construction change directive no. 2
In order to expedite the work and avoid or minimize delays in the Work which may affect the Contract Sum or Contract Time, the Construction Documents are hereby amended as described below. Proceed with this work promptly. Submit final costs for Work involved and change in Contract Time (if any) for inclusion in a subsequent Change Order
THIS IS THIS IS THIS IS
THIS IS AN AUTHORIZATION TO PROCEED WITH A CHANGE BASED ON AN UNDERSTANDING AN AUTHORIZATION TO PROCEED WITH A CHANGE BASED ON AN UNDERSTANDING AN AUTHORIZATION TO PROCEED WITH A CHANGE BASED ON AN UNDERSTANDING AN AUTHORIZATION TO PROCEED WITH A CHANGE BASED ON AN UNDERSTANDING CONCERNING CHANGES IN CONTRACT SUM AND CONTRACT TIME. A CHANGE ORDER CONCERNING CHANGES IN CONTRACT SUM AND CONTRACT TIME. A CHANGE ORDER CONCERNING CHANGES IN CONTRACT SUM AND CONTRACT TIME. A CHANGE ORDER CONCERNING CHANGES IN CONTRACT SUM AND CONTRACT TIME. A CHANGE ORDER SHOULD BE PROCESSED PROPTLY
SHOULD BE PROCESSED PROPTLYSHOULD BE PROCESSED PROPTLY SHOULD BE PROCESSED PROPTLY
description:
As discussed in today’s OAC meeting, and to my understanding based upon material lead times, please provide and install an electrical trench duct in the floor slab as directed by the equipment vendor (GE healthcare) and as per the attached email correspondence and current GE shop drawings.
attachments:
Emails dated 11-16-12 (10:28AM); 11-16-12 (2:22PM); 11-30-12 (7:12AM); 12-20-12 (8:31AM)
_________________________________________________________________________
Issued: Authorized: Confirmed:
By:______________________ By:______________________ By:______________________
Intergroup Architects Owner Contractor
END OF CONSTRUCTION CHANGE DIRECTIVE NO. 2
project:
MHS PET/CT Scan Room
date:
12-20-12
Cancer Center - 1st Floor
project #:
MS-8918
address:
1400 East Boulder
Colorado Springs, CO 80909
copy to:
owner
to contractor:
GH Phipps Construction Co.
architect
Attn: Dan Lane
contrac.
address:
496 Nevada Mesa View
consult.
Dale Skinner
From: Candler, Curt A (GE Healthcare) <[email protected]>
Sent: Friday, November 16, 2012 10:28 AM
To: Dan Lane; Tony Olguin
Cc: Dale Skinner
Subject: RE: MHS PET/CT - Trench duct submittal
Dan
GE requires the trench duct to be a minimum of 3” deep and 10” wide and have 2 dividers. So long as the wiremold trench duct has the cover still removeable and meets the other stated requirements, it is acceptable to GE
Curt Candler Project Manager
GE Healthcare
Healthcare Project Implementation
[email protected]
T 877 719 8013F 303 496 0363
For GE Healthcare Products, Site Planning Information:
http://www3.gehealthcare.com/en/Support/Site_Planning
.
GE imagination at work
From: Dan Lane [mailto:[email protected]]
Sent: Friday, November 16, 2012 9:29 AM
To: Dale Skinner; Tony Olguin
Subject: MHS PET/CT - Trench duct submittal
Dale, see attached trench duct submittal for your review.
Thank you,
Dale Skinner
From: Candler, Curt A (GE Healthcare) <[email protected]>
Sent: Friday, November 16, 2012 2:22 PM
To: Dale Skinner; Dan Lane; Tony Olguin
Cc: [email protected]; [email protected]
Subject: RE: MHS PET/CT - Trench duct submittal
Dale,
You are correct, GE will accept the 2.5” (clear inside dimension) for the duct so long as it meets the rest of the requirements.
Curt Candler Project Manager GE Healthcare
Healthcare Project Implementation
[email protected]
T 877 719 8013 F 303 496 0363
For GE Healthcare Products, Site Planning Information:
http://www3.gehealthcare.com/en/Support/Site_Planning
.
GE imagination at work
From: Dale Skinner [mailto:[email protected]] Sent: Friday, November 16, 2012 2:01 PM
To: Candler, Curt A (GE Healthcare); Dan Lane; Tony Olguin
Cc:[email protected]; [email protected] Subject: RE: MHS PET/CT - Trench duct submittal
Curt,
We discussed this back in August that this site specific condition of the existing floor structure does not not have a 3”
depth for the trench duct and that 2.5” was acceptable to GE. See attached email with correspondence dated 8-24-12.
Dale
intergroup
architectsdale skinner, Assoc. AIA
project managerLittleton, Colorado 80120 Tele: 303.738.8877 Fax : 303.738.2294
Please consider the environment before printing.
From: Candler, Curt A (GE Healthcare) [mailto:[email protected]] Sent: Friday, November 16, 2012 10:28 AM
To: Dan Lane; Tony Olguin Cc: Dale Skinner
Subject: RE: MHS PET/CT - Trench duct submittal Dan
GE requires the trench duct to be a minimum of 3” deep and 10” wide and have 2 dividers. So long as the wiremold trench duct has the cover still removeable and meets the other stated requirements, it is acceptable to GE
Curt Candler Project Manager GE Healthcare
Healthcare Project Implementation
[email protected]
T 877 719 8013 F 303 496 0363
For GE Healthcare Products, Site Planning Information:
http://www3.gehealthcare.com/en/Support/Site_Planning
.
GE imagination at work
From: Dan Lane [mailto:[email protected]] Sent: Friday, November 16, 2012 9:29 AM
To: Dale Skinner; Tony Olguin
Subject: MHS PET/CT - Trench duct submittal
Dale, see attached trench duct submittal for your review.
Thank you,
Dale Skinner
From: Candler, Curt A (GE Healthcare) <[email protected]>
Sent: Friday, November 30, 2012 7:12 AM
To: Dale Skinner; Dan Lane; Rod McCoy; Tony Olguin
Cc: Chris Wren ([email protected]); Roger McFarland ([email protected])
Subject: RE: 10" Trench Duct
Team
GE has no objection to having a 12” wide trench duct in lieu of the 10” wide trench duct.
Curt Candler Project Manager
GE Healthcare
Healthcare Project Implementation
[email protected]
T 877 719 8013F 303 496 0363
For GE Healthcare Products, Site Planning Information:
http://www3.gehealthcare.com/en/Support/Site_Planning
.
GE imagination at work
From: Dale Skinner [mailto:[email protected]] Sent: Thursday, November 29, 2012 8:41 PM
To: Dan Lane; Rod McCoy; Tony Olguin
Cc: Chris Wren ([email protected]); Roger McFarland ([email protected]); Candler, Curt A (GE Healthcare) Subject: RE: 10" Trench Duct
Dan,
This needs to be reviewed by the electrical consultant and the Vendors representative for the Discovery 610 equipment.
intergroup
architectsdale skinner, Assoc. AIA
project manager2000 West Littleton Boulevard Littleton, Colorado 80120
Tele: 303.738.8877 Fax : 303.738.2294
Please consider the environment before printing. From: Dan Lane [mailto:[email protected]] Sent: Thursday, November 29, 2012 5:35 PM To: Rod McCoy; Dale Skinner; Tony Olguin Subject: RE: 10" Trench Duct
Sorry guys, I thought you knew as we previously submitted this, only in 10”. It is provided by the electrical sub and was
originally reviewed by the electrical engineer. The 10” is 5-6 weeks out and we need to switch to 12” which is only 2
weeks out. It is going to be the same type as approved in the submittal, only 12” in lieu of 10”.
Dan Lane, LEED AP BD+C
Project Manager/Estimator – Special Projects GH PhippsConstruction Companies
496 Nevada Mesa View Colorado Springs, CO 80907
O: (719) 667-8526 |F: (719) 471-3169 M: (719) 357-1563 |E:[email protected]
From: Rod McCoy [mailto:[email protected]] Sent: Thursday, November 29, 2012 5:26 PM
To: Dan Lane; 'Dale Skinner'; Tony Olguin Subject: RE: 10" Trench Duct
This must be an elelctrical race way --- we don’t have anything like that
Rod
From: Dan Lane [mailto:[email protected]] Sent: Thursday, November 29, 2012 4:53 PM To: Dale Skinner; Tony Olguin
Cc: Rod McCoy ([email protected]) Subject: RE: 10" Trench Duct
PET/CT
Dan Lane, LEED AP BD+C
Project Manager/Estimator – Special Projects GH PhippsConstruction Companies
496 Nevada Mesa View Colorado Springs, CO 80907
O: (719) 667-8526 |F: (719) 471-3169 M: (719) 357-1563 |E:[email protected]
From: Dale Skinner [mailto:[email protected]] Sent: Thursday, November 29, 2012 3:37 PM
To: Dan Lane; Tony Olguin
Cc: Rod McCoy ([email protected]) Subject: RE: 10" Trench Duct
Dan,
What project is this for? I have multiple project with MHS. Please advise.
intergroup
architectsdale skinner, Assoc. AIA
project manager2000 West Littleton Boulevard Littleton, Colorado 80120 Tele: 303.738.8877 Fax : 303.738.2294
Please consider the environment before printing. From: Dan Lane [mailto:[email protected]] Sent: Thursday, November 29, 2012 12:45 PM To: Tony Olguin; Dale Skinner
Subject: FW: 10" Trench Duct
Tony, can you review this substitution to a 12” wide trench duct to see if there is any constructability issues and let me
know. Dale, if there are no constructability issues, do you need an RFI on this change? It would be means and methods
type of change, no cost impact. Let me know.
Thanks,
Dan Lane, LEED AP BD+C
Project Manager/Estimator – Special Projects GH PhippsConstruction Companies
496 Nevada Mesa View Colorado Springs, CO 80907
O: (719) 667-8526 |F: (719) 471-3169 M: (719) 357-1563 |E:[email protected]
From: [email protected] [mailto:[email protected]] Sent: Thursday, November 29, 2012 11:46 AM
To: Dan Lane
Subject: 10" Trench Duct
Dan - Legrand called today to notify me that the lead times for the 10" trench duct have been pushed out to 4-6
weeks. They can get me 12" (same depth) in 2-3 weeks. Is is acceptable to make that change? This would affect your saw cut.
Jeff Bowlus, RCDD
Denver Systems Manager Direct: 303-586-9141 Mobile: 720-480-2744 Main: 303-373-2400 Fax: 303-586-9181 Web: www.geco.com E-mail: [email protected]21250 East 31st Circle, Aurora, CO 80011 VIEW MAP
E-mail is not necessarily a secure means of communication. The information transmitted herewith is intended only for the person or entity to which it is addressed and contains confidential or privileged material. If you are not the intended recipient of this message, please disregard its contents and destroy the message and its attachments. We also ask that you notify the sender if you have received this message in error. Any improper use of this information is prohibited.
Dale Skinner
From: Candler, Curt A (GE Healthcare) <[email protected]>
Sent: Thursday, December 20, 2012 8:31 AM
To: Dan Lane
Cc: [email protected]; Dale Skinner; [email protected]; Tony
Olguin
Subject: RE: FW: MHS PET/CT RFI 014
Dan
I just wanted to follow up to our phone conversation this morning.
You will need a trench duct that ends at the point CTPT on the GE drawing sheet E1. The duct can be 10” wide, or it can be wider. This duct will need to connect to the horizontal wall duct at the rear of the room, and cannot conflict with the anchors for the system that are detailed on GE drawing sheet S1.
Curt Candler Project Manager GE Healthcare
Healthcare Project Implementation
[email protected]
T 877 719 8013 F 303 496 0363
For GE Healthcare Products, Site Planning Information:
http://www3.gehealthcare.com/en/Support/Site_Planning
.
GE imagination at work
From: Dan Lane [mailto:[email protected]]
Sent: Thursday, December 20, 2012 7:39 AM
To: [email protected]; Dale Skinner ([email protected]);
[email protected]; Candler, Curt A (GE Healthcare); Tony Olguin
Subject: RE: FW: MHS PET/CT RFI 014
Team, we need direction on the trench duct please as we need to order it now if it is indeed needed. Who needs to
make to call on this? Please advise now.
Thank you,
Dan Lane, LEED AP BD+C
Project Manager/Estimator – Special Projects GH PhippsConstruction Companies
496 Nevada Mesa View Colorado Springs, CO 80907
O: (719) 667-8526 |F: (719) 471-3169 M: (719) 357-1563 |E:[email protected]
From:[email protected] [mailto:[email protected]]
Sent: Wednesday, December 19, 2012 3:37 PM
To: Dan Lane
Subject: Re: FW: MHS PET/CT RFI 014 Dan - did we ever get direction on this?
Jeff Bowlus, RCDD
Denver Systems Manager Direct: 303-586-9141 Mobile: 720-480-2744 Main: 303-373-2400 Fax: 303-586-9181 Web: www.geco.com E-mail: [email protected]21250 East 31st Circle, Aurora, CO 80011 VIEW MAP
From: Dan Lane <[email protected]>
To: "Candler, Curt A (GE Healthcare) ([email protected]) ([email protected])" <[email protected]>, "[email protected]"
<[email protected]>, Tony Olguin <[email protected]>,
Cc: "[email protected]" <[email protected]>, "Dale Skinner ([email protected])" <[email protected]>
Date: 12/11/2012 07:28 AM
Subject: FW: MHS PET/CT RFI 014
Curt, see attached RFI regarding trench duct and advise if required.
Thank you,
Dan Lane, LEED AP BD+C
Project Manager/Estimator – Special Projects
GH PhippsConstruction Companies
496 Nevada Mesa View
Colorado Springs, CO 80907
O: (719) 667-8526 |F: (719) 471-3169
M: (719) 357-1563 |E:[email protected]
From: Dale Skinner [mailto:[email protected]]
Sent: Monday, December 10, 2012 2:08 PM
To: Dan Lane; Tony Olguin
Cc:[email protected]; Candler, Curt A (GE Healthcare) ([email protected])
Subject: RE: MHS PET/CT RFI 014
Dan,
Attached is the response to RFI-014.
intergroup architects
dale skinner, Assoc. AIA
project manager
2000 West Littleton Boulevard
Littleton, Colorado 80120
Tele: 303.738.8877
Fax : 303.738.2294
Please consider the environment before printing.
From: Dan Lane [mailto:[email protected]]
Sent: Monday, December 10, 2012 12:23 PM
To: Dale Skinner; Tony Olguin
Subject: MHS PET/CT RFI 014
Dale, see attached RFI for your response.
Thanks,
Dan[attachment "8918 RFI-014 - Response IGA 2012-12-10.pdf" deleted by Jeff Bowlus/GECO]
E-mail is not necessarily a secure means of communication. The information transmitted herewith is intended only for the person or entity to which it is addressed and contains confidential or privileged material. If you are not the intended recipient of this message, please disregard its contents and destroy the message and its attachments. We also ask that you notify the sender if you have received this message in error. Any improper use of this information is prohibited.