Triconex Corporation
Triconex Corporation
System
System
Grounding
Grounding
TRICON Hardware
TRICON Hardware
Electrical systems must be connected to ground in order to:
Protect personnel from electric shock.Protect personnel from electric shock.
Protect equipment from damage.Protect equipment from damage.
Protect the site from lightning damage.Protect the site from lightning damage.
Ensure the reliability and electrical integrity of the Ensure the reliability and electrical integrity of the system.
system.
What is Ground?
What is Ground?
It is a connection to the earth, or to something used It is a connection to the earth, or to something used in place of the earth.
in place of the earth.
Why do we require a ground?
Why do we require a ground?
The ground is required as it is used to establish and The ground is required as it is used to establish and maintain the potential of the earth.
TRICON System typically utilizes three (3) separate ground references:
AC safety or chassis ground (protective earth
ground) - TRICON Chassis Ground
Signal or Instrument (or Master Reference) ground
- TRICON Signal Ground (TSG)
AC Safety ground is applied to each chassis
Signal or Instrument (or Master Reference)
ground is the field loop power supply return
Field loop shield ground is for referencing
instrument loop wiring shields typically to instrument or Master Reference ground
TRICON TRICON Main Main Chassis Chassis
AC Safety Ground Bar
TRICON TRICON Expansion Expansion Chassis Chassis Each chassis
Each chassis MUST BEMUST BE connected to AC Safety
connected to AC Safety
ground to ensure personnel
ground to ensure personnel
safety! safety! TRICON TRICON Expansion Expansion Chassis Chassis
TRICON
TRICON
Chassis
Chassis
AC Safety Ground Bar
AC Safety Ground Bar
Each V5
Each V5 -- V8 Digital I/O V8 Digital I/O Term Panel
Term Panel MUST BEMUST BE connected to AC Safety
connected to AC Safety
ground to ensure personnel
ground to ensure personnel
safety!
safety!
Digital Input Term
AC Safety Ground MUST be applied to each
chassis (Main, Expansion & RXM) regardless of floating or non-floating systems.
AC Safety Ground MUST be applied to each V5
-V8 DI/DO Term Panel. (floating/non-floating) as the V5 - V8 I/O ELCO cables do not have a
connecting wire to chassis. Connection to AC Safety Ground for V9 Terms are not required.
AC Safety Ground MUST NOT be applied to
AC Safety Ground Analog System
AC Safety Ground Analog System
AC Safety AC Safety TRICON TRICON Chassis Chassis Isolated +24 Isolated +24 Power Supply Power Supply V+ V+ VV-
-Analog Input Term
Analog Input Term
Once V
Once V-- is connected to a is connected to a AI/AO Term Panel, it is
AI/AO Term Panel, it is
connected to the internal
connected to the internal
TRICON Signal Ground
TRICON Signal Ground
(TSG).
(TSG).
If the TRICON RC Clip is
If the TRICON RC Clip is
installed
installed, TSG is connected , TSG is connected to AC Safety Ground via a
to AC Safety Ground via a
parallel resistor/capacitor parallel resistor/capacitor circuit. circuit. TSG V TSG V-- is referenced to AC is referenced to AC Safety within
Safety within millivoltsmillivolts range.
Dedicated Ground Analog System
Dedicated Ground Analog System
If the TRICON RC Clip is
If the TRICON RC Clip is
removed, TSG is removed, TSG is disconnected from AC disconnected from AC Safety Ground. Safety Ground. TSG
TSG MUST BEMUST BE connected connected to a dedicated ground.
to a dedicated ground.
One connection is required
One connection is required
and is completed at the
and is completed at the
Main Chassis location
Main Chassis location & any & any remote RXM locations.
remote RXM locations.
The dedicated ground is
The dedicated ground is
typically considered a quiet
typically considered a quiet
earth ground or DCS
earth ground or DCS
Master Reference Ground.
Master Reference Ground.
Isolated +24 Isolated +24 Power Supply Power Supply V+ V+ VV- -TRICON TRICON Chassis Chassis
Analog Input Terms
Analog Input Terms
Dedicated Ground
Dedicated Ground
AC Safety
Dedicated Ground Analog System
Dedicated Ground Analog System
AC Safety
AC Safety
Dedicated Ground
Dedicated Ground
Field loop wiring shields
Field loop wiring shields
are typically connected to
are typically connected to
TRICON Term Panels.
TRICON Term Panels.
The TRICON Term Panel
The TRICON Term Panel
shield ground screws
shield ground screws
should be tied to
should be tied to
instrument ground or the
instrument ground or the
dedicated ground. dedicated ground. TRICON TRICON Chassis Chassis Isolated +24 Isolated +24 Power Supply Power Supply V+ V+ VV-
-Analog Input Terms
TRIOCN RC network
TRIOCN RC network
V5 V5 -- V8 SystemV8 System #8300/#8301/#8305/#8306 TRICON Power #8300/#8301/#8305/#8306 TRICON PowerModules are equipped with a simple RC network
Modules are equipped with a simple RC network
connected between the signal and chassis ground
connected between the signal and chassis ground
#8300A/#8301A/#8305A/#8306A TRICON Power
#8300A/#8301A/#8305A/#8306A TRICON Power
Modules allows one to disconnect the internal RC
Modules allows one to disconnect the internal RC
network and directly access the TRICON signal
network and directly access the TRICON signal
ground.
TRIOCN RC network
TRIOCN RC network
V9 System
V9 System
The RC network is external to the TRICON Power
The RC network is external to the TRICON Power
Modules.
TRIOCN RC network
TRIOCN RC network
Stand
Stand--Alone DigitalAlone Digital--Only SystemOnly System
Connecting the RC jumper will be sufficient
Stand
Stand--Alone AnalogAlone Analog--Only or Mixed Only or Mixed Analog/Digital System
Analog/Digital System
TRIOCN RC network
TRIOCN RC network
Integration with DCS
Integration with DCS
If TRICON is a stand-alone digital-only system, connection of the RC jumper (at the power module for V5 to V8) is sufficient
If TRICON is a stand-alone analog-only or mixed analog/digital system, a single connection must be made between TRICON signal ground and the common tie point of the DCS signal ground
A TriStation Link with model #410x ICM/EICM may cause a problem if the TriStation PC does not share the safety ground connection as the TRICON.
Exercise caution especially if the TRICON and the DCS are physically separated or reside in separate buildings. The same problem could also occur with any RS232 connection including any MODBUS connections.
Connecting two pieces of equipment located in Connecting two pieces of equipment located in
different buildings
different buildings
TRICON I/O bus RSTRICON I/O bus RS--485 connection 485 connection
extended beyond the control room.
extended beyond the control room.
Current flow via the Shield ground which is Current flow via the Shield ground which is
not held at a constant, non
not held at a constant, non--varying voltage.varying voltage.
Implementing a “floating” ground system.Implementing a “floating” ground system.
In most industrial control systems, the return side In most industrial control systems, the return side of the field power supply is directly connected to
of the field power supply is directly connected to
earth.
Emergency Shutdown (ESD) and Fire & Gas
Emergency Shutdown (ESD) and Fire & Gas
detection applications very often require the
detection applications very often require the
I/O system to be "floating".
I/O system to be "floating".
In a floating ground system, the field power
In a floating ground system, the field power
supply is not directly connected to earth
supply is not directly connected to earth
ground , but is connected to an artificial
ground , but is connected to an artificial
ground which can be created with a high
ground which can be created with a high-
-impedance resistor voltage divider.
24VDC POWER SUPPLY UNIT + -24VDC POWER SUPPLY UNIT + -EARTH GROUND TO ETP POWER 24VDC 0VDC R1 R2
The main use of a floating ground system with a
The main use of a floating ground system with a
suitable Ground Fault Detector allows for the
suitable Ground Fault Detector allows for the
implementation of a "no
implementation of a "no--fail system".fail system".
A “no
A “no--fail system” is faultfail system” is fault--tolerant of any tolerant of any singlesingle field
field--wiring fault to earth ground.wiring fault to earth ground.
These ground faults should be detectable by
These ground faults should be detectable by
the GFD, and if repaired in a timely manner, a
the GFD, and if repaired in a timely manner, a
shutdown or disturbance to the application
shutdown or disturbance to the application
should be avoided.
The main purpose of a GFD is to detect the The main purpose of a GFD is to detect the
presence of an unintentional connection to
presence of an unintentional connection to
earth ground, other than that of the fixed
earth ground, other than that of the fixed
high
high--impedance connection.impedance connection.
A GFD should provide some means of alarming A GFD should provide some means of alarming
upon detecting an ground fault.
The HOLEC GFD has a sensitivity of 20mA
The HOLEC GFD has a sensitivity of 20mA
minimum (between +
minimum (between +veve and and --veve), when used with ), when used with
an external 1.2k
an external 1.2k
Ω
resistor divider in 24VDC resistor divider in 24VDCapplications. applications. 24VDC POWER SUPPLY UNIT + -24VDC POWER SUPPLY UNIT + -EARTH GROUND HOLEC + -R1 R2
It is common to install multiple
It is common to install multiple GFDsGFDs in a in a
system, either one per Marshalling
system, either one per Marshalling
Cabinet or one per termination panel.
Cabinet or one per termination panel.
After a ground fault has been detected,
After a ground fault has been detected,
only the field wiring of the points
only the field wiring of the points
attached to the alarmed GFD needs to be
attached to the alarmed GFD needs to be
searched for the earth short.
Ground Fault Detection with D.I. Module
Ground Fault Detection with D.I. Module
EARTH GROUND R1 R2 HOLEC 24VDC 0VDC PS+ PS-+ -DI ETP DI MODULE
Ground Fault Detection with D.I. Module
Ground Fault Detection with D.I. Module
The following limitations apply to the use
The following limitations apply to the use
of
of GFDsGFDs with digital inputswith digital inputs::
A GFD always detects ground faults on A GFD always detects ground faults on
the positive side of the contact.
the positive side of the contact.
A GFD always detects ground faults on A GFD always detects ground faults on
the negative side of the contact when the
the negative side of the contact when the
contact is closed. When the contact is
contact is closed. When the contact is
open, the GFD might not detect the fault.
Ground Fault Detection with D.I. Module
Ground Fault Detection with D.I. Module
When the contact is open, the impedance When the contact is open, the impedance
of the input circuitry is in series with the
of the input circuitry is in series with the
fault impedance.
fault impedance.
If the sum of the impedances exceeds If the sum of the impedances exceeds
the sensitivity of the GFD, then the GFD
the sensitivity of the GFD, then the GFD
might not detect the fault.
Ground Fault Detection with D.O. Module
Ground Fault Detection with D.O. Module
EARTH GROUND R1 R2 HOLEC 24VDC 0VDC PS+ PS- + -DO ETP FROM DO MODULE
Ground Fault Detection with D.O. Module
Ground Fault Detection with D.O. Module
The following limitations apply to the use
The following limitations apply to the use
of
of GFDsGFDs with digital outputs:with digital outputs:
A GFD always detects ground faults on A GFD always detects ground faults on
the negative side of the load.
the negative side of the load.
A GFD always detects ground faults on A GFD always detects ground faults on
the positive side of the load when the
the positive side of the load when the
load is energized. When de
load is energized. When de--energized, a energized, a
GFD might not detect the fault.
Ground Fault Detection with D.O. Module
Ground Fault Detection with D.O. Module
When deWhen de--energized, the impedance of the energized, the impedance of the
load is in series with the fault impedance.
load is in series with the fault impedance.
If the sum of the impedances exceeds If the sum of the impedances exceeds
the sensitivity of the GFD, then the GFD
the sensitivity of the GFD, then the GFD
might not detect the fault.
Ground Fault Detection with A.I. Module
Ground Fault Detection with A.I. Module
EARTH GROUND R1 R2 HOLEC 24VDC 0VDC PS+ PS-+ -AI ETP Tx 250 180
Ground Fault Detection with A.I. Module
Ground Fault Detection with A.I. Module
From test results and the electrical
From test results and the electrical
circuit analysis, we confirmed that the
circuit analysis, we confirmed that the
accuracy degradation in the presence of a
accuracy degradation in the presence of a
ground fault is inherent in any 4
ground fault is inherent in any 4--20mA 20mA
instumentation
TRICONEX
TRICONEX
Your supplier for all
Your supplier for all
your Safety and Critical
your Safety and Critical
Control Needs
Control Needs
Defects
Down Time
False Trips
BACKPLANE 8-POINT ANALOG OUTPUT MODULE
P WRA (22A) RTN (22E) P WRB (24A) CABLE Selector Logic DAC TERMINATION PANEL RTN (24E) OUT1 (2A) RTN1 (2E) Selector Logic DAC Selector Logic DAC Loop powe r Curre nt loopba ck Curre nt loopba ck Curre nt loopba ck A B C
32-POINT ANALOG INPUT MODULES BACKPLANE CABLE to s pa re TERMINATION PANEL
Is ola tion/filte ring
ADC Amp 1 32 Mux Hi-Ref Low-Re f ADC Amp 1 32 Mux Hi-Ref Low-Re f ADC Amp 1 32 Mux Hi-Ref Low-Re f P S 1 P S 2 P S 1 P S 2 to othe r points 180 ohms Note 3
Types of Power Utility Power Mains Power UPS Clean Floating AC / DC
Types of Earth Connection
Clean Earth Dirty Earth Utility Earth Low noise System Computer
Basically on two types of Ground :-a) AC - dirty b) DC - clean System earth Instrument earth EMC Electromagnetic Compatibility
-> Started by the military application 15 yrs ago
Use 3 core power cables for optimal line filtering
Power source is reference to earth
Floating power contains much more noise than earth reference Floating power needs isolation transformer
Floating power may drift to any common mode potential Line filtering requires earth connection
Impedance if 3 core power is 100 ohms I/A designed by National Electrical Code
Normal and Common mode signals by : potential equalisation
Galvanic isolation Shielding
Enclosures
GROUNDING the TRICON GROUNDING the TRICON
Expansion Chassis
(Protective Earth)
AC SAFETY GROUND
1/4" Bolt on left side of each chassis Main Chassis
Expansion Chassis
AC Safety Ground