• No results found

Electrical Networking, Short Circuit Calculation, Discrimination

N/A
N/A
Protected

Academic year: 2021

Share "Electrical Networking, Short Circuit Calculation, Discrimination"

Copied!
158
0
0

Loading.... (view fulltext now)

Full text

(1)

© ABB Group

September 24, 2013 | Slide 1

Lionel Ng, LPBS - Low Voltage Products

Welcome To ABB

(2)

© ABB Group

September 24, 2013 | Slide 2

MV & LV Transformer Substations

Theory & Short Circuit Calculation

(3)

Contents

 General information on MV/LV transformer substations

 Calculation of short-circuit currents

 Choice of protection and control devices

 Example of study of a MV/LV network

(4)

 The electrical substations can be divided into

 public substations

 belong to the electricity utility

 supply private users in AC single-phase or three-phase current (230V and 400V)

 urban type in bricks

 rural type installed externally directly on the MV pylon

 private substations

 belong to the user

 civil users (schools, hospitals, etc.) and industrial users  are mostly located in the same rooms of the factory

General Information

(5)

 Typical structure of a substation

where the switching apparatus of the utility is installed.

where the measuring units are located

contains the transformer and the MV and LV switching apparatus

General Information

(6)

 Most common management methods

Substation with a single transformer

General Information

(7)

 Most common management methods

Substation with two transformers

(one as a spare for the other)

It is possible to use the Emax with a wire interlock (mechanical interlock) between two CBs

General Information

(8)

 Most common management methods

two transformers which operate

in parallel on the same busbar

General Information

(9)

two transformers which operate simultaneously on

two separate half-busbars

 Most common management methods

General Information

MV/LV Transformer Substations

It is possible to use the Emax with a wire interlock (mechanical interlock) between three CBs

(10)

 MV/LV transformers

 is the most important part of the transformer substation

 single transformer for low powers (up to 630kVA - 800kVA)

 several units in parallel for higher powers (1000kVA - 2500kVA)

 type of cooling system

 air  oil

 most used

 AN cooling with natural air circulation

 ONAN cooling with natural oil and air circulation types

General Information

(11)

ONAN transformer containing more than 500 kg of oil (> 800kVA)

General Information

MV/LV Transformer Substations

(12)

 MV/LV transformers

 one single trafo or two trafos in parallel?

U

U

750M

VA

400V

1600kVA

6%

800kVA

4%

800kVA

4%

400V

750M

VA

37 kA

55kA

General Information

MV/LV Transformer Substations

(13)

 Management philosophy for the protections

 L1 trip

 ensured service continuity

General Information

(14)

 Management philosophy for the protections

 I

LV1

and C

LV

trip

 power supply is maintained to the half-busbar

trip

trip

General Information

(15)

 Management philosophy for the protections

 I

MV1

and I

LV1

trip to isolate the trafo affected by the fault

 ensured service continuity

 a logic for the disconnection of non-priority loads should be

foreseen

General Information

(16)

 Management philosophy for the protections

 I

MV1

trip, I

LV1

trip for pulling

 service continuity of the whole plant

 a logic for the disconnection of non-priority loads should be

foreseen

General Information

(17)

 LV protection devices

L function protection against

overload

General Information

(18)

S function protection against delayed short-circuit

 LV protection devices

General Information

(19)

I function

protection

against instantaneous

short-circuit

 LV protection devices

General Information

MV/LV Transformer Substations

(20)

G function

protection

against earth-fault

 LV protection devices

General Information

(21)

 IEC 60909-0 (CEI 11-25)

 Short-circuit:

 “Accidental or intentional conductive path between two or more conductive parts forcing the electric potential differences between these conductive parts to be equal or close to zero”

 Short-circuit current:

 “Overcurrent resulting from a short-circuit in an electric system”

MV/LV Transformer Substations

(22)

 Main components involved in a short-circuit calculation

 Distribution networks

 Generators

 Transformers

 Asynchronous motors

 Cables

 Each component of the network is replaced by its

relevant impedance

U

Zknet ZcMV ZTR ZcLV

MV/LV Transformer Substations

(23)

 The equivalent network is solved according to standard

electrotechnical rules (circuits in series / in parallel)

knet cMVn TR cLV

k

Z

Z

Z

Z

3

U

I

U

n

Z

kne t

Z

cM V

Z

T R

Z

cLV

I

k

MV/LV Transformer Substations

(24)

 Distribution network

 it is necessary to know the network short-circuit power

 from 250MVA to 500MVA Un  30kV

 from 700MVA to 1500MVA Un > 30kV  according to IEC 60076-5 knet n knet 2 n knet

I

3

U

S

U

Z

MV/LV Transformer Substations

(25)

 Generators

 it is necessary to know

 rated apparent power Sn  rated voltage Un

 subtransient reactance x”d

 from 10% to 20% smooth rotor (isotropic machines)

 from 15% to 30% salient pole rotor (anisotropic machines)

n 2 n " d " d

S

U

100

x

X

MV/LV Transformer Substations

(26)

 Transformer

 it is necessary to know

 rated apparent power Sn

 primary rated voltage voltage U1n  secondary rated voltage U2n

 short-circuit voltage uk%from 4% to 8%  according to IEC 60076-5 n 2 n 2 % k TR

S

U

100

u

Z

MV/LV Transformer Substations

(27)

 Asynchronous motors

 In case of short-circuit it functions as a

generator with a x”

d

from 20% to 25%

 a current equal to 4-6 times the I

n

can be

assumed as contribution to the short-circuit

 the minimum criteria for taking into

consideration the phenomenon

 (Ik shortcircuit without motor contribution)

MV/LV Transformer Substations

(28)

 Example

U

S

k

= 500 MVA

U

MV

= 20 kV

Z

cMV

= 0.01

S

n

= 400 kVA

U= 20/0.4 kV

u

k%

= 4 %

Z

cLV

= 0.06

MV/LV Transformer Substations

(29)

U

S

k

= 500

MVA

U

MV

= 20 kV

Z

u

= 0.32

m

     0.8 10 500 10 20 S U Z 6 2 3 k 2 kV 20 u

 

     4 2 2 kV 20 u V 400 u 3.2 10 20000 400 Z Z

 Example

MV/LV Transformer Substations

(30)

U

Z

u

= 0.32 m

 

     6 2 2 kV 20 cMV V 400 cMV 4 10 20000 400 Z Z

Z

cMV

= 4

10

-3

m

Z

cMV

= 0.01

 Example

MV/LV Transformer Substations

(31)

U

Z

u

= 0.32 m

Z

cMV

= 4

10

-3

m

S

n

= 400 kVA

U= 20/0.4 kV

u

k%

= 4 %

 

    0.016 10 400 400 100 4 S U 100 u Z 3 2 n 2 nLV % k T

Z

T

= 0.016

 Example

MV/LV Transformer Substations

(32)

U

Z

u

= 0.32 m

Z

cMV

= 4

10

-3

m

Z

T

= 16 m

Z

cLV

= 0.61 m

Z

cLV

= 0.61

m

 Example

MV/LV Transformer Substations

(33)

U

S

k

= 500

MVA

U

MV

= 20 kV

Z

u

= 0.32 m

Z

cMV

= 4

10

-3

m

Z

T

= 16 m

Z

cLV

= 0.61 m

U

n

= 400 V

Z Z Z

14.1kA 3 U I T cMV u n k     

Z Z Z Z

13.6kA 3 U I cLV T cMV u n k      

 Example

MV/LV Transformer Substations

(34)

© ABB Group

September 24, 2013 | Slide 34

MV & LV Transformer Substations

General Information about Circuit

Breakers

(35)

Definitions

Circuit-breaker: a mechanical switching device capable of making,

carrying and breaking currents under normal circuit conditions and

also making, carrying for a specified time, and breaking currents

under specified abnormal circuit conditions such as those of

overload or short-circuit (IEC 60947-1 def. 2.2.11)

MV/LV Transformer Substations

(36)

Definitions

Moulded case CB:

a circuit-breaker having a supporting

housing of moulding insulating material forming an

integral part of the circuit-breaker (Isomax / Tmax /

Formula)

Air CB:

a circuit-breaker in which the contacts open and

close in air at atmospheric pressure (Emax)

MV/LV Transformer Substations

(37)

Definitions

Current-limiting circuit-breaker:

a circuit-breaker with a

break-time short enough to prevent the short-circuit

current reaching its peak value (IEC 60947-2 def. 2.3)

MV/LV Transformer Substations

(38)

Prospective

peak value

Limited

peak

value

Prospective

short-circuit current

Limited short-circuit

current

Specific let-through

energy (I

2

t)

I

t

MV/LV Transformer Substations

Current-Limiting Circuit Breakers

(39)

Prospecti

ve peak

value

Limited

peak

value

Prospective short-circuit current Limited short-circuit current Specific let-through energy

I

t

I2t Icc Ip Icc

go

MV/LV Transformer Substations

Current-Limiting Circuit Breakers

(40)

1E-2kA 0.1kA 1kA 10kA 1kA 10kA 100kA 1E3kA 1E4kA 1E5kA Curva di limitazione

40 kA

T2L160 In160 A

40 kA

16 kA

84 kA

Irms

Ip

Prospective

peak value

Limited peak

value

MV/LV Transformer Substations

Current-Limiting Circuit Breakers

(41)

 Generalities about the main electrical parameters

 Rated operational voltage U

e

: the value of voltage which

determines the application and to which all the other

parameters are referred to

 Rated uninterrupted current I

u

: the value of current which the

device is able to carry for an indefinite time. It defines the size

of the CB

 Rated current I

n

: the value of current which characterizes the

protection release installed. Is often related to the rated

current of the load protected

MV/LV Transformer Substations

Selection of Protective Devices

(42)

 Generalities about the main electrical parameters

 Rated ultimate short-circuit breaking capacity I

cu

: it is the

r.m.s. value of the symmetrical component of the short-circuit

current which the circuit-breaker is able to break (test cycle

O-t-CO)

 Rated service short-circuit breaking capacity I

cs

: it is the r.m.s.

value of the symmetrical component of the shortcircuit current

which the circuit-breaker is able to break (O-t-CO-t-CO)

T5N400 PR221DS-LS/I In 320

I

cu

MV/LV Transformer Substations

Selection of Protective Devices

(43)

MV/LV Transformer Substations

Selection of Protective Devices

Ultimate Short-Circuit Breaking Capacity (I

cu

):

breaking capacity for which the prescribed conditions

according to a specified test sequence do not include

the capability of the CB to carry its rated current

continuously

- test sequence: O - 3 min - CO

- dielectric withstand at 2

x

U

e

(44)

MV/LV Transformer Substations

Selection of Protective Devices

Service Short-Circuit Breaking Capacity (I

CS

):

breaking capacity for which the prescribed conditions

according to a specified test sequence include the

capability of the CB to carry its rated current continuously

- test sequence: O - 3 min - CO - 3 min – CO

(25%-50%-75%-100% of Icu)

- operational performance capability:

(5% of N°operating cycle

for operational performance capability- table 8 60947-2)

- dielectric withstand at 2 x

U

e

- verification of temperature rise at I

u

(the temperature doesn‟t

exceed the limits of table 7 60947-2)

(45)

 Generalities about the main electrical parameters

 Rated short-circuit making capacity I

cm

: it is the maximum

prospective peak current which the circuit-breaker must be

able to make

 Icm=n x Icu

T5N400 PR221DS-LS/I In 320

I

cu

36kA

I

cm

75.6 kA @415V

MV/LV Transformer Substations

Selection of Protective Devices

(46)

 Generalities about the main electrical parameters

 Rated short-time withstand current I

cw

: it is the r.m.s. value of

the alternate current component which the circuit-breaker is

able to withstand without damages for a determined time,

preferred values being 1s and 3 s

 Defined for category B only

MV/LV Transformer Substations

Selection of Protective Devices

(47)

MV/LV Transformer Substations

Selection of Protective Devices

(48)

 Generalities about the main electrical parameters

Don‟t forget

 Ue  Un  Icu or Ics  Ik  Icm  Ip

Ue, Icu, Ics, Icm?

MV/LV Transformer Substations

Selection of Protective Devices

(49)

 Protection of feeders

 against overload

 Ib ≤ In or I1 ≤ Iz

 against short-circuit

 I2t ≤ k2S2

I

n

I

z

S

I

b

MV/LV Transformer Substations

Selection of Protective Devices

(50)

MV/LV Transformer Substations

Selection of Protective Devices

(51)

MV/LV Transformer Substations

Selection of Protective Devices

(52)

 Protection of generators

 I

ngen

≤ I

1

I3 or I2 ≤ 2.5-4 x I

ngen

G

MV/LV Transformer Substations

Selection of Protective Devices

(53)

 Protection of transformers

 I

nT

≤ I

1

 Upstream CB

 I3 or I2  Iinrush

MV/LV Transformer Substations

Selection of Protective Devices

(54)

 Steps

 determining the short-circuit

currents

 choosing the CB

 setting of the MV overcurrent

protection

 setting of the LV overcurrent

protection

20kV

400V

MV/LV Transformer Substations

Example of an MV/LV Network

(55)

20kV

400V

MV/LV Transformer Substations

Example of an MV/LV Network

(56)

20kV

400V

MV/LV Transformer Substations

Example of an MV/LV Network

(57)

© ABB Group

September 24, 2013 | Slide 57

Low

voltage

selectivity

with

ABB

circuit

breakers

(58)

Definitions and Standards

Selectivity techniques

Definitions and Standards

Back-up protection

Agenda

(59)

Selectivity (or discrimination)

is a type of coordination of two or

more protective devices in series.

Selectivity is done between

one circuit breaker on the supply side

and one circuit breaker, or more than

one, on the load side.

A is the supply side circuit

breaker (or upstream)

B and C are the load side circuit

breakers (or downstream)

Introduction

(60)

 Better selectivity

FAULT CONTINUITY OF SERVICE

DAMAGE REDUCTION

Fast fault elimination

Reduce the stress and prevent damage

Minimize the area and the duration of

power loss

Introduction

(61)

Selective coordination among devices

is fundamental for economical and technical reasons

It is studied in order to

:

 rapidly identify the area involved in the problem;

 bound the effects of a fault by excluding just the affected zone of the network;

 preserve the continuity of service and good power quality to the sound parts of the network;

 provide a quick and precise identification of the fault to the personnel in charge of maintenance or to management system, in order to restore the service as rapidly as possible;

 achieve a valid compromise between reliability, simplicity and cost effectiveness.

Main purposes of coordination

(62)

The definition of selectivity

“Trip selectivity (for overcurrent) is a coordination between the

operating characteristics of two or more overcurrent protection

devices, so that, when an overcurrent within established limits

occurs, the device destined to operate within those limits trips

whereas the others do not trip”

IEC 60947-1 Standard: “Low voltage equipment

Part 1: General rules for low voltage equipment”

Standards

definition

Selectivity

IEC 60947-1

def. 2.5.23

(63)

In occurrence of a fault

(an overload or a short circuit)

if selectivity is provided

only the downstream circuit

breaker opens.

Overcurrent

selectivity

(64)

All the system is out of service!

In occurrence of a fault

(an overload or a short circuit)

if selectivity is not provided

both the upstream and the

downstream circuit breakers

could

open

Overcurrent

selectivity

(65)

A

and

B

connected

in

series:

partial

selectivity

and

total

selectivity.

Standards definition

Partial and total selectivity

IEC 60947-2

def. 2.17.2 - 2.17.3

(66)

“Partial selectivity is an overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load side protection device carries out the protection up to a given level of overcurrent, without making the other device trip.”

B opens only according to fault current lower than a certain current value; values equal or greater than Is will give the trip of both A and B.

Is is the ultimate selectivity value! Is = ImA

Standards definition

Partial selectivity

(67)

Only B trips for every current value lower or equal to the maximum short-circuit current.

“Total selectivity is an overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load side protection device carries out the protection without making the other device trip.”

B A

Is = Ik

Standards definition

(68)

Upstream circuit breaker A

T4N 250 PR221DS In = 250 (I

cu

= 36kA)

Downstream circuit breaker B

S 294 C100 (I

cu

= 15kA)

Standards definition

(69)

 Overload zone Thermal protection L protection 

Short-circuit

zone

Magnetic protection S, D, I and EF protections

Time-current selectivity

Current, time, energy, zone,

directional, zone directional selectivity

Selectivity

analysis

(70)

Real currents circulating through the circuit breakers

I>

A

B I> I> I>

A B I> I> I> I> I> A B I> I>

I

A

= I

B IA IB tA tB tA tB IA IB IA=IB tA tB

I

A

= I

B

+ I

loads

I

A

= (I

B

+ I

loads

)

/ 2

Selectivity

analysis

Real

currents

(71)

© ABB Group, BU Breakers and Switches September 24, 2013 | Slide 71

Definitions and Standards

Selectivity techniques

Selectivity techniques

Back-up protection

Agenda

(72)

© ABB Group, BU Breakers and Switches September 24, 2013 | Slide 72

Current selectivity

Time selectivity

Energy selectivity

Zone (logical) selectivity

Introduction

(73)

 The ultimate selectivity value

is equal to the instantaneous trip threshold of the upstream protection device

 Other methods are needed to have a total selectivity

A B

ImB ImA

 Current selectivity: closer to the power supply the fault point is, higher the fault current is

 In order to guarantee selectivity,

the protections must be set to different values of current thresholds

Ultimate selectivity value 1kA 3kA tB tA tA

Current selectivity

Base concept

(74)

A

B

Here the selectivity is a total selectivity,

because it is guaranteed up to the maximum value of the short-circuit current, 1kA.

Circuit breaker A will be set to a value which does not trip for faults which occur on the load side of B.

(I3Amin >1kA)

Circuit breaker B will be set to trip for faults which occur on its load side (I3Bmax < 1kA)

0.1kA 1kA 10kA

10-2s 10-1s 1s 10s 102s 103s 104s 3kA Is Is = I3Amin

Current selectivity

Example

(75)

Plus

Easy to be realized

Economic

Instantaneous

Minus

Selectivity

is

often

only

partial

Current

thresholds

rise

very

quickly

CURRENT SELECTIVITY

Current selectivity

(76)

 Time selectivity is based on a trip delay of the upstream circuit breaker, so to let to the downstream protection the time suitable to trip

B A

 Setting strategy:

progressively increase the trip delays getting closer to the power supply source  On the supply side

the S function is required

Time

selectivity

(77)

0.1kA 10kA 100kA 10-2s 10-1s 1s 10s 102s 103s 104s 1kA

The ultimate selectivity value is:

Is = IcwA (if function I = OFF) Is = I3minA (if function I = ON)

I

k

A will be set with the current threshold I2

adjusted so as not to create trip overlapping

and with a trip time t2 adjusted so that B always clears the fault before A

B will be set with an instantaneous trip against short-circuit B I2 t2 Is

Time

selectivity

Example

(78)

0.1kA 10kA 100kA 10-2s 10-1s 1s 10s 102s 103s 104s 1kA

The network must withstand high values of let-through energy!

If there are many hierarchical levels, the progressive delays could be significant!

I

k

Which is the problem of time selectivity?

In the case of fault occurring at the busbars, circuit breaker A takes a delayed trip time t2

B

t2

Time selectivity

(79)

Plus

Economic solution

Easy to be realized

Minus

TIME SELECTIVITY

Time

selectivity

Plus

and

minus

Quick rise of setting levels

(80)

 Energy selectivity is based on the

current-limiting characteristics of some circuit breakers

A

B

0.1kA 1kA 10kA 10-2s 10-1s 1s 10s 102s 103s 104s

Current-limiting circuit breaker has an extremely fast trip time, short enough to prevent the current from reaching its peak  The ultimate current

selectivity values is given by the manufacturer (Coordination tables)

Energy

selectivity

Base

concept

(81)

1kA 10kA 0.1kA 10-2s 10-1s 1s 10s 102s 103s 104s

Circuit breaker A conditions: I3=OFF

S as for time selectivity

A

B

Is = 20kA

Energy selectivity

(82)

PLUS

MINUS

ENERGY SELECTIVITY

Energy

selectivity

Plus

and

minus

High

selectivity

values

Reduced

tripping

times

Low

stress

and

network

disturbance

(83)

 Zone selectivity is an evolution of the time selectivity, obtained by means of a electrical interlock between devices

 The circuit breaker which detects a fault

communicates this to the one on the supply side, sending a locking signal

Fault locking

signal

 Only the downstream circuit breaker opens, with no need to increase the intentional time delay

Zone

selectivity

(84)

A Does Not Open B Does Not Open C Opens

A

B

C

Zone 1 Zon e 2 Zone 3

Zone

selectivity

Example

(85)

 Is up to 100kA for Tmax  Is up to Icw for Emax

 It is possible to obtain zone selectivity between Tmax and Emax

Zo ne 1 Zo ne 2 Zo ne 3

Zone

selectivity

needs:

 a shielded twisted pair cable  an external source of 24V  dedicated trip units

 PR223EF for Tmax T4, T5 and T6  PR332/P for Tmax T7 and T8

 PR122/P and PR123/P for Emax

 PR332/P and PR333/P for X1

Zone

selectivity

(86)

PLUS

MINUS

ZONE SELECTIVITY

Zone

selectivity

Plus

and

minus

Trip times reduced

Low thermal and dynamic stress

High number of hierarchical levels

Can be made between same size circuit breakers

Cost

and

complexity

of

the

installation

(87)

© ABB Group, BU Breakers and Switches September 24, 2013 | Slide 87

Definitions and Standards

Selectivity techniques

Back-up protection

Back-up protection

Agenda

(88)

Back-up protection (or cascading)

is a type of coordination of two protective

devices in series which is done in electrical

installations where continuous operation is

not an essential requirement.

Back-up protection

What is back-up protection?

Back-up protection

excludes the use

(89)

The definition of back-up is given by the

“Back-up is a coordination of two overcurrent protective

devices in series, where the protective device on the supply

side, with or without the assistance of the other protective

device, trips first in order to prevents any excessive stress on

downstream devices”.

IEC 60947-1 Standard: “Low voltage equipment

Part 1: General rules for low voltage equipment”

Back-up protection

Standards definition

IEC 60947-1

def. 2.5.24

(90)

Back-up is used by those who need

to contain the plant costs

The use of a current-limiting circuit

breaker on the supply side

permits the installation of lower performance

circuit breakers on the load side

Both the continuity of service and the selectivity are sacrificed

Back-up

protection

(91)

T4L 250 T1N 160 T1N 160 T1N 160 Ik= 100 kA T4L 250 T4L 250 T4L 250 Icu = 120kA Icu = 36kA Icu (T4L+T1N) = 100kA

Back-up protection

Application example

(92)
(93)

T4L 250 T1N 160 T1N 160 T1N 160 Ik= 100kA Icu (T4L+T1N) = 100kA Ik= 100kA A B C D

Back-up protection

Application example

General power supply

is always lost

(94)

Plus

Economic solution

Quick tripping times

Minus

No selectivity

Low power quality

BACK-UP PROTECTION

Back-up

protection

(95)

Incoming = T5H 630A (70kA rating) Outgoing = T3N 160A (36kA rating)

Results: The co-ordination

resulted in a conditional short-circuit of 65kA for the T3 mccb! The discrimination is up to 20kA.

Example of Selectivity

I

z

T5H 630A

70kA

T3N 160A

36kA

65kA

~

(96)

Example of Selectivity

(97)

Example of Selectivity

(98)

T5H 70kA

T3N 36kA

Example of Selectivity

Meaning of Selectivity Value

T3N 36kA

T5H

70kA

Y is 20kA

(99)

T3N 36kA

T5H

70kA

T5H

T3N

20kA

Example of Selectivity

(100)

5kA

T5H

T3N

5kA fault

ON

Trip

T3N 36kA

T5H

70kA

Example of Selectivity

(101)

T5H

T3N

5kA fault

ON

Trip

10kA fault

ON

Trip

10kA

T3N 36kA

T5H

70kA

Example of Selectivity

(102)

T3N 36kA

20kA

T5H

70kA

T5H

T3N

5kA fault

ON

Trip

10kA fault

ON

Trip

20kA fault

Trip

Trip

Example of Selectivity

(103)

T3N 36kA

36kA

T5H

70kA

T5H

T3N

5kA fault

ON

Trip

10kA fault

ON

Trip

20kA fault

Trip

Trip

36kA fault

Trip

Trip

Example of Selectivity

(104)

T3N

65kA

T5H

70kA

T5H

T3N

5kA fault

ON

Trip

10kA fault

ON

Trip

20kA fault

Trip

Trip

36kA fault

Trip

Trip

65kA fault

Trip

Trip

36kA

Example of Selectivity

(105)

 Motor co-ordination

 ABB offers co-ordination tables

MV/LV Transformer Substations

(106)

 Co-ordination between CBs and switch-disconnectors

T2S160

T1D160

400V

MV/LV Transformer Substations

(107)

© ABB Group

September 24, 2013 | Slide 107

DOC

Electrical Installation Calculation and

Dimensioning

(108)

Contents

Introduction

 Aim of the application  Target users

 Products managed

How it works

 Features

Support Tools

 ABB Software Desktop  Assistance

 How to obtain the software

(109)

© ABB Group

September 24, 2013 | Slide 109

DOC

(110)

Aim of the application

 DOC is the software for Electrical Installations Calculation and Dimensioning

 Draw single-line diagrams

 Perform electrical calculation according to the Standards

 Choose the correct switching and protecting devices (MV and lv devices)

 Set the trip units and check for discrimination  Prepare a complete project documentation

Introduction

Aim of the application

Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(111)

Target user

 DOC is complete and precise, but smart and flexible and can be used from everyone interested in calculating

electrical installation or part of them  Consultants

 Electrical Engineers  Panel builders

 Installers

Introduction

Aim of the application

Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(112)

Product managed

 DOC allows and the selection of a wide range of ABB Products

 Medium Voltage products  Low Voltage products  Motors

 Transformers

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(113)

Product managed

 Low Voltage Products  Air Circuit- Breakers

 New Emax

 Emax

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(114)

Product managed

 Low Voltage Products

 Molded Case Circuit Breakers

 Tmax

 Isomax

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(115)

Product managed

 Low Voltage Products

 Miniature Circuit Breakers

 System PRO M

 System PRO M Compact

 S800

 Smissline

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(116)

Product managed

 Low Voltage Products  RCCBs

 System PRO M

 System PRO M Compact

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(117)

Product managed

 Low Voltage Products  Fuses

 OFAX

 OFASB

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(118)

Product managed

 Low Voltage Products  Switch Fuses

 E930

 OESA

 OS

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(119)

Product managed

 Low Voltage Products  Disconnectors  New Emax MS  Emax MS  Tmax D  Isomax D  OT  OETL  E200 Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(120)

Product managed

 Low Voltage Products  Contactors  A  AF  EN  ESB  E250  E259  E260 Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(121)

Product managed

 Low Voltage Products  Manual Motor Starter

 MS116, MS325, MS450, MS495, MS496

 MO325, MO450, MO495, MO496 , MO497

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(122)

Product managed

 Low Voltage Products  Thermal Overload

 TAxxDU, ExxDU

 UMC-22

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(123)

Product managed

 Medium Voltage Products  Circuit breaker

 Secondary distribution SF6 and Vacuum up to 24kV 630A 16kA

 Primary distribution SF6 and Vacuum up to 36kV 3150A 50kA

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(124)

Product managed

 Medium Voltage Products  Circuit breaker  REF542Plus/DK  PR521/DK  PR521/P (50-51)  PR521/P (50-51-51N)  REF542Plus  REF610  REJ525  PR512/P (50-51)  PR512/P (50-51-50N-51N)  PR512/PD Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(125)

Product managed

 Medium Voltage Products  Disconnectors  SHS2/A  SHS2/I  SHS2/IB  SHS2/IF  SHS2/N-I  Earth Disconnectors Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(126)

Product managed

 Medium Voltage Products  Switch Disconnectors  SHS2/T1  SHS2/T1M  SHS2/T2  SHS2/T2F  SHS2/T2M  SHS2/T2MF  SHS2/N-T1  SHS2/N-T1M  SHS2/N-T2  SHS2/N-T2F  SHS2/N-T2M  SHS2/N-T2MF Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(127)

Product managed

 Medium Voltage Products  General Purpose Fuses

 CEF 7.2kV 200A  CEF 12kV 125A  CEF 17.5kV 100A  CEF 24kV 80A  Motor Fuses  CEM 7.2kV 315A  CEM 12kV 100A Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(128)

Product managed

 Medium Voltage Products  Cables

 Sized according to the ABB

“XLPE Cable Systems Users Guide"

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(129)

Product managed

 Other Products  Motors  M2xxx  M3xxx  Transformers

 Oil Distribution Transformers  RESIBLOC

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(130)

How it works

DOC

(131)

Features - Professional and Light Profiles

 DOC can be used with 2 different profiles

 Depending on the user needs and skills it can be recommended to use the Light Profile which hides the advanced and complex features

 DOC Light is for ...

 ... first time, unskilled DOC users

 ... installers – panel builders

who need a simple tool to draw and verify small networks

 DOC Professional is for ...

 ... skilled DOC users

 ... customers working on industrial applications

 ... engineering companies –

OEM‟s looking for a powerful calculation and design tool

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(132)

Features - Single line diagram drawing

 Different layout available:

 Blank Page  More flexible

 Allows representing rings and meshes

 Main project data available beside the objects

 Column Page

 Faster and easier drawing

 Main project data available in the grid

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(133)

Features - Single line diagram drawing

 Different ways to draw the symbols:

 By Single Objects  More flexible

 Allows representing rings and meshes

 By Macros

 Faster and easier drawing

 Note: it is possible to use Single Objects and Macros independently from the layout

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(134)

Features - Single line diagram drawing

 When using the Column layout, Objects are numbered by Page & Column

 All the object in the same feeder have the same number

 I.e: Page =1, Column=3 leads to QF1.3+ WC1.3 +L1.3

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(135)

Features - Single line diagram drawing

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

 It is possible to draw one scheme on more than one page

 Use the „Add Sheet‟ and „Change layout‟ commands to prepare new empty

pages

 Use the Cross References to connect two objects

(136)

Features - Plant General Properties Window

 This window is shown when starting a new project. Set all the options carefully to spare time when drawing and calculating the electrical installation

 Main options:

 Power supply definition

 Voltage level

 Default distribution system

 Default number of phases

 Method for SC calculations

 Method for cable sizing

 Options for addressing the device selection

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(137)

Features - Suggested Workflow

 A toolbar on the right side of the working area suggests the preferred way to develop a project with DOC

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

 MV diagram drawing  LV diagram drawing

 Calculation and automatic project dimensioning

 Protection and discrimination verification thru the curves

 Auxiliaries scheme drawing

 Switchboard configuration

(138)

Features - MV Diagram Drawing

 The Medium Voltage section of the project can be drawn by the Macros of the typical units of the Unimix switchboard or by Objects for more flexibility

 To pass to the Low Voltage section it is necessary to use the

transformers (when a low voltage section is not needed, the drawing can be completed with MV Loads or Motors)

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(139)

Features - Lv Diagram Drawing

 The Low Voltage section of the project can be drawn by the Macros or by Objects for more flexibility

 The Macros available represents the most common Objects

combinations; not available combinations can be realized using the Objects

 1 Macro = 1 Feeder = Many single objects

 I.e.: CB+Cable+Load

 I.e.: Fuse+Cable+Load

 Faster drawing

 Pop-up window

 When drawing a feeder it is possible to insert the main

data making the drawing phase faster

Power Supply

Switchboard Arrival

Sub-Switchboard

Interlock graphical representation

Feeders

Motor Coordination

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(140)

Features - Calculation and automatic dimensioning

 Load-Flow

 DOC can calculate the current distribution, the voltage profile and the voltage drop profile in load condition considering:

 Section with different number of phases

 Unbalanced loads (automatic balance is optional)

 Transformer Voltage Regulator

 Cable dimensioning

 Presence of meshes

 More distribution systems

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(141)

 Cable dimensioning

 Given the power required by the loads and the motors, DOC is able to size the cables in an iterative process bringing to the section optimization and the current profile calculation

 DOC implements several calculation methods

IEC 60364

 CEI 64-8 Italian standard

 VDE 298 German standard

 NFC 15-100 French standard

 UNE 20460 Spanish standard

 IEC 60092 (for naval installation)

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(142)

 Short Circuit

 DOC can calculate the maximum and minimum short circuit currents, with or without the motor contribution, for symmetrical and non-symmetrical faults, for different times

 DOC implements several calculation methods

IEC 60909 LV\MV network, AC, 50-60Hz

 IEC 60363 Naval

 NFC 15-100 French national standard

 Symmetrical components method

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

Features - Calculation and automatic dimensioning

(143)

 Configuration Management  In DOC it is possible to

simulate different

scenarios for the electrical installation defining the open/closed position for the switching and

protecting devices  The calculation are

performed in the worst condition

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(144)

 Devices Selection

 The calculation leads to an automatic proposal for all the devices drawn in the scheme

 When more than one product is technically suitable, DOC proposes the basic one

 It is possible to change the solution proposed by DOC and to lock the user choice thanks to the padlocks present in all the selection windows

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(145)

 DOC gives the possibility to perform the temperature rise-assessment according to IEC 60890 in a early stage of the installation design

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(146)

Features - Curves

With DOC it is possible to manage

 Time-current diagrams for the devices present in the scheme  Set the thermomagnetic and electronic trip units

 Realize discrimination studies involving MV and LV devices  Verify the cable protection

1E-2kA 0.1kA 1kA 10kA 100kA

1E-2s 0.1s 1s 10s 100s 1E3s 1E4s Time-Current curve LLL -QF2, HD4/UniMix-R 24.06.12 P230, REF542Plus/DK -TM1

-QF5, E4S 4000 PR121-LI 4000A

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(147)

Features – Switchboard configuration

 With DOC it is now possible to configure switchboard:

 By using a Wizar configuration: three steps guide procedure to create a switchboard.

 By using a toolbar on the left side of working area:  Insert and move column, Kit and device

 Tracking busbar system and temperature rise assessment

 Layer management (door, panel and plate layer, show hide busbars)

 Modify switchboard dimension

(148)

Features - Project documentation

 Different reports sections allows the creation of a unique file documenting the project

 The report sections can be added/removed according to the needs

 Calculation hypothesis

 Short circuit calculations

 Cable Protections

 MV / LV devices list and settings  Export in MS Excel is available

 The report language can be different from the current language

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(149)

Support Tools

DOC

(150)

ABB Software Desktop

ABB Software Desktop (ASD)

 ASD is automatically installed with the first installed software

 ASD functionalities:

Allows to run the software

Manage the language

Registration

Software upgrade

Contact Software Support

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(151)

© ABB Group

September 24, 2013 | Slide 152

ABB Software Desktop

Registration

 Visit www.bol.it.abb.com

 Click on Profile Management

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

Starting on a New Project

(152)

© ABB Group

September 24, 2013 | Slide 153

ABB Software Desktop

Registration

 Click on New User

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

Starting on a New Project

(153)

© ABB Group

September 24, 2013 | Slide 154

ABB Software Desktop

Registration

 Click on Subscribe

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

Starting on a New Project

(154)

ABB Software Desktop

Registration

 After registering via internet , you will receive immediately an e-mail with ID and PSW to access the Upgrade

Service

 Use them to check for

available Upgrades before starting using the Software

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

(155)

Upgrade DOC via internet

ABB Software Desktop

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance How to obtain the software

 Use The Automatic Upgrade Service allows you to

maintain the software aligned to the latest

improvements delivered from ABB SACE them to check for available

Upgrades before starting using the Software

(156)

Assistance

 How to contact us – Software support

Ask the ABB SACE Software Assistance for any question you may have regarding the software tools

 Email  [email protected]  Call Center  +39 035 395 570  On line  http://www.bol.it.abb.com Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance

How to obtain the software

(157)

How to obtain the software

 Refer to the ABB Local Sales Organization for a free copy of the software

Introduction

Aim of the application Target users Product managed How it works Features Support Tools ASD Assistance

How to obtain the software

(158)

References

Related documents