AIRPORT TERMINAL HVAC DESIGN

GUIDELINE

1. HEAT LOAD

Outdoor Condititons (Source - Hvac Specs 1 April 2015 ) Latitude 29.22 North

Longitude 47.98 E Altitude 55 M

Summer temperature: 48 °C db, 25.5 °C Wb

Winter temperature: Dry bulb: 4.5 °C Wet bulb: 2 °C Average daily temperature range: 13.33° C

(2)

Envelope Data (Source - CD-A0000-A-RPT-010-0) The minimum clearance below false ceiling in the main public spaces is 9m. The minimum clearance below false ceiling in the secondary public spaces is 4m. The minimum clearance below false ceiling in nonpublic spaces is 3.5 m

The minimum area of the clear openings in the landside facade is 2600 m² (excluding structure, mullions) The minimum area of the clear openings in the airside facade is 2800 m² (excluding structure, mullions) A minimum size of 4m² for at least 90% of the glazed curtain wall panels is required.

The visible width of the curtain wall mullions seen from the outside shall not exceed 80mm The Airside and Landside façade (Front entry and last check gates) are curtain walls.

The air intakes and exhausts shall be avoided The Side façade shall be covered with aluminum cladding.

The air intakes and exhausts shall be covered with louvers. The louvers design shall be consistent with the aluminum cladding covering the façade.

A minimum size of 2m² for at least 90% of the cladding panels is required

A minimum roof overhang (from the façade to the edge of the roof) of 2m is required above the side facades. A minimum roof overhang (from the façade to the edge of the roof) of 10m is required above the airside and landside facades.

A minimum roof overhang (from the façade to the edge of the roof) of 2m is required above the side facades.

The minimum area of the clear openings in the roof is 7500 m². For roof,

Extruded-Polystyrene Board Roof Insulation: ASTM C 578, of type VI, with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, per ASTM E 84.

1. Density 29 kg/cu m

2. Compressive Strength 276 kPa

3. Thermal Resistance: 50 mm thick 1.76 K.m2/W [10 F. ft2.h/Btu].

Thermal and Optical Performance Properties: Provide glass with performance properties specified based on Manufacturer's published test data, as indicated below:

1. Center-of-Glass U-Value for vertical glazing: ≤1.1 W/m².K.

2. Center-of-Glass U-Value for horizontal glazing (rooflights): ≤1.7 W/m².K. 3. Center-of-Glass Solar Heat Gain Coefficient: ≤ 25%.

4. Light Transmittance: ≤ 50%.

(3)

Louver Performance Ratings:

a. Free Area: Not less than 0.74 sq. m for 1,220-mm-wide by 1,220-mm-high louver. b. Air Performance: Not more than 25-Pa static pressure drop at 3.6-m/s free area velocity.

(4)

Description of the HVAC system:

During concept stage, it is very difficult to say the cooling load figures. Based on area, and activity, the tentative idea have been established. The calculation is required after architecture specify the shape and dimension etc. The cooling load will be within 2000 –2500 TR.

The following areas have to be looked into:

1) Provision of thermal energy storage according to Local code –

MEW. The

space requirement should be complied with architecture in design stage . It is advisable to discuss with MEW after plotting the cooling load profile related to requirement of thermal energy storage during peak load operation.

2) Energy recovery unit related to reduction of fresh air load should

be considered according to MEW code.

Primary – secondary system can be adopted related to chilled water distribution. Natural draft cooling towers can be placed on roof of plant room. Suitable location of thermal storage should be considered either in basement and can be interfaced with Chilled water distribution system.

In office areas, under floor distribution system can be considered with floor mounted air conditioning modules and floor mounted air diffuser – active type, controlled by individual controller in master‐ slave principle.

In big areas like hall, AHU should be placed in a corner or roof and duct can run at high level either by Jet diffuser or suitable wall induction displacement diffusers. In special areas where glazing is obstructing to run duct in perimeter side wall, under‐floor duct with free standing recirculation air cooling unit can be considered. Suitable Energy Recovery unit related to energy saving according to ASHRAE 90.1 and MEW guideline code should be adopted and the placement may be considered on roof in co ordination with Architecture.

Computer Room Air‐Conditioning (CRAC) system shall be provided for accurate control of temperature and relative humidity within the IT/Sever facility rooms. Smoke ventilation system should be provided as per KFD regulations and NFPA standards. Stairs and lift wells should be pressurized mechanically by Fresh Air fans. Smoke ventilation should be provided through smoke extraction fans located at mechanical floors or on the roofs

Public Hall, Large volume area smoke evacuation will be provided by inducting fresh air at the ground floor level (with the assistance of automatic doors), and will be exhausted through smoke exhaust fans

Ait filter will be as per ASHRAE 52 or Eurovent 779 ‐2002 eqv. The MERV is the best measure.

(5)

Office area ‐ MERV – 9 (Pre‐ MERV 7, Bag – MERV ‐ 9) Prayer Hall – MERV 13. (Pre‐ 7, Bag – 13)

Smoking room ‐ MERV – 16 or better. ( pre‐ 7, bag ‐13, absolute‐ 16) . All fresh air fans shall be provided with washable 50 mm thick

(6)

3. MEW REQUIREMENTS

Kuwait airport is 10 km far from sea and a coastal region

6.1.1 Walls and

Roofs

Table 6.1 provides a list of the maximum allowable overall heat transfer coefficients (U) for variety of wall and roof constructions and their external color.

a) Exposed floor: Exposed floors in multistory apartment buildings or similar

constructions shall not have a U value of more than 0.568 W/(m2 .K) (0.1 Btu/(h.ft2 . °F)).

(7)

b) Columns and beam insulation: Columns and beams should be insulated in a manner similar to corresponding walls and roofs. Accordingly, their U values should not exceed 0.568 W/(m2 .K) (0.1 Btu/(h.ft2 .°F)) for the columns and 0.0398 W/ (m2.K) (0.07 Btu/(h.ft2. oF)) for the beam. In case the columns and beams are not insulated, this requirement shall be compensated for by additional insulation on walls/roofs.

c) Slab-On-Grade Insulation (for buildings without basements): It should be water resistant, laid horizontally on the slab at the inner side of external walls and extends a distance of 120 cm from the wall. The R value for the insulation material should not be less than R7 (1.4 m2 .K/W).

d) Below-Grade Wall Insulation: Below-Grade Wall shall have a rated R-value not less than the R-value of the Above-Grade Wall.

Note: The envelope components (Exterior Walls, Roofs and Floors) of unconditioned spaces connected to conditioned spaces shall have U-values similar to the

(8)
(9)

Water-cooled

chillers shall be used

for all projects in the

interior region of

Kuwait with total

operating plant capacity

of 500 RT and above, as

well as for all projects in

the coastal region

of Kuwait with total

operating plant capacity

of 1,000 RT and above

Projects

with partial

occupancy and cooling

load

capacity in

the range from 500 to 1000 RT in the coastal region shall use air cooled chillers. The system type (air or water cooled) shall be based on the diversified cooling load before applying partial cool storage. All buildings shall use a CRU (such as rotary-wheel, etc.) when:

1. The recoverable exhaust air quantity is equal to or more than 2,000 CFM (940 l/s) for all buildings in the coastal region,

2. The recoverable exhaust air quantity is equal to or more than 3,000 CFM (1410 l/s) for buildings in the interior region. The CRU shall have a minimum efficiency of 75% for all buildings in the coastal region as well as in buildings with high ventilation rates (buildings peaking at wet bulb prioritization) in the interior region. For toilets use heat pipe recovery ahu units

Thermal Storage

Cool storage (ice, water or eutectic) is encouraged and recommended for partially occupied buildings with plant production capacity of below 500 RT. However, for buildings with plant production capacity of 500 RT and above, it is mandatory to use a thermal storage system. The capacity of such system shall be able to provide at least 25% of the total plant production capacity for 4 hours during the peak load period from 12 pm – 4 pm with figure of merit (FOM) of 0.85 or above, (i.e., 0.25x4xX, where X is the plant production capacity after applying diversity). For governmental buildings, the cool storage capacity shall be able to provide at least

(10)

50% of the total plant production capacity for the same period. The consulting office shall provide a daily building load profile that forms the basis for his design strategy.

All air conditioned spaces shall have a minimum quantity of ventilation air that is the highest of the following values:

1. ASHRAE 62.1 Standard (Ventilation for Acceptable Indoor Air Quality) 2. 0.250 ACH for pressurization + exhaust air from kitchens, toilets and other areas.

References

Related documents

armigera to deltamethrin revealed a high resistance pattern in cowpea (resistance factor (RF) = 2340), cotton (RF varying from 12 to 516) and tomato (RF=85) farms which is a concern

Data were obtained from four sources: a chart review for information on cardiac risk factors and evidence of liver dis- ease and ongoing infectious disease; results from the

Quality: We measure quality (Q in our formal model) by observing the average number of citations received by a scientist for all the papers he or she published in a given

In addition to treatment plans tailored to the patient's needs, the Cancer Program at Southern Ocean County Hospital also utilizes a multidisciplinary team approach to patient care

Feminist research paradigms, the history of breast cancer, the intersection of physical, psychological and social realms of experience of breast cancer and feminist approaches

Proprietary Schools are referred to as those classified nonpublic, which sell or offer for sale mostly post- secondary instruction which leads to an occupation..

Results suggest that the probability of under-educated employment is higher among low skilled recent migrants and that the over-education risk is higher among high skilled