• No results found

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

N/A
N/A
Protected

Academic year: 2021

Share "SECTION ( ) FIRE DETECTION AND ALARM SYSTEM"

Copied!
7
0
0

Loading.... (view fulltext now)

Full text

(1)
(2)
(3)
(4)
(5)
(6)
(7)

References

Related documents

Designer shall include in his/her bid package for the Contractor to fully coordinate design, equipment, devices, installation, wiring and connection of all fire alarm systems with

Audio/Visual and Visual only alarm signals shown on the Drawings to be ceiling mounted in areas with open structure (no suspended ceiling) shall be furnished by this contractor

System Expansion: Design the control units and enclosures so that the system can be expanded in the future (to include the addition of twenty percent more alarm initiating,

Provide the following common control switches and indicators: Detection Signal Operated LED, Common Trouble LED, Power ON LED, Enable Zone LED, Enable Zone Disconnect Switch and

Provide a signed letter and a notarized statement on the manufacturer’s letterhead stating that each analog addressable data communications circuit will support one hundred

programmable Notification circuit shall also be capable of providing auxiliary power when programmed as such. The control panel must have a built in annunciator with three

1. Steel, satin black, baked enamel cabinet with indicator viewing window, hinged door with cylinder lock and dead front construction when the outer door is open. System

Waterflow Detection: An alarm from a waterflow detection device shall activate the appropriate alarm message on the main panel display; turn on all programmed notification