Installation Fire Stopping For: Installation Fire Stopping For:

a.

a. uPVC, uPVC, PPR PPR pipes:pipes:

1. uPVC, PPR pipes smaller than 50mm. 1. uPVC, PPR pipes smaller than 50mm.

2. uPVC, PPR pipes from 50mm up to 160mm. 2. uPVC, PPR pipes from 50mm up to 160mm. 3. uPVC pipes over 160mm.

3. uPVC pipes over 160mm. b.

b. Metal pMetal pipes ipes and and air duct.air duct. c.

c. Electrical Electrical conduits.conduits. d.

d. Electric trunkElectric trunking, cabing, cable trayle tray, ladder., ladder. e.

e. Busduct Busduct system.system.

01/12/08

01/12/08 FIRST ISSUEFIRST ISSUE C.T.PC.T.P -.-.--.-.- L.Q.KL.Q.K J.R.PJ.R.P

A A

(2)

1. General: 1. General:

Items: - The Method Statement For Fire Stopping Works Items: - The Method Statement For Fire Stopping Works 2. Aim:

2. Aim:

The objectives is to describe Fire Stopping Works associated with installation The objectives is to describe Fire Stopping Works associated with installation of M&E services in compliance with

of M&E services in compliance with the contract specification, approved shopthe contract specification, approved shop drawings, combine and coordinated all services and structural penetration drawings, combine and coordinated all services and structural penetration shop drawings.

shop drawings. 3.

3. Scope Scope of of Works:Works:

This method statement covers work related to all M&E works of the SAIGON This method statement covers work related to all M&E works of the SAIGON M&C TOWER Project.

M&C TOWER Project. 4. Installation:

4. Installation: a.

a. uPVC, uPVC, PPR PPR pipes:pipes:

 For pipe smaller than 50mm: Use Fire SealantFor pipe smaller than 50mm: Use Fire Sealant -

- Clean Clean the the pipe.pipe. -

- Fill Fill rockwool rockwool to to sleeve sleeve (Sleeve (Sleeve size size follow follow table table 1).1). -

- Apply Apply fire fire sealant.sealant. -

- Smooth Smooth fire fire sealantsealant -

- Install Install G.I G.I sheet sheet 0.8mm 0.8mm thk thk - - If If the the pipes pipes exposed exposed ceiling.ceiling.

Table 1: Sleeves Size for Pipes smaller than 50mm Table 1: Sleeves Size for Pipes smaller than 50mm

S

Seerrvviicce e PPPPR R PPiippe e ssiizze e ((mmmm)) SSlleeeevve e SSiizzees s ((mmmm)) D D2200 7700 D D2255 7755 Wall/slab Wall/slab Rockwool (60 kg/m3) Rockwool (60 kg/m3) uPVC/PPR pipe uPVC/PPR pipe Fill Rockwool To Sleeve

Fill Rockwool To Sleeve Sleeve

(3)

Wall/Slab Sleeve

Rockwool (60 kg/m3)

Fire sealant uPVC/PPR i e Apply Fire Sealant

Fire sealant

Smooth Fire Sealant

Wall/Slab

uPVC, PPR pipe Sleeve

Fire sealant

Complete surface

Leave complete seal (The pipes concealed ceiling)

Wall/Slab

(4)

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only) uPVC, PPR pipe

Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm Rockwool (60 kg/m3)

Slab Sleeve

10÷15mm 70 mm

Detail Installation Fire Stopping For uPVC, PPR Pipe Through Slab

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only) Rockwool (60 kg/m3)

10÷15mm

Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm uPVC, PPR pipe

70 mm Wall Sleeve

(5)

 For pipe from 50mm up to 160mm: Use Fire Wrap - Clean the pipe.

- Cut fire wrap to the correct length (See application table). - Wrap fire wrap around pipe.

- Push fire wrap into the annular pace.

- Fill all gap of fire wrap by fire sealant (If any).

Wrap fire wrap around pipe Cut fire wrap

Fill all gap of fire wrap by fire sealant (If any)

Push fire wrap into the annular pace

(6)

Wall

uPVC/PPR pipe

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only)

25mm Sleeve

(Sleeve size follow table 2, 3)

Plastic anchor bolt M4x50mm

Fire wrap 70 mm

Detail Installation Fire Wrap For uPVC, PPR Pipe Through The Wall

Detail Installation Fire Wrap For uPVC, PPR Pipe Through Slab Fire wrap

Rockwool (60 kg/m3) uPVC/PPR pipe

Plastic anchor bolt M4x50mm G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only)

25mm 70mm Slab Sleeve (Sleeve size follow table 2, 3)

(7)

Table 2: Sleeves Size for Pipes from 50mm up to 160mm Service Pipe size Sleeve Size (mm)

40A 100 50A 110 65A 125 80A 140 100A 160 125A 190 150A 200

Table 3: Sleeves Size for Condensate Pipes from 50mm up to 160mm Condensate Pipe

Normal size

Condensate Pipe size

with Insulation (mm) Sleeve Size (mm)

20A 67 110 25A 74 120 32A 82 130 40A 90 140 50A 100 150 80A 130 180 100A 154 200

(8)

 For uPVC pipe over 160mm: Use Fire Collar

- Make measuring points according to pipe size

- Cut fire collar at marked measuring points according to pipe size. - Ben the intumescent side of the collar until it snap.

- Shape the collar to fit the pipe and bevel intumescent edge for  close fit.

- Wrap the collar around the pipe and clip the first bracket into slots on both ends.

- Complete other brackets and fit the collar onto wall/slab.

Make measuring points according to pipe size

Cut fire collar 

Ben the intumescent side of the collar until it snap

(9)

Wrap the collar around the pipe and clip the first bracket into slots on both ends

Complete other brackets and fit the collar onto wall/slab

Fire collar 

Wall uPVC Pipe

uPVC Pipe

Detail Installation Fire Collar For uPVC Through The Wall

Slab

Detail Installation Fire Collar For uPVC Through Slab

Fire collar uPVC pipe

(10)

b. Metal pipes & Air ducts: Use Fire Sealant - Clean the pipe, Air duct.

- Fill rockwool (60 kg/m3) to sleeve/opening. Size of sleeve follow table 4 & 6, size of opening follow table 5.

- Apply fire sealant. - Smooth fire sealant

- Install G.I sheet 0.8mm thk- If the pipes, Air duct exposed ceiling.

Wall/slab

Rockwool (60 kg/m3)

Metal pipe/Air duct Fill Rockwool To Sleeve

Sleeve

Wall/Slab

Fire sealant

Apply Fire Sealant Sleeve

Metal pipe/Air duct Rockwool (60 kg/m3)

(11)

Table 4: Sleeve size for metal pipes (w/o Insulation) Service Pipe size

(mm) Sleeve Sizes (mm) 15 70 20 80 25 80 32 90 40 100 50 110 65 125 80 140 100 165 125 190 150 220 200 270 250 320 300 370

Table 5: Opening size for installation ducts Ducts size (mm) Opening Sizes (mm) w/o Insulation Opening Sizes (mm) with Insulation

Wide (WD) High (HD) Wide (WO) High (HO) Wide (WO) High (HO)

WD HD WO = WD+50 HO=HD+50 WO = WD+75 HO=HD+75 Note: - WD: Wide of ducts. - WO: Wide of opening. - HD: High of duct. - HO: High of opening.

(12)

Table 6: Sleeve size for chiller pipes Service Pipe size

(mm)

Insulation thick (mm)

Pipe Sleeve Sizes (mm) 20 32 140 25 32 150 32 32 150 40 32 150 50 32 175 65 38 200 80 38 210 100 38 240 125 38 265 150 38 300 200 50 370 250 50 420 300 50 470 350 50 500 400 50 550 450 50 600 500 50 650 Fire sealant

Smooth Fire Sealant

Wall/Slab

Metal pipe/Air duct Sleeve

(13)

Fire sealant

Complete surface

Leave complete seal

Wall/Slab

Metal pipe/Air duct

Fire sealant Wall/Slab

Air duct

Metal pipe

Complete Fire Sealant For Metal Pipe/Air Duct Concealed Ceiling Through Wall/Slab

(14)

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only) Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm Rockwool (60 kg/m3) Metal pipe Slab Sleeve 10÷15mm 70 mm

Detail Installation Fire Stopping Metal Pipe Through Slab

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only) Rockwool (60 kg/m3)

10÷15mm

Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm Metal pipe

70 mm Wall Sleeve

(15)

Fire protection pipes

G.I. sheet cover 0.8mm thk

Detail Installation Fire Stopping For Fire Protection Pipes Exposed Ceiling Through The Wall

Rockwool (48 kg/m3) Insulation

50mm G.I. sheet cover 0.8mm thk

(For pipes exposed ceiling only) Wall

Detail Installation Fire Stopping For Chiller Pipes Through The Wall 70mm

Chiller insulation Rockwool (60 kg/m3)

Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm Chiller pipe

10÷15mm

(16)

Plastic anchor bolt M4x50mm Rockwool (48 kg/m3)

Insulation

70mm

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only) Rockwool (60 kg/m3)

Fire sealant; Depth: 10÷15mm

10÷15mm Chiller pipe Chiller insulation

Detail Installation Fire Stopping For Chiller Pipes Through Slab Sleeve

Slab 50mm

(17)

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only) Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm Rockwool (60 kg/m3) Air duct Slab Opening 10÷15mm 70 mm

Detail Installation Fire Stopping Air duct Through Slab

G.I. sheet cover 0.8mm thk (For pipes exposed ceiling only) Rockwool (60 kg/m3)

10÷15mm

Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm Air duct

70 mm Wall Opening

(18)

c. Electrical conduits: Use Fire Sealant.

- G.I. conduits: Method statement installation fire stopping for G.I. conduit through the wall/slab is the same Method statement installation fire stopping for metal pipes.

- PVC conduits: Method statement installation fire stopping for  PVC conduit through the wall/slab is the same Method statement installation fire stopping for uPVC, PPR pipes smaller than 50mm through wall/slab.

d. Electric trunking, cable tray, ladder: Use Fire Cement. - Clean electric trunking, cable tray, ladder.

- Install form work to side opening (For wall opening). - Install form work to bottom opening (For floor opening). - Apply fire cement to opening (Opening size follow table 4). - Take-out form work.

- Clean electric trunking, cable tray, ladder out-side the wall/slab (If  any).

Opening size max. Penetration type L x W (mm) Wall opening 600 x 600 Floor opening 600 x 400 Wall ≥90mm Wall opening ≥90mm ≤600mm Cable tray Fire cement Trunking

(19)

≤ 600mm Cable tray Cable trunking Fire cement Floor opening Slab ≥ 105mm

Detail Installation Fire Cement For Cable Trunking, Cable Tray Through Slab

Detail Installation Fire Cement For Cable Trunking Through Slab

Detail Installation Fire Cement For Cable Trunking and Cable Through The Wall

(20)

Busduct system: Use Rocwool and G.I. Sheet. - Clean busduct.

- Install G.I sheet 0.8mm thk to side opening (For wall opening). - Install G.I sheet 0.8mm thk to bottom opening (For floor 

opening).

- Apply rockwool to opening.

- Install G.I sheet 0.8mm thk to other side opening (For wall opening).

- Install G.I sheet 0.8mm thk to top opening (For floor opening). - Clean busduct, working area.

25mm

Busduct

G.I. sheet cover 

0.8mm thk

Slab

Detail Installation Fire Stopping For Busduct Throu h Slab

Rockwool (60 kg/m3)

(21)

G.I. sheet cover  0.8mm thk

Busduct

Detail Installation Fire Stopping For Busduct Through Slab ( Bottom View)

Busduct

Rockwool (60 kg/m3)

Detail Installation Fire Stopping For Busduct Through Slab (Top View – Befor Install G.I. Sheet Cover)

Busduct

G.I. sheet cover  0.8mm thk

Detail Installation Fire Stopping For Busduct Through Slab ( Top View)

(22)

Rockwool (60 kg/m3)

G.I. sheet cover 0.8mm thk 25mm

Detail Installation Fire Stopping For Busduct Through The Wall

Busduct

Wall

Detail Installation Fire Stopping For Busduct Through The Wall

References

Related documents

NRAM™ will be considerably faster and denser than DRAM, have substantially lower power consumption than DRAM or flash, be as portable as flash memory, and be highly resistant

Melodic knowledge is focused on the ability of systems in choosing and arranging notations that fit the characteristic sound of gamelan melody. Notation pattern recognition

Larger hamstring autograft diameter (> 8 mm) is associated with better patient-reported KOOS and IKDC scores 6 months after ACL

[r]

Rotorik actuators are designed to work for long periods of time in the most severe conditions. However, a preventative approach to maintenance helps prevent costly down time and can

Adequate word or a fedex commercial invoice was completed as that matters is required by customs handling is a purchase order.. Corresponding shipping label, why should use the

sff sff sff cresc.. sff

The length of the connection coupling should be adjusted so that approximately 10 mm of the ¾” pipe thread is exposed when the cover plate is tightened against the wall.. The thread