EPBD implementation in Finland
11.10.2012Jarek Kurnitski
• Primary energy kWh/m2 required as energy performance indicator
• Target of nearly zero energy buildings (nZEB):
- By 31 Dec 2020, for all new buildings
- After 31 Dec 2018, for new buildings public authorities occupy and own
• Cost optimal energy performance requirements to be set
2013 (=primary energy leading to minimum life cycle cost)
• Strengthening of energy performance certificates
• Energy performance requirements for major renovations • Requirements for technical systems
• Reference to EN standards to promote the use of standards and
harmonize national codes
• From boiler inspection to heating system inspections • Inspection of air conditioning systems
DIRECTIVE 2010/31/EU www.energy.eu/directives/2010-31-EU.pdf
EPBD recast 2010 is much more demanding
than 2002 directive
Implementation schedule
• The laws and regulations shall be adopted and published in Member States by 9 July 2012 and most of requirements shall apply from 9 January 2013
• Extra time for cost optimal reporting by 21 March 2013 (EC delegated
regulation published 21 March 2012)
• Intermediate targets for improving the energy performance of new
buildings, by 2015, with a view to preparing the implementation of nZEB targets
EPBD implementation situation in 2008
• Situation in the member states after EPBD implementation in June 2008 regarding EP requirements for new buildings and calculation methods
• In the figure, the most developed available calculation method is shown; in many countries simplified methods may be used in parallel or for some building types
Finland Lithuania Austria Czech Latvia Slovenia Denmark Italy Belgium Greece Germany Hungary Netherlands Portugal Poland France Sweden Norway UK Spain Estonia
Monthly simplifiedHourly simulationDynamic
For components Energy frame Primary en. or CO 2 em . EP requirements Calculation methods
Source: Kurnitski J. Contrasting the principles of EP
requirements and calculation methods in EU member states.
REHVA journal, December 2008, 22–28.
(Vapaavuori, Asuntoforum 2008)
Finland 2008: Discussion about primary energy
based energy frame was launched with the target
to implement in the code in 2012
2-kerroksinen kompakti pientalo 145 m2 D5:n ja
energiatodistuksen asetuksen mukaisesti laskettuna
Energiatodistus: virallisesti laskettu ja todellinen
energiatehokkuus
Laskentatapaus U-arvo, ulkoseinät LTO hyötysuhde ET-luku, kWh/br.m2,a ET-luokka -Ostoenergia, kWh/br.m2,a CO2-päästöt, kgCO2/br.m2,aPerustapaus suoralla sähkölämmityksellä 0.24 60 181 C 176 70
Perustapaus maalämpöpumpulla 0.24 60 187 C 106 42
Sähkölämm., parannettu n50, LTO ja U-arvot 0.19 80 146 A 140 56
Maalämpö, parannettu n50, LTO ja U-arvot 0.19 80 153 B 89 36
Nykyinen virallinen energiatehokkuustarkastelu johtaa päästöjen kasvuun kun lämmitystapaa ja primäärienergian
käyttöä ei oteta huomioon
NEW ENERGY PERFORMANCE CERTIFICATE (draft for comments 19.4.2012) WILL FIX THE MISMATCH OF
Development of energy codes in Finland
• 1976-78 codes were highly advanced for that time
• 25 years stagnant period before rapid changes after 2003
• In 2012 systemic change from component based requirements to primary
energy frame – no more restrictions – all solutions in direct competition
• Next changes: expected in one or two steps to nZEB requirements
C3 1976 C3 1978 C3 1985 C3 2003 C3 2007 C3 2010 D3 2012 ?
External wall, W/(m2 K) 0,40 0,29 0,28 0,25 0,24 0,17 0,17
Roof, W/(m2 K) 0,35 0,23 0,22 0,16 0,15 0,09 0,09
Slab on ground, W/(m2 K) 0,40 0,40 0,36 0,25 0,24 0,16 0,16
Window, W/(m2 K) 2,1 2,1 2,1 1,4 1,4 1,0 1,0
Heat loss compensation limit, % 10 20 30 vapaa
Building leakage rate at 50 Pa n50 = 4,0 n50 = 4,0 n50 = 4,0 q50 = 4,0
Heat recovery annual efficiency, % 30 30 45 45
Specific fan power, kW/(m3/s) 2,5 2,5 2,5 2,0
How to compare energy performance requirements?
• Energy performance requirements have been improved in many countries with 2-3 years interval
• EPBD requires the use of primary energy as energy performance indicator,
that is not yet implemented in all countries
- some national energy performance frameworks use still the delivered energy (i.e. energy purchased to building without primary energy factors)
- in some countries heat sources (heat pumps etc.) are not taken into account
- lighting is typically considered, but appliances (plug loads) are not taken into account in all countries
• Quantitative comparison needs recalculation from primary energy to delivered
energy, which can be compared in all countries
• A degree day correction of space heating is needed when comparing countries
Minimum energy performance requirements in some
countries – comparison for detached houses
• The figure shows maximum
allowed delivered energy
without household electricity and lighting (i.e. delivered
energy to heating, hot water and ventilation systems)
• 150 m2 house
• energy use for hot water heating 25 kWh/(m2 a) in all countries
• electricity use of 5 kWh/(m2a) for
fans of ventilation and 3
kWh/(m2a) for circulation pumps
of water based heating assumed
• the rest of space and ventilation heating energy is degree-day corrected (base 17°C) to Copenhagen 0 20 40 60 80 100 120 140
Denmark Norway Sweden Estonia Germany Finland
Max delivered energy, kWh/(m
2a)
Oil or gas boiler Electrical heating
Source: Kurnitski J. Do national energy
performance requirements promote or compromise good indoor climate? Healthy Buildings 2012.
Apartment and office buildings with district heating
0 20 40 60 80 100 120 140 160Denmark Norway Sweden Estonia Germany Finland
Max delivered energy, kWh/(m
2a)
Apartment building Office building
Maximum allowed delivered energy in apartment and office buildings with district heating: • Degree-day corrected to Copenhagen
• Delivered energy includes heating, hot water, ventilation and cooling in apartment buildings, and additionally lighting in office buildings
Cost optimal as a first step towards nZEB
• MS have to provide cost optimal calculations to evaluate the cost optimality of current minimum requirements (Articles 4&5):
- The methodology called “COMMISSION DELEGATED REGULATION (EU) No 244/2012 of 16 January 2012” published supplementing Directive 2010/31/EU
- A comparative methodology framework for calculating cost-optimal levels of minimum energy performance requirements
- Net present value calculation according to EN 15459
- Global cost (=life cycle cost) sums construction cost and discounted energy and maintenance etc. costs for 20-30 years period
- MS have 12 months since publication (21 March 2012 in OJ) to report the cost optimal calculations
- http://eur-lex.europa.eu/LexUriServ/LexUriServ.do?uri=OJ:L:2012:081:0018:0036:EN:PDF
EPBD recast – Nearly zero energy buildings nZEB
• In the directive ‘nearly zero-energy building’ means a building that has a very high energy performance. The nearly zero or very low amount of energy required should be covered to a very significant extent by energy from renewable sources, including energy from renewable sources produced on-site or nearby.
Þ nZEB = very high energy performance + on-site renewables
• Definition of “a very high energy performance“ and “significant extent
of renewables” let for Member States
• Not possible without the utilisation of generated electricity, i.e. feed-in tariffs of net metering needed
Towards nZEB:
• Many countries have prepared long term roadmaps with detailed targets towards nearly zero energy buildings to improve energy performance of new buildings
• Helps industry to
prepare/commit to the targets
• In Finland, the preparation
of the roadmap is one
measure in ERA17 national strategy 100 150 200 2a Estonia
nZEB – on site production needed
Primary energy E is calculated from delivered Edel,i and exported energy Eexp,i
accounted separately for each energy carrier i. Anet is useful floor area. Primary energy
Delivered – exported energy = energy use – on site renewable
(
)
(
)
net i i i i i del i del A f E f E Eå
å
-= exp, exp, , ,Total energy use of the building
Delivered energy
Exported energy
Building site = system boundary of delivered and exported energy
System boundary of building technical systems
Denmark: nZEB performance
requirements
2010 2015 2020 Primary energy Residential buildings 52.5 + 1650/A in kWh/m²a 30 + 1000/A in kWh/m²a20
kWh/m²a Non-residential buildings 71.3 + 1650/A in kWh/m²a 41 + 1000/A in kWh/m²a25
kWh/m²a Primary energy factors Electricity 2.5 2.5 1.8 District heat 1.0 0.8 0.6Estonia: nZEB performance
requirements
2013 Low-energy nZEB Primary energy (9 building types in total) Residential buildings 160 in kWh/m²a 120 in kWh/m²a50
kWh/m²a Office buildings 160 in kWh/m²a 130 in kWh/m²a100
kWh/m²a Primary energy factors Electricity 2.0 District heat 0.9• appliances and lighting in residential also included like in Finland (not in Denmark) • 2013 reqs based on cost optimal calculations (2011) and more strict than in Finland
Finnish nZEB definition – almost available
• Given in new energy performance certificate as class A (not published, draft version 19.4.2012, in residential buildings primary energy E=60 kWh/(m2 a))
Can nZEB buildings be constructed in Finland?
• RakMK D3 2012 system boundary:
TILOJEN ENERGIANTARVE Lämmitys Jäähdytys Ilmanvaihto Käyttövesi Valaistus Kuluttajalaitteet
Ostoenergian (järjestelmien) energiankulutuksen taseraja
lämmitysenergia jäähdytysenergia sähkö polttoaineet uusituvat ja uusiutumattomat TEKNISET JÄRJESTELMÄT Järjestelmähäviöt ja -muunnokset Uusiutuva oma-varaisenergia kaukolämpö kaukojäähdytys sähkö Auringon säteily ikkunoiden läpi
Lämpökuorma ihmisistä
Lämpöhäviöt
NETTOTARPEET
OSTOENERGIA
• New energy code RakMK D3 2012 is one of the most advanced in EU including simulation etc., but exported energy was left out from the system boundary in the last minute, because of ongoing process of preparation of feed-in rules
• To construct nZEB building one needs to assume feeding in to grid (and has to
System boundary in the draft of RakMK D3
16.05.2011 ENERGY NEED Heating Cooling Ventilation DHW Lighting Appliances Heat gains from occupantsSystem boundary of net delivered energy
Net delivered energy
(electricity, district heat, district cooling, fuels)
System boundary of delivered energy
heating energy cooling energy electricity fuels BUILDING TECHNICAL SYSTEMS Energy use and production System losses and conversions electricity cooling energy On site renewable
energy w/o fuels
district heat district cooling electricity heating energy Solar gains/loads Heat exchange NET ENERGY NEED DELIVERED ENERGY EXPORTED ENERGY (renewable and non-renewable)
Meaning of exported
electricity: Lantti
nZEB house/ Housing
Fair 2012 Tampere
• Grid connected and feeds to
grid about 4000 kWh/a
• Zero energy building
according to EPBD definition, E=-1 kWh/(m2 a)
• E = 50 kWh/(m2 a)
calculated with RakMK D3 2012 system boundary
Lantti zero energy house from Housing Fair
Tampere 2012
nZEB pilot apartment buildings in Kuopio and Järvenpää
Ympäristötalo, Viikki, 2011
• In use all over EU – not typical in the rest of world
• Classification defined on national bases
• Typically based on calculated energy use – allows
to compare buildings without the effects of operation times/user behaviour on energy use
• In some countries measured energy use included in parallel – positive feedback from UK
• If based only on measured energy use, the
certificate may lead to “wrong” energy savings (compromising indoor climate etc.)
• Indoor climate class very seldom included in the
certificate, however energy use has no meaning if indoor climate not known
Proposed requirements
in Finland for houses
(draft 19.4.2012)
• Classification scale is based on calculated primary energy (the same E-value in the building code RakMK D3 2012)
• E-value is calcuated with standard
use of building and calculation rules of building code
• Measured energy use may be
included on voluntary bases
• Recommendations for energy
performance improvement measures included
• Class A provides tentative definition
Inspection of heating and air-conditioning systems
included in EPBD
• Article 14 Inspection of heating systems
- Not limited to boilers but deals with all parts of heating system
• Article 15 Inspection of air-conditioning systems
- Not limited to chillers but deals with all accessible parts of air-conditioning systems
• For both inspections an alternative measures to advice users in
replacements and modifications of systems may be developed
• This alternative approach shall be with equivalent overall impact =
Conclusions
• Finland was a pioneer in energy efficiency in 1970s and 1980s, and a
new wave with rapid changes started about 5 years ago – too short period to achieve forerunner position
• nZEB pilot buildings, one of the most advanced new building code,
knowledge and skills to construct nZEB buildings exist in Finland – administrative capacity in the preparation of EPBD-compliant
legislation is likely the limiting factor:
- Exported energy left out from the official system boundary
- Energy performance certificate not yet published (two calculations, with old and new system, needed to apply the building permit)
- Cost optimal calculations ongoing
• First building code in Finnish history for renovation under preparation