Finger safe up to IP2
60 to 1000 Amp conductors in Standard or
Medium Heat cover
Cover shaped to shed water and dust
Horizontal conductors with contact from
underside
SAFELEC
I N S U L A T E D C O N D U C T O R B A R S
SAFELEC 2:
Technical Data
Galvanised Steel Conductor Bars; Expansion Sections Copper Conductor Bars; Expansion Sections
Aluminium / Stainless Steel Conductor Bars; Expansion Sections Joints
Jointing Compound
Powerfeeds: End Powerfeed; Joint Powerfeed Hanger Clamps: Standard Mount; Lateral Mount Hanger Clamps: with Insulator
Anchor Clamps End Caps Pick Up Guides
Isolation Sections: Galvanised Steel Bar; Copper Bar; Aluminium / Stainless Steel Bar Collectors
Collector Shoe + Holder Collector Bracket
Brackets: Single Sided Bracket; Double Sided Bracket; Web Bracket; Girder Clamp
System Dimensions Component Dimensions
Component Dimensions (Continued) Component Dimensions (Continued)
SAFELEC Insulated Conductor Bars
Typical Applications
Selection of Conductors
Technical Data
SAFELEC
ONTENTS
PAGE:
5 6 7 8 9 9 9 10 11 11 12 12 13 14 14 15 15 16 17 18 193
3
4
4
5
SAFELEC 3:
Technical DataCopper Conductor Bars; Expansion Sections
Aluminium / Stainless Steel Conductor Bars; Expansion Sections Joints
Jointing Compound
Powerfeeds: Joint Powerfeed
Powerfeed Sections: Copper Bar; Aluminium / Stainless Steel Bar Hanger Clamps: Standard Mount; with Insulator
Anchor Clamps End Caps
Isolation Sections: Copper Bar; Aluminium / Stainless Steel Bar Collectors
Collector Shoe + Holder Collector Bracket
Brackets: Single Sided Bracket; Double Sided Bracket; Web Bracket; Girder Clamp
System Dimensions Component Dimensions 20 21 22 23 23 23 24 25 25 26 26 27 27 28 28 29 30
20
V BAR:
Technical DataCopper Conductor Bars; Expansion Sections; Isolation Sections
Aluminium / Stainless Steel Conductor Bars; Expansion Sections; Isolation Sections Joints
Powerfeeds: Joint Powerfeed Hanger Clamps: with Insulator Anchor Clamps
End Caps Collectors
Collector Shoe + Holder Component Dimensions Notes page Notes page Notes page 31 32 33 34 34 34 34 34 35 35 36 37 38 39
31
C
SAFELEC
NSULATED
I
C
ONDUCTOR
B
ARS
SAFELEC
INSUL 8 supplies electrical power feed systems for moving machinery. Easy to install and maintain, the SAFELEC
range ensures a high level of reliability. It has been designed to meet the safety standards demanded in industry.
Advantages of conductor bars:
- Ability to feed several moving machines from the same conductor system
- Suitable for high amperage - Feed points can be placed at any location
- Compactness - Long system length possible - Suitable for both indoor and outdoor use
SAFELEC features:
- Easy installation, reduced and simple maintenance - Protection degree IP2, finger safe
- Insulating covers shaped to shed water and dust - Standard PVC cover for normal temperatures - Medium Heat cover available for high ambient temperatures
- Expansion sections not required for runs less than 150 m - Max travel speed: 200 m/min
SAFELEC complies with the following international standards: NFC 20-010, NFC 63-010, NFC 32-070, VDE 0470,
BSEN 60529, DIN 53438 Range of application:
Workshop cranes, iron and steel industry, railways, leisure industry, mines etc.
YPICAL
T
A
PPLICATIONS
Conveyor System
Multipole Feed System
Bridge Construction Crane Roller Coaster
ECHNICAL
T
D
ATA
SAFELEC
ELECTION OF
S
C
ONDUCTORS
L L/2 L/4 L/6 L/6 L/2 L/10 L/10The maximum permissible continuous current rating of the conductor bar depends on the duty factor of the cranes and the maximum ambient
temperature Ta. It can be established using the following formula:
3-Phase AC Single Phase AC Continuous current DC
Where:
³U: volt drop in Volts
³U%: volt drop in % of nominal voltage Un: nominal supply voltage in Volts
I: maximum current in Amps D: see opposite diagram R: resistance in Ohms per metre Z: impedance in Ohms per metre
³U = 3 x I x D x Z ³U = 2 x I x D x Z ³U = 2 x I x D x R Volt drop calculation ³U:
³U% = (³U x 100) / U
nEnd feed D = L
Feed point at L/10 and L/2 from each end
D = L/10 Feed point at L/6 from each end D = L/6
Feed point at each end D = L/4 Centre feed D = L/2 FACTOR “K” Standard cover
25
0C
1.000
0.905
0.798
0.674
0.775
0.707
0.632
1.118
1.011
0.892
0.754
0.866
0.791
0.707
1.291
1.168
1.030
0.870
1.000
0.913
0.816
1.581
1.430
1.261
1.066
1.225
1.118
1.000
2.236
2.023
1.784
1.508
1.732
1.581
1.414
35
0C
45
0C
55
0C
65
0C
75
0C
85
0C
Medium Heat cover Duty Ta 100% 80% 60% 40% 20%SAFELEC
ECHNICAL
T
D
ATA
MaterialPVC
180 KV/cm
10
11ž
>10
15ž/cm
84
0C
Self extinguishing
54%
1.5 g/cm
3BAYBLEND
240 KV/cm
>10
14ž
>10
16ž/cm
120
0C
Self extinguishing
24%
1.15 g/cm
3 Dielectric strength Surface resistivity Volume resistivity Vicat softening temperature(never expose PVC cover to temperatures in excess of 80oC)
Flame-test Oxygen index Specific density
CONDUCTOR BAR COVER STANDARD MEDIUM HEAT
CONDUCTOR BAR GALVANISED STEEL ALUMINIUM /
STAINLESS STEEL COPPER
Nominal current Cross sectional area Maximum system voltage (AC) (contact Insul-8 for other voltages) (DC) (contact Insul-8 for other voltages)
Resistance R (for DC) at 200C (ž/m)
Impedance Z (for AC) at 200C (ž/m)
Maximum allowable ambient temperature for 100% duty cycle
Bar length Support pitch Standard
Lateral
Minimum pitch centres Standard Lateral Expansion sections: not required for
runs less than
Minimum bending radius: (horizontal only)
60A 50mm2 1000V 1000V 0.003584 0.003604 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 100A 63mm2 1000V 1000V 0.002867 0.002891 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 125A 93mm2 1000V 1000V 0.001933 0.001968 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 160A 50mm2 1000V 1000V 0.000342 0.000364 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 250A 63mm2 1000V 1000V 0.000274 0.000300 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 400A 93mm2 1000V 1000V 0.000184 0.000221 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 200A 104mm2 1000V 1000V 0.000301 0.000325 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 315A 120mm2 1000V 1000V 0.000261 0.000288 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m 400A 156mm2 1000V 1000V 0.000199 0.000234 250C 4.5m 1500mm 1125mm 43mm 60mm 150m 1.5m
An accurate choice of conductors can be made when all the following information is known: - The type of current: single or three phase AC ; continuous (DC) - The maximum current power and duty cycle
- The allowable volt drop for the machines being supplied - The ambient temperature
- Environment (dusty, coastal, humid, acidic etc.)
SAFELEC
ALVANISED
G
S
TEEL
C
ONDUCTOR
B
ARS
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
XPANSION
E
S
ECTIONS
Expansion sections are required on all systems over 150m long. The maximum gap of the expansion
section is 50mm. The expansion section is 4.5m long and is installed in place of one length of conductor bar.
CURRENT RATING 60A 100A 125A
2.34
310002
310001
2.76
310102
310101
3.76
310202
Medium Heat cover
(grey)
310003
310056
310103
310156
310203
310256
310201
Earth Phase
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 60A 100A 125A
3.06
310008
310007
3.32
310108
310107
4.20
310208
Medium Heat cover
(grey)
310009
310058
310109
310158
310209
310258
310207
Earth Phase Standard Phase cover Standard Earth cover Medium Heat cover Expansion section 310007SAFELEC
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 160A 250A 400A
2.76
310302
310301
3.04
310402
310401
4.40
310502
Medium Heat cover
(grey)
310303
310356
310403
310456
310503
310556
310501
Earth Phase
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 160A 250A 400A
3.28
310308
310307
3.86
310408
310407
4.74
310508
Medium Heat cover
(grey)
310309
310358
310409
310458
310509
310558
310507
Earth Phase Standard Phase cover Standard Earthcover Medium Heat cover
ONDUCTOR
C
OPPER
C
B
ARS
XPANSION
E
S
ECTIONS
Expansion sections are required on all systems over 150m long.
The maximum gap of the expansion section is 50mm.
The expansion section is 4.5m long and is installed in place of one length of conductor bar.
Expansion section 310307
SAFELEC
LUMINIUM
A
/
S
TAINLESS
S
TEEL
C
ONDUCTOR
B
ARS
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
XPANSION
E
S
ECTIONS
Expansion sections are required on all systems over 150m long. The maximum gap of the expansion
section is 50mm. The expansion section is 4.5m long and is installed in place of one length of conductor bar.
CURRENT RATING 200A 315A 400A
2.12
310602
310601
2.18
310702
310701
2.50
399102
Medium Heat cover
(grey)
310603
310656
310703
310756
399103
399156
399101
Earth Phase
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 200A 315A 400A
3.23
310608
310607
3.43
310708
310707
3.80
399108
Medium Heat cover
(grey)
310609
310658
310709
310758
399109
399158
399107
Earth Phase Standard Phase cover Standard Earth cover Medium Heat cover Expansion section 3106070.049
0.044
0.032
0.2
SAFELEC
Standard Phase cover (orange)
JOINT COVER
Standard Earth cover (green)
Medium Heat cover Heavy Duty cover
Weight (Kg) green black
OINTS
J
OINTING
J
C
OMPOUND
310850
310851
310855
310856
0.027
399541
Steel JOINT Weight (Kg)310872
Copper310873
Aluminium310874
Heavy Duty Copper399549
0.225
JOINTING COMPOUND Weight (Kg)
310932
Steel Joint 310872 Aluminium Joint 310874 Copper Joint 310873Standard Phase cover 310850
Heavy Duty Copper Joint 399549
Heavy Duty Joint cover 399541
Jointing compound should be applied to the contact surfaces of the joint and bar at every joint on copper and aluminium systems. One tube is sufficient for over 300 connections.
OWERFEEDS: END POWERFEED
P
OWERFEEDS: JOINT POWERFEED
P
Powerfeed installed in place of an end cover.
Maximum cable connection size: 16mm2
0.037
UP TO 100A Weight (Kg)310911
End Powerfeed 310911 Standard cover (orange) Medium Heat cover(red)
Weight (Kg)
CURRENT RATING UP TO 60A UP TO 250A UP TO 400A
0.028
310066
310034
0.25
310913
310910
0.30
310915
310912
Powerfeed for connection of one or two flexible cables.310910 has single cable connection. 310912 has double cable connection. Powerfeed is usually installed in place of a joint.
Maximum cable connection size: 60A Joint Powerfeed
SAFELEC
Lateral mount hangers are supplied with 20mm spacers to provide clearance for joint covers. Maximum support spacing is 1.125m. Standard hangers are acetyl. Maximum support spacing is 1.5m.
ANGER
H
C
LAMPS: STANDARD MOUNT
ANGER
H
C
LAMPS: LATERAL MOUNT
POLYCARBONATE (RED) WEIGHT (Kg) STANDARD (BLACK) Single pole Two pole Three pole Four pole
310824
310882
310861
310821
0.03
0.04
0.05
0.057
310829
310899
310871
310857
POLYCARBONATE (RED) WEIGHT (Kg) STANDARD (BLACK) Single pole Two pole Three pole Four pole399431
399432
399433
399381
0.05
0.06
0.07
0.12
399434
399435
399436
399382
Four pole (without spacer)310835
310859
0.08
Single pole hanger 310824
Two pole hanger 310882
Four pole hanger 310821
Three pole hanger 310861
Single pole lateral mount hanger
399431
Four pole lateral mount hanger
SAFELEC
ANGER
H
C
LAMPS: WITH INSULATOR
NCHOR
A
C
LAMPS
WEIGHT (Kg) Single pole Single pole Single pole Single pole(Black)
(Red)
Stainless steel
Two part
0.10
0.10
0.106
0.08
Two pole
Two part
310918
310834
310827
399544
399627
0.174
Single pole hanger 310918
Two pole two part hanger
399627
Single pole two part hanger 399544 Stainless steel hanger with insulator 310827
In particularly dusty or humid environments, hangers with insulator should be used. WEIGHT (Kg) Standard With insulator Lateral mount Without top bolt (two required per anchor point)
0.06
0.12
0.10
0.05
310832
WEIGHT (Kg)Heavy duty anchor
399546
0.48
310969
399383
310831
Anchor clamp 310832 Anchor clamp without top bolt310831 Anchor clamp with insulator 310969 Heavy duty anchor clamp 399546
Anchor points are usually situated in the middle of a conductor system.
Additional anchor points are required for systems with expansion sections.
SAFELEC
Transfer caps are suitable for air gaps up to 10mm. Vertical tolerance 5mm Horizontal tolerance 2mm
ND
E
C
APS
WEIGHT (Kg)Steel / copper bar Aluminium bar Transfer cap
0.04
0.02
0.10
310892
310893
310951
+ _ + _End cap for steel / copper bar
310892
Transfer end cap
310951
Special collectors are required for systems where pick up guides are fitted.
ICK
P
U
P
G
UIDES
Four pole pick up guide 310929 WEIGHT (Kg) Two pole Single pole Three pole1.27
1.72
2.16
310920
399532
399502
Four pole310929
2.54
SAFELEC
Isolation sections provide electrical separation between adjacent sections of conductor bar.
Only for use in dry, clean conditions. The Isolation section is 4.5m long and is installed in place of one length of conductor bar.
It is recommended that Isolation sections are not fitted in earth conductors.
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 60A 100A 125A
2.71
310026
310025
3.16
310126
310125
4.19
310226
Medium Heat cover
(grey)
310027
310064
310127
310164
310227
310264
310225
earth phaseSOLATION
I
GALVANISED STEEL BAR
S
ECTIONS
COPPER BAR
ALUMINIUM / STAINLESS STEEL
Isolation section310025
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 160A 250A 400A
2.97
310326
310325
3.42
310426
310425
4.68
310526
Medium Heat cover
(grey)
310327
310364
310427
310464
310564
310527
310525
earth phase Isolation section 310325 Isolation section 310625Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 200A 315A 400A
2.4
310626
310625
2.6
310726
310725
2.9
399126
Medium Heat cover
(grey)
310627
310664
310727
310764
399127
399128
399125
earth phase
SAFELEC
The copper graphite shoe ensures electrical continuity, a smooth contact with the conductor bar and a good resistance to wear. 50A and 100A collectors are supplied
without cable. Stranded cable terminal clamps are
included. 250A collectors are supplied with
2 x 1m 35mm2 cable.
OLLECTORS
C
Weight (Kg)
CURRENT RATING 50A 100A 250A
0.38
399360
Phase0.8
310990
2.00
34956
399380
Earth - without deflector
399355
399373
Earth - right hand
399340
399372
Earth - left hand
399352
CURRENT RATING 50A + 100APhase - red Earth - green50A + 100A
310993
Code Weight (Kg)0.06
0.06
399357
250A0.28
35289
HOE
S
OLLECTOR
C
+
H
OLDER
50A Phase Collector 399360 250A Collector 34956 100A Collector (Earth left) 399352 100A Phase Collector
310990
250A Collector Shoe and Holder
35289 50 / 100A Collector
Shoe and Holder 310993
50A Collector (Earth left)
SAFELEC
OLLECTOR
C
B
RACKET
Single 13mm SQUARE310994
0.36
310991
0.88
Double310898
0.74
310992
1.84
Single collector bracket 310994
Single collector bracket 310991
Double collector bracket 310898
Double collector bracket 310992
Weight (Kg) 25mm SQUARE Weight (Kg)
25mm square, 400mm long for use with 100A and 250A collectors.
13mm square, 200mm long for use with 50A collector.
RACKETS: SINGLE SIDED BRACKET
B
310980 - to suit beam flange 80-155mm. 310982 - to suit beam flange 155-305mm. WEIGHT (Kg)
0.66
310980
0.86
310982
310980 310982RACKETS: DOUBLE SIDED BRACKET
B
RACKETS: WEB BRACKET
B
RACKETS: GIRDER CLAMP
B
310981 - to suit beam flange 80-185mm. 310983 - to suit beam flange 185-305mm. WEIGHT (Kg)
0.84
310981
1.08
310983
310981 310983 WEIGHT (Kg)0.62
310984
310984 WEIGHT (Kg)0.08
310985
SAFELEC
IMENSIONS
D
YSTEM
S
STANDARD HANGER CLAMPS
SAFELEC
C
OMPONENT
D
IMENSIONS
60A STANDARD PHASE COVER - Expansion Section (310007)
250A JOINT POWERFEED (310910)
END POWERFEED (310911) ALUMINIUM JOINT
(310874)
60A JOINT POWERFEED (310034)
STANDARD PHASE COVER (310850) STEEL JOINT (310872) 250A JOINT POWERFEED (310910) SINGLE POLE HANGER CLAMP Standard Mount
SAFELEC
C
OMPONENT
D
IMENSIONS (Continued)
TWO POLE HANGER CLAMP Standard Mount (310882) THREE POLE HANGER CLAMP Standard Mount (310861)
END CAP TRANSFER END CAP
ANCHOR CLAMP With Insulator (310969) STAINLESS STEEL HANGER CLAMP with Insulator (310827) FOUR POLE HANGER CLAMP Standard Mount (310821) ANCHOR CLAMP (310832) SINGLE POLE HANGER CLAMP with Insulator (310918) END CAP for Steel / Copper Bar
SAFELEC
C
OMPONENT
D
IMENSIONS (Continued)
STANDARD PHASE COVER Isolation Section
(310025)
SINGLE COLLECTOR BRACKET 13mm square
(310994)
DOUBLE SIDED BRACKET
(310981) DOUBLE SIDED BRACKET(310983)
SINGLE SIDED BRACKET (310980)
SINGLE COLLECTOR BRACKET 25mm square
(310991)
SINGLE SIDED BRACKET (310982)
DOUBLE COLLECTOR BRACKET 13mm square
(310898)
GIRDER CLAMP (310985)
SAFELEC
ECHNICAL
T
D
ATA
MaterialPVC
180 KV/cm
10
11ž
>10
15ž/cm
84
0C
Self extinguishing
54%
1.5 g/cm
3BAYBLEND
240 KV/cm
>10
14ž
>10
16ž/cm
120
0C
Self extinguishing
24%
1.15 g/cm
3 Dielectric strength Surface resistivity Volume resistivity Vicat softening temperature(never expose PVC cover to temperatures in excess of 80oC)
Flame-test Oxygen index Specific density
CONDUCTOR BAR COVER STANDARD MEDIUM HEAT
CONDUCTOR BAR ALUMINIUM /
STAINLESS STEEL COPPER
Nominal current Cross sectional area Maximum system voltage (AC) (contact Insul-8 for other voltages) (DC) (contact Insul-8 for other voltages)
Resistance R (for DC) at 200C (ž/m)
Impedance Z (for AC) at 200C (ž/m)
Maximum allowable ambient temperature for 100% duty cycle
Bar length Support pitch Standard
Lateral
Minimum pitch centres Standard Lateral Expansion sections: not required for
runs less than
Minimum bending radius: (horizontal only)
500A 115mm2 1000V 1000V 0.000149 0.000189 250C 4.5m 1500mm 1125mm 60mm 60mm 150m 1.5m 800A 171mm2 1000V 1000V 0.000100 0.000154 250C 4.5m 1500mm 1125mm 60mm 60mm 150m 1.5m 1150A 339mm2 1000V 1000V 0.000051 0.000127 250C 4.5m 1500mm 1125mm 60mm 60mm 150m 1.5m 630A 277mm2 0.000113 0.000162 1000V 1000V 250C 4.5m 1500mm 1125mm 60mm 60mm 150m 1.5m
SAFELEC 3
Electric Mining Vehicles Railway
Shore Supply
SAFELEC
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 500A 800A 1150A
5.40
319202
319201
7.65
319402
319401
14.34
319502
Medium Heat cover
(grey)
319203
319204
319403
319404
319462
319463
319501
Earth Phase
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 500A 800A 1150A
7.40
319208
319207
10.15
319408
319407
16.84
319508
Medium Heat cover
(grey)
319209
319210
319409
319410
319466
319467
319507
Earth Phase Standard Phase cover Standard Earth cover Medium Heat coverONDUCTOR
C
OPPER
C
B
ARS
XPANSION
E
S
ECTIONS
Expansion sections are required on all systems over 150m long.
The maximum gap of the expansion section is 50mm.
The expansion section is 4.5m long and is installed in place of one length of conductor bar.
Expansion section 319407
SAFELEC
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 630A
4.23
319302
319301
Medium Heat cover
(grey) Earth
319303
319304
PhaseStandard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 630A
6.50
319308
319307
Medium Heat cover
(grey) Earth
319309
319310
Phase Standard Phase cover Standard Earth cover Medium Heat cover Expansion section 319307LUMINIUM
A
/
S
TAINLESS
S
TEEL
C
ONDUCTOR
B
ARS
XPANSION
E
S
ECTIONS
Expansion sections are required on all systems over 150m long. The maximum gap of the expansion
section is 50mm. The expansion section is 4.5m long and is installed in place of one length of conductor bar.
SAFELEC
OWERFEEDS: JOINT POWERFEED
P
OINTS
J
0.25
0.202
0.08
Standard Phase cover (orange)
JOINT COVER
Standard Earth cover (green) Medium Heat cover
Weight (Kg) grey
319850
319851
319472
319473
0.04
Copper (up to 800A) JOINT Weight (Kg)319874
Copper 1150A319515
Aluminium319873
Standard cover (orange) Medium Heat cover(red)
POWERFEED
319870
319909
Powerfeed has cable connection for maximum 2 x 50mm2 cables.
Joint Powerfeed
800A Copper Joint 319874
Aluminium Joint 319873
1150A Copper Joint 319515
OINTING
J
C
OMPOUND
0.225
JOINTING COMPOUND Weight (Kg)
310932
Jointing compound should be applied to the contact surfaces of the joint and bar at every joint on copper and aluminium systems. One tube is sufficient for over 300 connections.
Standard Phase cover 319850
COPPER BAR
ALUMINIUM / STAINLESS STEEL BAR
SAFELEC
OWERFEED
P
S
ECTIONS
Standard Phase cover Double cable connection
319918
Standard Phase cover (orange) Standard Earth cover
(green)
Medium Heat Phase cover (grey)
Weight (Kg)
SINGLE CABLE CONNECTION 500A
6.56
319913
319912
319926
Medium Heat Earth cover
(grey)
319927
Standard Phase cover (orange) Standard Earth cover
(green)
Medium Heat Phase cover (grey)
Weight (Kg)
SINGLE CABLE CONNECTION 630A
5.39
319917
319916
319930
Medium Heat Earth cover
(grey)
319931
Standard Phase cover (orange) Standard Earth cover
(green)
Medium Heat Phase cover (grey)
DOUBLE CABLE CONNECTION 630A
319919
319918
319932
Medium Heat Earth cover
(grey)
319934
Standard Phase cover (orange) Standard Earth cover
(green)
Medium Heat Phase cover (grey)
Weight (Kg)
DOUBLE CABLE CONNECTION 500A 800A 1500A
8.0
319915
319914
10.25
319911
319910
16.94
319524
319928
319468
319470
Medium Heat Earth cover
(grey)
319929
319469
319471
319523
Standard Phase cover Single cable connection
319912
Standard Phase cover Double cable connection
319914
Standard Phase cover Single cable connection
319916
Powerfeed sections are 4.5m long and should be fitted in place of a length of conductor bar. Suitable for connection of 1 or 2 cables
SAFELEC
Standard hangers are acetyl. Maximum support spacing is 1.5m.
ANGER
H
C
LAMPS: STANDARD MOUNT
ANGER
H
C
LAMPS: WITH INSULATOR
POLYCARBONATE
(RED) ZINC PLATED HARDWARESTAINLESS STEEL WITH STANDARD (BLACK) Single pole Weight
319821
0.027
319826
0.070
319829
0.030
Single pole hanger
319821 Stainless steel hanger319826
NCHOR
A
C
LAMPS
WEIGHT (Kg) Single pole Single pole Single pole Single pole(Black)
(Red)
Stainless steel
Two part
0.10
0.10
0.106
0.08
Two pole
Two part
319834
319839
319827
319833
319838
0.174
In particularly dusty or humid environments, hangers with insulator should be used.
WEIGHT (Kg)
Standard With insulator Without top bolt (two required per anchor point)
0.06
0.12
0.05
319832
319964
319963
Anchor points are usually situated in the middle of a conductor system.
Additional anchor points are required for systems with expansion sections. Stainless steel
hanger with insulator
319827
Two pole two part hanger
319838
Single pole two part hanger
319833
Anchor clamp 319832
SAFELEC
Isolation sections provide electrical separation between adjacent sections of conductor bar. Only for use in dry, clean conditions. The Isolation section is 4.5m long and
is installed in place of one length of conductor bar. It is recommended that Isolation sections
are not fitted in earth conductors.
SOLATION
I
S
ECTIONS
COPPER BAR
ALUMINIUM / STAINLESS STEEL
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 500A 800A 1500A
2.97
319013
319012
3.42
319426
319425
4.68
319475
Medium Heat cover
(grey)
319015
319016
319431
319432
319476
319477
319474
earth phase Isolation section 319425 Isolation section 319311Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 630A
2.4
319312
319311
Medium Heat cover
(grey) earth
319313
319314
phase WEIGHT (Kg) End cap319892
0.04
ND
E
C
APS
End cap 319892SAFELEC
OLLECTORS
C
HOE
S
OLLECTOR
C
+
H
OLDER
The copper graphite shoe ensures electrical continuity, a smooth contact with the conductor bar and a good resistance to wear.
100A collectors are supplied without cable.
Stranded cable terminal clamps are included.
250A collectors are supplied with 2 x 1m 35mm2 cable.
Weight (Kg)
CURRENT RATING 100A 250A
0.8
310990
Phase2.00
34956
399355
Earth - without deflector
399340
Earth - right hand
399352
Earth - left hand
250A Collector 34956
100A Collector (Earth left)
399352 100A Phase Collector
310990
250A Collector Shoe and Holder
35289 50 / 100A Collector
Shoe and Holder 310993
CURRENT RATING Phase - red50A + 100A Earth - green50A + 100A
310993
Code Weight (Kg)0.06
0.06
399357
250A0.28
35289
SAFELEC
OLLECTOR
C
B
RACKET
Single 13mm SQUARE310994
0.36
310991
0.88
Double310898
0.74
310992
1.84
Single collector bracket 310994
Single collector bracket 310991
Double collector bracket 310898
Double collector bracket 310992
Weight (Kg) 25mm SQUARE Weight (Kg)
25mm square, 400mm long for use with 100A and 250A collectors. 13mm square, 200mm long for use with
50A collector.
RACKETS: SINGLE SIDED BRACKET
B
319980 - to suit beam flange 80-155mm. 319982 - to suit beam flange 155-305mm.
WEIGHT (Kg)
0.66
319980
0.86
319982
319980 319982RACKETS: DOUBLE SIDED BRACKET
B
RACKETS: WEB BRACKET
B
RACKETS: GIRDER CLAMP
B
319981 - to suit beam flange 80-185mm. 319983 - to suit beam flange 185-305mm.
WEIGHT (Kg)
0.84
319981
1.08
319983
319981 319983 WEIGHT (Kg)0.62
319984
319984 WEIGHT (Kg)0.08
310985
310985SAFELEC
IMENSIONS
D
YSTEM
S
STANDARD HANGER CLAMPS
SAFELEC
C
OMPONENT
D
IMENSIONS
500A STANDARD PHASE COVER - Expansion Section (319207)
COPPER JOINT (up to 800A)
(319874)
STANDARD ANCHOR CLAMP (319832)
END CAP (319892) STAINLESS STEEL HANGER
(319826) STAINLESS STEEL HANGER CLAMP with Insulator (319827) JOINT POWERFEED (319909) ALUMINIUM JOINT (319873)
SINGLE POLE HANGER (319821) STANDARD PHASE COVER
SAFELEC
ECHNICAL
T
D
ATA
MaterialPVC
180 KV/cm
10
11ž
>10
15ž/cm
84
0C
Self extinguishing
54%
1.5 g/cm
3BAYBLEND
240 KV/cm
>10
14ž
>10
16ž/cm
120
0C
Self extinguishing
24%
1.15 g/cm
3 Dielectric strength Surface resistivity Volume resistivity Vicat softening temperature(never expose PVC cover to temperatures in excess of 80oC)
Flame-test Oxygen index Specific density
CONDUCTOR BAR COVER STANDARD MEDIUM HEAT
CONDUCTOR BAR ALUMINIUM /
STAINLESS STEEL COPPER
Nominal current Cross sectional area Maximum system voltage (AC) (contact Insul-8 for other voltages) (DC) (contact Insul-8 for other voltages)
Resistance R (for DC) at 200C (ž/m)
Impedance Z (for AC) at 200C (ž/m)
Maximum allowable ambient temperature for 100% duty cycle
Bar length Support pitch Standard
Lateral
Minimum pitch centres Standard Lateral Expansion sections: not required for
runs less than
500A 115mm2 1000V 1000V 0.000149 0.000189 250C 6m 1500mm 1125mm 70mm 70mm 150m 800A 171mm2 1000V 1000V 0.000100 0.000154 250C 6m 1500mm 1125mm 70mm 70mm 150m 1150A 339mm2 1000V 1000V 0.000051 0.000127 250C 6m 1500mm 1125mm 70mm 70mm 150m 630A 277mm2 0.000113 0.000162 1000V 1000V 250C 6m 1500mm 1125mm 70mm 70mm 150m
V BAR
For use in applications where regular disconnection and reconnection of current collectors is required: for example in
mining and quarrying.
The specially designed profile of the insulating cover guides the collector shoe onto the sliding surface of the
conductor bar, providing greater tolerance and allowing the collectors to be correctly located without direct access to
the bar.
Standard Phase cover
Standard Earth cover
SAFELEC
Standard Phase cover (orange)
Standard Earth cover (green)
Weight (Kg)
CURRENT RATING 500A 800A 1150A
6.33
319869
319250
8.55
319452
319451
15.15
319552
319551
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 500A 800A 1150A
8.93
319258
319257
11.15
319458
319457
17.75
319558
319557
ONDUCTOR
C
OPPER
C
B
ARS
XPANSION
E
S
ECTIONS
Expansion sections are required on all systems over 150m long. The maximum gap of the expansion
section is 50mm. The expansion section is 1.5m long.
Expansion section 319457
Isolation sections provide electrical separation between adjacent sections of conductor bar.
Only for use in dry, clean conditions. It is recommended that Isolation sections are not fitted in earth conductors.
SOLATION
I
S
ECTIONS
Standard Phase cover (orange)
Weight (Kg)
CURRENT RATING 500A 800A 1500A
7.3
319253
9.55
319453
16.26
319553
Standard Earth cover Standard Phase
cover
SAFELEC
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 630A
5.13
319352
319351
Standard Phase cover (orange) Standard Earth cover
(green)
Weight (Kg)
CURRENT RATING 630A
7.73
319358
319357
Expansion section 319357
Expansion sections are required on all systems over 150m long.
The maximum gap of the expansion section is 50mm.
The expansion section is 1.5m long.
LUMINIUM
A
/
S
TAINLESS
S
TEEL
C
ONDUCTOR
B
ARS
XPANSION
E
S
ECTIONS
Isolation sections provide electrical separation between adjacent sections of conductor bar.
Only for use in dry, clean conditions. It is recommended that Isolation sections are not fitted in earth conductors.
SOLATION
I
S
ECTIONS
Standard Phase cover (orange)
Weight (Kg)
CURRENT RATING 630A
6.1
OWERFEEDS: JOINT POWERFEED
P
OINTS
J
SAFELEC
0.25
0.202
6.08
Standard cover JOINT COVER Weight (Kg)319840
0.168
Copper 500/800A JOINT Weight (Kg)319885
Copper 1150A319515
Aluminium319873
500/800A Copper Joint 319885
Aluminium Joint 319873 1150A Copper Joint
319515 Standard cover (black) Weight (Kg) POWERFEED
0.16
319845
ANGER
H
C
LAMPS: WITH INSULATOR
NCHOR
A
C
LAMPS
WEIGHT (Kg)
Single pole
Two part
319844
0.114
WEIGHT (Kg)
Heavy duty anchor
319843
0.7
Heavy duty anchor clamp 319843 WEIGHT (Kg)
ND
E
C
APS
Single pole two part hanger 319844 Standard cover 319840 In particularly dusty or humid environments, hangers with insulator should be used
SAFELEC
The copper graphite shoe ensures electrical continuity, a smooth contact with the conductor bar and a good resistance to wear.
100A collectors are supplied without cable.
Stranded cable terminal clamps are included.
250A collectors are supplied with 2 x 1m 35mm2 cable.
OLLECTORS
C
HOE
S
OLLECTOR
C
+
H
OLDER
Weight (Kg)CURRENT RATING 100A 250A
0.8
310990
Phase2.00
34956
399355
Earth - without deflector
399340
Earth - right hand
399352
Earth - left hand
250A Collector 34956
100A Collector (Earth left)
399352 100A Phase Collector
310990
250A Collector Shoe and Holder
35289 50 / 100A Collector
Shoe and Holder 310993
CURRENT RATING 50A + 100APhase - red Earth - green50A + 100A
310993
Code Weight (Kg)0.06
0.06
399357
250A0.28
35289
SAFELEC
C
OMPONENT
D
IMENSIONS
800A STANDARD PHASE COVER Expansion Section
(319457)
SINGLE POLE TWO PART HANGER (319844)
JOINT COVER Standard
(319840)
SAFELEC
SAFELEC
SAFELEC
Subsidiary companies
AUSTRALIA
CONDUCTIX Pty. Ltd. (Insul-8) Dandenong Tel: + (61) 3 97 06 88 44 Fax: + (61) 3 97 94 92 98 [email protected] www.conductix.com.au
BENELUX
CONDUCTIX Benelux Brussels Tel: + (32) (0) 2 469 25 60 Fax: + (32) (0) 2 469 29 35 [email protected] www.conductix.beGERMANY / AUSTRIA
CONDUCTIX GmbH Offenbach / Main Tel: + (49) 69 98 40 23 0 Fax: + (49) 69 98 40 23 99 [email protected] www.conductix.deMEXICO
CONDUCTIX S.de R.L. de C.V. (Insul-8) Monterrey Tel: + (52) 811 090 9013 Fax: + (52) 811 090 9014 [email protected] www.conductix.com-mx
UNITED KINGDOM
CONDUCTIX Ltd (Insul-8) Salford Tel: + (44) 161 848 01 61 Fax: + (44) 161 873 70 17 [email protected] www.conductix.co.ukITALY
CONDUCTIX Srl (Comes) Milan Tel: + 39 (0) 39 607 431 Fax: + 39 (0) 39 607 43292 [email protected] www.conductix.it Turin Tel: + 39 (0) 11 45 09 007 Fax: + 39 (0) 11 42 41 008 [email protected] www.conductix.itUNITED STATES
CONDUCTIX, Inc. (Insul-8) Omaha, NE Tel: + (1) 402 339 9300 Fax: + (1) 402 339 9627 [email protected] www.conductix.us Harlan, IA Tel: + (1) 712 755 2246 Fax: + (1) 402 952 9381 [email protected] www.conductix.us
CANADA
CONDUCTIX Corp. (Insul-8) St Jérôme Tel: + (1) 450 565 9900 Fax: + (1) 450 432 6985 [email protected] www.conductix.us
CHINA
CONDUCTIX Ltd (Han Fa) Wuhan Tel: + (86) 27 83 49 99 88 Fax: + (86) 27 83 49 99 89 [email protected] www.conductix.cn