormal condition register cleared. 0x0A60 Informational UPS: Bit 48 of the second abnormal condition register set. 0x0A61 Severe UPS: Bit 48 of the second abnormal condition register cleared. 0x0A62 Informational UPS: Bit 49 of the second abnormal condition register set. 0x0A63 Severe UPS: Bit 49 of the second abnormal condition register cleared. 0x0A64 Informational UPS: Bit 50 of the second abnormal condition register set. 0x0A65 Severe UPS: Bit 50 of the second abnormal condition register cleared. 0x0A66 Informational UPS: Bit 51 of the second abnormal condition register set. 0x0A67 Severe UPS: Bit 51 of the second abnormal condition register cleared. 0x0A68 Informational UPS: Bit 52 of the second abnormal condition register set. 0x0A69 Severe UPS: Bit 52 of the second abnormal condition register cleared. 0x0A6A Informational UPS: Bit 53 of the second abnormal condition register set. 0x0A6B Severe UPS: Bit 53 of the second abnormal condition register cleared. 0x0A6C Informational UPS: Bit 54 of the second abnormal condition register set. 0x0A6D Severe UPS: Bit 54 of the second abnormal condition register cleared. 0x0A6E Informational UPS: Bit 55 of the second abnormal condition register set. 0x0A6F Severe UPS: Bit 55 of the second abnormal condition register cleared. 0x0A70 Informational UPS: Bit 56 of the second abnormal condition register set. 0x0A71 Severe UPS: Bit 56 of the second abnormal condition register cleared. 0x0A72 Informational UPS: Bit 57 of the second abnormal condition register set. 0x0A73 Severe UPS: Bit 57 of the second abnormal condition register cleared. 0x0A74 Informational UPS: Bit 58 of the second abnormal condition register set. 0x0A75 Severe UPS: Bit 58 of the second abnormal condition register cleared. 0x0A76 Informational UPS: Bit 59 of the second abnormal condition register set. 0x0A77 Severe UPS: Bit 59 of the second abnormal condition register cleared. 0x0A78 Informational UPS: Bit 60 of the second abnormal condition register set. 0x0A79 Severe UPS: Bit 60 of the second abnormal condition register cleared. 0x0A7A Informational UPS: Bit 61 of the second abnormal condition register set. 0x0A7B Severe

(20)

Symmetra 3-Phase (continued)

Event Event

Code Default Severity

UPS: Bit 61 of the second abnormal condition register cleared. 0x0A7C Informational UPS: Bit 62 of the second abnormal condition register set. 0x0A7D Severe UPS: Bit 62 of the second abnormal condition register cleared. 0x0A7E Informational UPS: Bit 63 of the second abnormal condition register set. 0x0A7F Severe UPS: Bit 63 of the second abnormal condition register cleared. 0x0A80 Informational

(21)

Environmental Monitor

Event Event

Code Default Severity

Environment: Contact 1 fault. 0x0301 Severe

Environment: Contact 1 fault cleared. 0x0302 Informational

Environment: Contact 2 fault. 0x0303 Severe

Environment: Contact 2 fault cleared. 0x0304 Informational

Environment: Contact 3 fault. 0x0305 Severe

Environment: Contact 3 fault cleared. 0x0306 Informational

Environment: Contact 4 fault. 0x0307 Severe

Environment: Contact 4 fault cleared. 0x0308 Informational

Environment: Low temperature threshold violation on probe 1. 0x0309 Severe Environment: Low temperature threshold violation on probe 1 cleared. 0x030A Informational Environment: High temperature threshold violation on probe 1. 0x030B Severe Environment: High temperature threshold violation on probe 1 cleared. 0x030C Informational Environment: Low humidity threshold violation on probe 1. 0x030D Severe Environment: Low humidity threshold violation on probe 1 cleared. 0x030E Informational Environment: High humidity threshold violation on probe 1. 0x030F Severe Environment: High humidity threshold violation on probe 1 cleared. 0x0310 Informational Environment: Low temperature threshold violation on probe 2. 0x0311 Severe Environment: Low temperature threshold violation on probe 2 cleared. 0x0312 Informational Environment: High temperature threshold violation on probe 2. 0x0313 Severe Environment: High temperature threshold violation on probe 2 cleared. 0x0314 Informational Environment: Low humidity threshold violation on probe 2. 0x0315 Severe Environment: Low humidity threshold violation on probe 2 cleared. 0x0316 Informational Environment: High humidity threshold violation on probe 2. 0x0317 Severe Environment: High humidity threshold violation on probe 2 cleared. 0x0318 Informational

Environment: Communications established. 0x0319 Informational

Environment: Communications lost. 0x031A Severe

Environment: Integrated contact fault. 0x031B Severe

Environment: Integrated contact fault cleared. 0x031C Informational Environment: Low temperature threshold violation on integrated probe. 0x031D Severe Environment: Low temperature threshold violation on integrated probe

cleared. 0x031E Informational

Environment: High temperature threshold violation on integrated probe. 0x031F Severe Environment: High temperature threshold violation on integrated probe

cleared.

0x0320 Informational

Environment: Low humidity threshold violation on integrated probe. 0x0321 Severe Environment: Low humidity threshold violation on integrated probe cleared. 0x0322 Informational Environment: High humidity threshold violation on integrated probe. 0x0323 Severe Environment: High humidity threshold violation on integrated probe cleared. 0x0324 Informational

Environment: Integrated relay output fault. 0x0325 Warning

Environment: Integrated relay output fault cleared. 0x0326 Warning

(22)

References

Related documents

It is recommended that the humidity probe with a section of probe cable be mounted inside the chamber (see Figure 1) to make sure that whole probe is in temperature

[15] The aim of this study was to report an interesting early diagnosed case of AF which affected mandible of a young girl and was associated with an

PrimerSeq incorporates user-provided tran- scriptome profiles (i.e., RNA-seq data) in the design process, and is particularly useful for large- scale quantitative analysis of AS

The main economic impacts of tourism relate to foreign exchange earnings, contributions to government revenues, generation of employment and income, and inspiration to

An in-depth discussion of the financial system is beyond the scope of this article and for now the focus will only be on the Islamic Securitization structures (Sukukization) for

Available with a number of different probe configurations and with display of relative humidity, absolute humidity and temperature, the DM Series is suitable for a wide range

The projects highlight the first two phases of the DBR framework, involving the exploration of mobile virtual reality (VR) to enhance the learning environment, and the design

When mounting the testo 6614 heated probe version, the temperature probe must be secured as close to the humidity probe as possible (max.. An appropriate assembly tool is supplied