• No results found

Functional Testing of G60-A Test Results Engro

N/A
N/A
Protected

Academic year: 2021

Share "Functional Testing of G60-A Test Results Engro"

Copied!
14
0
0

Loading.... (view fulltext now)

Full text

(1)

Customer

Customer Engro Engro PowergenPowergen Relay

Relay Type Type Numerical Numerical Generator Generator Management Management RelayRelay Panel

Panel Identification Identification Generator Generator Protection Protection Panel Panel GPPGPP Relay

Relay Identification Identification Generator Generator ProtectionProtection Relay

Relay Make Make GENERAL GENERAL ELECTRICELECTRIC

Model G60-G01-HCH-F8F-H67-M8F-P6D-U6D-W6C

Model G60-G01-HCH-F8F-H67-M8F-P6D-U6D-W6C

Serial

Serial No. No. AALC07000443AALC07000443 Firmware

Firmware Revision Revision 5.45.4 Auxiliary

Auxiliary Voltage Voltage 125V 125V DCDC Test

Test Starting Starting Date Date 16-04-201516-04-2015 Test

Test Set Set Used Used Freja 300Freja 300 Tested By

Tested By Mr.Mubasher Ahmed, Testing/Commissioning Engineer.Mr.Mubasher Ahmed, Testing/Commissioning Engineer.

Contact Number: +92 333 408 30 86 Contact Number: +92 333 408 30 86

Witnessed By

Witnessed By Mr.Ijlal, Engro PowergenMr.Ijlal, Engro Powergen

General Data General Data Generator

Generator Genout Genout Voltage Voltage 11.0 11.0 kVkV Connection

Connection Type Type WYEWYE CT

CT Ratio Ratio Genout Genout Side Side (CT-6) (CT-6) 8000/18000/1 CT

CT Ratio Ratio Neutral Neutral Side Side (CT-1) (CT-1) 8000/18000/1 VT

VT Ratio Ratio (VT-G) (VT-G) 13.8kV/100V13.8kV/100V Aux.

Aux. Neutral Neutral VT(NET) VT(NET) 13.8kV/200V13.8kV/200V

Testing Procedure Testing Procedure

1.

1. Verify that the relay rear Verify that the relay rear connection/wiring is according to referred drawings.connection/wiring is according to referred drawings. 2.

2. Power up relay at its rated voltage mentioned on face plate of relay.Power up relay at its rated voltage mentioned on face plate of relay. 3.

3. Verify that “ In Service” green LED on face plate is lit up.Verify that “ In Service” green LED on face plate is lit up. 4.

4. Verify that different protection units inside Verify that different protection units inside the relay are configured on desiredthe relay are configured on desired settings.

settings. 5.

5. Isolate the relay from field side wiring as per referred drawing.Isolate the relay from field side wiring as per referred drawing. 6.

6. Inject different voltage & current values (according to Inject different voltage & current values (according to relay trip settings) torelay trip settings) to relay and check its functionality and behavior.

relay and check its functionality and behavior. 7.

(2)

1. Measuring / Metering Accuracy Source Phase Involved Ratio Applied Analog Signals (Secondary) Measured Value (Primary) Source 2,Line Side Ia1 8000/1 1.000A 7.994-0kA

Source 2, Line Side Ia2 8000/1 1.00 240A 8.002-119 kA

Source 2, Line Side Ia3 8000/1 1.00 120A 7.994-240kA

Source 1, Neutral Side Ib1 8000/1 1.000A 7.995-0kA

Source 1, Neutral Side Ib2 8000/1 1.00 240A 8.002-119 kA

Source 1, Neutral Side Ib3 8000/1 1.00 120A 7.994-240kA

Main PTs (VTG-P) V1 13.8kV/100V (57.70)100V 13.796-330 kV

Main PTs (VTG-P) V2 13.8kV/100V (57.7240)100V 13.794-90 kV

Main PTs (VTG-P) V3 13.8kV/100V (57.7120)100V 13.808-210 kV

 NET VT 13.8kV/220V 1000 V 6.27-0kV

2. Stator Differential Protection (87G)

Pickup = 0.083 P.U Slope 1 = 10 % Break 1 = 1.00 P.U Break 2 = 3.07 P.U Slope 2 = 60 % 2.1 Pickup Accuracy Sr.

I Applied at Gen out Side( (Amp) I Applied at Neutral Side (Amp)

Status Ia1 Φ Ia2 Φ Ia3 Φ Ib1 Φ Ib2 Φ Ib3 Φ

1 1.00 0 1.00 240 1.00 120 1.00 0 1.00 240 1.00 120 Stable 2 0.90 0 0.90 240 0.90 120 0.810 0 0.810 240 0.810 120 No Pickup 3 0.90 0 0.90 240 0.90 120 0.809 0 0.809 240 0.809 120 Pickup 4 3.50 0 3.50 240 3.50 120 1.41 0 1.41 240 1.41 120 No Pickup 5 3.50 0 3.50 240 3.50 120 1.40 0 1.40 240 1.40 120 Pickup

(3)

2.2 Operating Time Accuracy

Sr. I Applied at Genout Side( (Amp) I Applied at Neutral Side (Amp)

Measured Time (msec)

Status Ia1 Φ Ia2 Φ Ia3 Φ Ib1 Φ Ib2 Φ Ib3 Φ

1 1.00 0 1.00 240 1.00 120 0.00 0 0.00 240 0.00 120 13.00 Trip

3. Negative Phase Sequence (Generator Unbalance Alarm 46A) 3.1 Pickup Accuracy

Inom. = 0.830 P.U.

Stage 2 Pickup = 10.00% Time Delay = 6.0 sec

Sr. Applied Current Gen out Source 2 (Amp) Status

Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 0.050 0.050 0.050 0 120 240 No Pickup

2 0.051 0.051 0.051 0 120 240 Pickup

: Phase T

OC and Stator Diff. Settings should be switched off to test this function. 4. Negative Phase Sequence ( Generator Unbalance Trip 46T)

4.1 Pickup Accuracy

Stage 1 Pickup = 10.00 % Stage 1 K Value = 6.40 Stage 1 min. = 0.250 Sec Stage 1 max. = 640.0 Sec Stage 1 K Reset = 256.0 Sec

Sr. Applied Current Gen Out Source 2 (Amp) Status

Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 0.084 0.084 0.084 0 120 240 No Pickup

(4)

4.2 Operating Time Accuracy

Sr. Applied Current Neutral Source 2 (Amp) Measured Time ( Sec )

Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 1.00 1.00 1.00 0 120 240 4.434

2 1.50 1.50 1.50 0 120 240 1.994

3 2.50 2.50 2.50 0 120 240 0.733

5. Sensitive Directional Power Stage 1(32 N. Stop) 5.1 Pickup Accuracy

Directional Power RCA = 180

Stage 1 SMIN = 0.035 P.U

Stage 1 Delay = 3.0 Sec

Sr. Applied Voltage (Volts) Applied Current Source 2 (Amp) Status V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 57.70 57.70 57.70 0 240 120 0.035 0.035 0.035 180 60 300  No

Pickup

2 57.70 57.70 57.70 0 240 120 0.036 0.036 0.036 180 60 300 Pickup 5.2 Operating Time Accuracy

Sr.

Applied Voltage (Volts) Applied Current Source 2 (Amp) Measured Time (m

Sec) V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 57.70 57.70 57.70 0 240 120 0.2 0.2 0.2 180 60 300 3.074

6. Sensitive Directional Power Stage 2 (32-2) 6.1 Pickup Accuracy

Directional Power RCA = 180

Stage 2 SMIN = -0.007

Stage 2 Delay = 0.50 Sec

Sr. Applied Voltage (Volts) Applied Current Source 2 (Amp) Status V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 57.70 57.70 57.70 0 240 120 0.007 0.007 0.007 180 60 300  No

Pickup

(5)

6.2 Operating Time Accuracy

Sr.

Applied Voltage (Volts) Applied Current Source 2 (Amp) Measured Time (mSec) V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 57.70 57.70 57.70 0 240 120 0.005 0.005 0.005 180 60 300 579

7. Loss of Field Stage 1 (40): 7.1 Pickup Accuracy

Center = 44.14 ohm Radius = 34.76 ohm Time Delay = 1.000 sec Off Set = 9.38 ohm

Sr. Applied Voltage (Volts) Applied Current Sorce 2 (Amp) Z

ohm Pickup V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 20 20 20 0 240 120 0.254 0.254 0.254 90 330 210 78.74  No

2 20 20 20 0 240 120 0.255 0.255 0.255 90 330 210 78.41 Yes

7.2 Operating Time Accuracy

Sr.

Applied Voltage (Volts) Applied Current Sorce 2 (Amp) Measured Time

(sec) V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 20 20 20 0 240 120 0.51 0.51 0.51 90 330 210 1.024

8. Loss of Field Stage 2 (40): 8.1 Pickup Accuracy

Center = 80.98 ohm

Radius = 71.60 ohm

Time Delay = 1.00 sec

Off Set = 9.38

Sr. Applied Voltage (Volts) Applied Current Sorce 2 (Amp) Z

ohm Status V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 20 20 20 0 240 120 0.132 0.132 0.132 90 330 210 151.52  No

Pickup 2 20 20 20 0 240 120 0.133 0.133 0.133 90 330 210 150.38 Yes

(6)

8.2 Operating Time Accuracy (at 36.0 ohm)

Sr. Applied Voltage (Volts) Applied Current Source 2 (Amp) Measured Time (sec) V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 20 20 20 0 240 120 0.17 0.17 0.17 90 330 210 1.034

9. Phase Over Voltage Element (59P1): 9.1 Pickup Accuracy

Pickup = 1.200 P.U. Time Delay = 0.50 Sec

Sr. Applied Voltage (Volts) Status

V1 V2 V3 VΦ1 VΦ2 VΦ3

1 69.18 69.18 69.18 0 240 120 No Pickup

2 69.19 69.19 69.19 0 240 120 Pickup

9.2 Operating Time Accuracy

Sr. Applied Voltage (Volts) Measured Time

(Sec)

V1 V2 V3 VΦ1 VΦ2 VΦ3

1 75.00 75.00 75.00 0 240 120 0.554

10. Under Frequency (81-1U): 10.1 Pickup Accuracy Pickup Level = 49.00 Hz Sr. Voltage Applied (Volts) Applied Frequency (Hz) Status 1 63.50 49.01 No Pickup 2 63.50 49.00 Pickup

(7)

11. Under Frequency (81-2U): 11.1 Pickup Accuracy

Pickup Level = 47.50 Hz Time Delay = 3.00 Sec

Sr. Voltage Applied (Volts) Applied Frequency (Hz) Status 1 63.50 47.50 No Pickup 2 63.50 47.49 Pickup

11.2 Operating Time Accuracy

Sr. Voltage Applied (Volts) Applied Frequency (Hz) Measured Time ( Sec) 1 63.50 47.00 3.10 Sec 12. Over-Frequency (81-1O): 12.1 Pickup Accuracy Pickup Level = 51.00 Hz Sr. Voltage Applied (Volts) Applied Frequency (Hz) Status 1 63.50 50.98 No Pickup 2 63.50 50.99 Pickup 13. Over-Frequency (81-2O): 13.1 Pickup Accuracy Pickup Level = 52.50 Hz

Time Delay = 3.00Sec

Sr. Voltage Applied (Volts) Applied Frequency (Hz) Status 1 63.50 52.49 No Pickup 2 63.50 52.50 Pickup

(8)

13.2 Operating Time Accuracy Sr. Voltage Applied (Volts) Applied Frequency (Hz) Measured Time ( Sec) 1 63.50 53.00 3.10 14. Over-Frequency (81-3O): 14.1 Pickup Accuracy Pickup Level = 52.50 Hz Time Delay = 30.00 Sec Sr. Voltage Applied (Volts) Applied Frequency (Hz) Status 1 63.50 52.49 No Pickup 2 63.50 52.50 Pickup

14.2 Operating Time Accuracy

Sr. Voltage Applied (Volts) Applied Frequency (Hz) Measured Time ( Sec) 1 63.50 53.00 30.10

 Note: Overfrequency Stage 2 & Stage 3 has same pickups

15. Phase Under Voltage (27-U1): 15.1 Pickup Accuracy

Pickup = 0.90 P.U (Phase to Ground)

Curve = Definite Time

Time Delay = 10.00 Sec

Sr. Applied Voltage (Volts) Status

V1 V2 V3 VΦ1 VΦ2 VΦ3

1 51.94 51.94 51.94 0 240 120 No Pickup

(9)

16. Phase Under Voltage (27-U2): 16.1 Pickup Accuracy

Pickup = 0.90 P.U (Phase to Ground)

Curve = Definite Time

Time Delay = 3.00Sec

Sr. Applied Voltage (Volts) Status

V1 V2 V3 VΦ1 VΦ2 VΦ3

1 40.41 40.41 40.41 0 240 120 No Pickup

2 40.40 40.40 40.40 0 240 120 Pickup

16.2 Operating Time Accuracy

Sr. Applied Voltage (Volts) Measured Time

(Sec)

V1 V2 V3 VΦ1 VΦ2 VΦ3

1 30.0 30.0 30.0 0 240 120 3.034

17. Phase Time Over Current with Voltage Restraint (51V) 17.1 Pickup Accuracy

Pickup Level = 0.997 P.U Curve = IEEE Mod Inv TD Multiplier = 2.00

Voltage Restrained = Enabled

Sr. Applied Voltage (Volts) Applied Current Source 2 (Amp) Status V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 57.70 57.70 57.70 0 240 120 0.997 0.997 0.997 0 240 120  No Pickup 2 57.70 57.70 57.70 0 240 120 0.998 0.998 0.998 0 240 120 Pickup 3 0.00 0.00 0.00 0 240 120 0.100 0.100 0.100 0 240 120  No Pickup 4 0.00 0.00 0.00 0 240 120 0.101 0.101 0.101 0 240 120 Pickup

(10)

17.2 Operating Time Accuracy

Sr. Applied Voltage (Volts) Applied Current Source 2 (Amp) Measured Time(Sec) V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 57.70 57.70 57.70 0 240 120 2.00 2.00 2.00 0 240 120 7.574 2 50.00 50.00 50.00 0 240 120 2.00 2.00 2.00 0 240 120 6.334 3 40.00 40.00 40.00 0 240 120 2.00 2.00 2.00 0 240 120 5.044 4 30.00 30.00 30.00 0 240 120 2.00 2.00 2.00 0 240 120 4.004 5 10.00 10.00 10.00 0 240 120 2.00 2.00 2.00 0 240 120 2.294 6 0.00 0.00 0.00 0 240 120 2.00 2.00 2.00 0 240 120 1.915

18. Phase Instantaneous Time Over Current-1 for (50 P) 18.1 Pickup Accuracy

Pickup Level = 3.076 P.U

Time Delay = 0.01Sec

Sr. Applied Current Source 2 (Amp) Status

Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 3.077 3.077 3.077 0 240 120 No Pickup

2 3.078 3.078 3.078 0 240 120 Pickup

18.2 Operating Time Accuracy

Sr. Applied Current Neutral Source 1 (Amp) Measured Time ( Sec )

Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

(11)

19. Phase Instantaneous Time Over Current-1 for (50BF) 19.1 Operating Time Accuracy

Pickup Level = 0.200 P.U

Time Delay = 0.250 Sec (in logic)

Sr. Applied Current Source 2 (Amp) Measured Time

(mSec)

Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 1.39 1.39 1.39 0 240 120 268.9

20. Over Excitation Protection Stage 1(24): 20.1 Pickup Accuracy

Pickup = 1.12 P.U.

Curve = Definite Time

T.D = 5.00

Sr. Applied Voltage (Volts) Applied Freq Status

V1 V2 V3 VΦ1 VΦ2 VΦ3 Hz

1 64.59 64.59 64.59 0 240 120 50 No Pickup

2 64.60 64.60 64.60 0 240 120 50 Pickup

20. Over Excitation Protection Stage 2(24 T): 20.1 Pickup Accuracy

Pickup = 1.15 pu

Curve = Definite Time

T.D = 3.00

Sr. Applied Voltage (Volts) Applied Freq Status

V1 V2 V3 VΦ1 VΦ2 VΦ3 Hz

1. 66.30 66.30 66.30 0 240 120 50 No Pickup 2. 66.32 66.32 66.32 0 240 120 50 Pickup

(12)

20.2 Operating Time Accuracy

Sr. Applied Voltage (Volts) Applied Freq Measured Time ( Sec )

V1 V2 V3 VΦ1 VΦ2 VΦ3 Hz

1. 72.0 72.0 72.0 0 240 120 50 3.114

21. 3rd Harmonic Neutral Under Voltage Protection (27TN) 21.1 Pickup Accuracy

Pickup Level = 0.0087 pu Time Delay = 5.00 sec

Sr. Voltage Applied Neutral Source 1 Aux VT (Volts) Status

1 2.00 No Pickup

2 1.90 Pickup

23. Accidental Energization(AE)

23.1 Pickup Accuracy

AE Armed = UV & OFFLINE Under Voltage = 0.7 PU

Over Current = 0.3 PU

Sr. Applied Voltage (Volts) Applied Current Source 2 (Amp) Status V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 0.00 0.00 0.00 0 240 120 0.301 0.301 0.301 0 240 120  No Pickup 2 0.00 0.00 0.00 0 240 120 0.300 0.300 0.300 0 240 120 Pickup 3 41.50 41.50 41.50 0 240 120 0.301 0.301 0.301 0 240 120 Normal 4 41.60 41.60 41.60 0 240 120 0.300 0.300 0.300 0 240 120 De-latched

(13)

23.2 Operating Time Accuracy

Sr.

Applied Voltage (Volts) Applied Current Source 2 (Amp) Measured Time(msec) V1 V2 V3 VΦ1 VΦ2 VΦ3 Ia1 Ia2 Ia3 IΦ1 IΦ2 IΦ3

1 0.00 0.00 0.00 0 240 120 0.80 0.80 0.80 0 240 120 23.50 hase TOC and Stator Diff.

Settings should

 be switched off to test this function.

24. Ground Time Over Current-1 (51G)

24.1 Pickup Accuracy

Pickup Level = 0.065 P.U Time Delay = 1.00 Sec

Sr. Applied Ground Current (Amp) Status

Ig IΦ1

1 0.066 0 No Pickup

2 0.067 0 Pickup

24.2 Operating Time Accuracy

Sr. Applied Ground Current (Amp) Measured Time

(Sec)

Ig IΦ1

(14)

25. Verification of LED’s

Sr. Configuration Remarks

1 Stator differential Functional

2 Phase TOC Functional

3 Phase IOC Functional

4 Ground TOC Functional

5 Generator Unbalance Functional

6 Phase UV 1 Functional

7 Phase UV 2 Functional

8 Phase OV 1 Functional

9 Volts Per Hz 1 Functional

10 Volts Per Hz 2 Functional

11 Loss of excitation Functional

12 Accidental Energization Functional

13 3rdharmonic under voltage Functional 14 Sensitive directional Power stage 1 Functional 15 Sensitive directional Power stage 2 Functional

Tested By Witnessed By

Mr.Mubasher Ahmed Mr.Ijlal

References

Related documents

The adsorption of anionic - sodium dodecylbenzenesulfonate (NaDBS), cationic – cetyl trimethyl ammonium bromide (CTAB) and nonionic - Triton X-100 (TX-100) surfactants under

Many companies, with the approval of shareholders, retained discretion on salary and salary increases and flexibility on recruitment policies.. It will be interesting to see

The outbreak investigation started on the 21 st January and stopped at the end of February when a large rainfall event forced oyster farmers to move most oysters located in the

The advantages of using p-y analyses are that p-y curves are the p-y curves are capable of representing a wide variety of soil and loading conditions in a realistic manner, p-y

Interestingly, our findings indicated that there are positive attitudes towards physical working conditions in the industry, contradicting the findings made by Walsh and

pink, bell shaped], votive candle stand [black candles, all lit], messy table [stone, mess of papers, books, mortar and pestle, broken jars, dice, two white rabbits in a cage

The web form will triage (by issue type) the routing of a ticket request to the NRAA HIE, NRAA Business Office or QualityNet ESRD Help Desk based on the categories outlined in

fire modeling systems (e.g., NEXUS, FFE-FVS, FARSITE, FlamMap) in relation to the Rothermel (1972, 1991) surface and crown fire rate of spread models and Van Wagner’s