VICINITY MAP
PROJECT DATA
316 LOTTIE STREET, BELLINGHAM, WA 98225
CENTRAL SHOPS VEHICLE EXHAUST SYSTEMS UPGRADES - NORTH END
WHATCOM COUNTY FACILITIES
901 WEST SMITH ROAD
KEY PLAN
PROJECT TEAM
SHEET INDEX
09-28-2018
BID SET
AREA OF WORK
OWNER:
WHATCOM COUNTY, WASHINGTON
OWNER REPRESENTATIVE:
ERIC EAMES
FACILITIES TECHNICAL SPECIALIST WHATCOM COUNTY FACILITIES MGMT. 316 LOTTIE STREET
BELLINGHAM, WA. 98225 360-778-5360
MECHANICAL ENGINEER:
BOGARD ENGINEERS, P.S. 22121 17TH AVE SE, SUITE 111 BOTHELL, WA 98021
PHONE: 425.415.6100 FAX: 425.415.6117
MECHANICAL:
M-0 COVER SHEET
M-1 MECHANICAL LEGEND, NOTES AND SCHEDULES M-2 MECHANICAL DEMOLITION PLAN
M-3 MECHANICAL FLOOR PLAN M-4 MECHANICAL MEZZANINE PLANS M-5 MECHANICAL SECTIONS AND DETAILS
PROJECT ADDRESS: 901 W. SMITH RD BELLINGHAM, WA. 98225 PROPERTY: PROPERTY ID: LEGAL DESCRIPTION: NA NA
LAND USE CODE: NA
JURISDICTION: WHATCOM COUNTY
PROJECT DISCRIPTION:
MODIFICATIONS TO THE VEHICLE EXHAUST SYSTEMS.
GEOGRAPHIC ID: NA
WHATCOM COUNTY CENTRAL SHOPS
N
N
SITE
W. SMITH RD
I-5
architect manager drawn by checked by project numberproject issue date:
Whatcom County
Administrative Services
FACILITIES MANAGEMENT 316 Lottie Street Bellingham, WA 98225 (360) 778-536010-04-2018
CENTRAL SHOPS
901 W. SMITH ROAD
BELLINGHAM, WASHINGTON
WHATCOM COUNTY
revisions
no. description date
BID SET
3 7 62 2 ST ERED I T G N I H S A W A L ENGI O B E F O SI G ON ER R RO E P E L AT TS FE R E S D N O G NE A WB
OGARDE
NGINEERS PSMechanical Engineering Consultants
22121 17th Avenue SE, Suite 111 Bothell, Washington 98021
Phone: 425-415-6100 Fax: 425-415-6117 e-mail: [email protected]
VEHICLE EXHAUST SYSTEM UPGRADES - NORTH END
M-0
JK LWB
EQUIPMENT
A. UPSTREAM OF HOSE REELS +6.0" A
1 GRILLE MARK 300 CFM 24x12 RG DETAIL REFERENCE SECTION REFERENCE 00 M 20"Ø 20x12 T S C
ENERGY CODE NOTES
GENERAL NOTES
PROVIDE CONICAL SPIN-IN FITTINGS FOR ALL 90 DEGREE ROUND DUCT BRANCHES FROM RECTANGULAR SUPPLY DUCTWORK. DO NOT USE STRAIGHT FITTINGS.
THE MECHANICAL CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BEGINNING WORK IN ORDER TO OBSERVE EXISTING CONDITIONS. VERIFY EXACT SIZE, LOCATION AND CONDITION OF ALL EXISTING SYSTEMS, DUCTS PIPES, UTILITIES AND BUILDING STRUCTURE.
COORDINATE INSTALLATION OF MECHANICAL SYSTEMS WITH BUILDING STRUCTURE AND ALL OTHER TRADES.
MECHANICAL DRAWINGS ARE DIAGRAMMATIC IN NATURE, AND DO NOT NECESSARILY REFLECT EVERY REQUIRED OFF-SET, FITTING OR ACCESSORY.
INSTALL SEISMIC BRACING FOR ALL DUCTWORK, EQUIPMENT AND PIPING PER I.B.C. REQUIREMENTS.
PROVIDE GRAVITY BACKDRAFT AND MOTORIZED DAMPERS WHERE SHOWN ON DRAWINGS AND/OR SPECIFIED, THAT WILL CLOSE AUTOMATICALLY WHEN IT'S RESPECTIVE SYSTEM IS OFF, OR UPON POWER FAILURE. SEE SPECIFICATIONS.
DUCTWORK TRANSVERSE SEAMS SHALL BE SEALED IN ACCORDANCE WITH SMACNA DUCT METAL AND FLEXIBLE CONSTRUCTION STANDARDS, MOST RECENT EDITION. 4. DUCTWORK STATIC PRESSURE AND SEAL CLASS, BASED UPON SMACNA:
3. REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES, ETC. FLOOR PLANS AND SECTIONS INDICATE EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY. PROVIDE PIPING SHOP DRAWINGS COORDINATED WITH OTHER TRADES. REFER TO SPEC. FOR ADDITIONAL SHOP DRAWING REQUIREMENTS.
2. PROVIDE A VOLUME DAMPER FOR EACH EXHAUST OPENING, AND ELSEWHERE AS NOTED ON DRAWINGS OR IN SPECIFICATIONS.
DUCT
SYSTEM PRESSURESTATIC SEALCLASS
VEHICLE EXHAUST HOSE REEL SCHEDULE
DRAWING INDEX
COVER SHEET
MECHANICAL LEGEND, NOTES AND SCHEDULES MECHANICAL DEMOLITION FLOOR PLAN
MECHANICAL FLOOR PLAN
MECHANICAL MEZZANINE PLANS AND DETAILS MECHANICAL SECTIONS AND DETAILS
M-5 M-4 M-3 M-2 M-1 M-0 DWG. DESCRIPTION REMARKS MOUNTING HEIGHT, FT. MOTORIZED DAMPER STATIC PRESSURE DROP, IN. HOSE LENGTH, FT. HOSE SIZE, IN. MODEL CFM MARK
HR-1 600 AQC MAXIREEL 6 30 2 YES 16
HR-2 HR-3 HR-4 HR-5
HR-6 15
600 AQC MAXIREEL 30 2 YES
600 AQC MAXIREEL 30 2 YES
600 AQC MAXIREEL 30 2 YES
600 AQC MAXIREEL 30 2 YES
600 AQC MAXIREEL 30 2 YES
S 6 6 6 6 6 16 16 16 16 DRAWING ON WHICH SECTION IS LOCATED DETAIL NUMBER DESIGN CFM RG = RETURN GRILLE EG = EXHAUST GRILLE SG = SUPPLY GRILLE TG = TRANSFER GRILLE TYPE GRILLE WIDTH GRILLE LENGTH SECTION NUMBER FLAG NOTE REVISION IDENTIFICATION DRAWING ON WHICH SECTION IS LOCATED RECTANGULAR DUCT (INSIDE DIMENSION)
ROUND DUCT FLEX CONNECTION
90° CONICAL SPIN-IN FITTING TURNING VANE VOLUME DAMPER MOTORIZED DAMPER BACKDRAFT DAMPER THERMOSTAT SENSOR CO2 SENSOR AIR FILTER FAN SWITCH CEILING GRILLE CLEANOUT COEFFICIENT OF PERFORMANCE CONTINUATION DRAWING EXISTING ITEMS EXHAUST AIR
ENTERING AIR TEMP.
ENERGY EFFICIENCY RATING EFFICIENCY / EFFICIENT ELECTRICAL
FLOOR CLEANOUT
INTEGRATED PART LOAD VALUE INVERT ELEVATION
LEAVING AIR TEMP. LINEAR FOOT MECHANICAL CONTRACTOR MECHANICAL NON POTABLE OUTSIDE AIR POINT OF CONNECTION RETURN / RELIEF GRILLE SUPPLY AIR
SENSOR
SUPPLY GRILLE THERMOSTAT TYPICAL
UNLESS OTHERWISE NOTED VENT
VENT THROUGH ROOF WASTE WALL CLEANOUT CG CO COP CONT. DWG (E) EA EAT EER EFF ELECT. FCO IPLV I.E. LAT LF MC MECH. NP OSA P.O.C. RG SA SENS SG T'STAT TYP U.O.N. V VTR W WCO
1
M2
A
M-2
architect manager drawn by checked by project numberproject issue date: 10-04-2018
CENTRAL SHOPS
901 W. SMITH ROAD
BELLINGHAM, WASHINGTON
WHATCOM COUNTY
revisions
no. description date
BID SET
3 7 62 2 ST ERED I T G N I H S A W AL ENGI O B E F O SI G ON ER R RO E P E L AT TS FE R E S D N O G NE A WB
OGARDE
NGINEERS PSMechanical Engineering Consultants
22121 17th Avenue SE, Suite 111 Bothell, Washington 98021
Phone: 425-415-6100 Fax: 425-415-6117 e-mail: [email protected]
VEHICLE EXHAUST SYSTEM UPGRADES - NORTH END
FOR CONT. SEE 2 M-4 (E)12"Ø (E)10"Ø (E)8"Ø DEMO BRANCH
DUCT AND HOSE
DEMO BRANCH DUCT AND HOSE
DISCONNECT BRANCH DUCT DISCONNECT AND CAP BRANCH
DUCT AT MAIN DUCT. DEMO BRANCH DUCT AND BLAST GATE.
DISCONNECT BRANCH DUCT
DISCONNECT BRANCH DUCT
DEMO BRANCH DUCT AND HOSE
DEMO BRANCH DUCT AND HOSE DISCONNECT BRANCH DUCT FROM MAIN DUCT AND DEMO BRANCH DUCT, SUPPORT ARM AND HOSE
SCALE:
M-2
1
MECHANICAL DEMOLITION FLOOR PLAN
1/8" = 1'-0"
N
architect manager drawn by checked by project numberproject issue date:
Whatcom County
Administrative Services
FACILITIES MANAGEMENT 316 Lottie Street Bellingham, WA 98225 (360) 778-536010-04-2018
CENTRAL SHOPS
901 W. SMITH ROAD
BELLINGHAM, WASHINGTON
WHATCOM COUNTY
revisions
no. description date
BID SET
3 7 62 2 ST ERED I T G N I H S A W A L ENGI O B E F O SI G ON ER R RO E P E L AT TS FE R E S D N O G NE A WB
OGARDE
NGINEERS PSMechanical Engineering Consultants
22121 17th Avenue SE, Suite 111 Bothell, Washington 98021
Phone: 425-415-6100 Fax: 425-415-6117 e-mail: [email protected]
VEHICLE EXHAUST SYSTEM UPGRADES - NORTH END
FOR CONT.
SEE 2
M-4
(E)12" Ø VEHICLE EXHAUST (E)10" Ø
(E)8"Ø
(E)5"Ø TO EXT. ARM AND WELDING
HOOD, SEE DETAIL 6" Ø 6" Ø 6" Ø 6" Ø 6" Ø 6" Ø HR-1 HR-2 HR-5 HR-6 HR-4 HR-3 P.O.C. P.O.C. P.O.C. P.O.C. (E)12"Ø 8" Ø P.O.C. (E)5" Ø SEE DETAIL 1 M-5 S S S S S S
VEHICLE EXHAUST FAN SWITCH ON PENDANT MOUNTED CORD, TYPICAL ALL HOSE REELS
2
M-5
S SEE ENLARGED PLAN 3 M-5 SCALE:M-3
1
MECHANICAL FLOOR PLAN
1/8" = 1'-0"
N
architect manager drawn by checked by project numberproject issue date: 10-04-2018
CENTRAL SHOPS
901 W. SMITH ROAD
BELLINGHAM, WASHINGTON
WHATCOM COUNTY
revisions
no. description date
BID SET
3 7 62 2 ST ERED I A L ENGI E SI G ON ER RO P FESR NEB
OGARDE
NGINEERS PSMechanical Engineering Consultants
22121 17th Avenue SE, Suite 111 Bothell, Washington 98021
Phone: 425-415-6100 Fax: 425-415-6117 e-mail: [email protected]
VEHICLE EXHAUST SYSTEM UPGRADES - NORTH END
M-3
JK LWB
2 M-4
(E)18" Ø
(E)12" Ø EXHAUST DUCT
SEE SEE M-3 FOR CONT. (E)18"Ø (E)12" Ø EF-1 (E)12" Ø EF-2 (E) (E) (E)VFD DRIVES (E)EXHAUST DUCT UP THROUGH ROOF
VEHICLE EXHAUST DUCT
EA
SPP-2
EF-2
H
EA
HOSE REELS
DIFFERENTIAL
PRESSURE
SENSOR
2
ALARM
SENSOR
VFD-1
S
PENDANT MOUNTED SWITCHES
ADJACENT TO WELDING HOOD,
FLEX DUCT W/ SUPPORT BRACKET
AND EACH HOSE REEL.
S
SCALE:
M-4
1
MECHANICAL MEZZANINE PLAN
1/8" = 1'-0"
N
SCALE:
M-4
2
ENLARGED PARTIAL MEZZANINE PLAN
1/2" = 1'-0"
N
M-4
3
EF-2 CONTROL DIAGRAM
LOCATION: MECH MEZZANINE SERVES: NORTH HOSE REELS
architect manager drawn by checked by project number
project issue date:
Whatcom County
Administrative Services
FACILITIES MANAGEMENT 316 Lottie Street Bellingham, WA 98225 (360) 778-536010-04-2018
CENTRAL SHOPS
901 W. SMITH ROAD
BELLINGHAM, WASHINGTON
WHATCOM COUNTY
revisions
no. description date
BID SET
3 7 62 2 ST ERED I T G N I H S A W AL ENGI O B E F O SI G ON ER R RO E P E L AT TS FE R E S D N O G NE A WB
OGARDE
NGINEERS PSMechanical Engineering Consultants
22121 17th Avenue SE, Suite 111 Bothell, Washington 98021
Phone: 425-415-6100 Fax: 425-415-6117 e-mail: [email protected]
VEHICLE EXHAUST SYSTEM UPGRADES - NORTH END
6" Ø 8" Ø HR-5 (E)12" Ø P.O.C. (E)12" Ø MOUNT CENTERLINE OF HOSE REEL @16' ABOVE FLOOR HR-6 6" Ø (E)5" Ø P.O.C. P.O.C. MOUNT CENTERLINE OF HOSE REEL @15' ABOVE FLOOR VOLUME DAMPER, TYP.
NOTE: SUPPORT HOSE REELS FROM STEEL BEAMS OR
PURLINS WITH THREADED ROD SUPPORTS, TYPICAL.
HOSE REEL BRACKET
STEEL GIRDER
ATTACH HOSE REEL TO STEEL FRAMING WITH UNISTRUT 7'-0" 8'-0" 4'-0" WELDING HOOD LIGHTS (E)WELDING TABLE (E)LEGS DUCT COUNTER WEIGHT
BASE PLATE, BOLT SUPPORT ARM TO EXISTING STEEL COLUMN.
8"x10" STEEL COLUMN FLOOR P.O.C. TO (E)DUCT 6"ø EXHAUST
DUCT NEW 6"ø FLEX
WELDING EXHAUST DUCT WITH NOZZLE PROVIDE 20' OF NEW FLEX WELDING EXHAUST HOSE. CONNECT TO (E)6"ø DUCT.
6"ø EXHAUST DUCT TO HR-3 P.O.C. TO
(E)DUCT P.O.C. TO
(E)DUCT (E)10"ø EXHAUST
DUCT 6"ø EXHAUST
DUCT TO HR-4
(E)6"ø EXHAUST DUCT AND ADJUSTABLE SUPPORT BRACKET TRANSITION 12"ø EXHAUST DUCT TO HOOD (E)6"ø (E)SUPPORT ARM 8'-4" WELDING EXHAUST DUCT ELBOW SEE DETAIL
4
M-5
CABLE HINGE PULLEY PULLEY ATTACH CABLES TO HOODSTEEL SUPPORT ARM
M INTERLOCK WITH
HOOD FAN SWITCH MOTORIZED DAMPER 6"ø EXHAUST DUCT TO HR-3 6"ø EXH. DUCT TO HR-4 WELDING HOOD
5
C
2
M-5
12"ø EXH. DUCT TO HOOD P.O.C. TO (E)10"ø EXH. DUCT(E)10"ø EXH. DUCT (E)6"ø P.O.C. TO (E)6"ø EXH. DUCT CAP (E)BRANCH DUCT PROVIDE 20' OF NEW
FLEX HOSE. CONNECT TO (E)6"ø DUCT
COLUMN (E)8"ø DUCT
(E)6"ø EXH. DUCT AND ADJ. SUPPORT BRACKET (E)6"ø EXHAUST DUCT
ON SUPPORT BRACKET P.O.C. TO (E)6"ø 18"ø 2-1/2" 60" 72"
5-1/2"ø FOR INSERT INTO NZ-06SD TAILPIPE ADAPTOR 6"ø
"VICEGRIP" STYLE CLAMP
WELDING FLEX HOSE
ABRASION RESISTANT POLYURETHANE CUFF SCALE:
M-5
1
VEHICLE HOSE REEL MOUNTING DETAIL
NONE
SCALE:
M-5
2
WELDING HOOD DETAIL
1/2" = 1'-0" SCALE:
M-5
3
ENLARGED PLAN
1/4" = 1'-0" SCALE:M-5
4
NOZZEL ADAPTOR DETAIL
NOT TO SCALE SCALE:
M-5
A
SECTION A
1/4" = 1'-0" architect manager drawn by checked by project numberproject issue date:
Whatcom County
Administrative Services
FACILITIES MANAGEMENT 316 Lottie Street Bellingham, WA 98225 (360) 778-536010-04-2018
CENTRAL SHOPS
901 W. SMITH ROAD
BELLINGHAM, WASHINGTON
WHATCOM COUNTY
revisions
no. description date
BID SET
3 7 62 2 ST ERED I T G N I H S A W A L ENGI O B E F O SI G ON ER R RO E P E L AT TS FE R E S D N O G NE A WB
OGARDE
NGINEERS PSMechanical Engineering Consultants
22121 17th Avenue SE, Suite 111 Bothell, Washington 98021
Phone: 425-415-6100 Fax: 425-415-6117 e-mail: [email protected]