ETAP 5.0
ETAP 5.0
Copyright 2003 Operation Technology, Inc.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 2
System Concepts
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 3
jQ
P
I
V
S
S
I
V
S
LL
LN
+
=
×
=
×
=
=
*
1
3
*
1
3
3
φ
φ
φ
Inductive loads have lagging Power Factors.
Capacitive loads have leading Power Factors.
Power in Balanced 3-Phase
Systems
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 4
Leading & Lagging Power
Factors
PowerStation displays lagging Power Factors as positive and leading Power
Factors as negative. The Power Factor is displayed in percent.
Leading
Power
Factor
Lagging
Power
Factor
+
P
j Q
j Q
P
+
j Q
P
−
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 5
3-Phase Per Unit System
B
2
B
B
B
B
B
MVA
)
kV
(
Z
kV
3
kVA
I
=
=
B
actual
pu
B
actual
pu
Z
Z
Z
I
I
I
=
=
B
actual
pu
B
actual
pu
S
S
S
V
V
V
=
=
=
=
=
=
B
2
B
B
B
B
B
S
V
Z
V
3
S
I
ZI
3
V
VI
3
S
If you have two bases:
Then you may calculate the other two
by using the relationships enclosed in
brackets. The different bases are:
•I
B
(Base Current)
•Z
B
(Base Impedance)
•V
B
(Base Voltage)
•S
B
(Base Power)
PowerStation selects for LF:
•100 MVA for S
B
which is fixed for the
entire system.
•The kV rating of reference point is
used along with the transformer turn
ratios are applied to determine the
base voltage for different parts of the
system.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 6
Example 1: The diagram shows a simple radial system. PowerStation converts the
branch impedance values to the correct base for Load Flow calculations. The LF
reports show the branch impedance values in percent. The transformer turn ratio
(N1/N2) is 3.31 and the X/R = 12.14
2
B
1
B
kV
2
N
1
N
kV
=
2
pu
pu
R
X
1
R
X
Z
X
+
×
=
Transformer T7: The following equations are used to find
the impedance of transformer T7 in 100 MVA base.
=
R
X
x
R
pu
pu
1
B
kV
2
B
kV
Transformer Turn Ratio: The transformer turn ratio is
used by PowerStation to determine the base voltage for
different parts of the system. Different turn ratios are
applied starting from the utility kV rating.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 7
005336
.
0
14
.
12
06478
.
0
R
pu
=
=
06478
.
0
)
14
.
12
(
1
)
14
.
12
(
065
.
0
X
2
pu
=
+
=
The transformer impedance must be converted to 100 MVA base and therefore the
following relation must be used, where “n” stands for new and “o” stands for old.
)
3538
.
1
j
1115
.
0
(
5
100
5
.
13
8
.
13
)
06478
.
0
j
10
33
.
5
(
S
S
V
V
Z
Z
2
3
o
B
n
B
2
n
B
o
B
o
pu
n
pu
=
+
+
×
=
=
−
38
.
135
j
15
.
11
Z
100
Z
%
=
×
pu
=
+
Impedance Z1: The base voltage is determined by using the transformer turn ratio. The base
impedance for Z1 is determined using the base voltage at Bus5 and the MVA base.
165608
.
0
100
)
0695
.
4
(
MVA
V
Z
2
2
B
B
=
=
=
0695
.
4
31
.
3
5
.
13
2
N
1
N
kV
V
B
utility
=
=
=
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 8
The per-unit value of the impedance may be determined as soon as the base
impedance is known. The per-unit value is multiplied by one hundred to obtain
the percent impedance. This value will be the value displayed on the LF report.
)
0382
.
6
j
6038
.
0
(
1656
.
0
)
1
j
1
.
0
(
Z
Z
Z
B
actual
pu
=
+
+
=
=
8
.
603
j
38
.
60
Z
100
Z
%
=
×
pu
=
+
The LF report generated by PowerStation displays the following percent impedance
values in 100 MVA base
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 9
Load Flow Analysis
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 10
Load Flow Problem
• Given
– Load Power Consumption at all buses
– Configuration
– Power Production at each generator
• Basic Requirement
– Power Flow in each line and transformer
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 11
Load Flow Studies
• Determine Steady State Operating Conditions
– Voltage Profile
– Power Flows
– Current Flows
– Power Factors
– Transformer LTC Settings
– Voltage Drops
– Generator’s Mvar Demand (Qmax & Qmin)
– Total Generation & Power Demand
– Steady State Stability Limits
– MW & Mvar Losses
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 12
Size & Determine System
Equipment & Parameters
• Cable / Feeder Capacity
• Capacitor Size
• Transformer MVA & kV Ratings (Turn Ratios)
• Transformer Impedance & Tap Setting
• Current Limiting Reactor Rating & Imp.
• MCC & Switchgear Current Ratings
• Generator Operating Mode (Isochronous / Droop)
• Generator’s Mvar Demand
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 13
Optimize Operating
Conditions
• Bus Voltages are Within Acceptable Limits
• Voltages are Within Rated Insulation Limits
of Equipment
• Power & Current Flows Do Not Exceed the
Maximum Ratings
• System MW & Mvar Losses are Determined
• Circulating Mvar Flows are Eliminated
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 14
Calculation Process
Assume V
R
Calc: I = S
load
/ V
R
Calc: Vd = I * Z
Re-Calc V
R
= Vs - Vd
• Non-Linear System
• Calculated Iteratively
– Assume the Load
Voltage (Initial Conditions)
– Calculate the Current I
– Based on the Current,
Calculate Voltage Drop Vd
– Re-Calculate Load Voltage VR
– Re-use Load Voltage as initial condition until the
results are within the specified precision.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 15
1.
Accelerated Gauss-Seidel Method
•
Low Requirements on initial values,
but slow in speed.
2.
Newton-Raphson Method
•
Fast in speed, but high requirement on
initial values.
•
First order derivative is used to speed up
calculation.
3. Fast-Decoupled Method
•
Two sets of iteration equations: real
power – voltage angle,
reactive power – voltage magnitude.
•
Fast in speed, but low in solution
precision.
•
Better for radial systems and
systems with long lines.
Load Flow Calculation
Methods
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 16
Load Nameplate Data
kV
kVA
FLA
kV
kVA
FLA
Eff
PF
HP
Eff
PF
kW
kVA
Rated
Rated
Rated
Rated
=
×
=
×
×
=
×
=
φ
φ
1
3
3
7457
.
0
kV
kVA
1000
I
)
kV
3
(
kVA
1000
I
kVA
kW
PF
)
kVar
(
)
kW
(
kVA
1
3
2
2
×
=
×
×
=
=
+
=
φ
φ
Where PF and Efficiency are taken at 100 %
loading conditions
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 17
Constant Power Loads
•
In Load Flow calculations induction,
synchronous and lump loads are treated
as constant power loads.
•
The power output remains constant even
if the input voltage changes (constant
kVA).
•
The lump load power output behaves like
a constant power load for the specified %
motor load.
Constant Impedance Loads
• In Load Flow calculations Static Loads, Lump Loads
(% static), Capacitors and Harmonic Filters and Motor
Operated Valves are treated as Constant Impedance
Loads.
• The Input Power increases proportionally to the
square of the Input Voltage.
• In Load Flow Harmonic Filters may be used as
capacitive loads for Power Factor Correction.
• MOVs are modeled as constant impedance loads
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 19
• The current remains constant even if the
voltage changes.
• DC Constant current loads are used to test
Battery discharge capacity.
• AC constant current loads may be used to test
UPS systems performance.
• DC Constant Current Loads may be defined in
PowerStation by defining Load Duty Cycles
used for Battery Sizing & Discharge purposes.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 20
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 21
Generic Loads
Exponential Load
Polynomial Load
Comprehensive
Load
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 22
Generator Operation Modes
Feedback Voltage
•AVR: Automatic Voltage
Regulation
•Fixed: Fixed Excitation
(no AVR action)
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 23
Governor Operating Modes
• Isochronous: This governor setting allows the
generator’s power output to be adjusted based on
the system demand.
• Droop: This governor setting allows the generator
to be Base Loaded, meaning that the MW output is
fixed.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 24
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 25
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 26
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 27
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 28
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 29
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 30
In PowerStation Generators and Power Grids have four
operating modes that are used in Load Flow calculations.
Swing Mode
•Governor is operating in
Isochronous mode
•Automatic Voltage Regulator
Voltage Control
•Governor is operating in
Droop Mode
•Automatic Voltage Regulator
Mvar Control
•Governor is operating in
Droop Mode
•Fixed Field Excitation (no
AVR action)
PF Control
•Governor is operating in
Droop Mode
•AVR Adjusts to Power Factor
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 31
• In the Swing Mode, the voltage is kept fixed. P & Q can vary
based on the Power Demand
• In the Voltage Control Mode, P & V are kept fixed while Q & θ
are varied
• In the Mvar Control Mode, P and Q are kept fixed while V & θ
are varied
• If in Voltage Control Mode, the limits of P & Q are reached, the
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 32
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 33
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 34
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 35
Field Winding Heating Limit
Armature Winding Heating Limit
Machine Rating (Power Factor Point)
Steady State Stability Curve
Maximum & Minimum
Reactive Power
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 36
Generator Capability Curve
Field Winding
Heating Limit
Machine Rating
(Power Factor
Point)
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 37
Generation Categories
Generator/Power Grid Rating Page
Load Flow Loading Page
10 Different Generation
Categories for Every
Generator or Power Grid
in the System
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 38
Power Flow
∠
=
∠
=
2
2
2
1
1
1
V
V
V
V
δ
δ
X
V
)
*COS(
X
*V
V
Q
)
(
*SIN
X
*V
V
P
X
V
)
(
*COS
X
*V
V
j
)
(
*SIN
X
*V
V
jQ
P
I
*
V
S
2
2
2
1
2
1
2
1
2
1
2
2
2
1
2
1
2
1
2
1
−
−
=
−
=
−
−
+
−
=
+
=
=
δ
δ
δ
δ
δ
δ
δ
δ
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 39
Example: Two voltage sources designated as V1 and V2 are
connected as shown. If V
1
= 100 /0° , V
2
= 100 /30° and X = 0 +j5
determine the power flow in the system.
I
var
536
5
35
.
10
X
|
I
|
268
j
1000
)
68
.
2
j
10
)(
50
j
6
.
86
(
I
V
268
j
1000
)
68
.
2
j
10
(
100
I
V
68
.
2
j
10
I
5
j
)
50
j
6
.
86
(
0
j
100
X
V
V
I
2
2
*
2
*
1
2
1
=
×
=
−
−
=
+
−
+
=
+
−
=
+
−
=
−
−
=
+
−
+
=
−
=
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 40
The following graph shows the power flow from Machine M2. This
machine behaves as a generator supplying real power and
absorbing reactive power from machine M1.
2
1
0
1
Real Power Flow
Reactive Power Flow
Power Flow
1
2
−
V E
⋅
(
)
X
⋅
sin
( )
δ
∆
V E
⋅
(
)
X
⋅
cos
( )
δ
∆
V
2
X
−
π
0
δ
∆
S
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 41
Bus Voltage
PowerStation displays bus voltage values in two ways
•kV value
•Percent of Nominal Bus kV
%
83
.
97
100
%
5
.
13
min
=
×
=
=
al
No
Calculated
Calculated
kV
kV
V
kV
kV
No
min
al
=
13
.
8
For Bus4:
For Bus5:
%
85
.
96
100
%
03
.
4
min
=
×
=
=
al
No
Calculated
Calculated
kV
kV
V
kV
kV
No
min
al
=
4
.
16
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 43
Lump Load Negative
Loading
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 44
Load Flow Adjustments
• Transformer Impedance
– Adjust transformer impedance based on possible length variation
tolerance
• Reactor Impedance
– Adjust reactor impedance based on specified tolerance
• Overload Heater
– Adjust Overload Heater resistance based on specified tolerance
• Transmission Line Length
– Adjust Transmission Line Impedance based on possible length
variation tolerance
• Cable Length
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 45
Load Flow Study Case
Adjustment Page
Adjustments applied
•Individual
•Global
Temperature Correction
• Cable Resistance
• Transmission Line
Resistance
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 46
Allowable Voltage Drop
NEC and ANSI C84.1
Power Grid
1000 MVAsc
X/R = 22
Gen1
10 MW
Voltage Control
Design:
%Pf = 85
MW = 5
Max Q = 4
Min Q = -1
Impedance
Z1
13.8 kV
100MVA
% Z = 0.01+j1
Load Flow Example 1
Part 1
Transformers
T1 = 30 MVA
T2 = 15 MVA
T3 = 5 MVA
T4 = 3 MVA
Select typical %Z &
X/R
Cable1
ICEA 15kV 3/C CU,
100%
Size= 250
Length= 400 ft
Cable2
KERITE 5kV 3/C
CU, 100%
Size= 500
Length= 300 ft
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 48
Load Flow Example 1
Part 2
Cable3
ICEA 5kV 3/C
CU, 133%
Size= 500
Length= 100 ft
Transformer
T5 = 5 MVA
Select typical %Z
& X/R
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 49
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 50
Equipment Overload Alerts
Bus Alerts
Monitor Continuous Amps
Cable
Monitor Continuous Amps
Reactor
Monitor Continuous Amps
Line
Monitor Line Ampacity
Transformer
Monitor Maximum MVA Output
DC Link
DC Link Loading Capability (Idc,
Max. MVA)
Panel
Monitor Panel Continuous Amps
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 51
Protective Device Alerts
Protective Devices
Monitored parameters %
Condition reported
Low Voltage Circuit Breaker
Continuous rated Current
OverLoad
High Voltage Circuit Breaker
Continuous rated Current
OverLoad
Fuses
Rated Current
OverLoad
Contactors
Continuous rated Current
OverLoad
SPDT / SPST switches
Continuous rated Current
OverLoad
If the Auto Display
feature is active, the
Alert View Window
will appear as soon as
the Load Flow
calculation has
finished.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 53
Advanced LF Topics
Advanced LF Topics
Load Flow Convergence
Voltage Control
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 54
Load Flow Convergence
• Negative Impedance
• Zero or Very Small Impedance
• Widely Different Branch Impedance Values
• Long Radial System Configurations
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 55
Voltage Control
• Under/Over Voltage Conditions must be
fixed for proper equipment operation and
insulation ratings be met.
• Methods of Improving Voltage Conditions:
– Transformer Replacement
– Capacitor Addition
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 56
Under-Voltage Example
• Create Under Voltage
Condition
– Change Syn2 Quantity to 6.
(Info Page, Quantity Field)
– Run LF
– Bus8 Turns Magenta (Under
Voltage Condition)
• Method 1 - Change Xfmr
– Change T4 from 3 MVA to 8
MVA, will notice slight
improvement on the Bus8 kV
– Too Expensive and time
consuming
• Method 2 - Shunt
Capacitor
– Add Shunt Capacitor to Bus8
– 300 kvar 3 Banks
– Voltage is improved
• Method 3 - Change Tap
– Place LTC on Primary of T6
– Select Bus8 for Control Bus
– Select Update LTC in the
Study Case
– Run LF
– Bus Voltage Comes within
specified limits
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 57
Mvar Control
• Vars from Utility
– Add Switch to CAP1
– Open Switch
– Run LF
• Method 1 – Generator
– Change Generator from
Voltage Control to Mvar
Control
– Set Mvar Design Setting to 5
Mvars
• Method 2 – Add Capacitor
– Close Switch
– Run Load Flow
– Var Contribution from the
Utility reduces
• Method 3 – Xfmr MVA
– Change T1 Mva to 40 MVA
– Will notice decrease in the
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 58
Panel Systems
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 59
Panel Boards
• They are a collection of branch circuits
feeding system loads
• Panel System is used for representing power
and lighting panels in electrical systems
Click to drop once on OLV
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 60
Representation
A panel branch circuit load can be modeled as
an internal or external load
Advantages:
1. Easier Data Entry
2. Concise System
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 61
Pin Assignment
Pin 0 is the top pin of the panel
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 62
Assumptions
• V
rated
(internal load) = V
rated
(Panel Voltage)
• Note that if a 1-Phase load is connected to a
3-Phase panel circuit, the rated voltage of the panel
circuit is (1/√3) times the rated panel voltage
• The voltage of L1 or L2 phase in a 1-Phase 3-Wire
panel is (1/2) times the rated voltage of the panel
• There are no losses in the feeders connecting a
load to the panel
• Static loads are calculated based on their rated
voltage
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 63
Line-Line Connections
Load Connected Between Two Phases of a
3-Phase System
A
B
C
Load
I
BCI
C= -I
BCA
B
C
LoadB
I
B= I
BCAngle by which load current I
BClags the load voltage = θ°
Therefore, for load connected between phases B and C:
S
BC= V
BC.I
BCP
BC= V
BC.I
BC.cos θ
Q
BC= V
BC.I
BC.sin θ
For load connected to phase B
SB = VB.IB
PB = VB.IB.cos (θ - 30)
QB = VB.IB.sin (θ - 30)
And, for load connected to phase C
SC = VC.IC
PC = VC.IC.cos (θ + 30)
QC = VC.IC.sin (θ + 30)
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 64
Info Page
NEC Selection
A, B, C from top to bottom or
left to right from the front of
the panel
Phase B shall be the highest
voltage (LG) on a 3-phase,
4-wire delta connected system
(midpoint grounded)
3-Phase 4-Wire Panel
3-Phase 3-Wire Panel
1-Phase 3-Wire Panel
1-Phase 2-Wire Panel
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 65
Rating Page
Intelligent kV Calculation
If a 1-Phase panel is connected to a 3-Phase bus
having a nominal voltage equal to 0.48 kV, the
default rated kV of the panel is set to (0.48/1.732
=) 0.277 kV
For IEC, Enclosure Type
is Ingress Protection
(IPxy), where IP00 means
no protection or shielding
on the panel
Select ANSI or IEC
Breakers or Fuses from
Main Device Library
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 66
Schedule Page
Circuit Numbers with
Standard Layout
Circuit Numbers with
Column Layout
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 67
Description Tab
First 14 load items in the list are based on NEC 1999
Last 10 load types in the Panel Code Factor Table are user-defined
Load Type is used to determine the Code Factors used in calculating the
total panel load
External loads are classified as motor load or static load according to the
element type
For External links the load status is determined from the connected load’s
demand factor status
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 68
Rating Tab
Enter per phase VA, W, or
Amperes for this load.
For example, if total Watts
for a 3-phase load are
1200, enter W as 400
(=1200/3)
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 69
Loading Tab
For internal loads, enter the % loading for the selected loading category
For both internal and external loads, Amp values are
calculated based on terminal bus nominal kV
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 70
Protective Device Tab
Library Quick Pick
-LV Circuit Breaker
(Molded Case, with
Thermal Magnetic
Trip Device) or
Library Quick Pick –
Fuse will appear
depending on the
Type of protective
device selected.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 71
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 72
Action Buttons
Copy the content of the selected
row to clipboard. Circuit number,
Phase, Pole, Load Name, Link
and State are not copied.
Paste the entire content (of the
copied row) in the selected row.
This will work when the Link
Type is other than space or
unusable, and only for fields
which are not blocked.
Blank out the contents of the entire
selected row.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 73
Summary Page
Continuous Load – Per Phase and Total
Non-Continuous Load – Per Phase and Total
Connected Load – Per Phase and Total (Continuous + Non-Continuous Load)
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 74
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 75