Telecom m unications Infrastructure

Standard for Data Centers

802.3 Tutorial

Prepared by: Jonathan Jew - J&M Consultants and

Prepared by: Jonathan Jew - J&M Consultants and

Chris DiMinico - MC Communications - Co-chairs TR42.1.1

(2)

TR42: Data Center Standard

PN-3-0092 PN-3-0092

Telecommunications Infrastructure Standard Telecommunications Infrastructure Standard

for Data Centers for Data Centers

Draft 2.0 Draft 2.0 July 9, 2003 July 9, 2003

(3)

Customer Premise Internet Data Center Local Loop -service provided Service provider - Distribution Node -Central Office Service Provider Backbone •Customer lease Customer Premise Internet Data Center DATA/Voice Infrastructure Local Loop -service provided Home SOHO Home SOHO

Telecommunication Infrastructure

Service provider - Distribution Node -Central Office Enterprise Enterprise • Data Center

• EFM- Access Networks

(4)
(5)
(6)

n Network infrastructure required to drive web hosted Internet applications.

(7)

Service Provider Distribution Node- Central Office

(8)

Switch File Servers Firewall WAN Router Internet Web Servers Email Servers Application Servers Backbone Switch / Router 1 Gb/s 10 Gb/s 100 Mb/s 10 Mb/s 1 Gb/s DWDM Infrastructure Remote Enterprise 10 Gb/s -Internet Data Center -Computer Room 1 Gb/s Equipment Room 10 Gb/s 10 Gb/s SAN 10 Gb/s LAN WAN

(9)

Cable Element Customer Premises ISO/IEC 11801-TIA

Data Center Central Office

Equipment Room

Horizontal Cabling

≤≤100 meters ≤≤100 meters ≤≤100 meters NA

Equipment-to-Equipment

≤≤100 meters ≤≤100 meters 30 meter

Cabling Topologies and Distances

(10)

Who is Developing the Standard

n

n The standard is being developed by the TIA/TR42The standard is being developed by the TIA/TR42

Engineering Committee - subcommittee-TR-42.1.1 Engineering Committee - subcommittee-TR-42.1.1

Network Distribution Nodes - Project No. 3-0092 Network Distribution Nodes - Project No. 3-0092

n

n Participants include:Participants include: u

u Architecture & Engineering FirmsArchitecture & Engineering Firms

u

u ConsultantsConsultants

u

u End UsersEnd Users

u

u ManufacturersManufacturers

n

n The standard will become TIA-942The standard will become TIA-942

n

(11)

Status of the Standard

n

n 22ndnd draft released for industry ballot July 2003. draft released for industry ballot July 2003.

n

n Draft posted to IEEE Draft posted to IEEE websitewebsite

n

n Ballot comments to be resolved October 2003.Ballot comments to be resolved October 2003.

n

n Liaison with other standards organizations (IEEE,Liaison with other standards organizations (IEEE,

CENELEC, BICSI, ISO,ASHRE) CENELEC, BICSI, ISO,ASHRE)

n

n Liaison with data center industry organizationsLiaison with data center industry organizations

(7X24 Exchange,Uptime Institute) (7X24 Exchange,Uptime Institute)

n

n Liaison with network and computer equipmentLiaison with network and computer equipment

manufacturers manufacturers

n

(12)

Purpose of the Standard

n

n

Enabling planning for data centers to occur

Enabling planning for data centers to occur

earlier in the building development process

earlier in the building development process

(architectural, facilities, and IT).

(architectural, facilities, and IT).

n

n

Fill a void by providing standards for

Fill a void by providing standards for

planning of data centers, computer rooms,

planning of data centers, computer rooms,

server rooms, and similar spaces.

server rooms, and similar spaces.

n

n

The standard encompasses much more than

The standard encompasses much more than

just telecommunications infrastructure.

just telecommunications infrastructure.

n

n

Close to half of the technical content deals

Close to half of the technical content deals

with facility specifications.

(13)

Purpose of the standard

n

n Specifications for data center telecommunicationsSpecifications for data center telecommunications

cabling, pathways and spaces cabling, pathways and spaces

n

n Recommendations on media and distance andRecommendations on media and distance and

restrictions for data center applications over restrictions for data center applications over

structured cabling system (TIA 232, TIA 561, T1, structured cabling system (TIA 232, TIA 561, T1,

E1, T3, E3, 1 & 10 Gigabit Ethernet, Fibre E1, T3, E3, 1 & 10 Gigabit Ethernet, Fibre

Channel) Channel)

n

n Establish a standard for data center tiers to replaceEstablish a standard for data center tiers to replace

several proprietary standards. The TIA data center several proprietary standards. The TIA data center

tier standard is: tier standard is:

• A tool to evaluate existing data centersA tool to evaluate existing data centers

(14)

TR42.1 Study Group: Telecommunications Cabling

TR42.1 Study Group: Telecommunications Cabling

Infrastructure for Network Distribution Nodes

Infrastructure for Network Distribution Nodes

Scope:

Scope:

Develop cabling topology, recognized mediaDevelop cabling topology, recognized media types, cabling requirements, and requirements for types, cabling requirements, and requirements for

pathways & spaces for

pathways & spaces for data centersdata centers

n

n Cabling DesignCabling Design

n

n Network DesignNetwork Design

n

n Facility DesignFacility Design

n

(15)

Cabling Design:

Cabling Design:

n

n Copper and fiber cabling performance Copper and fiber cabling performance

n

n Connectors, cables, distribution hardware Connectors, cables, distribution hardware

n

n Cabling distances Cabling distances

n

n Space management Space management

Facility Design:

Facility Design:

n

nData center sizingData center sizing

n

nPower distribution methodologiesPower distribution methodologies

n

nPathways and spacesPathways and spaces

n

nHVAC, security, operations, and administration.HVAC, security, operations, and administration.

n

nFlexibility, scalability, reliability and space managementFlexibility, scalability, reliability and space management

Design Elements:

(16)

Network Design: Network Design:

n

nSupport legacy systemsSupport legacy systems

n

nEnable rapid deployment of new technologies such Enable rapid deployment of new technologies such

as the emerging 10 Gb/s applications.

as the emerging 10 Gb/s applications.

Design Elements:

(17)

Normative:

Normative:

n

nClause 5.Clause 5. cabling spaces - definitions cabling spaces - definitions

n

nClause 6.Clause 6. Data center cabling Data center cabling

–definitionsdefinitions

–topology topology

–recognized mediarecognized media

–redundancyredundancy

n

nClause 7.Clause 7. Data Center Cabling Pathways Data Center Cabling Pathways

Overview of key elements - Normative

(18)

Informative:

Informative:

n

nClause 8:Clause 8: Redundancy Redundancy

n

nAnnex:Annex:

–application distancesapplication distances

–administrationadministration

–carrier informationcarrier information

–site selectionsite selection

–infrastructure tieringinfrastructure tiering

–design examplesdesign examples

Overview of key elements - Informative

(19)

Cabling elements Cabling elements n nCross-connectCross-connect n nInterconnectInterconnect Distribution Areas Distribution Areas n

nMain Distribution Area -MDAMain Distribution Area -MDA

n

nHorizontal Distribution Area -HDAHorizontal Distribution Area -HDA

n

nZone Distribution Area - ZDAZone Distribution Area - ZDA

n

nEquipment Distribution Area -EDAEquipment Distribution Area -EDA

n

nEntrance RoomEntrance Room

Distribution Areas - Spaces for cabling elements

(20)

Purpose of the standard

n

n Define a standard telecommunicationsDefine a standard telecommunications

infrastructure for data centers infrastructure for data centers

n

n Structured cabling system for data centers usingStructured cabling system for data centers using

standardized architecture and media standardized architecture and media

n

n Accommodates a wide range of applicationsAccommodates a wide range of applications

(LAN, WAN, SAN, channels, consoles) (LAN, WAN, SAN, channels, consoles)

n

n Accommodates current and known futureAccommodates current and known future

protocols (10 Gigabit Ethernet) protocols (10 Gigabit Ethernet)

n

n Replaces unstructured point-to-point cabling thatReplaces unstructured point-to-point cabling that

uses different cabling for different applications uses different cabling for different applications

(21)

Relationship of Spaces

BUILDING SITE DATA CENTER DATA CENTER ELECTRICAL & MECHANICAL ROOMS SUPPORT STAFF OFFICES OPERATIONS CENTER STORAGE ROOMS & LOADING DOCKS

BUILDING SHELL GENERAL OFFICE SPACE OFFICE BUILDING SUPPORT SPACE ENTRANCE ROOM(S)

TELECOM ROOMS & EQUIPMENT ROOMS

for spaces outside data center

COMPUTER ROOM

TELECOM ROOM(S) for data center support spaces

(22)

Data Center Telecommunications Spaces

Entrance Room

(Carrier Equip & Demarcation)

Carriers

Horiz Dist Area

(LAN/SAN/KVM Switches )

Equip Dist Area

(Rack/Cabinet)

Computer Room

Horiz Dist Area

(LAN/SAN/KVM Switches )

Zone Dist Area Offices,

Operations Center, Support Rooms

Telecom Room

(Office & Operations Center LAN switches)

Optional Backbone Cabling Main Dist Area

(Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes)

Horiz Dist Area

(LAN/SAN/KVM Switches )

Equip Dist Area

(Rack/Cabinet)

Equip Dist Area

(Rack/Cabinet)

(23)

TIA-942 Spaces

n

n

Entrance Room (ER) - location of interface

Entrance Room (ER) - location of interface

with campus and carrier entrance facilities

with campus and carrier entrance facilities

n

n

Main Distribution Area (MDA) – location

Main Distribution Area (MDA) – location

of main cross-connect (MC)

of main cross-connect (MC)

n

n

Horizontal Distribution Area (HDA) –

Horizontal Distribution Area (HDA) –

location of horizontal cross-connect (HC)

location of horizontal cross-connect (HC)

n

n

Zone Distribution Area (ZDA) – location of

Zone Distribution Area (ZDA) – location of

zone outlet (ZO) or consolidation point (CP)

zone outlet (ZO) or consolidation point (CP)

n

n

Equipment Distribution Area (EDA) –

Equipment Distribution Area (EDA) –

location of equipment cabinets and racks

(24)

Entrance Room

(Carrier Equip & Demarcation)

Carriers

Horiz Dist Area

(LAN/SAN/KVM Switches )

Equip Dist Area

(Rack/Cabinet)

Computer Room

Horiz Dist Area

(LAN/SAN/KVM Switches )

Zone Dist Area Offices,

Operations Center, Support Rooms

Telecom Room

(Office & Operations Center LAN switches)

Main Dist Area

(Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes)

Horiz Dist Area

(LAN/SAN/KVM Switches )

Equip Dist Area

(Rack/Cabinet)

Equip Dist Area

(Rack/Cabinet)

Carriers

Backbone cabling

Horizontal cabling Horizontal cabling Horizontal cabling

Horizontal cabling

Backbone cabling Backbone

cabling Horizontal cabling

(25)

Distributed Topology with Multiple ERs

Primary Entrance

Room

(Carrier Equip & Demarcation)

Carriers

Horiz Dist Area

(LAN/SAN/KVM Switches )

Equip Dist Area

(Rack/Cabinet)

Computer Room

Horiz Dist Area

(LAN/SAN/KVM Switches )

Horiz Dist Area

(LAN/SAN/KVM Switches )

Carriers Carriers

Zone Dist Area Offices,

Operations Center, Support Rooms

Telecom Room

(Office & Operations Center LAN switches)

Carriers

Secondary Entrance Room

(Carrier Equip & Demarcation)

Main Dist Area

(Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes)

Horiz Dist Area

(LAN/SAN/KVM Switches )

Equip Dist Area

(Rack/Cabinet)

Equip Dist Area

(Rack/Cabinet)

Equip Dist Area

(Rack/Cabinet) Backbo ne cab ling Bac kbon e ca blin g B ac kb o ne ca b lin g B ackb one ca bling Bac kbon e cabl ing B a c k b o n e c a b li n g Backbone cabling Backbone cabling B a c k b o n e c a b lin g Horizontal cabling Horizontal cabling Horizontal cabling Horizontal cabling Horizontal cabling Horizontal cabling

(26)

Backbone Topology

n

n Includes cabling from MDA to ER, HDA, TRIncludes cabling from MDA to ER, HDA, TR

n

n Optional cabling between HDAs allowedOptional cabling between HDAs allowed

n

n Maximum backbone cable lengths based onMaximum backbone cable lengths based on

applications distances applications distances

n

n Centralized optical fiber cabling supported withCentralized optical fiber cabling supported with

interconnect, splice, or pull-through at the HDA interconnect, splice, or pull-through at the HDA

n

n Star topology with no intermediate cross-connectsStar topology with no intermediate cross-connects

n

n Various topologies permit redundancy andVarious topologies permit redundancy and

flexibility to support various data center sizes flexibility to support various data center sizes

(27)

Horizontal Topology

n

n

Defined as cabling from horizontal cross-

Defined as cabling from horizontal

cross-connect (HC) to the equipment distribution

connect (HC) to the equipment distribution

area (EDA)

area (EDA)

n

n

Star topology with termination on HC in

Star topology with termination on HC in

HDA or MDA

HDA or MDA

n

(28)

Horizontal and Backbone Cabling

n

n

Recognized Cables:

Recognized Cables:

F a) 100-ohm twisted-pair cable

(ANSI/TIA/EIA-568-B.2), category 6 recommended (ANSI/TIA/EIA-568-B.2-1)

F b) multimode optical fiber cable, 50/125 micron

(ANSI/TIA/EIA-568-B.3) and 62.5/125 micron or 50/125 micron (ANSI/TIA/EIA-568-B.3)

F c) singlemode optical fiber cable

(ANSI/TIA/EIA-568-B.3)

F d) 75-ohm (734 and 735 type) coaxial cable

(29)

Carrier Circuit Lengths in Data Centers

Maximum cable lengths for common circuits: Maximum cable lengths for common circuits:

n

n E-1’E-1’s over 24 AWG Cat 5/5e/6 UTP:s over 24 AWG Cat 5/5e/6 UTP:

532 ft (152 m) -

532 ft (152 m) - 16.4 ft (5 m) per patch panel 16.4 ft (5 m) per patch panel

n

n T-1’T-1’s over 24 AWG Cat 5/5e/6 UTP:s over 24 AWG Cat 5/5e/6 UTP:

731 ft (223 m) - 16.4 ft (5 m) per patch panel

731 ft (223 m) - 16.4 ft (5 m) per patch panel

n

n E-3’s over 734 coax:E-3’s over 734 coax:

618 ft (188m) – 19.8 ft (6 m) per patch panel

618 ft (188m) – 19.8 ft (6 m) per patch panel

n

n T-3’s over 734 coax:T-3’s over 734 coax:

513 ft (156m) – 15.4 ft (4.7 m) per patch panel

513 ft (156m) – 15.4 ft (4.7 m) per patch panel

Distances are from carrier demarcation point to Distances are from carrier demarcation point to end equipment and assume no customer DSX. end equipment and assume no customer DSX.

(30)

Carrier Circuit Lengths in Data Centers

n

n Common data center configurations include 6Common data center configurations include 6

patch panels: 1 in ER, 2 in MDA, 2 in HDA, and 1 patch panels: 1 in ER, 2 in MDA, 2 in HDA, and 1

in the EDA in the EDA

n

n Cat 3 instead of Cat 5 reduces circuit lengths forCat 3 instead of Cat 5 reduces circuit lengths for

T-1s and E-1s significantly T-1s and E-1s significantly

n

n 735 coax (mini-coax) reduces circuit lengths for735 coax (mini-coax) reduces circuit lengths for

T-3s, E-1s, and E-3s significantly T-3s, E-1s, and E-3s significantly

n

n Circuit length restrictions may :Circuit length restrictions may : u

u require additional ERs,require additional ERs,

u

u limit location of telecom equipment,limit location of telecom equipment,

u

(31)

Computer Room Requirements

n

n Similar to Equipment Room reqts from TIA-569Similar to Equipment Room reqts from TIA-569

n

n Min clear height of 2.6m/8.5 ftMin clear height of 2.6m/8.5 ft

n

n Min door size 1m/3ft wide 2.13/7ft highMin door size 1m/3ft wide 2.13/7ft high

n

n Min dist floor loading 7.2 kPA/150lbf/ftMin dist floor loading 7.2 kPA/150lbf/ft22,,

recommended min 12 kPA/250 lbf/ft recommended min 12 kPA/250 lbf/ft22

n

n Dedicated HVAC system preferredDedicated HVAC system preferred

n

n 2020ooC to C 2525ooCC

n 40% to 55% relative humidity (reduces ESD) n Signal reference grid –equipotential ground

reference and reduces stray high frequency signals

(32)

Entrance Room

n

n

Demarcation to carriers

Demarcation to carriers

n

n

Telecom Entrance & Campus Conduits

Telecom Entrance & Campus Conduits

n

n

Carrier Racks

Carrier Racks

u

u Coordinate power and space requirements withCoordinate power and space requirements with

each carrier each carrier

u

u Provide either AC or DC power to carriers.Provide either AC or DC power to carriers.

u

u If ER only has AC power, carriers install DCIf ER only has AC power, carriers install DC

power from rectifiers to their racks & cabinets power from rectifiers to their racks & cabinets

n

n

Plywood for protectors

Plywood for protectors

u

u Not required if no copper entrance cables or ifNot required if no copper entrance cables or if

carrier will install protectors on frames or racks carrier will install protectors on frames or racks

(33)

Entrance Room

n

n

ER may be inside data center but, location

ER may be inside data center but, location

outside data center provides best security

outside data center provides best security

n

n

ER may be consolidated with MDA

ER may be consolidated with MDA

n

n

ER requires the same redundancy for power

ER requires the same redundancy for power

and cooling as the computer room space

and cooling as the computer room space

n

n

Locate ER to avoid exceeding maximum

Locate ER to avoid exceeding maximum

cable lengths for circuits

cable lengths for circuits

n

n

Cabling distances for carrier circuits may

Cabling distances for carrier circuits may

dictate multiple ERs in large data centers

(34)

Main Distribution Area

n

n

Location of Main Cross-Connect (MC), the

Location of Main Cross-Connect (MC), the

central point of distribution for data center

central point of distribution for data center

structured cabling system

structured cabling system

n

n

Centrally located to avoid exceeding

Centrally located to avoid exceeding

maximum distance restrictions (typically for

maximum distance restrictions (typically for

E-1s, E-3s, T-1s and T-3s)

E-1s, E-3s, T-1s and T-3s)

n

n

Install separate racks for Fiber, UTP, and

Install separate racks for Fiber, UTP, and

coaxial cable distribution

(35)

Main Distribution Area

n

n Data center size may dictate use of Cat 5e or 6Data center size may dictate use of Cat 5e or 6

UTP for Fractional T-1, E-1, T-1, ISDN PRI UTP for Fractional T-1, E-1, T-1, ISDN PRI

n

n Copper-pair cabling for LAN backbone cabling (inCopper-pair cabling for LAN backbone cabling (in

smaller data centers) and out-of-band management smaller data centers) and out-of-band management

using Cat 5e or 6 UTP using Cat 5e or 6 UTP

n

n AT&T 734-type 75 ohm coaxial cable for E-1,AT&T 734-type 75 ohm coaxial cable for E-1,

E-3, T-3 cabling (two coax per circuit) E-3, T-3 cabling (two coax per circuit)

n

n Multimode and Single-mode fiber cabling for OC-Multimode and Single-mode fiber cabling for

OC-3, OC-12, OC-48, MAN, LAN & SAN backbone. 3, OC-12, OC-48, MAN, LAN & SAN backbone.

(36)

Horizontal Distribution Area

n

n

Location of Horizontal Cross-Connect

Location of Horizontal Cross-Connect

(HC), the distribution point for cabling to

(HC), the distribution point for cabling to

equipment distribution area

equipment distribution area

n

n

Distribution LAN, SAN, KVM switches

Distribution LAN, SAN, KVM switches

and console servers located in HDA

and console servers located in HDA

n

n

MDA may also include an HC for nearby

MDA may also include an HC for nearby

equipment distribution area

equipment distribution area

n

n

Number of HDAs depends on the density of

Number of HDAs depends on the density of

cabling and the size of the data center

(37)

Horizontal Distribution Area

n

n The capacity of the cable tray system and the sizeThe capacity of the cable tray system and the size

of the cross-connect creates practical limits on the of the cross-connect creates practical limits on the

size of the HC size of the HC

n

n Guideline is maximum of 2,000 4-pair UTP orGuideline is maximum of 2,000 4-pair UTP or

coax cable terminations per HDA coax cable terminations per HDA

n

n Arrange patch bays to minimize patch cableArrange patch bays to minimize patch cable

lengths and to simplify cable management lengths and to simplify cable management

u

u Separate racks for fiber, UTP, and coaxSeparate racks for fiber, UTP, and coax

u

u Locate switches and patch panels to minimizeLocate switches and patch panels to minimize

patch cord lengths patch cord lengths

(38)

Zone Distribution Area

n

n Rack, cabinet, or under floor enclosure that housesRack, cabinet, or under floor enclosure that houses

a zone outlet (ZO) or consolidation point (CP) a zone outlet (ZO) or consolidation point (CP)

n

n ZO - structured cabling termination for floor-ZO - structured cabling termination for

floor-standing equipment that cannot accept patch standing equipment that cannot accept patch

panels (e.g. mainframes and large servers). panels (e.g. mainframes and large servers).

n

n CP - intermediate termination point (e.g. cablingCP - intermediate termination point (e.g. cabling

to areas where floor plan is uncertain or dynamic) to areas where floor plan is uncertain or dynamic)

n

n No cross-connects within the ZDANo cross-connects within the ZDA

n

n No active equipment shall be located in the ZDANo active equipment shall be located in the ZDA

n

n Maximum of 144 connections in a ZDAMaximum of 144 connections in a ZDA

n

n Maximum of one ZDA within a horizontal cableMaximum of one ZDA within a horizontal cable

run run

(39)

Equipment Racks & Cabinets

n

n Cabinets and racks should be arranged in anCabinets and racks should be arranged in an

alternating pattern (with fronts of rows of alternating pattern (with fronts of rows of

cabinets/racks facing each other) to create hot and cabinets/racks facing each other) to create hot and

cold aisles cold aisles

n

n Cold aisles are front of racks/cabinets – if there isCold aisles are front of racks/cabinets – if there is

a raised floor, PDU cables are run here on the slab. a raised floor, PDU cables are run here on the slab.

n

n Hot aisles are rear of racks/cabinets – cable traysHot aisles are rear of racks/cabinets – cable trays

for telecom cabling are typically placed here. for telecom cabling are typically placed here.

n

(40)

CABINETS CABINETS CABINETS

HOT AND COLD EQUIPMENT AISLES

PREFORATED TILES PREFORATED TILES TELECOM CABLE TRAYS TELECOM CABLE TRAYS FRONT

POWER CABLES POWER CABLES

FRONT FRONT

(41)

Equipment Racks & Cabinets

n

n Equipment is mounted in racks & cabinets fromEquipment is mounted in racks & cabinets from

the front – provide adequate clearance for the front – provide adequate clearance for

installation of equipment (minimum of 3 feet, 4 installation of equipment (minimum of 3 feet, 4

feet is recommended). feet is recommended).

n

n Cabinets should be aligned with one edge alongCabinets should be aligned with one edge along

the edge of the floor tile. the edge of the floor tile.

n

n Arrange cabinets and racks on raised floor toArrange cabinets and racks on raised floor to

permit tiles along the front and rear of the cabinets permit tiles along the front and rear of the cabinets

to be lifted to be lifted

n

n Floor tile cuts should be no larger than necessaryFloor tile cuts should be no larger than necessary

to minimize air pressure loss. to minimize air pressure loss.

(42)

Equipment Cabinets

n Front rails of cabinets

must be recessed to

provide adequate room for patch cables and wire

managers

n Adequate space for cable

management

n Arrange switches and

patch panels to minimize patching between cabinets & racks

n Perforated tiles at front of

cabinets

n One edge of cabinets

(43)

Raised Floor

n

n

More flexible cooling with raised floor than

More flexible cooling with raised floor than

ducted air

ducted air

n

n

Most stand-alone computer systems are

Most stand-alone computer systems are

designed for cabling from below

designed for cabling from below

n

n

Coordinate under floor cabling with

Coordinate under floor cabling with

mechanical & electrical engineers

mechanical & electrical engineers

n

n

Recommend wire basket cable trays in hot

Recommend wire basket cable trays in hot

aisles for telecom cabling

(44)

Example of Wire Basket Cable Trays

For Cabling Under Raised Floor

24" On Center

RAISED FLOOR TILE

SUPPORT STRUT 36" 24" 4" 9" FIBER 5" SUPPORT STRUT 18" COPPER CABLING 4" 13.5" DIVIDER FIBER 5" 18" COPPER CABLING 12" 1.375" 1" 1" Open Area

(45)

Under Floor Space

Example

n

n Color-coded PDUColor-coded PDU

cables in hot aisles cables in hot aisles

each cabinet fed from each cabinet fed from

2 PDUs 2 PDUs

n

n Locking electricalLocking electrical

receptacles NEMA receptacles NEMA

L5-20R L5-20R

n

n Signal Reference GridSignal Reference Grid

(SRG) using bare (SRG) using bare copper conductor copper conductor

n

n Each cabinet bondedEach cabinet bonded

to SRG to SRG

(46)

Overhead Cable Trays

n

n Less expensive than raised floor systemsLess expensive than raised floor systems

n

n Cable trays can be attached to the top of racks andCable trays can be attached to the top of racks and

cabinets (if they are uniform in height) cabinets (if they are uniform in height)

n

n Cable trays suspended from the ceiling providesCable trays suspended from the ceiling provides

more flexibility for supporting cabinets/racks of more flexibility for supporting cabinets/racks of

various heights and for adding and removing various heights and for adding and removing

cabinets/racks. cabinets/racks.

n

n Cable trays can be installed with several layersCable trays can be installed with several layers

n

n Coordinate location with lighting, ducts, overheadCoordinate location with lighting, ducts, overhead

conduits, overhead power distribution conduits, overhead power distribution

(47)

Overhead Cable Tray Example

3 Layer cable tray system: 3 Layer cable tray system:

n

n Bottom layer – copperBottom layer – copper

n

n Middle layer – fiberMiddle layer – fiber

n

n Top layer – powerTop layer – power

n

n Signal Reference Grid inSignal Reference Grid in

brackets attached to brackets attached to lower layer of trays lower layer of trays

n

n Fiber patch cables mayFiber patch cables may

be in fiber duct attached be in fiber duct attached

to threaded rods to threaded rods

(48)

Infrastructure Administration

n

n

Informative annex with TIA-606-A

Informative annex with TIA-606-A

standards compliant labeling scheme for all

standards compliant labeling scheme for all

components.

components.

n

n

Labeling scheme extended for use in data

Labeling scheme extended for use in data

centers

centers

n

n

Cabinets and racks labeled by location

Cabinets and racks labeled by location

using tile grid or row/position identifiers

using tile grid or row/position identifiers

n

n

All cabinets, racks, patch panels, cables,

All cabinets, racks, patch panels, cables,

and patch cords should be labeled

(49)

Facilities Specifications & Tiers

n

n Informative annex with general architectural,Informative annex with general architectural,

structural, electrical, mechanical, and structural, electrical, mechanical, and

telecommunications recommendations telecommunications recommendations

requirements requirements

n

n Annex includes detailed architectural, security,Annex includes detailed architectural, security,

electrical, mechanical, and telecommunications electrical, mechanical, and telecommunications

recommendations for each Tier recommendations for each Tier

n

n Recommended specifications by tier are a uniformRecommended specifications by tier are a uniform

way to rate aspects of a data center design and are way to rate aspects of a data center design and are

a starting point for initiating design requirements a starting point for initiating design requirements

with qualified architects and engineers with qualified architects and engineers

(50)

Redundant Topologies

Primary Entrance Room (Tier 1 and higher)

Horiz Dist Area

Equip Dist Area Computer

Room

Horiz Dist Area Zone Dist Area

Offices, Operations Center, Support Rooms Telecom Room Optional Cabling

Main Dist Area (Tier 1 and higher)

Horiz Dist Area

Equip Dist Area Equip Dist Area Secondary Entrance Room (Tier 3 and higher)

Secondary Dist Area (Optional for Tier 4)

Carriers

Primary Customer Maintenance Hole (Tier 1 and higher)

Secondary Customer Maintenance Hole (Tier 2 and higher)

Tier 1 Tier 3 Tier 1 Tier 4 Tier 3 Tier 2 Tier 4 Tier 3 Tier 4

Carriers Carriers Carriers

Data Center

(51)

Conclusion

§

§

TIA-942 is the first standard that specificallyTIA-942 is the first standard that specifically addresses data center infrastructure.

addresses data center infrastructure.

§

§

Primarily a telecom infrastructure standard, butPrimarily a telecom infrastructure standard, but about half of the content deals with facility

about half of the content deals with facility requirements.

requirements.

§

§

Provides a flexible and manageable structuredProvides a flexible and manageable structured cabling system using standard media.

cabling system using standard media.

§

§

Builds on existing standards, where applicableBuilds on existing standards, where applicable

§

§

Guidelines on a wide range of subjects useful toGuidelines on a wide range of subjects useful to someone designing or managing a data center. someone designing or managing a data center.

§

§

An official tiering standard for determining theAn official tiering standard for determining the quality of a center

quality of a center. . A way to objectively compareA way to objectively compare

one center with another. one center with another.

References

Related documents

l8nuoonjn

Pharmaceutical reverse distributors are only subject to this proposed rule for the accumulation of potentially creditable hazardous waste pharmaceuticals and evaluated

Currently, slightly fewer than two thirds of PhDs are employed in university or academic positions three years after obtaining their doctorates, while only one quarter are employed

There is a fabulous resource that is called 'Ready to Progress', which focusses on the most important aspects of maths, which will be taught in depth to ensure children can move to

On-Premises Computing Storage Servers Networking O/S Middleware Virtualization Data Applications Runtime Infrastructure (as a Service) Storage Servers Networking O/S

Optical Networking in Data Centers Servers Optical Switch ( ~ 1000 ports) Border Router Racktop Switches Controller • Fast (< 10 ns) • Low crosstalk • Low power 10 – 100

Two-Port 10 Gb/s Opt iSCSI Module iSCSI module with two 10 Gb/s Ethernet ports and choice of SFP+ optical connection or active Twinax copper connection to Ethernet switch; includes

dence was presented in the rulemaking record that misfueling with an unap- proved fuel is common, especially where the approved fuel is more expensive than the unapproved fuel.