© ABB Group
September 24, 2013 | Slide 1
Lionel Ng, LPBS - Low Voltage Products
Welcome To ABB
© ABB Group
September 24, 2013 | Slide 2
MV & LV Transformer Substations
Theory & Short Circuit Calculation
Contents
General information on MV/LV transformer substations
Calculation of short-circuit currents
Choice of protection and control devices
Example of study of a MV/LV network
The electrical substations can be divided into
public substations
belong to the electricity utility
supply private users in AC single-phase or three-phase current (230V and 400V)
urban type in bricks
rural type installed externally directly on the MV pylon
private substations
belong to the user
civil users (schools, hospitals, etc.) and industrial users are mostly located in the same rooms of the factory
General Information
Typical structure of a substation
where the switching apparatus of the utility is installed.
where the measuring units are located
contains the transformer and the MV and LV switching apparatus
General Information
Most common management methods
Substation with a single transformer
General Information
Most common management methods
Substation with two transformers
(one as a spare for the other)
It is possible to use the Emax with a wire interlock (mechanical interlock) between two CBs
General Information
Most common management methods
two transformers which operate
in parallel on the same busbar
General Information
two transformers which operate simultaneously on
two separate half-busbars
Most common management methods
General Information
MV/LV Transformer Substations
It is possible to use the Emax with a wire interlock (mechanical interlock) between three CBs
MV/LV transformers
is the most important part of the transformer substation
single transformer for low powers (up to 630kVA - 800kVA)
several units in parallel for higher powers (1000kVA - 2500kVA)
type of cooling system
air oil
most used
AN cooling with natural air circulation
ONAN cooling with natural oil and air circulation types
General Information
ONAN transformer containing more than 500 kg of oil (> 800kVA)
General Information
MV/LV Transformer Substations
MV/LV transformers
one single trafo or two trafos in parallel?
U
U
750M
VA
400V
1600kVA
6%
800kVA
4%
800kVA
4%
400V
750M
VA
37 kA
55kA
General Information
MV/LV Transformer Substations
Management philosophy for the protections
L1 trip
ensured service continuity
General Information
Management philosophy for the protections
I
LV1and C
LVtrip
power supply is maintained to the half-busbar
trip
trip
General Information
Management philosophy for the protections
I
MV1and I
LV1trip to isolate the trafo affected by the fault
ensured service continuity
a logic for the disconnection of non-priority loads should be
foreseen
General Information
Management philosophy for the protections
I
MV1trip, I
LV1trip for pulling
service continuity of the whole plant
a logic for the disconnection of non-priority loads should be
foreseen
General Information
LV protection devices
L function protection against
overload
General Information
S function protection against delayed short-circuit
LV protection devices
General Information
I function
protection
against instantaneous
short-circuit
LV protection devices
General Information
MV/LV Transformer Substations
G function
protection
against earth-fault
LV protection devices
General Information
IEC 60909-0 (CEI 11-25)
Short-circuit:
“Accidental or intentional conductive path between two or more conductive parts forcing the electric potential differences between these conductive parts to be equal or close to zero”
Short-circuit current:
“Overcurrent resulting from a short-circuit in an electric system”
MV/LV Transformer Substations
Main components involved in a short-circuit calculation
Distribution networks
Generators
Transformers
Asynchronous motors
Cables
Each component of the network is replaced by its
relevant impedance
U
Zknet ZcMV ZTR ZcLV
MV/LV Transformer Substations
The equivalent network is solved according to standard
electrotechnical rules (circuits in series / in parallel)
knet cMVn TR cLV
kZ
Z
Z
Z
3
U
I
U
nZ
kne tZ
cM VZ
T RZ
cLVI
kMV/LV Transformer Substations
Distribution network
it is necessary to know the network short-circuit power
from 250MVA to 500MVA Un 30kV from 700MVA to 1500MVA Un > 30kV according to IEC 60076-5 knet n knet 2 n knet
I
3
U
S
U
Z
MV/LV Transformer Substations
Generators
it is necessary to know
rated apparent power Sn rated voltage Un subtransient reactance x”d
from 10% to 20% smooth rotor (isotropic machines)
from 15% to 30% salient pole rotor (anisotropic machines)
n 2 n " d " d
S
U
100
x
X
MV/LV Transformer Substations
Transformer
it is necessary to know
rated apparent power Sn primary rated voltage voltage U1n secondary rated voltage U2n
short-circuit voltage uk%from 4% to 8% according to IEC 60076-5 n 2 n 2 % k TR
S
U
100
u
Z
MV/LV Transformer Substations
Asynchronous motors
In case of short-circuit it functions as a
generator with a x”
dfrom 20% to 25%
a current equal to 4-6 times the I
ncan be
assumed as contribution to the short-circuit
the minimum criteria for taking into
consideration the phenomenon
(Ik shortcircuit without motor contribution)
MV/LV Transformer Substations
Example
U
S
k= 500 MVA
U
MV= 20 kV
Z
cMV= 0.01
S
n= 400 kVA
U= 20/0.4 kV
u
k%= 4 %
Z
cLV= 0.06
MV/LV Transformer Substations
U
S
k= 500
MVA
U
MV= 20 kV
Z
u= 0.32
m
0.8 10 500 10 20 S U Z 6 2 3 k 2 kV 20 u
4 2 2 kV 20 u V 400 u 3.2 10 20000 400 Z Z Example
MV/LV Transformer Substations
U
Z
u= 0.32 m
6 2 2 kV 20 cMV V 400 cMV 4 10 20000 400 Z ZZ
cMV= 4
10
-3m
Z
cMV= 0.01
Example
MV/LV Transformer Substations
U
Z
u= 0.32 m
Z
cMV= 4
10
-3m
S
n= 400 kVA
U= 20/0.4 kV
u
k%= 4 %
0.016 10 400 400 100 4 S U 100 u Z 3 2 n 2 nLV % k TZ
T= 0.016
Example
MV/LV Transformer Substations
U
Z
u= 0.32 m
Z
cMV= 4
10
-3m
Z
T= 16 m
Z
cLV= 0.61 m
Z
cLV= 0.61
m
Example
MV/LV Transformer Substations
U
S
k= 500
MVA
U
MV= 20 kV
Z
u= 0.32 m
Z
cMV= 4
10
-3m
Z
T= 16 m
Z
cLV= 0.61 m
U
n= 400 V
Z Z Z
14.1kA 3 U I T cMV u n k
Z Z Z Z
13.6kA 3 U I cLV T cMV u n k Example
MV/LV Transformer Substations
© ABB Group
September 24, 2013 | Slide 34
MV & LV Transformer Substations
General Information about Circuit
Breakers
Definitions
Circuit-breaker: a mechanical switching device capable of making,
carrying and breaking currents under normal circuit conditions and
also making, carrying for a specified time, and breaking currents
under specified abnormal circuit conditions such as those of
overload or short-circuit (IEC 60947-1 def. 2.2.11)
MV/LV Transformer Substations
Definitions
Moulded case CB:
a circuit-breaker having a supporting
housing of moulding insulating material forming an
integral part of the circuit-breaker (Isomax / Tmax /
Formula)
Air CB:
a circuit-breaker in which the contacts open and
close in air at atmospheric pressure (Emax)
MV/LV Transformer Substations
Definitions
Current-limiting circuit-breaker:
a circuit-breaker with a
break-time short enough to prevent the short-circuit
current reaching its peak value (IEC 60947-2 def. 2.3)
MV/LV Transformer Substations
Prospective
peak value
Limited
peak
value
Prospective
short-circuit current
Limited short-circuit
current
Specific let-through
energy (I
2t)
I
t
MV/LV Transformer Substations
Current-Limiting Circuit Breakers
Prospecti
ve peak
value
Limited
peak
value
Prospective short-circuit current Limited short-circuit current Specific let-through energyI
t
I2t Icc Ip Iccgo
MV/LV Transformer Substations
Current-Limiting Circuit Breakers
1E-2kA 0.1kA 1kA 10kA 1kA 10kA 100kA 1E3kA 1E4kA 1E5kA Curva di limitazione
40 kA
T2L160 In160 A
40 kA
16 kA
84 kA
Irms
Ip
Prospective
peak value
Limited peak
value
MV/LV Transformer Substations
Current-Limiting Circuit Breakers
Generalities about the main electrical parameters
Rated operational voltage U
e: the value of voltage which
determines the application and to which all the other
parameters are referred to
Rated uninterrupted current I
u: the value of current which the
device is able to carry for an indefinite time. It defines the size
of the CB
Rated current I
n: the value of current which characterizes the
protection release installed. Is often related to the rated
current of the load protected
MV/LV Transformer Substations
Selection of Protective Devices
Generalities about the main electrical parameters
Rated ultimate short-circuit breaking capacity I
cu: it is the
r.m.s. value of the symmetrical component of the short-circuit
current which the circuit-breaker is able to break (test cycle
O-t-CO)
Rated service short-circuit breaking capacity I
cs: it is the r.m.s.
value of the symmetrical component of the shortcircuit current
which the circuit-breaker is able to break (O-t-CO-t-CO)
T5N400 PR221DS-LS/I In 320
I
cuMV/LV Transformer Substations
Selection of Protective Devices
MV/LV Transformer Substations
Selection of Protective Devices
Ultimate Short-Circuit Breaking Capacity (I
cu):
breaking capacity for which the prescribed conditions
according to a specified test sequence do not include
the capability of the CB to carry its rated current
continuously
- test sequence: O - 3 min - CO
- dielectric withstand at 2
xU
eMV/LV Transformer Substations
Selection of Protective Devices
Service Short-Circuit Breaking Capacity (I
CS):
breaking capacity for which the prescribed conditions
according to a specified test sequence include the
capability of the CB to carry its rated current continuously
- test sequence: O - 3 min - CO - 3 min – CO
(25%-50%-75%-100% of Icu)
- operational performance capability:
(5% of N°operating cycle
for operational performance capability- table 8 60947-2)
- dielectric withstand at 2 x
U
e- verification of temperature rise at I
u(the temperature doesn‟t
exceed the limits of table 7 60947-2)
Generalities about the main electrical parameters
Rated short-circuit making capacity I
cm: it is the maximum
prospective peak current which the circuit-breaker must be
able to make
Icm=n x Icu
T5N400 PR221DS-LS/I In 320
I
cu36kA
I
cm75.6 kA @415V
MV/LV Transformer Substations
Selection of Protective Devices
Generalities about the main electrical parameters
Rated short-time withstand current I
cw: it is the r.m.s. value of
the alternate current component which the circuit-breaker is
able to withstand without damages for a determined time,
preferred values being 1s and 3 s
Defined for category B only
MV/LV Transformer Substations
Selection of Protective Devices
MV/LV Transformer Substations
Selection of Protective Devices
Generalities about the main electrical parameters
Don‟t forget
Ue Un Icu or Ics Ik Icm IpUe, Icu, Ics, Icm?
MV/LV Transformer Substations
Selection of Protective Devices
Protection of feeders
against overload
Ib ≤ In or I1 ≤ Iz against short-circuit
I2t ≤ k2S2I
nI
zS
I
bMV/LV Transformer Substations
Selection of Protective Devices
MV/LV Transformer Substations
Selection of Protective Devices
MV/LV Transformer Substations
Selection of Protective Devices
Protection of generators
I
ngen≤ I
1
I3 or I2 ≤ 2.5-4 x I
ngenG
MV/LV Transformer Substations
Selection of Protective Devices
Protection of transformers
I
nT≤ I
1 Upstream CB
I3 or I2 IinrushMV/LV Transformer Substations
Selection of Protective Devices
Steps
determining the short-circuit
currents
choosing the CB
setting of the MV overcurrent
protection
…
setting of the LV overcurrent
protection
…
20kV
400V
MV/LV Transformer Substations
Example of an MV/LV Network
20kV
400V
MV/LV Transformer Substations
Example of an MV/LV Network
20kV
400V
MV/LV Transformer Substations
Example of an MV/LV Network
© ABB Group
September 24, 2013 | Slide 57
Low
voltage
selectivity
with
ABB
circuit
breakers
Definitions and Standards
Selectivity techniques
Definitions and Standards
Back-up protection
Agenda
Selectivity (or discrimination)
is a type of coordination of two or
more protective devices in series.
Selectivity is done between
one circuit breaker on the supply side
and one circuit breaker, or more than
one, on the load side.
A is the supply side circuit
breaker (or upstream)
B and C are the load side circuit
breakers (or downstream)
Introduction
Better selectivity
FAULT CONTINUITY OF SERVICE
DAMAGE REDUCTION
Fast fault elimination
Reduce the stress and prevent damage
Minimize the area and the duration of
power loss
Introduction
Selective coordination among devices
is fundamental for economical and technical reasons
It is studied in order to
:
rapidly identify the area involved in the problem;
bound the effects of a fault by excluding just the affected zone of the network;
preserve the continuity of service and good power quality to the sound parts of the network;
provide a quick and precise identification of the fault to the personnel in charge of maintenance or to management system, in order to restore the service as rapidly as possible;
achieve a valid compromise between reliability, simplicity and cost effectiveness.
Main purposes of coordination
The definition of selectivity
“Trip selectivity (for overcurrent) is a coordination between the
operating characteristics of two or more overcurrent protection
devices, so that, when an overcurrent within established limits
occurs, the device destined to operate within those limits trips
whereas the others do not trip”
IEC 60947-1 Standard: “Low voltage equipment
Part 1: General rules for low voltage equipment”
Standards
definition
Selectivity
IEC 60947-1
def. 2.5.23
In occurrence of a fault
(an overload or a short circuit)
if selectivity is provided
only the downstream circuit
breaker opens.
Overcurrent
selectivity
All the system is out of service!
In occurrence of a fault
(an overload or a short circuit)
if selectivity is not provided
both the upstream and the
downstream circuit breakers
could
open
Overcurrent
selectivity
A
and
B
connected
in
series:
partial
selectivity
and
total
selectivity.
Standards definition
Partial and total selectivity
IEC 60947-2
def. 2.17.2 - 2.17.3
“Partial selectivity is an overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load side protection device carries out the protection up to a given level of overcurrent, without making the other device trip.”
B opens only according to fault current lower than a certain current value; values equal or greater than Is will give the trip of both A and B.
Is is the ultimate selectivity value! Is = ImA
Standards definition
Partial selectivity
Only B trips for every current value lower or equal to the maximum short-circuit current.
“Total selectivity is an overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load side protection device carries out the protection without making the other device trip.”
B A
Is = Ik
Standards definition
Upstream circuit breaker A
T4N 250 PR221DS In = 250 (I
cu= 36kA)
Downstream circuit breaker B
S 294 C100 (I
cu= 15kA)
Standards definition
Overload zone Thermal protection L protection
Short-circuit
zone
Magnetic protection S, D, I and EF protectionsTime-current selectivity
Current, time, energy, zone,
directional, zone directional selectivity
Selectivity
analysis
Real currents circulating through the circuit breakers
I>
A
B I> I> I>
A B I> I> I> I> I> A B I> I>
I
A= I
B IA IB tA tB tA tB IA IB IA=IB tA tBI
A= I
B+ I
loadsI
A= (I
B+ I
loads)
/ 2Selectivity
analysis
Real
currents
© ABB Group, BU Breakers and Switches September 24, 2013 | Slide 71
Definitions and Standards
Selectivity techniques
Selectivity techniques
Back-up protection
Agenda
© ABB Group, BU Breakers and Switches September 24, 2013 | Slide 72
Current selectivity
Time selectivity
Energy selectivity
Zone (logical) selectivity
Introduction
The ultimate selectivity value
is equal to the instantaneous trip threshold of the upstream protection device
Other methods are needed to have a total selectivity
A B
ImB ImA
Current selectivity: closer to the power supply the fault point is, higher the fault current is
In order to guarantee selectivity,
the protections must be set to different values of current thresholds
Ultimate selectivity value 1kA 3kA tB tA tA
Current selectivity
Base concept
A
B
Here the selectivity is a total selectivity,
because it is guaranteed up to the maximum value of the short-circuit current, 1kA.
Circuit breaker A will be set to a value which does not trip for faults which occur on the load side of B.
(I3Amin >1kA)
Circuit breaker B will be set to trip for faults which occur on its load side (I3Bmax < 1kA)
0.1kA 1kA 10kA
10-2s 10-1s 1s 10s 102s 103s 104s 3kA Is Is = I3Amin
Current selectivity
Example
Plus
Easy to be realized
Economic
Instantaneous
Minus
Selectivity
is
often
only
partial
Current
thresholds
rise
very
quickly
CURRENT SELECTIVITY
Current selectivity
Time selectivity is based on a trip delay of the upstream circuit breaker, so to let to the downstream protection the time suitable to trip
B A
Setting strategy:
progressively increase the trip delays getting closer to the power supply source On the supply side
the S function is required
Time
selectivity
0.1kA 10kA 100kA 10-2s 10-1s 1s 10s 102s 103s 104s 1kA
The ultimate selectivity value is:
Is = IcwA (if function I = OFF) Is = I3minA (if function I = ON)
I
k
A will be set with the current threshold I2
adjusted so as not to create trip overlapping
and with a trip time t2 adjusted so that B always clears the fault before A
B will be set with an instantaneous trip against short-circuit B I2 t2 Is
Time
selectivity
Example
0.1kA 10kA 100kA 10-2s 10-1s 1s 10s 102s 103s 104s 1kA
The network must withstand high values of let-through energy!
If there are many hierarchical levels, the progressive delays could be significant!
I
k
Which is the problem of time selectivity?
In the case of fault occurring at the busbars, circuit breaker A takes a delayed trip time t2
B
t2
Time selectivity
Plus
Economic solution
Easy to be realized
Minus
TIME SELECTIVITY
Time
selectivity
Plus
and
minus
Quick rise of setting levels
Energy selectivity is based on the
current-limiting characteristics of some circuit breakers
A
B
0.1kA 1kA 10kA 10-2s 10-1s 1s 10s 102s 103s 104s
Current-limiting circuit breaker has an extremely fast trip time, short enough to prevent the current from reaching its peak The ultimate current
selectivity values is given by the manufacturer (Coordination tables)
Energy
selectivity
Base
concept
1kA 10kA 0.1kA 10-2s 10-1s 1s 10s 102s 103s 104s
Circuit breaker A conditions: I3=OFF
S as for time selectivity
A
B
Is = 20kA
Energy selectivity
PLUS
MINUS
ENERGY SELECTIVITY
Energy
selectivity
Plus
and
minus
High
selectivity
values
Reduced
tripping
times
Low
stress
and
network
disturbance
Zone selectivity is an evolution of the time selectivity, obtained by means of a electrical interlock between devices
The circuit breaker which detects a fault
communicates this to the one on the supply side, sending a locking signal
Fault locking
signal
Only the downstream circuit breaker opens, with no need to increase the intentional time delay
Zone
selectivity
A Does Not Open B Does Not Open C Opens
A
B
C
Zone 1 Zon e 2 Zone 3Zone
selectivity
Example
Is up to 100kA for Tmax Is up to Icw for Emax
It is possible to obtain zone selectivity between Tmax and Emax
Zo ne 1 Zo ne 2 Zo ne 3
Zone
selectivity
needs:
a shielded twisted pair cable an external source of 24V dedicated trip units
PR223EF for Tmax T4, T5 and T6 PR332/P for Tmax T7 and T8
PR122/P and PR123/P for Emax
PR332/P and PR333/P for X1
Zone
selectivity
PLUS
MINUS
ZONE SELECTIVITY
Zone
selectivity
Plus
and
minus
Trip times reduced
Low thermal and dynamic stress
High number of hierarchical levels
Can be made between same size circuit breakers
Cost
and
complexity
of
the
installation
© ABB Group, BU Breakers and Switches September 24, 2013 | Slide 87
Definitions and Standards
Selectivity techniques
Back-up protection
Back-up protection
Agenda
Back-up protection (or cascading)
is a type of coordination of two protective
devices in series which is done in electrical
installations where continuous operation is
not an essential requirement.
Back-up protection
What is back-up protection?
Back-up protection
excludes the use
The definition of back-up is given by the
“Back-up is a coordination of two overcurrent protective
devices in series, where the protective device on the supply
side, with or without the assistance of the other protective
device, trips first in order to prevents any excessive stress on
downstream devices”.
IEC 60947-1 Standard: “Low voltage equipment
Part 1: General rules for low voltage equipment”
Back-up protection
Standards definition
IEC 60947-1
def. 2.5.24
Back-up is used by those who need
to contain the plant costs
The use of a current-limiting circuit
breaker on the supply side
permits the installation of lower performance
circuit breakers on the load side
Both the continuity of service and the selectivity are sacrificed
Back-up
protection
T4L 250 T1N 160 T1N 160 T1N 160 Ik= 100 kA T4L 250 T4L 250 T4L 250 Icu = 120kA Icu = 36kA Icu (T4L+T1N) = 100kA
Back-up protection
Application example
T4L 250 T1N 160 T1N 160 T1N 160 Ik= 100kA Icu (T4L+T1N) = 100kA Ik= 100kA A B C D
Back-up protection
Application example
General power supply
is always lost
Plus
Economic solution
Quick tripping times
Minus
No selectivity
Low power quality
BACK-UP PROTECTION
Back-up
protection
Incoming = T5H 630A (70kA rating) Outgoing = T3N 160A (36kA rating)
Results: The co-ordination
resulted in a conditional short-circuit of 65kA for the T3 mccb! The discrimination is up to 20kA.
Example of Selectivity
I
z
T5H 630A
70kA
T3N 160A
36kA
65kA
~
Example of Selectivity
Example of Selectivity
T5H 70kA
T3N 36kA
Example of Selectivity
Meaning of Selectivity Value
T3N 36kA
T5H
70kA
Y is 20kA
T3N 36kA
T5H
70kA
T5H
T3N
20kA
Example of Selectivity
5kA
T5H
T3N
5kA fault
ON
Trip
T3N 36kA
T5H
70kA
Example of Selectivity
T5H
T3N
5kA fault
ON
Trip
10kA fault
ON
Trip
10kA
T3N 36kA
T5H
70kA
Example of Selectivity
T3N 36kA
20kA
T5H
70kA
T5H
T3N
5kA fault
ON
Trip
10kA fault
ON
Trip
20kA fault
Trip
Trip
Example of Selectivity
T3N 36kA
36kA
T5H
70kA
T5H
T3N
5kA fault
ON
Trip
10kA fault
ON
Trip
20kA fault
Trip
Trip
36kA fault
Trip
Trip
Example of Selectivity
T3N
65kA
T5H
70kA
T5H
T3N
5kA fault
ON
Trip
10kA fault
ON
Trip
20kA fault
Trip
Trip
36kA fault
Trip
Trip
65kA fault
Trip
Trip
36kA
Example of Selectivity
Motor co-ordination
ABB offers co-ordination tables
MV/LV Transformer Substations
Co-ordination between CBs and switch-disconnectors
T2S160
T1D160
400V
MV/LV Transformer Substations
© ABB Group
September 24, 2013 | Slide 107
DOC
Electrical Installation Calculation and
Dimensioning
Contents
Introduction
Aim of the application Target users
Products managed
How it works
Features
Support Tools
ABB Software Desktop Assistance
How to obtain the software
© ABB Group
September 24, 2013 | Slide 109
DOC
Aim of the application
DOC is the software for Electrical Installations Calculation and Dimensioning
Draw single-line diagrams
Perform electrical calculation according to the Standards
Choose the correct switching and protecting devices (MV and lv devices)
Set the trip units and check for discrimination Prepare a complete project documentation
Introduction
Aim of the application
Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Target user
DOC is complete and precise, but smart and flexible and can be used from everyone interested in calculating
electrical installation or part of them Consultants
Electrical Engineers Panel builders
Installers
Introduction
Aim of the application
Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
DOC allows and the selection of a wide range of ABB Products
Medium Voltage products Low Voltage products Motors
Transformers
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products Air Circuit- Breakers
New Emax
Emax
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products
Molded Case Circuit Breakers
Tmax
Isomax
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products
Miniature Circuit Breakers
System PRO M
System PRO M Compact
S800
Smissline
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products RCCBs
System PRO M
System PRO M Compact
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products Fuses
OFAX
OFASB
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products Switch Fuses
E930
OESA
OS
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products Disconnectors New Emax MS Emax MS Tmax D Isomax D OT OETL E200 Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products Contactors A AF EN ESB E250 E259 E260 Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products Manual Motor Starter
MS116, MS325, MS450, MS495, MS496
MO325, MO450, MO495, MO496 , MO497
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Low Voltage Products Thermal Overload
TAxxDU, ExxDU
UMC-22
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Medium Voltage Products Circuit breaker
Secondary distribution SF6 and Vacuum up to 24kV 630A 16kA
Primary distribution SF6 and Vacuum up to 36kV 3150A 50kA
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Medium Voltage Products Circuit breaker REF542Plus/DK PR521/DK PR521/P (50-51) PR521/P (50-51-51N) REF542Plus REF610 REJ525 PR512/P (50-51) PR512/P (50-51-50N-51N) PR512/PD Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Medium Voltage Products Disconnectors SHS2/A SHS2/I SHS2/IB SHS2/IF SHS2/N-I Earth Disconnectors Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Medium Voltage Products Switch Disconnectors SHS2/T1 SHS2/T1M SHS2/T2 SHS2/T2F SHS2/T2M SHS2/T2MF SHS2/N-T1 SHS2/N-T1M SHS2/N-T2 SHS2/N-T2F SHS2/N-T2M SHS2/N-T2MF Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Medium Voltage Products General Purpose Fuses
CEF 7.2kV 200A CEF 12kV 125A CEF 17.5kV 100A CEF 24kV 80A Motor Fuses CEM 7.2kV 315A CEM 12kV 100A Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Medium Voltage Products Cables
Sized according to the ABB
“XLPE Cable Systems Users Guide"
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Product managed
Other Products Motors M2xxx M3xxx Transformers Oil Distribution Transformers RESIBLOC
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
How it works
DOC
Features - Professional and Light Profiles
DOC can be used with 2 different profiles
Depending on the user needs and skills it can be recommended to use the Light Profile which hides the advanced and complex features
DOC Light is for ...
... first time, unskilled DOC users
... installers – panel builders
who need a simple tool to draw and verify small networks
DOC Professional is for ...
... skilled DOC users
... customers working on industrial applications
... engineering companies –
OEM‟s looking for a powerful calculation and design tool
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Single line diagram drawing
Different layout available:
Blank Page More flexible
Allows representing rings and meshes
Main project data available beside the objects
Column Page
Faster and easier drawing
Main project data available in the grid
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Single line diagram drawing
Different ways to draw the symbols:
By Single Objects More flexible
Allows representing rings and meshes
By Macros
Faster and easier drawing
Note: it is possible to use Single Objects and Macros independently from the layout
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Single line diagram drawing
When using the Column layout, Objects are numbered by Page & Column
All the object in the same feeder have the same number
I.e: Page =1, Column=3 leads to QF1.3+ WC1.3 +L1.3
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Single line diagram drawing
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
It is possible to draw one scheme on more than one page
Use the „Add Sheet‟ and „Change layout‟ commands to prepare new empty
pages
Use the Cross References to connect two objects
Features - Plant General Properties Window
This window is shown when starting a new project. Set all the options carefully to spare time when drawing and calculating the electrical installation
Main options:
Power supply definition
Voltage level
Default distribution system
Default number of phases
Method for SC calculations
Method for cable sizing
Options for addressing the device selection
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Suggested Workflow
A toolbar on the right side of the working area suggests the preferred way to develop a project with DOC
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
MV diagram drawing LV diagram drawing
Calculation and automatic project dimensioning
Protection and discrimination verification thru the curves
Auxiliaries scheme drawing
Switchboard configuration
Features - MV Diagram Drawing
The Medium Voltage section of the project can be drawn by the Macros of the typical units of the Unimix switchboard or by Objects for more flexibility
To pass to the Low Voltage section it is necessary to use the
transformers (when a low voltage section is not needed, the drawing can be completed with MV Loads or Motors)
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Lv Diagram Drawing
The Low Voltage section of the project can be drawn by the Macros or by Objects for more flexibility
The Macros available represents the most common Objects
combinations; not available combinations can be realized using the Objects
1 Macro = 1 Feeder = Many single objects
I.e.: CB+Cable+Load
I.e.: Fuse+Cable+Load
Faster drawing
Pop-up window
When drawing a feeder it is possible to insert the main
data making the drawing phase faster
Power Supply
Switchboard Arrival
Sub-Switchboard
Interlock graphical representation
Feeders
Motor Coordination
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Calculation and automatic dimensioning
Load-Flow
DOC can calculate the current distribution, the voltage profile and the voltage drop profile in load condition considering:
Section with different number of phases
Unbalanced loads (automatic balance is optional)
Transformer Voltage Regulator
Cable dimensioning
Presence of meshes
More distribution systems
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Cable dimensioning
Given the power required by the loads and the motors, DOC is able to size the cables in an iterative process bringing to the section optimization and the current profile calculation
DOC implements several calculation methods
IEC 60364
CEI 64-8 Italian standard
VDE 298 German standard
NFC 15-100 French standard
UNE 20460 Spanish standard
IEC 60092 (for naval installation)
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Short Circuit
DOC can calculate the maximum and minimum short circuit currents, with or without the motor contribution, for symmetrical and non-symmetrical faults, for different times
DOC implements several calculation methods
IEC 60909 LV\MV network, AC, 50-60Hz
IEC 60363 Naval
NFC 15-100 French national standard
Symmetrical components method
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Calculation and automatic dimensioning
Configuration Management In DOC it is possible to
simulate different
scenarios for the electrical installation defining the open/closed position for the switching and
protecting devices The calculation are
performed in the worst condition
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Devices Selection
The calculation leads to an automatic proposal for all the devices drawn in the scheme
When more than one product is technically suitable, DOC proposes the basic one
It is possible to change the solution proposed by DOC and to lock the user choice thanks to the padlocks present in all the selection windows
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
DOC gives the possibility to perform the temperature rise-assessment according to IEC 60890 in a early stage of the installation design
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features - Curves
With DOC it is possible to manage
Time-current diagrams for the devices present in the scheme Set the thermomagnetic and electronic trip units
Realize discrimination studies involving MV and LV devices Verify the cable protection
1E-2kA 0.1kA 1kA 10kA 100kA
1E-2s 0.1s 1s 10s 100s 1E3s 1E4s Time-Current curve LLL -QF2, HD4/UniMix-R 24.06.12 P230, REF542Plus/DK -TM1
-QF5, E4S 4000 PR121-LI 4000A
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Features – Switchboard configuration
With DOC it is now possible to configure switchboard:
By using a Wizar configuration: three steps guide procedure to create a switchboard.
By using a toolbar on the left side of working area: Insert and move column, Kit and device
Tracking busbar system and temperature rise assessment
Layer management (door, panel and plate layer, show hide busbars)
Modify switchboard dimension
Features - Project documentation
Different reports sections allows the creation of a unique file documenting the project
The report sections can be added/removed according to the needs
Calculation hypothesis
Short circuit calculations
Cable Protections
MV / LV devices list and settings Export in MS Excel is available
The report language can be different from the current language
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Support Tools
DOC
ABB Software Desktop
ABB Software Desktop (ASD)
ASD is automatically installed with the first installed software
ASD functionalities:
Allows to run the software
Manage the language
Registration
Software upgrade
Contact Software Support
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
© ABB Group
September 24, 2013 | Slide 152
ABB Software Desktop
Registration
Visit www.bol.it.abb.com
Click on Profile Management
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Starting on a New Project
© ABB Group
September 24, 2013 | Slide 153
ABB Software Desktop
Registration
Click on New User
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Starting on a New Project
© ABB Group
September 24, 2013 | Slide 154
ABB Software Desktop
Registration
Click on Subscribe
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Starting on a New Project
ABB Software Desktop
Registration
After registering via internet , you will receive immediately an e-mail with ID and PSW to access the Upgrade
Service
Use them to check for
available Upgrades before starting using the Software
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Upgrade DOC via internet
ABB Software Desktop
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software
Use The Automatic Upgrade Service allows you to
maintain the software aligned to the latest
improvements delivered from ABB SACE them to check for available
Upgrades before starting using the Software
Assistance
How to contact us – Software support
Ask the ABB SACE Software Assistance for any question you may have regarding the software tools
Email [email protected] Call Center +39 035 395 570 On line http://www.bol.it.abb.com Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance
How to obtain the software
How to obtain the software
Refer to the ABB Local Sales Organization for a free copy of the software
Introduction
Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance
How to obtain the software