NEW PORT PROJECT

NEW PORT PROJECT

NEW PORT PROJECT

NEW PORT PROJECT

CONTAINER TERMINAL, INFRASTRUCTURE AND

UTILITY BUILDINGS

NPP/0026

Document Title :

CONTAINER TERMINAL-1

LV CABLE SIZING CALCULATIONS

Document No. DPCT-TCC-CAL-EL-00066

TEYSEER CONTRACTING COMPANY WLL/

CONSOLIDATED CONTRACTORS GROUP S.A.L.

(OFFSHORE) (CCC) JV

TCC/CCC JV

01 RE-ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash

00 ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash

Rev Description Prepared

by Reviewed by Approved by Signature: Date: 14.08.2014 14.08.2014 14.08.2014

(2)

TABLE OF CONTENTS

1.

SCOPE ... 3

2.

REFERENCE DOCUMENTS ... 3

3.

INITIAL DATA AND ASSUMPTIONS ... 3

4.

CABLE SIZING CRITERIA ... 4

4.1.

VOLTAGE DROP ... 5

4.2.

AMPACITY ... 6

4.3.

SHORT CIRCUIT ... 6

5.

CABLE SIZING REQUIREMENTS ... 7

5.1.

VOLTAGE DROP ... 7

5.2.

AMPACITY ... 7

6.

DE-RATING FACTORS FOR CABLES. ... 8

6.1.

De-rating factors for cables installed in Ducts in the ground. ... 8

6.2.

De-rating factors for cables Installed in Air. ... 9

6.3.

THERMAL SHORT CIRCUIT CAPACITY... 10

(3)

1. SCOPE

The objective of this calculation report is to establish the method to be used for the sizing of the Low Voltage

power cables for the Low Voltage power distribution system and motors at Container Terminal-1 Utility

Buildings and Infrastructure of New Doha Port Project.

2. REFERENCE DOCUMENTS

The following documents have been taken into account for the cable sizing calculation:

• Specification Section 21: Electrical Works

:

9224-05-EL-SPC-7001

• Regulation for Installation of Electrical

Wiring, Electrical Equipment and Air

Conditioning Equipment-Dec 2010

:

QGEWC / KAHRAMAA

• IEC Electrical Installation of Buildings

:

IEC-60364-5-52-2001

Selection and erection of Electrical

Equipment – Wiring Systems

• “DOHA CABLES” Catalogue for XLPE Insulated

Low Voltage Cables.

3. INITIAL DATA AND ASSUMPTIONS

The power cables have been sized taking into consideration the following data and cable type:

• Nominal voltage system: 240 / 415V

• Cable insulation level BS(IEC) kV: 0.6/1 kV (0.6/1 kV)

• Conductor material: Cu (Copper)

• Insulation material: XLPE

o

Maximum conductor operating temperature: 90ºC

o

Maximum short circuit temperature: 250ºC

• Thermal Resistivity values for direct buried cable installations: 2.0°C. m/W

(KM standards section 3.3.12.1 and Specification Section 21: Electrical Works)

• Design conditions for electrical cables:

o

Underground cable (buried)

40°C

o

In air

50°C

The LV cables for power distribution system and the loads shall be as follows:

• Cable shall comprise of plain copper, stranded circular conductors insulated with an adequate

thickness of extruded cross linked polyethylene (XLPE).

(4)

• Up to 10 Sqmm Cu/XPLE/PVC, unarmoured cable for indoor installations.

• 16 Sqmm and above Cu/XLPE/SWA/PVC for armoured multicore cable for both indoor and outdoor

installations.

• Cu/XLPE/SWA/LSHF armoured cable for the power supply to D & B (Manned) Buildings from the

Utility Buildings.

• Armoured multicore cable shall have steel wire armouring and extruded sheath of black PVC.

• Armoured single core cable shall have aluminium wire armouring and extruded sheath of black PVC.

The cable sizing will be performed considering multi-core cables up to 240 mm

2

for distribution cables. For

power, lighting and control cables the minimum cross section shall be 2.5 mm

2

. Maximum cross section for

single-core cables shall be 630mm

2

. Single core cables may be used for practical and/or economic reasons,

e.g., transformer secondary cables or in case of high current ratings where two parallel multicore cables of

the largest cross section permitted would not suffice. All three single core cables shall be laid in trefoil

formation.

Sizing of motor feeders and power feeders will be performed taken into account the Full Load Ampacity

(FLA) of the equipment (100% loaded). The system voltage is assumed to be at 100% nominal voltage.

Standard power factors and efficiencies at 90% load will be used in this calculation, in case of absence of

precise data.

All LV Cables shall be installed in ducts throughout the Container Terminal-1 Area. The uPVC ducts are

provided with the concrete encasement for LV Cables at road crossings only. The LV Cables shall be laid at

a depth of 600mm as minimum.

In the Container Terminal-1 Area, all the ducts shall be installed with minimum ground cover of 900mm

otherwise it shall be concrete encased.

All LV cables in Buildings shall be installed on cable trays/ Trunking/ Conduits as per Specification section

21: Electrical Works Doc. No.: 9224-05-EL-SPC-7001 clause 9.3.3.

The correction factors / de-rating factors for the cables installed in Ducts and in Air are taken from “DOHA

CABLES” Catalogue.

4. CABLE SIZING CRITERIA

Sizing of LV cables will be based on the compliance of all of the following criteria:

• Voltage Drop

• Continuous Current Carrying Capacity (Ampacity)

• Thermal Short Circuit Capacity

(5)

4.1. VOLTAGE DROP

A feeder shall be sized in such a way that the maximum voltage drop over the cable ensures the proper

operation of the associated equipment in normal service. Excessive voltage drop will result in unsatisfactory

operation of electrical equipment, and represents energy wasted in the cabling system. Voltage drop can

also cause damage to electrical Equipment.

The following formula will determine the voltage drop:

• For feeders and motors under running conditions (three phases and single phase):

• For motors under starting conditions (three phases and single phase):

(

)

V

n

Xc

Rc

l

I

k

V

d starting s s

·

100

·

· sin

·cos

·

·

·

ϕ

+

ϕ

=

• DC voltage drop can be computed using the formula:

V

n

Rdc

l

I

V

N d

·

100

·

·

·

·

2

=

Where: V

d

Voltage drop in percentage

I

N

Rated current (FLA for motors) in Amps

I

starting

Starting rated current in Amps

V

System voltage in volts

n

Number of parallel runs

l

Length (km)

R

c

AC conductor resistance at rated conductor temperature at 90 Degree C in (Ω/km)

X

c

Reactance of the cable (Ω/km) at 50Hz, (For R

c

and X

c

Values see Appendix 14).

cos

ϕ Power factor

cos

ϕ

s

Starting power factor

k

√3 for three-phase consumers and 2 for single phase consumers.

Note: The voltage drops are related to the terminals of the end equipment, and assumes that the associated

main switchboard from which the equipment is fed will normally be operated at a voltage of not less than

100% of system voltage.

(

)

V

n

Xc

Rc

l

I

k

V

N d

·

100

·

· sin

· cos

·

·

·

ϕ

+

ϕ

=

(6)

4.2. AMPACITY

The current carrying capacity of a cable corresponds to the maximum current that it can carry under

specified conditions without the conductor exceeding the permissible limit of steady state temperature for the

type of insulation concerned. De-rating or correction factors are applied where the installation conditions

differ from those for which values of current carrying capacity are defined. The following de-rating factors will

be applied depending on the type of installation.

• Installation Trenches and Duct Banks (Below ground)

o

Thermal resistivity of soil : F

s

o

Depth of laying : F

d

o

Ground temperature : F

t

o

Grouping factor : F

g

• Above ground installation (In Air – Indoor / Outdoor)

o

Ambient air temperature : F

t

o

Grouping factor : F

g

The current carrying capacity required under given conditions can be calculated as follows:

Where:

I

cable_amp

Cable ampacity (current rating of the cable for the conditions defined in the

manufacturer’s catalogue, see Clause 5.2 below)

I

N

Load Current

F

G

Global de-rating factor (F

G

= F

g

·F

t

·F

d

·F

s

)

F

g

De-rating grouping factor (e.g. 5 cables spaced 0.150m direct buried)

F

t

De-rating temperature factor (e.g. soil temperature 40ºC instead of 15ºC)

F

d

De-rating factor for depths of laying of cables

F

s

De-rating factor for thermal resistivity of soil

F

D

Design factor

4.3. SHORT CIRCUIT

The minimum conductor sizes suitable to withstand the applicable short circuit conditions are calculated

based on the maximum permissible conductor temperature of 250ºC as follows (valid where t ≤ 5sec).

2

ln

1

mm

t

I

K

S

i f

β

θ

β

θ

+

+

×

×

G D N amp cable

F

F

I

I

_

(7)

Where:

S

Minimum cross-section area of the cable (mm

2

)

I

Short circuit current

t

Short circuit time rating (seconds)

θi

Max. permissible continuous conductor temperature ºC, (XLPE insulation: 90ºC)

θ

f

Max. allowable conductor temp. at end of short circuit (XLPE insulation:250 ºC)

β

It is the reciprocal of the resistance variation of the conductor at 0º C. (Copper β=234.5)

K

Constant. Depends on material of the conductor (Copper K =143.08)

5. CABLE SIZING REQUIREMENTS

5.1. VOLTAGE DROP

As per BS 7671: 4%

As per QGEWC: 2.5% (From utility LV Connection Point)

The maximum permissible voltage drop for three phase 415V system shall be 4%.

The Voltage drop is measured from the LV terminal of the Transformer to the final load in a LV Circuit.

5.2. AMPACITY

Cable size will be selected in order to comply with ampacity criterion. The allowable cable ampacities for this

project are determined following the application of the appropriate correction/de-rating factors which are

applied where the installation and environmental conditions differ from those for which the values of current

carrying capacity are defined.

The following factors (de-rating and over-sizing factors) will be used in the calculation depending on the type

of installation:

(8)

6. De-rating factors for cables.

Ampacities data were taken from “DOHA CABLES” Catalogue (Appendix 1). The data is based upon normal

conditions which are:

• Ground temperature:

35ºC

• Ambient Air temperature:

40ºC

• Depth of laying:

0.5m

• Soil Thermal resistivity:

1.2 K·m/W

In order to update them to the project conditions the following correction factors from “DOHA CABLES”

Catalogue will be used:

6.1. De-rating factors for cables installed in Ducts in the ground.

Total de-rating factors will be as follows:

De-Rating Factors

Value

Reference “DOHA CABLES”

Catalogue

Ground temperature @ 40ºC : F

t

0.95

Appendix-3

Depth of laying @ 2m – Multi

Core : F

d

0.88

Appendix-5

Depth of laying @ 2m – Single

Core : F

d

0.85

Appendix-5

Soil thermal resistivity @ 2.0

K·m/W – Three Core and Single

Core Cables : F

s

0.80

Appendix-6

Cable grouping factor – Multicore

Cables : F

g

0.67

Appendix-8

Cable grouping factor – Single

Core Cables : F

g

(Trefoil formation)

0.64

Appendix-7

Global de-rating factors will be as follows:

De-Rating Factors

Multicore cables

Single-core cables

Ground temperature : F

t

0.95

0.95

Depth of laying @ 2m : F

d

0.88

0.85

Soil thermal resistivity @ 2.0 : F

s

0.80

0.80

Grouping factor : F

g

0.67

0.64

(9)

6.2. De-rating factors for cables Installed in Air.

Ampacities data were taken from “DOHA CABLES” Catalogue (Appendix 1).

In order to update them to the project conditions the following correction factors from “DOHA CABLES”

Catalogue will be used:

De-rating factors

Value

Ref. “DOHA CABLES”

Catalogue

Ambient temperature @ 50ºC – Installed Outdoor / Non

Air-conditioned Area : F

t

0.89

Appendix 4

Ambient temperature @ 35ºC – Installed Indoor /

Air-conditioned Area : F

t

1.05

Appendix 4

Cable grouping factor for Multicore cables : F

g

0.93

Appendix 9

Cable grouping factor for Single core cables : F

g

0.90

Appendix 10

Design Factor

125%

Note: De-rating grouping factor corresponds to a single layer installation in a ladder type cable tray with a

maximum grouping of 3 three-phase circuits for single core cables (up to 6 circuits for multi-core cables) and

up to 3 levels of cable trays (300mm spacing between trays). The different circuits for single core cables

must be installed spaced at least two (2) external diameters of the single-core cable.

• Global De-rating factors will be as follows:

De-rating factors for cables Installed in Air (Installed Indoor / Air-conditioned Area).

Multicore cables

Single-core cables

Temperature factor : F

t

1.05

1.05

Grouping factor : F

g

0.93

0.90

Global De-rating : F

G

0.97

0.94

De-rating factors for cables Installed in Air (Installed Outdoor / Non Air-conditioned Area).

Multicore cables

Single-core cables

Temperature factor : F

t

0.89

0.89

Grouping factor : F

g

0.93

0.90

Global De-rating : F

G

0.82

0.80

The design factor of 25% will be employed to oversize incoming cables to LV switchgears to allow 25%

spare capacity for the future loads on all the incoming cables.

(10)

6.3. THERMAL SHORT CIRCUIT CAPACITY

For incomer cables to all the switchgears the short circuit rating of the switchgear shall be used for the value

of short circuit current. The value for t has been taken as 1 sec for incomer circuit breakers.

According to the equation under paragraph 4.3 and taking into account the above clearance times, the

minimum conductor sizes shall be calculated.

The minimum calculated Short Circuit Ratings of conductor from “DOHA CABLES” manufacturer are

provided in the Appendix-11:

For switchgear outgoings (feeders and motor starters) the current limiting characteristic of the circuit breaker

has been taken into account in order to size the minimum cable sizes. For that purpose, let-through energy

curves of circuit breakers to be installed in the switchgear have been analysed.

The following formulae will be used:

2 2 2

mm

k

t

I

S

×

Where:

I

2

·t = Specific circuit breaker let-through energy

(11)

• Circuit breakers ≤ 63A (ABB Tmax T2 160A)

I

rms

= 80Ka

I

2

·t = 0.22 10

6

(12)

• Circuit breakers ≤ 160A (ABB Tmax T2 160A)

I

rms

= 80Ka

I

2

·t = 0.39 10

6

(13)

• Circuit breakers > 160A & ≤ 800A (ABB T6 800A)

I

rms

= 80Ka

I

2

·t = 19 10

6

(14)

7. APPENDICES

Appendix 1.

Current ratings for single and multi-core cables (“DOHA CABLES” Catalogue).

Appendix 2.

AC resistance (R) and reactance (X) for Single and multi-core Cables,

reference from “DOHA CABLES” catalogue.

Appendix 3.

Rating Factors for Ground Temperature, Reference from “DOHA CABLES”

Catalogue.

Appendix 4.

Rating Factors for Air Temperature, Reference from “DOHA CABLES”

Catalogue.

Appendix 5.

Rating Factors for Depth of Laying, Reference from “DOHA CABLES”

Catalogue.

Appendix 6.

Rating Factors for Variation in Thermal Resistivity of Soil (average values),

Reference from “DOHA CABLES” Catalogue.

Appendix 7.

Rating Factors for Trefoil Formation for Three Single Core Cables Laid Direct

in Ground, Reference from “DOHA CABLES” Catalogue.

Appendix 8.

Rating Factors for Trefoil Formation for Multi-Core Cables Laid Direct in

Ground. Reference from “DOHA CABLES” Catalogue.

Appendix 9.

Rating Factors for groups of more than one multi-core cable in air

To be applied to the current-carrying capacity for one multi-core cable in free

air. Reference from “DOHA CABLES” Catalogue.

Appendix 10

Rating Factors for groups of more than one circuit of single-core cables

To be applied to the current-carrying capacity for one circuit of single-core

cables in free air. Reference from “DOHA CABLES” Catalogue.

Appendix 11

Short Circuit Ratings of Conductors for 1 Sec in kA. Reference from “DOHA

CABLES” Catalogue.

Appendix 12

Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air

(Indoor) on cable trays (Power Distribution Feeders - From LV Switch Board to

Distribution Panels).

Appendix 13

Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/PVC cables –

Laid in Air (Indoor) on cable trays (From LV Switch Board to Final Loads.).

Appendix 14

Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC

cables – Laid in Air (Indoor/Outdoor) on cable trays (Power Distribution

Feeders - From LV Switch Board to Distribution Panels).

Appendix 15

Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC

cables – Laid in Air (Indoor/Outdoor) on cable (From LV Switch Board to Final

Loads).

(15)

Appendix 16

Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC

cables – Laid in Ducts (Outdoor), (Power Distribution Feeders - From LV

Switch Board to Distribution Panels).

Appendix 17

Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC

cables – Laid in Ducts (Outdoor), (From LV Switch Board to Final Loads).

Appendix 18

Cable selection chart for 230V-1 Phase, Multi Core Cu/XLPE/PVC cables –

Laid in Air (Indoor) on cable trays (From LV Switch Board to Final Loads).

Appendix 19

Cable selection chart for 230V-1 Phase, Multi Core Cu/XLPE/SWA/PVC

cables – Laid in Air (Indoor/Outdoor) on cable trays (From LV Switch Board to

Final Loads).

Appendix 20

Cable selection chart for 230V-1 Phase, Multi Core Cu/XLPE/SWA/PVC

cables – Laid in Ducts (Indoor/Outdoor) on cable trays (From LV Switch Board

to Final Loads).

Appendix 21

Cable selection chart for 415V-3 Phase, Single Core Cu/XLPE/SWA/PVC

cables – Laid in Air (Indoor/Outdoor) on cable trays (Power Distribution

Feeders - From LV Switch Board to Distribution Panels).

Appendix 22

Cable selection chart for 415V-3 Phase, Single Core Cu/XLPE/SWA/PVC

cables – Laid in Ducts (Outdoor), (Power Distribution Feeders - From LV

Switch Board to Distribution Panels).

Appendix 23

Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air

(Indoor) on cable trays (For 3 Phase LV Motor Feeders – At Run - From LV

Switch Board to LV Motors).

Appendix 24

Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air

(Indoor) on cable trays (For 3 Phase LV Motor Feeders – At Starting - From

LV Switch Board to LV Motors).

Appendix 25

Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air

(Indoor) on cable trays (For 3 Phase LV Motor Feeders – Selection Sheet -

From LV Switch Board to LV Motors).

Appendix 26

Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in

Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders –At Run -

From LV Switch Board to LV Motors).

Appendix 27

Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in

Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders – At

Starting - From LV Switch Board to LV Motors).

Appendix 28

Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in

Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders –

Selection Sheet - From LV Switch Board to LV Motors).

Appendix 29

Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in

Ducts (For 3 Phase LV Motor Feeders – At Run - From LV Switch Board to LV

Motors).

(16)

Appendix 30

Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in

Ducts (For 3 Phase LV Motor Feeders – At Starting - From LV Switch Board to

LV Motors).

Appendix 31

Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in

Ducts (For 3 Phase LV Motor Feeders – Selection Sheet - From LV Switch

Board to LV Motors).

(17)

Appendix 1 & 2. Current ratings and AC resistance (R) & reactance (X) for Single and

multi-core Cables, reference from “DOHA CABLES” catalogue.

Note: The Current Carrying Capacities, Cable Resistances & Reactances and Cable

overall diameter is typical for the LSHF cables (Low Smoke Halogen Free).

(18)

Note: The Current Carrying Capacities, Cable Resistances & Reactances and Cable

overall diameter is typical for the LSHF cables (Low Smoke Halogen Free).

(19)

Appendix 3. Rating Factors for Ground Temperature, Reference from “DOHA

CABLES” Catalogue.

Appendix 4. Rating Factors for Air Temperature, Reference from “DOHA CABLES”

Catalogue.

Appendix 5. Rating Factors for Depth of Laying, Reference from “DOHA CABLES”

Catalogue.

(20)

Appendix 6. Rating Factors for Variation in Thermal Resistivity of Soil (average

values). Reference from “DOHA CABLES” Catalogue.

Appendix 7. Rating Factors for Trefoil Formation for Three Single Core Cables Laid

Direct in Ground. Reference from “DOHA CABLES” Catalogue.

(21)

Appendix 8. Rating Factors for Trefoil Formation for Multi-Core Cables Laid Direct in

Ground. Reference from “DOHA CABLES” Catalogue.

(22)

Appendix 9. Rating Factors for groups of more than one multi-core cable in air

To be applied to the current-carrying capacity for one multi-core cable in free air.

Reference from “DOHA CABLES” Catalogue.

(23)

Appendix 10. Rating Factors for groups of more than one circuit of single-core cables

To be applied to the current-carrying capacity for one circuit of single-core cables in

free air. Reference from “DOHA CABLES” Catalogue.

(24)

Appendix 11. Short Circuit Ratings of Conductors for 1 Sec in kA. Reference from

“DOHA CABLES” Catalogue.

(25)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01 415 V 3-PH POWER FEEDER

0.6/1 kV, CU/XLPE/PVC(FOUR CORES CABLE - UNARMOURED)

50 Hz 1 0.97 4 X 4 4 X 6 4 X 10 - - - - - - - - - - - - - -36 44 60 - - - -34.92 42.68 58.2 - - - -5.8800 3.9300 2.3300 - - - -0.0933 0.0888 0.0856 - - - -LOAD RATING kW

I

N LOAD F.L.C AMPS** COSΦ SINΦ 0.25 0.41 0.85 0.53 1160.19 1728.72 2890.83 - - - -0.37 0.61 0.85 0.53 783.91 1168.05 1953.27 - - - -0.55 0.90 0.85 0.53 527.36 785.78 1314.02 - - - -0.75 1.23 0.85 0.53 386.73 576.24 963.61 - - - -1.50 2.46 0.85 0.53 193.36 288.12 481.81 - - - -2.50 4.09 0.85 0.53 116.02 172.87 289.08 - - - -3.00 4.91 0.85 0.53 96.68 144.06 240.90 - - - -4.00 6.55 0.85 0.53 72.51 108.04 180.68 - - - -5.50 9.00 0.85 0.53 52.74 78.58 131.40 - - - -7.50 12.28 0.85 0.53 38.67 57.62 96.36 - - - -11.00 18.00 0.85 0.53 26.37 39.29 65.70 - - - -15.00 24.55 0.85 0.53 19.34 28.81 48.18 - - - -18.50 30.28 0.85 0.53 15.68 23.36 39.07 - - - -22.00 36.01 0.85 0.53 - 19.64 32.85 - - - -25.00 40.92 0.85 0.53 - 17.29 28.91 - - - -30.00 49.10 0.85 0.53 - - 24.09 - - - -37.00 60.56 0.85 0.53 - - - -45.00 73.65 0.85 0.53 - - - -55.00 90.02 0.85 0.53 - - - -61.00 99.84 0.85 0.53 - - - -75.00 122.75 0.85 0.53 - - - -110.00 180.04 0.85 0.53 - - - -132.00 216.05 0.85 0.53 - - - -150.00 245.51 0.85 0.53 - - - -160.00 261.87 0.85 0.53 - - - -185.00 302.79 0.85 0.53 - - - -200.00 327.34 0.85 0.53 - - - -220.00 360.08 0.85 0.53 - - - -250.00 409.18 0.85 0.53 - - - -280.00 458.28 0.85 0.53 - - -

-**

I

N

(FLC) = (LOAD x 1000)

***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT)

SQRT(3) x

I

N

x (RcosΦ + XsinΦ)

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

* SITE CABLE RATING = CCC x DERATING FACTOR

DERATING FACTOR = CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING

*

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) CABLE SELECTION CHART FOR CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP = % AT F.L.C

(26)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01 415 V 3-PH POWER FEEDER

0.6/1 kV, CU/XLPE/PVC(FOUR CORES CABLE - UNARMOURED)

50 Hz 2.5 0.97 4 X 4 4 X 6 4 X 10 - - - - - - - - - - - - - -36 44 60 - - - -34.92 42.68 58.2 - - - -5.8800 3.9300 2.3300 - - - -0.0933 0.0888 0.0856 - - - -LOAD RATING kW

I

N LOAD F.L.C AMPS** COSΦ SINΦ 0.25 0.41 0.85 0.53 2900.47 4321.80 7227.08 - - - -0.37 0.61 0.85 0.53 1959.78 2920.13 4883.16 - - - -0.55 0.90 0.85 0.53 1318.40 1964.45 3285.04 - - - -0.75 1.23 0.85 0.53 966.82 1440.60 2409.03 - - - -1.50 2.46 0.85 0.53 483.41 720.30 1204.51 - - - -2.50 4.09 0.85 0.53 290.05 432.18 722.71 - - - -3.00 4.91 0.85 0.53 241.71 360.15 602.26 - - - -4.00 6.55 0.85 0.53 181.28 270.11 451.69 - - - -5.50 9.00 0.85 0.53 131.84 196.45 328.50 - - - -7.50 12.28 0.85 0.53 96.68 144.06 240.90 - - - -11.00 18.00 0.85 0.53 65.92 98.22 164.25 - - - -15.00 24.55 0.85 0.53 48.34 72.03 120.45 - - - -18.50 30.28 0.85 0.53 39.20 58.40 97.66 - - - -22.00 36.01 0.85 0.53 - 49.11 82.13 - - - -25.00 40.92 0.85 0.53 - 43.22 72.27 - - - -30.00 49.10 0.85 0.53 - - 60.23 - - - -37.00 60.56 0.85 0.53 - - - -45.00 73.65 0.85 0.53 - - - -55.00 90.02 0.85 0.53 - - - -61.00 99.84 0.85 0.53 - - - -75.00 122.75 0.85 0.53 - - - -110.00 180.04 0.85 0.53 - - - -132.00 216.05 0.85 0.53 - - - -150.00 245.51 0.85 0.53 - - - -160.00 261.87 0.85 0.53 - - - -185.00 302.79 0.85 0.53 - - - -200.00 327.34 0.85 0.53 - - - -220.00 360.08 0.85 0.53 - - - -250.00 409.18 0.85 0.53 - - - -280.00 458.28 0.85 0.53 - - -

-**

I

N

(FLC) = (LOAD x 1000)

***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT)

SQRT(3) x

I

N

x (RcosΦ + XsinΦ)

% AT F.L.C

From LV Switch Board to Final Loads.

DERATING FACTOR = CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING

*

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE SELECTION CHART FOR

CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP =

CABLE REACTANCE in OHM/KM (X)

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

(27)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01 415 V 3-PH POWER FEEDER

0.6/1 kV, CU/XLPE/PVC(FOUR CORES CABLE - ARMOURED)

50 Hz 1 0.82 4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240) 37 45 61 80 109 131 164 196 243 280 334 365 434 560 668 730 868 30.34 36.9 50.02 65.6 89.38 107.4 134.48 160.7 199.26 229.6 273.9 299.3 355.9 459.2 547.76 598.6 711.76 5.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.0982 0.0799 0.0642 0.0494 0.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355 LOAD RATING kWLOAD F.L.C

I

N

AMPS** COSΦ SINΦ

0.25 0.41 0.85 0.53 1160.52 1729.85 2886.47 4539.39 7044.45 9593.14 12746.06 17738.65 23614.98 28656.19 33819.04 39958.97 48241.67 57312.37 67638.07 79917.94 96483.35 - -0.37 0.61 0.85 0.53 784.14 1168.82 1950.32 3067.16 4759.76 6481.85 8612.20 11985.57 15956.07 19362.29 22850.70 26999.30 32595.72 38724.58 45701.40 53998.61 65191.45 - -0.55 0.90 0.85 0.53 527.51 786.29 1312.03 2063.36 3202.02 4360.52 5793.66 8063.02 10734.08 13025.54 15372.29 18163.17 21928.03 26051.08 30744.58 36326.33 43856.07 - -0.75 1.23 0.85 0.53 386.84 576.62 962.16 1513.13 2348.15 3197.71 4248.69 5912.88 7871.66 9552.06 11273.01 13319.66 16080.56 19104.12 22546.02 26639.31 32161.12 - -1.50 2.46 0.85 0.53 193.42 288.31 481.08 756.56 1174.07 1598.86 2124.34 2956.44 3935.83 4776.03 5636.51 6659.83 8040.28 9552.06 11273.01 13319.66 16080.56 - -2.50 4.09 0.85 0.53 116.05 172.98 288.65 453.94 704.44 959.31 1274.61 1773.86 2361.50 2865.62 3381.90 3995.90 4824.17 5731.24 6763.81 7991.79 9648.33 - -3.00 4.91 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -4.00 6.55 0.85 0.53 72.53 108.12 180.40 283.71 440.28 599.57 796.63 1108.67 1475.94 1791.01 2113.69 2497.44 3015.10 3582.02 4227.38 4994.87 6030.21 - -5.50 9.00 0.85 0.53 52.75 78.63 131.20 206.34 320.20 436.05 579.37 806.30 1073.41 1302.55 1537.23 1816.32 2192.80 2605.11 3074.46 3632.63 4385.61 - -7.50 12.28 0.85 0.53 38.68 57.66 96.22 151.31 234.81 319.77 424.87 591.29 787.17 955.21 1127.30 1331.97 1608.06 1910.41 2254.60 2663.93 3216.11 - -11.00 18.00 0.85 0.53 26.38 39.31 65.60 103.17 160.10 218.03 289.68 403.15 536.70 651.28 768.61 908.16 1096.40 1302.55 1537.23 1816.32 2192.80 - -15.00 24.55 0.85 0.53 19.34 28.83 48.11 75.66 117.41 159.89 212.43 295.64 393.58 477.60 563.65 665.98 804.03 955.21 1127.30 1331.97 1608.06 - -18.50 30.28 0.85 0.53 15.68 23.38 39.01 61.34 95.20 129.64 172.24 239.71 319.12 387.25 457.01 539.99 651.91 774.49 914.03 1079.97 1303.83 - -22.00 36.01 0.85 0.53 - 19.66 32.80 51.58 80.05 109.01 144.84 201.58 268.35 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -25.00 40.92 0.85 0.53 - - 28.86 45.39 70.44 95.93 127.46 177.39 236.15 286.56 338.19 399.59 482.42 573.12 676.38 799.18 964.83 - -30.00 49.10 0.85 0.53 - - 24.05 37.83 58.70 79.94 106.22 147.82 196.79 238.80 281.83 332.99 402.01 477.60 563.65 665.98 804.03 - -37.00 60.56 0.85 0.53 - - - 30.67 47.60 64.82 86.12 119.86 159.56 193.62 228.51 269.99 325.96 387.25 457.01 539.99 651.91 - -45.00 73.65 0.85 0.53 - - - - 39.14 53.30 70.81 98.55 131.19 159.20 187.88 221.99 268.01 318.40 375.77 443.99 536.02 - -55.00 90.02 0.85 0.53 - - - 43.61 57.94 80.63 107.34 130.26 153.72 181.63 219.28 260.51 307.45 363.26 438.56 - -61.00 99.84 0.85 0.53 - - - 39.32 52.24 72.70 96.78 117.44 138.60 163.77 197.71 234.89 277.21 327.53 395.42 - -75.00 122.75 0.85 0.53 - - - 42.49 59.13 78.72 95.52 112.73 133.20 160.81 191.04 225.46 266.39 321.61 - -110.00 180.04 0.85 0.53 - - - 53.67 65.13 76.86 90.82 109.64 130.26 153.72 181.63 219.28 - -132.00 216.05 0.85 0.53 - - - 54.27 64.05 75.68 91.37 108.55 128.10 151.36 182.73 - -150.00 245.51 0.85 0.53 - - - 56.37 66.60 80.40 95.52 112.73 133.20 160.81 - -160.00 261.87 0.85 0.53 - - - 52.84 62.44 75.38 89.55 105.68 124.87 150.76 - -185.00 302.79 0.85 0.53 - - - 65.19 77.45 91.40 108.00 130.38 - -200.00 327.34 0.85 0.53 - - - 60.30 71.64 84.55 99.90 120.60 - -220.00 360.08 0.85 0.53 - - - 65.13 76.86 90.82 109.64 - -250.00 409.18 0.85 0.53 - - - 57.31 67.64 79.92 96.48 - -280.00 458.28 0.85 0.53 - - - 51.17 60.39 71.36 86.15 -

-**

I

N

(FLC) = (LOAD x 1000)

***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT)

SQRT(3) x

I

N

x (RcosΦ + XsinΦ)

% AT F.L.C

DERATING FACTOR =

CABLE REACTANCE in OHM/KM (X) SITE CABLE RATING

*

* SITE CABLE RATING = CCC x DERATING FACTOR

Power Distribution Feeders - From LV Switch Board to Distribution Panels

CABLE SELECTION CHART FOR

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** CURRENT CARRYING CAPACITY (CCC) in AMPS

CABLE C.S.A in mm2

CONDUCTOR RESIST. IN OHM/KM (90o C) MAXIMUM PERMISSIBLE VOLT DROP = CABLE SPECIFICATION:

(28)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01 415 V 3-PH POWER FEEDER

0.6/1 kV, CU/XLPE/PVC(FOUR CORES CABLE - ARMOURED)

50 Hz 2.5 0.82 4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240) 37 45 61 80 109 131 164 196 243 280 334 365 434 560 668 730 868 30.34 36.9 50.02 65.6 89.38 107.4 134.48 160.7 199.26 229.6 273.9 299.3 355.9 459.2 547.76 598.6 711.76 5.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.098 0.080 0.064 0.049 0.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355 LOAD RATING kWLOAD F.L.C

I

N

AMPS** COSΦ SINΦ

0.25 0.41 0.85 0.53 2901.30 4324.62 7216.18 11348.47 17611.12 23982.84 31865.15 44346.62 59037.45 71640.46 84547.59 99897.42 120604.18 143280.93 169095.18 199794.84 241208.36 - -0.37 0.61 0.85 0.53 1960.34 2922.04 4875.80 7667.89 11899.41 16204.62 21530.50 29963.93 39890.17 48405.72 57126.75 67498.26 81489.31 96811.44 114253.50 134996.51 162978.62 - -0.55 0.90 0.85 0.53 1318.77 1965.74 3280.08 5158.40 8005.06 10901.29 14484.16 20157.55 26835.21 32563.85 38430.72 45407.92 54820.08 65127.69 76861.44 90815.84 109640.17 - -0.75 1.23 0.85 0.53 967.10 1441.54 2405.39 3782.82 5870.37 7994.28 10621.72 14782.21 19679.15 23880.15 28182.53 33299.14 40201.39 47760.31 56365.06 66598.28 80402.79 - -1.50 2.46 0.85 0.53 483.55 720.77 1202.70 1891.41 2935.19 3997.14 5310.86 7391.10 9839.58 11940.08 14091.26 16649.57 20100.70 23880.15 28182.53 33299.14 40201.39 - -2.50 4.09 0.85 0.53 290.13 432.46 721.62 1134.85 1761.11 2398.28 3186.51 4434.66 5903.75 7164.05 8454.76 9989.74 12060.42 14328.09 16909.52 19979.48 24120.84 - -3.00 4.91 0.85 0.53 241.78 360.38 601.35 945.71 1467.59 1998.57 2655.43 3695.55 4919.79 5970.04 7045.63 8324.79 10050.35 11940.08 14091.26 16649.57 20100.70 - -4.00 6.55 0.85 0.53 181.33 270.29 451.01 709.28 1100.70 1498.93 1991.57 2771.66 3689.84 4477.53 5284.22 6243.59 7537.76 8955.06 10568.45 12487.18 15075.52 - -5.50 9.00 0.85 0.53 131.88 196.57 328.01 515.84 800.51 1090.13 1448.42 2015.76 2683.52 3256.38 3843.07 4540.79 5482.01 6512.77 7686.14 9081.58 10964.02 - -7.50 12.28 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -11.00 18.00 0.85 0.53 65.94 98.29 164.00 257.92 400.25 545.06 724.21 1007.88 1341.76 1628.19 1921.54 2270.40 2741.00 3256.38 3843.07 4540.79 5482.01 - -15.00 24.55 0.85 0.53 48.36 72.08 120.27 189.14 293.52 399.71 531.09 739.11 983.96 1194.01 1409.13 1664.96 2010.07 2388.02 2818.25 3329.91 4020.14 - -18.50 30.28 0.85 0.53 39.21 58.44 97.52 153.36 237.99 324.09 430.61 599.28 797.80 968.11 1142.53 1349.97 1629.79 1936.23 2285.07 2699.93 3259.57 - -22.00 36.01 0.85 0.53 - 49.14 82.00 128.96 200.13 272.53 362.10 503.94 670.88 814.10 960.77 1135.20 1370.50 1628.19 1921.54 2270.40 2741.00 - -25.00 40.92 0.85 0.53 - - 72.16 113.48 176.11 239.83 318.65 443.47 590.37 716.40 845.48 998.97 1206.04 1432.81 1690.95 1997.95 2412.08 - -30.00 49.10 0.85 0.53 - - 60.13 94.57 146.76 199.86 265.54 369.56 491.98 597.00 704.56 832.48 1005.03 1194.01 1409.13 1664.96 2010.07 - -37.00 60.56 0.85 0.53 - - - 76.68 118.99 162.05 215.31 299.64 398.90 484.06 571.27 674.98 814.89 968.11 1142.53 1349.97 1629.79 - -45.00 73.65 0.85 0.53 - - - - 97.84 133.24 177.03 246.37 327.99 398.00 469.71 554.99 670.02 796.01 939.42 1109.97 1340.05 - -55.00 90.02 0.85 0.53 - - - 109.01 144.84 201.58 268.35 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -61.00 99.84 0.85 0.53 - - - 98.29 130.59 181.75 241.96 293.61 346.51 409.42 494.28 587.22 693.01 818.83 988.56 - -75.00 122.75 0.85 0.53 - - - 106.22 147.82 196.79 238.80 281.83 332.99 402.01 477.60 563.65 665.98 804.03 - -110.00 180.04 0.85 0.53 - - - 134.18 162.82 192.15 227.04 274.10 325.64 384.31 454.08 548.20 - -132.00 216.05 0.85 0.53 - - - 135.68 160.13 189.20 228.42 271.37 320.26 378.40 456.83 - -150.00 245.51 0.85 0.53 - - - 140.91 166.50 201.01 238.80 281.83 332.99 402.01 - -160.00 261.87 0.85 0.53 - - - 132.11 156.09 188.44 223.88 264.21 312.18 376.89 - -185.00 302.79 0.85 0.53 - - - 162.98 193.62 228.51 269.99 325.96 - -200.00 327.34 0.85 0.53 - - - 150.76 179.10 211.37 249.74 301.51 - -220.00 360.08 0.85 0.53 - - - 162.82 192.15 227.04 274.10 - -250.00 409.18 0.85 0.53 - - - 143.28 169.10 199.79 241.21 - -280.00 458.28 0.85 0.53 - - - 127.93 150.98 178.39 215.36 -

-**

I

N

(FLC) = (LOAD x 1000)

***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT)

SQRT(3) x

I

N

x (RcosΦ + XsinΦ)

% AT F.L.C

From LV Switch Board to Final Loads.

DERATING FACTOR = CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING

*

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE SELECTION CHART FOR

CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP =

CABLE REACTANCE in OHM/KM (X)

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

(29)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01 415 V 3-PH POWER FEEDER (LAID IN DUCTS) - OUTDOOR

0.6/1 kV, CU/XLPE/SWA/PVC(FOUR CORES CABLE - ARMOURED)

50 Hz 1 0.45 4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240) 35 44 58 72 98 116 138 171 200 233 261 295 347 466 522 590 694 15.75 19.8 26.1 32.4 44.1 52.2 62.1 77.0 90 104.9 117.5 132.8 156.2 209.7 234.9 265.5 312.3 5.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.098 0.080 0.064 0.049 0.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355 LOAD RATING kW

I

N LOAD F.L.C AMPS** COSΦ SINΦ 0.25 0.41 0.85 0.53 1160.52 1729.85 2886.47 4539.39 7044.45 9593.14 12746.06 17738.65 23614.98 28656.19 33819.04 39958.97 48241.67 57312.37 67638.07 79917.94 96483.35 - -0.37 0.61 0.85 0.53 784.14 1168.82 1950.32 3067.16 4759.76 6481.85 8612.20 11985.57 15956.07 19362.29 22850.70 26999.30 32595.72 38724.58 45701.40 53998.61 65191.45 - -0.55 0.90 0.85 0.53 527.51 786.29 1312.03 2063.36 3202.02 4360.52 5793.66 8063.02 10734.08 13025.54 15372.29 18163.17 21928.03 26051.08 30744.58 36326.33 43856.07 - -0.75 1.23 0.85 0.53 386.84 576.62 962.16 1513.13 2348.15 3197.71 4248.69 5912.88 7871.66 9552.06 11273.01 13319.66 16080.56 19104.12 22546.02 26639.31 32161.12 - -1.50 2.46 0.85 0.53 193.42 288.31 481.08 756.56 1174.07 1598.86 2124.34 2956.44 3935.83 4776.03 5636.51 6659.83 8040.28 9552.06 11273.01 13319.66 16080.56 - -2.50 4.09 0.85 0.53 116.05 172.98 288.65 453.94 704.44 959.31 1274.61 1773.86 2361.50 2865.62 3381.90 3995.90 4824.17 5731.24 6763.81 7991.79 9648.33 - -3.00 4.91 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -4.00 6.55 0.85 0.53 72.53 108.12 180.40 283.71 440.28 599.57 796.63 1108.67 1475.94 1791.01 2113.69 2497.44 3015.10 3582.02 4227.38 4994.87 6030.21 - -5.50 9.00 0.85 0.53 52.75 78.63 131.20 206.34 320.20 436.05 579.37 806.30 1073.41 1302.55 1537.23 1816.32 2192.80 2605.11 3074.46 3632.63 4385.61 - -7.50 12.28 0.85 0.53 38.68 57.66 96.22 151.31 234.81 319.77 424.87 591.29 787.17 955.21 1127.30 1331.97 1608.06 1910.41 2254.60 2663.93 3216.11 - -11.00 18.00 0.85 0.53 - 39.31 65.60 103.17 160.10 218.03 289.68 403.15 536.70 651.28 768.61 908.16 1096.40 1302.55 1537.23 1816.32 2192.80 - -15.00 24.55 0.85 0.53 - - 48.11 75.66 117.41 159.89 212.43 295.64 393.58 477.60 563.65 665.98 804.03 955.21 1127.30 1331.97 1608.06 - -18.50 30.28 0.85 0.53 - - - 61.34 95.20 129.64 172.24 239.71 319.12 387.25 457.01 539.99 651.91 774.49 914.03 1079.97 1303.83 - -22.00 36.01 0.85 0.53 - - - - 80.05 109.01 144.84 201.58 268.35 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -25.00 40.92 0.85 0.53 - - - - 70.44 95.93 127.46 177.39 236.15 286.56 338.19 399.59 482.42 573.12 676.38 799.18 964.83 - -30.00 49.10 0.85 0.53 - - - 79.94 106.22 147.82 196.79 238.80 281.83 332.99 402.01 477.60 563.65 665.98 804.03 - -37.00 60.56 0.85 0.53 - - - 86.12 119.86 159.56 193.62 228.51 269.99 325.96 387.25 457.01 539.99 651.91 - -45.00 73.65 0.85 0.53 - - - 98.55 131.19 159.20 187.88 221.99 268.01 318.40 375.77 443.99 536.02 - -55.00 90.02 0.85 0.53 - - - 130.26 153.72 181.63 219.28 260.51 307.45 363.26 438.56 - -61.00 99.84 0.85 0.53 - - - 117.44 138.60 163.77 197.71 234.89 277.21 327.53 395.42 - -75.00 122.75 0.85 0.53 - - - 133.20 160.81 191.04 225.46 266.39 321.61 - -110.00 180.04 0.85 0.53 - - - 130.26 153.72 181.63 219.28 - -132.00 216.05 0.85 0.53 - - - 128.10 151.36 182.73 - -150.00 245.51 0.85 0.53 - - - 133.20 160.81 - -160.00 261.87 0.85 0.53 - - - 124.87 150.76 - -185.00 302.79 0.85 0.53 - - - 130.38 - -200.00 327.34 0.85 0.53 - - - -220.00 360.08 0.85 0.53 - - - -250.00 409.18 0.85 0.53 - - - -280.00 458.28 0.85 0.53 - - -

-**

I

N

(FLC) = (LOAD x 1000)

***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT)

SQRT(3) x

I

N

x (RcosΦ + XsinΦ)

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

* SITE CABLE RATING = CCC x DERATING FACTOR

DERATING FACTOR = CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING

*

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) CABLE SELECTION CHART FOR CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP = % AT F.L.C

(30)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01 415 V 3-PH POWER FEEDER

0.6/1 kV, CU/XLPE/SWA/PVC(FOUR CORES CABLE - ARMOURED)

50 Hz 2.5 0.45 4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240) 35 44 58 72 98 116 138 171 200 233 261 295 347 466 522 590 694 15.75 19.8 26.1 32.4 44.1 52.2 62.1 77.0 90 104.9 117.5 132.8 156.2 209.7 234.9 265.5 312.3 5.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.098 0.080 0.064 0.049 0.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355 LOAD RATING kW

I

N LOAD F.L.C AMPS** COSΦ SINΦ 0.25 0.41 0.85 0.53 2901.30 4324.62 7216.18 11348.47 17611.12 23982.84 31865.15 44346.62 59037.45 71640.46 84547.59 99897.42 120604.18 143280.93 169095.18 199794.84 241208.36 - -0.37 0.61 0.85 0.53 1960.34 2922.04 4875.80 7667.89 11899.41 16204.62 21530.50 29963.93 39890.17 48405.72 57126.75 67498.26 81489.31 96811.44 114253.50 134996.51 162978.62 - -0.55 0.90 0.85 0.53 1318.77 1965.74 3280.08 5158.40 8005.06 10901.29 14484.16 20157.55 26835.21 32563.85 38430.72 45407.92 54820.08 65127.69 76861.44 90815.84 109640.17 - -0.75 1.23 0.85 0.53 967.10 1441.54 2405.39 3782.82 5870.37 7994.28 10621.72 14782.21 19679.15 23880.15 28182.53 33299.14 40201.39 47760.31 56365.06 66598.28 80402.79 - -1.50 2.46 0.85 0.53 483.55 720.77 1202.70 1891.41 2935.19 3997.14 5310.86 7391.10 9839.58 11940.08 14091.26 16649.57 20100.70 23880.15 28182.53 33299.14 40201.39 - -2.50 4.09 0.85 0.53 290.13 432.46 721.62 1134.85 1761.11 2398.28 3186.51 4434.66 5903.75 7164.05 8454.76 9989.74 12060.42 14328.09 16909.52 19979.48 24120.84 - -3.00 4.91 0.85 0.53 241.78 360.38 601.35 945.71 1467.59 1998.57 2655.43 3695.55 4919.79 5970.04 7045.63 8324.79 10050.35 11940.08 14091.26 16649.57 20100.70 - -4.00 6.55 0.85 0.53 181.33 270.29 451.01 709.28 1100.70 1498.93 1991.57 2771.66 3689.84 4477.53 5284.22 6243.59 7537.76 8955.06 10568.45 12487.18 15075.52 - -5.50 9.00 0.85 0.53 131.88 196.57 328.01 515.84 800.51 1090.13 1448.42 2015.76 2683.52 3256.38 3843.07 4540.79 5482.01 6512.77 7686.14 9081.58 10964.02 - -7.50 12.28 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -11.00 18.00 0.85 0.53 - 98.29 164.00 257.92 400.25 545.06 724.21 1007.88 1341.76 1628.19 1921.54 2270.40 2741.00 3256.38 3843.07 4540.79 5482.01 - -15.00 24.55 0.85 0.53 - - 120.27 189.14 293.52 399.71 531.09 739.11 983.96 1194.01 1409.13 1664.96 2010.07 2388.02 2818.25 3329.91 4020.14 - -18.50 30.28 0.85 0.53 - - - 153.36 237.99 324.09 430.61 599.28 797.80 968.11 1142.53 1349.97 1629.79 1936.23 2285.07 2699.93 3259.57 - -22.00 36.01 0.85 0.53 - - - - 200.13 272.53 362.10 503.94 670.88 814.10 960.77 1135.20 1370.50 1628.19 1921.54 2270.40 2741.00 - -25.00 40.92 0.85 0.53 - - - - 176.11 239.83 318.65 443.47 590.37 716.40 845.48 998.97 1206.04 1432.81 1690.95 1997.95 2412.08 - -30.00 49.10 0.85 0.53 - - - 199.86 265.54 369.56 491.98 597.00 704.56 832.48 1005.03 1194.01 1409.13 1664.96 2010.07 - -37.00 60.56 0.85 0.53 - - - 215.31 299.64 398.90 484.06 571.27 674.98 814.89 968.11 1142.53 1349.97 1629.79 - -45.00 73.65 0.85 0.53 - - - 246.37 327.99 398.00 469.71 554.99 670.02 796.01 939.42 1109.97 1340.05 - -55.00 90.02 0.85 0.53 - - - 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -61.00 99.84 0.85 0.53 - - - 293.61 346.51 409.42 494.28 587.22 693.01 818.83 988.56 - -75.00 122.75 0.85 0.53 - - - 332.99 402.01 477.60 563.65 665.98 804.03 - -110.00 180.04 0.85 0.53 - - - 325.64 384.31 454.08 548.20 - -132.00 216.05 0.85 0.53 - - - 320.26 378.40 456.83 - -150.00 245.51 0.85 0.53 - - - 332.99 402.01 - -160.00 261.87 0.85 0.53 - - - 312.18 376.89 - -185.00 302.79 0.85 0.53 - - - 325.96 - -200.00 327.34 0.85 0.53 - - - -220.00 360.08 0.85 0.53 - - - -250.00 409.18 0.85 0.53 - - - -280.00 458.28 0.85 0.53 - - -

-**

I

N

(FLC) = (LOAD x 1000)

***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT)

SQRT(3) x

I

N

x (RcosΦ + XsinΦ)

% AT F.L.C

From LV Switch Board to Final Loads.

DERATING FACTOR = CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING

*

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE SELECTION CHART FOR

CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP =

CABLE REACTANCE in OHM/KM (X)

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

(31)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01

CABLE SELECTION CHART FOR 240 V 1- PH POWER FEEDER (LAID IN AIR - ON CABLE LADDER - INDOOR)

50 Hz 2.5 % AT F.L.C. 0.97 3 X 4 3 X 6 3 X 10 - - - -36.00 45.00 60.00 - - - -34.92 43.65 58.20 - - - -5.8783 3.9274 2.33 - - - -0.0933 0.0888 0.0856 - - - -LOAD RATING kW

IN

LOAD F.L.C AMPS** COSΦ SINΦ 0.25 1.23 0.85 0.53 485.17 723.18 1208.54 - - - -0.37 1.81 0.85 0.53 327.81 488.63 816.58 - - - -0.55 2.70 0.85 0.53 220.53 328.72 549.33 - - - -0.75 3.68 0.85 0.53 161.72 241.06 402.85 - - - -1.50 7.35 0.85 0.53 80.86 120.53 201.42 - - - -2.20 10.78 0.85 0.53 55.13 82.18 137.33 - - - -3.00 14.71 0.85 0.53 40.43 60.26 100.71 - - - -4.00 19.61 0.85 0.53 30.32 45.20 75.53 - - - -5.50 26.96 0.85 0.53 22.05 32.87 54.93 - - - -6.00 29.41 0.85 0.53 20.22 30.13 50.36 - - - -11.00 53.92 0.85 0.53 - - 27.47 - - - -15.00 73.53 0.85 0.53 - - - -18.50 90.69 0.85 0.53 - - - -22.00 107.84 0.85 0.53 - - - -27.50 134.80 0.85 0.53 - - - -32.00 156.86 0.85 0.53 - - - -35.00 171.57 0.85 0.53 - - - -45.00 220.59 0.85 0.53 - - - -58.00 284.31 0.85 0.53 - - - -75.00 367.65 0.85 0.53 - - - -88.00 431.37 0.85 0.53 - - - -110.00 539.22 0.85 0.53 - - - -132.00 647.06 0.85 0.53 - - - -150.00 735.29 0.85 0.53 - - - -175.00 857.84 0.85 0.53 - - - -185.00 906.86 0.85 0.53 - - -

-**

IN

(FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 X n

(P.F xVOLT)

2 x

IN

x (RcosΦ + XsinΦ)

CABLE SPECIFICATION:

* SITE CABLE RATING = CCC x DERATING FACTOR

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

0.6/1 kV, CU/XLPE/PVC(THREE CORES CABLE - UNARMOURED)

MAXIMUM PERMISSIBLE VOLT DROP = FREQUENCY

DERATING FACTOR =

CABLE REACTANCE in OHM/KM (X) CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE C.S.A in mm2

SITE CABLE RATING

*

CURRENT CARRYING CAPACITY (CCC) in AMPS

(32)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01

CABLE SELECTION CHART FOR 240 V 1- PH POWER FEEDER (LAID IN AIR - INDOOR / OUTDOOR)

50 Hz 2.5 % AT F.L.C. 0.82 3 X 4 3 X 6 3 X 10 3 X 16 3 X 25 3 X 35 3 X 50 37.00 45.00 61.00 80.00 109.00 131.00 164.00 30.34 36.90 50.02 65.60 89.38 107.42 134.48 5.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.494 0.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 LOAD RATING kW

IN

LOAD F.L.C AMPS** COSΦ SINΦ 0.25 1.23 0.85 0.53 485.17 723.18 1206.71 1897.73 2944.99 4010.49 5328.59 0.37 1.81 0.85 0.53 327.81 488.63 815.35 1282.25 1989.86 2709.79 3600.40 0.55 2.70 0.85 0.53 220.53 328.72 548.51 862.60 1338.63 1822.95 2422.09 0.75 3.68 0.85 0.53 161.72 241.06 402.24 632.58 981.66 1336.83 1776.20 1.50 7.35 0.85 0.53 80.86 120.53 201.12 316.29 490.83 668.41 888.10 2.20 10.78 0.85 0.53 55.13 82.18 137.13 215.65 334.66 455.74 605.52 3.00 14.71 0.85 0.53 40.43 60.26 100.56 158.14 245.42 334.21 444.05 4.00 19.61 0.85 0.53 30.32 45.20 75.42 118.61 184.06 250.66 333.04 5.50 26.96 0.85 0.53 22.05 32.87 54.85 86.26 133.86 182.29 242.21 6.00 29.41 0.85 0.53 20.22 30.13 50.28 79.07 122.71 167.10 222.02 11.00 53.92 0.85 0.53 - - - 43.13 66.93 91.15 121.10 15.00 73.53 0.85 0.53 - - - - 49.08 66.84 88.81 18.50 90.69 0.85 0.53 - - - 54.20 72.01 22.00 107.84 0.85 0.53 - - - 60.55 27.50 134.80 0.85 0.53 - - - -32.00 156.86 0.85 0.53 - - - -35.00 171.57 0.85 0.53 - - - -45.00 220.59 0.85 0.53 - - - -58.00 284.31 0.85 0.53 - - - -75.00 367.65 0.85 0.53 - - - -88.00 431.37 0.85 0.53 - - - -110.00 539.22 0.85 0.53 - - - -132.00 647.06 0.85 0.53 - - - -150.00 735.29 0.85 0.53 - - - -175.00 857.84 0.85 0.53 - - - -185.00 906.86 0.85 0.53 - - -

-**

IN

(FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 X n

(P.F xVOLT)

2 x

IN

x (RcosΦ + XsinΦ)

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE C.S.A in mm2

SITE CABLE RATING

*

CURRENT CARRYING CAPACITY (CCC) in AMPS

From LV Switch Board to Final Loads.

CABLE SPECIFICATION:

* SITE CABLE RATING = CCC x DERATING FACTOR

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

0.6/1 kV, CU/XLPE/SWA/PVC(THREE CORES CABLE - ARMOURED)

MAXIMUM PERMISSIBLE VOLT DROP = FREQUENCY

DERATING FACTOR =

(33)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01

CABLE SELECTION CHART FOR 240 V 1- PH POWER FEEDER (LAID IN DUCTS - INDOOR / OUTDOOR)

50 Hz 2.5 % AT F.L.C. 0.45 3 X 4 3 X 6 3 X 10 3 X 16 3 X 25 3 X 35 3 X 50 35 44 58 72 98 116 138 15.75 19.80 26.10 32.40 44.10 52.20 62.10 5.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.494 0.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 LOAD RATING kWLOAD F.L.C

I

N AMPS ** COSΦ SINΦ 0.25 1.23 0.85 0.53 485.17 723.18 1206.71 1897.73 2944.99 4010.49 5328.59 0.37 1.81 0.85 0.53 327.81 488.63 815.35 1282.25 1989.86 2709.79 3600.40 0.55 2.70 0.85 0.53 220.53 328.72 548.51 862.60 1338.63 1822.95 2422.09 0.75 3.68 0.85 0.53 161.72 241.06 402.24 632.58 981.66 1336.83 1776.20 1.50 7.35 0.85 0.53 80.86 120.53 201.12 316.29 490.83 668.41 888.10 2.20 10.78 0.85 0.53 55.13 82.18 137.13 215.65 334.66 455.74 605.52 3.00 14.71 0.85 0.53 40.43 60.26 100.56 158.14 245.42 334.21 444.05 4.00 19.61 0.85 0.53 - 45.20 75.42 118.61 184.06 250.66 333.04 5.50 26.96 0.85 0.53 - - - 86.26 133.86 182.29 242.21 6.00 29.41 0.85 0.53 - - - 79.07 122.71 167.10 222.02 11.00 53.92 0.85 0.53 - - - 121.10 15.00 73.53 0.85 0.53 - - - -18.50 90.69 0.85 0.53 - - - -22.00 107.84 0.85 0.53 - - - -27.50 134.80 0.85 0.53 - - - -32.00 156.86 0.85 0.53 - - - -35.00 171.57 0.85 0.53 - - - -45.00 220.59 0.85 0.53 - - - -58.00 284.31 0.85 0.53 - - - -75.00 367.65 0.85 0.53 - - - -88.00 431.37 0.85 0.53 - - - -110.00 539.22 0.85 0.53 - - - -132.00 647.06 0.85 0.53 - - - -150.00 735.29 0.85 0.53 - - - -175.00 857.84 0.85 0.53 - - - -185.00 906.86 0.85 0.53 - - -

-**

I

N

(FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 X n

(P.F xVOLT)

2 x

I

N

x (RcosΦ + XsinΦ)

CABLE REACTANCE in OHM/KM (X)

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

* SITE CABLE RATING = CCC x DERATING FACTOR

DERATING FACTOR = CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING

*

CONDUCTOR RESIST. IN OHM/KM (90o C)

CABLE SPECIFICATION: 0.6/1 kV, CU/XLPE/SWA/PVC(THREE CORES CABLE - ARMOURED)

FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP =

(34)

0.6/1 kV, CU/XLPE/AWA/PVC(SINGLE CORE CABLE - ARMOURED) 50 Hz 1.0 0.801 4X(1 X 50) 4X(1 X 70) 4X(1 X 95) 4X(1 X 120) 4X(1 X 150) 4X(1 X 185) 4X(1 X 240) 4X(1 X 300) 4X(1 X 400) 4X(1 X 500) 4X(1 X 630) 4X(2 X 300) 4X(2 X 400) 4X(2 X 500) 4X(2 X 630) 154 199 244 287 328 372 453 523 603 687 808 1046 1206 1374 1616 123.35 159.40 195.44 229.89 262.73 297.97 362.85 418.92 483.00 550.29 647.21 837.85 966.01 1100.57 1294.42 0.4940 0.3430 0.2480 0.1970 0.1600 0.1290 0.0991 0.0810 0.0638 0.0517 0.0418 0.041 0.032 0.026 0.021 0.1140 0.1080 0.1040 0.1010 0.0990 0.0960 0.0930 0.0910 0.0900 0.0870 0.0823 0.0455 0.0450 0.0435 0.0412 LOAD RATING kWLOAD F.L.C IN

AMPS** COSΦ SINΦ

25.00 40.92 0.85 0.53 - - - 122.00 168.05 220.48 265.38 311.22 365.47 439.53 501.39 576.11 652.26 742.31 1002.79 1152.23 1304.52 1484.62 - - -50.00 81.84 0.85 0.53 - - - 61.00 84.03 110.24 132.69 155.61 182.74 219.76 250.70 288.06 326.13 371.15 501.39 576.11 652.26 742.31 - - -75.00 122.75 0.85 0.53 - - - 40.67 56.02 73.49 88.46 103.74 121.82 146.51 167.13 192.04 217.42 247.44 334.26 384.08 434.84 494.87 - - -100.00 163.67 0.85 0.53 - - - 55.12 66.34 77.80 91.37 109.88 125.35 144.03 163.06 185.58 250.70 288.06 326.13 371.15 - - -125.00 204.59 0.85 0.53 - - - 53.08 62.24 73.09 87.91 100.28 115.22 130.45 148.46 200.56 230.45 260.90 296.92 - - -150.00 245.51 0.85 0.53 - - - 51.87 60.91 73.25 83.57 96.02 108.71 123.72 167.13 192.04 217.42 247.44 - - -175.00 286.42 0.85 0.53 - - - 52.21 62.79 71.63 82.30 93.18 106.04 143.26 164.60 186.36 212.09 - - -200.00 327.34 0.85 0.53 - - - 54.94 62.67 72.01 81.53 92.79 125.35 144.03 163.06 185.58 - - -225.00 368.26 0.85 0.53 - - - 55.71 64.01 72.47 82.48 111.42 128.03 144.95 164.96 - - -250.00 409.18 0.85 0.53 - - - 50.14 57.61 65.23 74.23 100.28 115.22 130.45 148.46 - - -275.00 450.10 0.85 0.53 - - - 52.37 59.30 67.48 91.16 104.75 118.59 134.97 - - -300.00 491.01 0.85 0.53 - - - 54.35 61.86 83.57 96.02 108.71 123.72 - - -325.00 531.93 0.85 0.53 - - - 50.17 57.10 77.14 88.63 100.35 114.20 - - -350.00 572.85 0.85 0.53 - - - 53.02 71.63 82.30 93.18 106.04 - - -375.00 613.77 0.85 0.53 - - - 49.49 66.85 76.82 86.97 98.97 - - -400.00 654.68 0.85 0.53 - - - 62.67 72.01 81.53 92.79 - - -425.00 695.60 0.85 0.53 - - - 58.99 67.78 76.74 87.33 - - -450.00 736.52 0.85 0.53 - - - 55.71 64.01 72.47 82.48 - - -475.00 777.44 0.85 0.53 - - - 52.78 60.64 68.66 78.14 - - -500.00 818.36 0.85 0.53 - - - 50.14 57.61 65.23 74.23 - - -525.00 859.27 0.85 0.53 - - - 54.87 62.12 70.70 - - -550.00 900.19 0.85 0.53 - - - 52.37 59.30 67.48 - - -575.00 941.11 0.85 0.53 - - - 50.10 56.72 64.55 - - -600.00 982.03 0.85 0.53 - - - 54.35 61.86 - - -625.00 1022.95 0.85 0.53 - - - 52.18 59.38 - - -650.00 1063.86 0.85 0.53 - - - 50.17 57.10 - - -** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT) SQRT(3) x IN x (RcosΦ + XsinΦ) % AT F.L.C

DERATING FACTOR =

CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS

SITE CABLE RATING *

CONDUCTOR RESIST. IN OHM/KM (90o C)

CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP =

CABLE REACTANCE in OHM/KM (X)

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

(35)

0.6/1 kV, CU/XLPE/AWA/PVC(SINGLE CORE CABLE - ARMOURED) 50 Hz 1.0 0.41 4X(1 X 50) 4X(1 X 70) 4X(1 X 95) 4X(1 X 120) 4X(1 X 150) 4X(1 X 185) 4X(1 X 240) 4X(1 X 300) 4X(1 X 400) 4X(1 X 500) 4X(1 X 630) 4X(2 X 300) 4X(2 X 400) 4X(2 X 500) 4X(2 X 630) 146 180 217 246 279 317 363 412 464 515 587 824 928 1030 1174 59.86 73.80 88.97 100.86 114.39 129.97 148.83 168.92 190.24 211.15 240.67 337.84 380.48 422.30 481.34 0.4940 0.3430 0.2480 0.1970 0.1600 0.1290 0.0991 0.0810 0.0638 0.0517 0.0418 0.041 0.032 0.026 0.021 0.1140 0.1080 0.1040 0.1010 0.0990 0.0960 0.0930 0.0910 0.0900 0.0870 0.0823 0.0455 0.0450 0.0435 0.0412 LOAD RATING kW

I

N LOAD F.L.C AMPS** COSΦ SINΦ 25.00 40.92 0.85 0.53 - - - 122.00 168.05 220.48 265.38 311.22 365.47 439.53 501.39 576.11 652.26 742.31 1002.79 1152.23 1304.52 1484.62 - - -50.00 81.84 0.85 0.53 - - - 110.24 132.69 155.61 182.74 219.76 250.70 288.06 326.13 371.15 501.39 576.11 652.26 742.31 - - -75.00 122.75 0.85 0.53 - - - 121.82 146.51 167.13 192.04 217.42 247.44 334.26 384.08 434.84 494.87 - - -100.00 163.67 0.85 0.53 - - - 125.35 144.03 163.06 185.58 250.70 288.06 326.13 371.15 - - -125.00 204.59 0.85 0.53 - - - 130.45 148.46 200.56 230.45 260.90 296.92 - - -150.00 245.51 0.85 0.53 - - - 167.13 192.04 217.42 247.44 - - -175.00 286.42 0.85 0.53 - - - 143.26 164.60 186.36 212.09 - - -200.00 327.34 0.85 0.53 - - - 125.35 144.03 163.06 185.58 - - -225.00 368.26 0.85 0.53 - - - 128.03 144.95 164.96 - - -250.00 409.18 0.85 0.53 - - - 130.45 148.46 - - -275.00 450.10 0.85 0.53 - - - 134.97 - - -300.00 491.01 0.85 0.53 - - - -325.00 531.93 0.85 0.53 - - - -350.00 572.85 0.85 0.53 - - - -375.00 613.77 0.85 0.53 - - - -400.00 654.68 0.85 0.53 - - - -425.00 695.60 0.85 0.53 - - - -450.00 736.52 0.85 0.53 - - - -475.00 777.44 0.85 0.53 - - - -500.00 818.36 0.85 0.53 - - - -525.00 859.27 0.85 0.53 - - - -550.00 900.19 0.85 0.53 - - - -575.00 941.11 0.85 0.53 - - - -600.00 982.03 0.85 0.53 - - - -625.00 1022.95 0.85 0.53 - - - -650.00 1063.86 0.85 0.53 - - - -**

I

N (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n

(SQRT 3 x P.F xVOLT) SQRT(3) x

I

N x (RcosΦ + XsinΦ)

CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP = % AT F.L.C DERATING FACTOR =

CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING *

CONDUCTOR RESIST. IN OHM/KM (90o

C) CABLE REACTANCE in OHM/KM (X)

*MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

(36)

415 V 3- PH MOTORS RUNNING 50 Hz 2.5 0.97 3 X 4 3 X 6 3 X 10 - - - - - - - - - -36.00 45.00 60.00 - - - -34.92 43.65 58.20 - - - -5.8783 3.9274 2.33 - - - -0.0933 0.0888 0.0856 - - - -MOTOR RATING kW

I

N LOAD F.L.C AMPS ** MOTOR L.R.C AMPS **** COSΦ SINΦ 0.25 0.43 2.61 0.80 0.60 2895.38 4312.09 7193.43 - - - -0.37 0.64 3.86 0.80 0.60 1956.34 2913.58 4860.42 - - - -0.55 0.96 5.74 0.80 0.60 1316.08 1960.04 3269.74 - - - -0.75 1.30 7.83 0.80 0.60 965.13 1437.36 2397.81 - - - -1.50 2.61 15.65 0.80 0.60 482.56 718.68 1198.90 - - - -2.20 3.83 22.95 0.80 0.60 329.02 490.01 817.43 - - - -3.00 5.22 31.30 0.80 0.60 241.28 359.34 599.45 - - - -4.00 6.96 41.74 0.80 0.60 180.96 269.51 449.59 - - - -5.50 9.56 57.39 0.80 0.60 131.61 196.00 326.97 - - - -7.50 13.04 78.26 0.80 0.60 96.51 143.74 239.78 - - - -11.00 19.13 114.77 0.80 0.60 65.80 98.00 163.49 - - - -15.00 26.09 156.51 0.80 0.60 48.26 71.87 119.89 - - - -18.50 32.17 193.03 0.80 0.60 39.13 58.27 97.21 - - - -22.00 38.26 229.55 0.80 0.60 - 49.00 81.74 - - - -25.00 43.48 260.85 0.80 0.60 - 43.12 71.93 - - - -30.00 52.17 313.02 0.80 0.60 - - 59.95 - - - -37.00 64.34 386.06 0.80 0.60 - - - -45.00 78.26 469.53 0.80 0.60 - - - -55.00 95.65 573.87 0.80 0.60 - - - -61.00 106.08 636.48 0.80 0.60 - - - -75.00 130.43 782.55 0.80 0.60 - - - -110.00 191.29 1147.74 0.80 0.60 - - - -132.00 229.55 1377.29 0.80 0.60 - - - -150.00 260.85 1565.11 0.80 0.60 - - - -160.00 278.24 1669.45 0.80 0.60 - - - -185.00 321.72 1930.30 0.80 0.60 - - - -***L = ****L.R.C = 6 x F.LC SQRT(3) x IN x (RcosΦ + XsinΦ)

CABLE SELECTION CHART FOR

CABLE SPECIFICATION: 0.6/1 kV, CU/XLPE/PVC (THREE CORE CABLES - UNARMOURED)

FREQUENCY

CABLE REACTANCE in OHM/KM (X)

MAXIMUM PERMISSIBLE VOLT DROP = % AT MOTOR F.L.C DERATING FACTOR =

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

* SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (Vd%) x V x 1000

SITE CABLE RATING *

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS

(37)

PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No.01 415 V 3- PH MOTORS STARTING

0.6/1 kV, CU/XLPE/PVC (THREE CORE CABLES - UNARMOURED)

50 Hz 15 0.97 3 X 4 3 X 6 3 X 10 - - - - - - - - - -36.00 45.00 60.00 - - - -34.92 43.65 58.20 - - - -5.8783 3.9274 2.33 - - - -0.0933 0.0888 0.0856 - - - -MOTOR RATING kW

I

N LOAD F.L.C AMPS ** MOTOR L.R.C AMPS **** COSΦ SINΦ 0.25 0.43 2.61 0.20 0.98 10873.86 15791.66 25056.81 - - - -0.37 0.64 3.86 0.20 0.98 7347.20 10670.04 16930.28 - - - -0.55 0.96 5.74 0.20 0.98 4942.67 7178.03 11389.46 - - - -0.75 1.30 7.83 0.20 0.98 3624.62 5263.89 8352.27 - - - -1.50 2.61 15.65 0.20 0.98 1812.31 2631.94 4176.13 - - - -2.20 3.83 22.95 0.20 0.98 1235.67 1794.51 2847.36 - - - -3.00 5.22 31.30 0.20 0.98 906.16 1315.97 2088.07 - - - -4.00 6.96 41.74 0.20 0.98 679.62 986.98 1566.05 - - - -5.50 9.56 57.39 0.20 0.98 494.27 717.80 1138.95 - - - -7.50 13.04 78.26 0.20 0.98 362.46 526.39 835.23 - - - -11.00 19.13 114.77 0.20 0.98 247.13 358.90 569.47 - - - -15.00 26.09 156.51 0.20 0.98 181.23 263.19 417.61 - - - -18.50 32.17 193.03 0.20 0.98 146.94 213.40 338.61 - - - -22.00 38.26 229.55 0.20 0.98 - 179.45 284.74 - - - -25.00 43.48 260.85 0.20 0.98 - 157.92 250.57 - - - -30.00 52.17 313.02 0.20 0.98 - - 208.81 - - - -37.00 64.34 386.06 0.20 0.98 - - - -45.00 78.26 469.53 0.20 0.98 - - - -55.00 95.65 573.87 0.20 0.98 - - - -61.00 106.08 636.48 0.20 0.98 - - - -75.00 130.43 782.55 0.20 0.98 - - - -110.00 191.29 1147.74 0.20 0.98 - - - -132.00 229.55 1377.29 0.20 0.98 - - - -150.00 260.85 1565.11 0.20 0.98 - - - -160.00 278.24 1669.45 0.20 0.98 - - - -185.00 321.72 1930.30 0.20 0.98 - - - -***L = ****L.R.C = 6 x F.LC CABLE C.S.A in mm2

CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING

*

CABLE SELECTION CHART FOR CABLE SPECIFICATION: FREQUENCY

MAXIMUM PERMISSIBLE VOLT DROP = % AT MOTOR L.R.C

DERATING FACTOR =

MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

* SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (Vd%) x VL x 1000

CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X)

References

Outline

Related documents

reaction bles LV fire-resistant cables Pre-wired conduits Radiant heating cables Solar panel cables Elevator cables MV cables CATV cables CCTV cables LAN copper cables LAN

KYJV22 Copper core XLPE insulated PVC sheathed steel tape armored control cable Laid indoors, and in cable trenches, pipelines, direct-buring and other fixed places capable of

Characterizing HV XLPE cables by electrical, chemical and microstructural measurements on cable peeling: Effects of surface roughness, thermal treatment and peeling

The new electrical equipment range is wide: extension cords for indoor and outdoor use, extension cords with or without switches, cable reels, wireless sockets, doorbells,

Construction 0.6/1kV cables, XLPE insulated, fixed conductors, laid up with the three earths disposed in interstices of the power cores, PVC bedded, collective copper tape

W h e re multiconductor cables are installed in a single layer in uncovered trays, with a maintained spacing of not less than one cable diameter between cables, the

Havells Brand Power Cables, Solid Aluminum Conductor Up To 10 Sqmm Balance Stranded Conductor, XLPE Insulated,Cores Laid Up, PVC Innersheathed, Unarmoured/Armoured (Aluminium Wire

With spare capacity of 10%, size required = 480 mm Recommended tray size for single layer of LT cables:. Select from the Standard Cable tray sizes available