• No results found

RPM 8 Manual

N/A
N/A
Protected

Academic year: 2021

Share "RPM 8 Manual"

Copied!
37
0
0

Loading.... (view fulltext now)

Full text

(1)

INSTRUCTION MANUAL

FOR

RPM-8

Reactive Power Manager

Relay – 8 Stage

(2)

CONTENTS

Sl.No. Topic Description Page No.

1.0 Introduction 1

2.0 Installation & Wiring 4 3.0 Settings & Programming 8

3.2 Menu Structure 11

4.0 Display & Menu Operations 12

5.0 RPM-8 Operation 21

6.0 Alarms in RPM-8 25

7.0 Technical Specifications 28

8.0 Warranty 32

Appendix-1 Guidelines for Cap. Bank selection 33 Appendix-2 Effect of high rate of load fluctuation 34

(3)

-1-

1.0 INTRODUCTION

Reactive Power Manager Relay (Model RPM-8) is designed for

automatic control of capacitor banks in 3 phase 4 wire LT distribution systems. The relay maintains the system power factor at a set value, under fluctuating load conditions, by connecting or disconnecting capacitor banks to the 415V bus. The relay employs state of the art micro controller design for measurement of reactive power compensation required, system power factor, voltage and current. A specially formulated optimization program for capacitor bank switching ensures accurate power factor control at the set point and hunt free operation.

RPM-8 is designed to control up to 8 capacitor banks. The front panel arrangements and other features of the unit are explained in the following sections:

1.1 Non uniform Banks: RPM-8 can accept capacitor banks whose values are at random (i.e.) it is not necessary to connect banks in ratios of 1: 1: 1: or 1: 2: 2: or 1: 2: 4: …etc. The kVAR ratings of the banks can be in any random denomination. It is not necessary that the banks should be in multiples of the smallest bank. This feature helps in providing maximum kVAR compensation with least number of banks (the number banks can go up to 8)

(4)

1.2 Bank Configuration: The user will have facility to enter the bank size of each bank (in kVAR) at the time of commissioning. Any bank which is not connected will have to be entered as zero kVAR. The banks whose values are entered as zero will be treated as unconnected banks. The relay will not switch these „zero value‟ banks in its normal operation. Consequently the time for PF correction will be minimized.

1.3 Automatic c/k selection: The user need not perform complicated mathematics to calculate c/k ratio and set in the relay. The relay will do the PF correction without the need for c/k ratio. It automatically calculates the threshold kVAR by taking into account the bank values already entered. Hence there is no need to set the c/k ratio.

1.4 Accurate display of Power Factor: The unit uses a specially designed measurement circuit, which facilitates accurate measurement and steady display of PF, even in conditions where harmonics are present.

1.5 Optimization of connected banks: RPM-8 will constantly monitor the kVAR compensation required and select the right combination of banks to ensure that the plant PF is maintained very close or equal to the set value.

1.6 Hunt Free operation: A unique optimization program for bank switching, combined with online monitoring of total reactive compensation required as mentioned above, ensures that the relay does not hunt at a bank value during load fluctuations.

(5)

-3-

1.7 Multi parameter Display: RPM-8 has a 4 digits, seven segment, super bright LED display on the front panel. The unit shows the plant PF as a default display. On demand, the unit can also display feeder current, bus voltage, kVAR, settings and bank values.

1.8 Measurement sensitivity of 1%: The unit can continue PF correction even when the load current goes up to 1% of the rated value. Thus PF correction is ensured even in very low load conditions (like in night times or during the initial stages of a plant commissioning).

1.9 Alarms: RPM-8 provides an alarm contact whenever there is an abnormality – like over voltage, under current, CT polarity reversal, over compensation and under compensation.

1.10 Design Philosophy: RPM-8 uses a unique combination of two powerful, state of the art integrated circuits – one for doing analog measurements accurately and the other for doing the peripheral functions efficiently. The analog IC carries out the measurement of Voltage, current, active energy and apparent energy with the accuracy levels required in energy measurement instruments. The measured values are transferred to a high memory micro controller with built in EEPROM – which carries out the peripheral functions like display, switching logic and push button access for menu options. Consequently, the circuit has very few components, which increases the reliability of the device as a whole.

(6)

2.0 INSTALLATION & WIRING

2.1 Preliminary checks: The relay package consists of: - 1 no. RPM-8 Relay

- 2 nos. mounting clamps - 1 no. Instruction Manual - 1 no. Test certificate

Check the RPM-8 relay for any damage. If damaged, please inform nearest L&T office or dealer. If found OK, follow the instructions below for basic functional checks:

a) Remove the terminal cover from the rear terminal block and Connect 240 V AC supply at terminals 1 & 2.

b) Switch on the supply voltage. The display will show PFR8, the power factor and then the error code uCrr. The LEDs marked Auto and Alarm will glow continuously. All other LEDs will remain off.

If the unit has passed above checks, it is ready for panel mounting.

(7)

-5- 2.1 MOUNTING ON PANEL:

RPM-8 relay is designed for flush mounting on any control panel. Please refer to the dimensional drawing shown below for understanding the overall & cutout dimensions of RPM-8.

Provide a cut-out of 138mm x 138 mm on the panel. Push the RPM-8 relay through the cut out and fix the relay to the panel by means of the two mounting clamps.

(8)

2.3 WIRING OF RPM-8 RELAY ON PANEL:

Please refer wiring diagram shown below (the same is affixed on top side of the unit). There are 4 groups of connections as explained below:

a) Auxiliary supply to RPM-8: Please connect R phase voltage of the capacitor bank panel to terminals 1 & 2 of the unit. Please note that it should be 240 V AC 50 Hz supply (Phase to neutral voltage). Phase is connected to 1 terminal and neutral is connected to the 2 terminal of the unit. RPM-8 uses this supply as the auxiliary supply for electronic circuit as well as measuring voltage for PF and kVAR computation.

(9)

-7-

b) CT input to RPM-8: The unit is suitable for connecting to CT secondary of either 1A or 5A rating. Please ensure that the CT is on R phase. CT secondary is to be connected as follows:

1A rating – Terminals 8 & 9 5A rating – Terminals 7 & 9

c) Supply to Capacitor Bank contactor coil supply: RPM-8 is meant for connecting up to 8 capacitor banks through external contactors. Consequently it provides 8 relay contact outputs. - One terminal of all 8 contactor coils is to be connected to

neutral of the contactor coil supply.

- The other terminal of each of the contactor coil has to be connected to RPM-8 terminals 17 to 24 as shown in the wiring diagram.

- The phase supply of contactor coil should be connected to terminal 14 of RPM-8

d) Alarm Circuit: RPM-8 provides a change over contact at terminals 4, 5, 6. this is an 8A rated contact and can be used for energizing a buzzer.

Note: Please ensure that:

a) The auxiliary supply is 240 V ac

b) The CT is on the same phase as the auxiliary supply c) Earth connection to the relay is provided properly

(10)

The relay terminals are suitable for 2.5 sq.mm lugs. After completing the wiring, fix the protective cover back on the terminal block with the help of 4 screws.

3.0

SETTINGS & PROGRAMMING

3.1 FRONT PANEL OF RPM-8

As shown in Fig. 1 on page 9, the front panel of RPM-8 has the following provisions:

3.1.1. 4 digit seven segment LED display:

The on line measured values and various set values will be displayed in the seven segment display. The default display is the plant PF. All other parameters are to be read by manipulating the PBs as explained in Section 4.

3.1.2 A row of 8 nos. Capacitor bank status LEDs:

The row of 8 LEDs will indicate Capacitor bank (CB) on / off status. Since the relay is meant for connecting up to 8 stages of capacitor banks, there are 8 LEDs in a row, each with the bank number associated with it.

If a particular LED is on, the respective CB is switched on. If the LED is off, the respective CB is switched off. For example, if LED 4 is on, capacitor bank 4 (CB04) is switched on.

(11)

-9-Fig.-1

(12)

3.1.3 A column 5 nos. Plant status Leeds:

The column of 5 LEDs indicates the plant status. “Lead” LED will be ON during leading PF in the plant.

“Lag” LED will be ON during lagging PF in the plant.

“Auto” LED will be ON at all times, except when the PBs are pressed for some kind of manual operation. This LED indicates that the RPM-8 relay is in auto mode of PF correction.

“Manual” LED will come ON whenever the RPM-8 relay is taken in to manual mode of operation.

“Alarm” LED will come ON if the plant goes into any of the alarm conditions as explained in Section 6.

3.1.4 Push buttons (PBs):

The 4 PBs, marked as “Menu”, “▲”, “▼”, and “Enter” are used to view display parameters, settings in the relay and to change / programmed the settings in the relay as is explained in detail in Section 4.

(13)

.-11-

(14)

4.0

DISPLAY & MENU OPERATIONS

RPM-8 will display plant PF at all times as a default display. The user can also view and programme many other parameters as explained in following sections.

4.1.1 Main Menu:

Connect auxiliary supply to RPM-8. Press the PBs in the sequence shown in the table below and observe the respective displays.

Operation Display

Press Menu d.dAt

Press ▲ d.SEt

Press ▲ P.SEt

Press ▲ d.dAt

It can be seen that, when the Menu PB is pressed, it opens up three more sub menu options namely:

a) d.dAt : In this option, RPM-8 displays on line data. b) d.SEt : In this option, RPM-8 displays all the parameter

Settings.

c) P.SEt : In this option, user can change the set parameters. (Programme settings).

(15)

-13-

4.1.2 Online value display - d.dAt menu options:

As mentioned earlier, this sub menu helps user to view on line values. Following table shows the procedure to view on line values:

Display of measured values

Operation Display Remarks

Press Menu d.dAt

Press Enter volt Displays value of phase to neutral voltage of the bus. Press Enter 0246

Press Enter Cur Displays value of feeder Current

Press Enter 0127

Press Enter vAr Displays plant kVAr value Press Enter 0056

Press Enter volt Repeat show

(16)

4.3 Parameter settings display - d.SEt menu options

This sub menu helps the user to view all settings of various feeder parameters as listed below:

Display of parameter settings

Operation Display Remarks

Press Menu d.dAt

Press ▲ d.Set Choose dset option Press Enter TrPF Display of

Target PF Press Enter 00.98

Press Enter CtSl Display of CT secondary rating (1A or 5A)

Press Enter 0005

Press Enter Ctrt Display of feeder CT ratio

Press Enter 0050

Press Enter Td Display of interbank Switch on delay (sec) Press Enter 0030

Press Enter Cb01 Display of kVAR

connected at Bank1 Press Enter 0005

Press Enter Cb02 Display of kVAR

connected at Bank2 Press Enter 0010

Press Enter Cb03 Display of kVAR

connected at Bank3 Press Enter 0015

Press Enter Cb04 Display of kVAR

connected at Bank4 Press Enter 0020

(17)

-15-

Display of parameter settings (contd…) Operation Display Remarks

Press Enter Cb05 Display of kVAR

connected at Bank5 Press Enter 0025

Press Enter Cb06 Display of kVAR

connected at Bank6 Press Enter 0030

Press Enter Cb07 Display of kVAR

connected at Bank7 Press Enter 0040

Press Enter Cb08 Display of kVAR

connected at Bank8 Press Enter 0050

Press Enter TrPF Repeat show 4.4 Parameter programming - P.SEt menu option:

This option helps the user to programme the feeder parameters in RPM-8. Once the feeder parameters are entered correctly, the RPM-8 will do PF correction automatically, 24 hours a day. Before entering into this menu, please keep the following feeder related values at hand.

- the CT ratio

- kVAR values of all banks connected at stages 1 to 8 - recommended time delay in sec. for inter bank switch on - target PF required to be achieved

Since Programming/changing the set values in the RPM-8 is an authorized function, entry into P.Set option is made tricky. Please refer table below for entering into PSEt option and do programming.

(18)

Parameter Programming – P.SEt Menu Operation Display Remarks

Press Menu d.dAt

Press ▲ d.Set Choose d.set option Press ▲ P.Set Choose P.set option Press Enter, then ▼,

and release Enter

TrPF Ready to change target pF setting

Press Enter 00.95

(flash)

Set value of target PF (00.95) will flash

Press ▲ for increase or ▼ for decrease of display value trPF 00.98 (flash) The trPF value is changed to 00.98 (will remain flashing)

Press Enter (after reaching the desired value for trPF

setting)

CtSl

New trPF value is registered. Next setting CT sec. ready is ready to be changed.

Press Enter 0005

(flash)

The set value of CT sec (0005) will flash

Press ▲ for increase or ▼ for decrease of display value Ctrt

0001 (flash)

The new CtSl value is changed to 0001 (1A) (will remain flashing) Press Enter (after

reaching the desired value of CtSL sec setting)

Ctrt The CtSL value is registered. Next setting CT ratio is ready to be changed

(19)

-17-

Parameter Programming (contd…)

Operation Display Remarks

Press Enter 0250

(flash)

The set value of CT ratio (0250) will flash

Press ▲ for increase or ▼ for decrease of display value Ctrt

0300 (flash)

The new Ctrt value is changed to 0300 (will remain flashing)

Press Enter (after reaching the desired value for Ctrt

setting)

Td The Ctrt value is

registered. Next setting Cap. Bank switch on time delay is ready to be changed

Press Enter 0035

(flash)

The set value of time delay (0035) will flash Press ▲ for increase

or ▼ for decrease of display value td

0030 (flash)

The new td value is changed to 0030 sec (will remain flashing) Press Enter (after

reaching the desired value for td setting)

Cb01

The td value is registered. Next setting, Bank 1 kVAR value is ready to be changed.

Press Enter 0001

(flash)

Already set value of Bank 1 kVAR (0001) will flash

Press ▲ for increase or ▼ for decrease of display value Cb01 0005 (flash) CB01 value is changed to 0005 kVAR (will remain flashing)

(20)

Parameter Programming (contd…)

Operation Display Remarks

Press Enter (after reaching the desired value for Cb01

setting)

Cb02

The new Cb01 value is registered. Next setting, Bank 2 kVAR value is ready to be changed.

Press Enter 0003

(flash)

Already set value of Bank 2 kVAR (0003) will flash

Press ▲ for increase or ▼ for decrease of display value Cb02

0010 (flash)

CB02 value has been changed to 0010 kVAR (will remain flashing)

Press Enter (after reaching the desired value for Cb02

setting)

Cb03

The new Cb02 value is registered. Next setting, Bank 3 kVAR value is ready to be changed.

Press Enter 0006

(flash)

Already set value of bank 3 kVAR (0006) will flash Press ▲ for increase

or ▼ for decrease of display value Cb03

0015 (flash)

CB03 value has been changed to 0015 kVAR (will remain flashing)

Press Enter (after reaching the desired value for Cb03

setting)

Cb04

The new Cb03 value is registered. Next setting, Bank 4 kVAR value is ready to be changed.

(21)

-19-

Parameter Programming (contd…)

Operation Display Remarks

Press Enter 0008

(flash)

Already set value of bank 4 kVAR (0008) will flash Press ▲ for increase

or ▼ for decrease of display value Cb04

0020 (flash)

CB04 value has been changed to 0020 kVAR (will remain flashing)

Press Enter (after reaching the desired value for Cb04

setting)

Cb05

The new Cb04 value is registered. Next setting, Bank 5 kVAR value is ready to be changed.

Press Enter 0010

(flash)

Already set value of bank 5 kVAR (0010) will flash Press ▲ for increase

or ▼ for decrease of display value Cb05

0025 (flash)

CB05 value has been changed to 0025 kVAR (will remain flashing)

Press Enter (after reaching the desired value for Cb05

setting)

Cb06

The new Cb05 value is registered. Next setting, Bank 6 kVAR value is ready to be changed.

Press Enter 0015

(flash)

Already set value of bank 6 kVAR (0015) will flash Press ▲ for increase

or ▼ for decrease of display value Cb06

0030 (flash)

CB06 value has been changed to 0030 kVAR (will remain flashing)

(22)

Parameter Programming (contd…)

Operation Display Remarks

Press Enter (after reaching the desired value for Cb06

setting)

Cb07

The new Cb06 value is registered. Next setting, Bank 7 kVAR value is ready to be changed.

Press Enter 0020

(flash)

Already set value of bank 7 kVAR (0020) will flash Press ▲ for increase

or ▼ for decrease of display value Cb07

0035 (flash)

CB07 value has been changed to 0035 kVAR (will remain flashing)

Press Enter (after reaching the desired value for Cb07

setting)

Cb08

The new Cb07 value is registered. Next setting, Bank 8 kVAR value is ready to be changed.

Press Enter 0025

(flash)

Already set value of bank 8 kVAR (0025) will flash Press ▲ for increase

or ▼ for decrease of display value Cb08

0040 (flash)

CB08 value has been changed to 0040 kVAR (will remain flashing)

Press Enter (after reaching the desired value for Cb08

setting)

TrPF

The new Cb08 value is registered and the menu will return to the first parameter, the target PF

(23)

-21-

As can be seen, there are a total of 11 parameters to be set in the relay RPM-8 for satisfactory PF control.

5.0

RPM-8 OPERATION

Main objective of RPM-8 relay to perform PF control in a LT sub-station, by adding or deleting capacitor banks to / from a three phase 415V bus.

RPM-8 can work in two modes - Auto and manual mode. 5.1.1 Operation in Auto mode: Whenever powered on, RPM-8 goes

into auto mode operation by default (since its function is to correct power factor automatically). No special activity is required to bring the unit to auto mode.

In this mode, the unit continuously displays the plant PF, measures the required kVAR for compensation and carries out the power factor correction as per set parameters automatically, without any intervention from the operator.

5.1.2 Operation in Manual mode: In this mode the user can add or delete capacitor banks by pressing the PBs on the front panel of the RPM-8. The main purpose of providing this feature is to check the wiring of RPM-8 to various banks, while commissioning.

Procedure for manual operation is explained in following table. ………22

(24)

Manual addition of Capacitor banks from RPM-8

Operation Display Remarks

Press Menu d.dAt

Press ▲ d.Set Choose dset menu Press Enter TrPF Display of target PF Press Enter 00.98

Press Enter CtSL Display of CT Ratio Press Enter 0005

Press Enter Ctrt Display of CT sec. Rating Press Enter 0250

Press Enter Td Display of time bank switching time delay

Press Enter 0030

Press Enter Cb01 Display of Bank 1 kVAR value Press Enter 0005

Press ▲ 0005 Bank 1 will be switched on. Press ▼ 0005 Bank 1 will be switched off. Press Enter CB02 Display of Bank 2 kVAR Press Enter 0010

Press ▲ 0010 Bank 2 will be switched on. Press ▼ 0010 Bank 2 will be switched off. Press Enter CB03 Display of Bank 3 kVAR Press Enter 0015

(25)

-23-

Manual addition of Capacitor banks from RPM-8 (Contd.)

Operation Display Remarks

Press ▲ 0015 Bank 3 will be switched on. Press ▼ 0015 Bank 3 will be switched off. Press Enter CB04 Display of Bank 4 kVAR Press Enter 0020

Press ▲ 0020 Bank 4 will be switched on. Press ▼ 0020 Bank 4 will be switched off. Press Enter CB05 Display of Bank 5 kVAR Press Enter 0025

Press ▲ 0025 Bank 5 will be switched on. Press ▼ 0025 Bank 5 will be switched off. Press Enter CB06 Display of Bank 6 kVAR Press Enter 0030

Press ▲ 0030 Bank 6 will be switched on. Press ▼ 0030 Bank 6 will be switched off. Press Enter CB07 Display of Bank 7 kVAR Press Enter 0035

Press ▲ 0035 Bank 7 will be switched on. Press ▼ 0035 Bank 7 will be switched off. Press Enter CB08 Display of Bank 8 kVAR Press Enter 0040

Press ▲ 0040 Bank 8 will be switched on. Press ▼ 0040 Bank 8 will be switched off.

(26)

-24-

It should be noted that, RPM-8 goes to manual

Mode, only when any PB is pressed on the front

panel. If no PB is pressed for more than 30 sec

(approx.), the unit returns to Auto mode by itself.

In manual mode, the unit does not perform any measurement or PF correction. The operator is expected to do the PF correction by manually adding / deleting the capacitor banks. In case it is required to do PF correction in manual mode for a long duration, following provisions should be made on the PF correction panel.

a) A pair of dedicated On/Off PBs for each capacitor bank b) An Auto/Manual switch

- This switch has to be kept in Auto position when the PF correction is to be done automatically by RPM-8. Wiring should be such that, the phase supply of all contactor coils will be connected to terminal 14 of RPM-8 only if the this switch is in auto position.

- The switch is to be kept in manual position, when capacitor banks are to be added / deleted manually. When in manual position, the phase supply of all contactor coils will be

disconnected to terminal 14 of RPM-8.

(27)

-25-

- Thus the RPM-8 will be prevented to do any capacitor bank addition /deletion. However, the operator is free to add / delete the capacitor banks by means of the dedicated PBs on the main control panel. The RPM-8 will keep indicating the PF and guiding the operator as to whether the target PF has been reached or not.

6.0

ALARMS IN RPM-8

RPM-8 is designed to provide alarms under 5 abnormal conditions. The alarm will be in the form of a change over contact output at terminals 4, 5, 6 and an error code display on the front seven segments LED. Following are the details of alarms.

6.1.1 CT polarity reversal ( Ctrv ) :

As explained earlier, the RPM-8 needs a 240 V AC input and 1A/5A CT secondary input for measuring PF and kVAR. Both these inputs must be from the same phase in the APFC panel. Some times the polarity of S1 & S2 terminals of CT may be reversed when connecting the CT input to RPM-8. If this happens, the PF calculations will go wrong. RPM-8 has a built in check system for detecting CT polarity problem at the commissioning stage itself.

Immediately after power on, with all banks in switched off condition, the unit will show Ctrv display if there is a CT reversal. At the same time the alarm contact will come on. This alarm is indicated only for first 30 second.

(28)

If this alarm is observed following must be done: a) Switch off the voltage connection

b) Short the CT secondary terminals at the terminal strip at bottom of the panel

c) Interchange the CT connection at terminals 9 & 7of RPM-8 d) Power on again and ensure that the alarm is off.

6.2 Under Current Alarm (Ucrr):

RPM-8 is designed to work up to a load current level of 1% of rated value. Some times this current can go even below 1% - any PF correction at this stage may take the plant to leading PF state for a long time - which may not be desirable. RPM-8 gives an alarm Ucrr under such conditions – and all the capacitor banks will be switched off so that plant PF does not go to leading PF unnecessarily.

6.3 Over Compensation alarm ( OCPn ):

Many times, if the load is small, the PF may go lead even without the least capacitor bank on. This is a case of over compensation – this will result in pulling down average PF of the plant.

RPM-8 will give OCPn alarm under such condition 6.4 Under compensation ( UCPn )

There can be condition (particularly when the plant is on full load) that all 8 banks are switched on – but the target PF is not reached.

(29)

-27-

This is a clear indication that the capacitor banks, as sized, are inadequate for the plant. Under such conditions, RPM-8 will give UCPn alarm – so that user can re-configure the capacitor bank sizes.

6.5 Over Voltage alarm ( OvoL )

RPM-8 has a built in over voltage protection at +20% of rated voltage (288 V). If the input voltage exceeds the 2885 V point, the RPM-8 will give OvoL alarm. At the same time all banks will be switched off so that, the capacitor banks are saved from exposure to over voltages.

(30)

7.0

TECHNICAL SPECIFICATIONS OF RPM-8

Voltage Input 240V AC  15%, 50 Hz,

Current Input 5A / 1A from CT secondary (Field selectable)

Rated Frequency 50 Hz  2.5%

Accuracy of 1% ±1digit between 0.7 lag to 0.8 lead

PF Display other ranges 2% ±1digit.

Accuracy of other 2% ± digit

Display Parameter

Target PF setting 0.7 lags to 0.9 lead

CT ratio For 1 Amp secondary 1 to 6400 For 5 Amp secondary 1 to 1280

Threshold reactive Auto Current setting (C/K ratio)

Bank selection Relay will recognize number of Connected banks automatically

Bank configuration Suitable for non-uniform cap. Banks Safety lock out time 30 sec 10%

Auto / Manual

Operation Selectable

(31)

-29-

Capacitor bank a) 1 to 250sec in steps of 1 sec

Switching on delay for switching between two

different banks b) 60 sec for same Bank switching

(Timing Accuracy ± 10%)

Operational LEDs for all relays‟ status Indicators LED for `ALARM`

LED for `AUTO/MANUAL` LEDs for Lead / Lag

Four 7-segment displays for display of Plant PF, Current, kVAR, ALARM-Codes, capacitor bank values, Target PF, and Time delay for switching.

Power Factor From 1% to 120% of rated current

Control Range

Burden < 0.3 VA at CT input at nominal voltage

< 15VA at PT input at nominal voltage

Out put contacts a) 8 nos. N/O contacts for bank contactor switching

b) 1 N/O for alarm

(32)

Contact rating 250V AC, 5A for bank contactor switching, 250V AC, 6A for alarm

Resistance to As per IEC 255-21-1/2 Class 1

Vibration &Shocks

Temperature Operating Temperature 00 to 600 C Storage temperature -200 to 700 C Case Front Bezel 144 x 144 mm Panel Cutout 138 x 138 mm Depth 100 mm Weight 2 kg approx.

Electrical Performance specifications:

a) Insulation

As per IEC 60255-5, 2 kV AC, RMS, 50 Hz for one minute across independent circuits & 1 kV AC, RMS, 50 Hz for one minute across open contacts

b) Impulse withstand

5 kV (CM), 2kV (DM) peak, 1.2/50 micro sec, as per IEC 60255-5

(33)

-31- c) Surge Immunity

As per IEC 61000-4-5, Level 4, 4 kV (CM), 2kV (DM) d) Electrical fast Transient

As per IEC 60255-22-4, 2 kV, 5 kHz e) Conducted Disturbance

As per IEC 61000-4-6, Level 3, 10V, 150 kHz to 80 MHz f) Electro Static Discharge

As per IEC 60255-22-2, air discharge 8 kV

g) Immunity to voltage Variations, dips and short Interrupts

As per IEC 61000-4-11, 200 ms

(34)

8.0

WARRANTY

LARSEN & TOUBRO LIMITED (L&T) warrants that the

protective Relay model RPM-8 will meet L&T„s published specifications and will be free from defects in workmanship and materials for a period of 12 months from the date of shipment. L&T‟s obligation under this warranty shall be limited to servicing or replacing the defective parts provided that notice of such defects and satisfactory proof thereof is given to L&T by it‟s customer within the warranty period.

This warranty does not cover any defect caused by accident, misuse, neglect alteration, modification or substitution of any of the components or parts or any attempts at internal adjustment by unauthorized service personnel.

Under no circumstances shall L&T be liable for any consequential damage, resulting injury, loss or expense, directly or indirectly, arising from the use of this product.

This forgoing warranty is in lieu of all other warranties expressed or implied and is the sole and exclusive remedy for any claim arising from the defect in the product.

(35)

-33-

Appendix-1

Guidelines for selection of Capacitor Bank size:

The RPM-8 relay will continuously evaluate the required kVAR compensation and keep adding to the bus- thus bringing the plant PF close to the set value. Some times, in operation, RPM-8 may not find the closest match for the required kVAR and may stop adding. This may result in a PF much less than the set target.

In order that RPM-8 brings the plant PF closest to target PF, the system should have right denomination of capacitor banks as required by the load conditions of the plant. To determine, the right denomination of bank sizes (8 in total), following approach may be followed:

Plant kVAR requirement >100kVAR

Plant kVAR requirement < 100kVAR

Bank no.

Size (kVAR) Bank no. Size (kVAR)

1 X 1 X 2 2X 2 X 3 3X 3 2X 4 5X 4 2X 5 10X 5 3X 6 20X 6 5X 7 30X 7 10X 8 40X 8 15X ………34

(36)

Appendix-2

Effect of high rate of load fluctuation on PF control:

RPM-8 corrects PF by adding or deleting the connected capacitor banks. As per the requirement of standards for Capacitor banks, the banks are switched on / off with a set time delay. This inter bank switch on delay is normally of the order of 15 to 30 sec.

In case the loads are fluctuating faster than this 15 sec, the time delay can be reduced to the order of 5 sec. However, whenever the same bank is switched on, the delay is preset to 60 sec as required by the Standards. It can now be seen that whenever the load fluctuates in less than 15 sec period, the switching action of RPM-8 may not match with the correction requirements. This is mainly because, the load changes before the action of RPM-8 is completed- with the result that RPM-8 may not add capacitor at all.

This will lead to a situation where despite installing RPM-8, there is a large gap between the target PF and actual plant PF reached – like target PF may be 0.95, actual may be 0.87. It should be noted that RPM-8 has brought the plant PF up to 0.87 – it is not able to improve because it is not able to add additional capacitors due to rapid fluctuations in load. This is particularly true for small plants where the total kVAR itself is less than 10 kVAR.

For such applications it is advisable to have more small value banks- like 1 kVAR, 1.5 kVAR etc. Alternately it is better to have individual capacitors connected across each load.

(37)

Manufactured by

LARSEN & TOUBRO LIMITED, KIADB INDUSTRIAL ESTATE, HEBBAL, HOOTAGALLY, MYSORE – 570 018. INDIA. Visit us @ www.lntmps.com www.lntebg.com www.larsentoubro.com Reach us @ [email protected]

References

Related documents

Strategies for success Everything students need to get ready for the SAT and SAT Subject Tests TM can be found at sat.collegeboard.org/practice, including a variety

If sperm leaks from the vas deferens during or after a vasectomy, it can cause a sperm granuloma, when the fibrous tissue at the end of the vas deferens thickens. Most times,

 If you move to other functions or stop the music using Z STOP on the unit (or Z on the remote control) on AUTO DJ mode, AUTO DJ function will be disable..  AUTO DJ function

 If you move to other functions or stop the music using Z STOP on the unit (or Z on the remote control) on AUTO DJ mode, AUTO DJ function will be disable..  AUTO DJ function

In AUTO mode the unit automatically chooses the fan speed and the mode of operation (COOL,DRY or FAN).In this mode the fan speed and the temperature are set automatically according

Based on how many years of actual yield data are available, an individual’s APH yield average cannot fall below a given level in relationship to the county T-yield.. For a

Fax / Image send settings Operation manual (for facsimile) and Operation manual (for image send) TONER SAVE IN PRINTER MODE TONER SAVE IN COPY MODE AUTO POWER SHUT-OFF KEYS

A student who has fewer than 64 transfer credits and who does not have an Associate in Arts or Associate in Science degree from a New Jersey community college must meet the