Example 1 . A three-phase, Y-connected generator is rated at 100 kVa, 60
cycles, 2300 volts. The effective resistance of the armature is 1.5 ohms per
leg. The test data are given below:
Field Current (A) 10 20 30 40 Terminal Volts (OC) 1200 2100 2830 3460
Calculate the synchronous impedance and the synchronous reactance per
phase for this machine, using the highest point given on the saturation or
open circuit voltage curve to obtain the values.
Volts (OC) SC
Current
13.2 26.0
Example 2 . A three-phase, slow speed, Y-connected alternator is rated at
5000 kVA and 13,200 volts. The resistance of the armature between terminals
is 0.192 ohm at 75 C. The effective resistance is 1.6 times the dc-value at 75
C.. The test data on this machine is given below.
Field
Current (A)
90 135 180 225
Terminal 9800 13000 14900 15800
a) Calculate the regulation at a pf of 0.8 lagging.
b) Calculate the regulation for a load of unity pf.
Terminal Volts (OC)
9800 13000 14900 15800 SC Current 195 291
Example 3: A 3-phase, 800 kVA, 3000 V, 50 Hz alternator gave the
following results:
Exciting Current (A) 30 35 40 50 60 65 70 75 77.5 80 85 90 100 110 O.C. volt (line) _ _ _ 2560 300 0 3250 3300 3450 3500 3600 3700 3800 3960 4050 S.C. current 140 150 170 190 _ _ _ _ _ _ _ _ _ _a) A field current of 110 A is found necessary to circulate a full load
current on short circuit of the alternator. The armature resistance per
phase is 0.27225 Ω. Calculate the voltage regulation at 0.8 p.f.
lagging and 0.9 p.f leading, using synchronous impedance method.
Show also the vector diagram.
Example 4 . A 30-kVA, Y-connected alternator rated at 555 volts at 50 Hz has
the open circuit characteristics given by the following data:
A field current of 25 A is found necessary to circulate a full load current on
short circuit of the alternator. Calculate the voltage regulation at 0.8 p.f.
lagging and 0.8 p.f. leading, using synchronous impedance method. Show
Field Current (A) 2 4 7 9 12 15 20 22 24 25 Terminal Volts 155 287 395 440 475 530 555 560 610 650
lagging and 0.8 p.f. leading, using synchronous impedance method. Show
also the vector diagram.
Solution:IL= 30 kVA /(√3) (650) = 26.6469355 A ZS= [ 650 / (√3) ] / 26.6469355 = 14.08333333 A Ra=0; XS= ZS IXS= 375.2776749 V Eph = Vph + IL ( Ra + j XL) ; Vph + IXS< 53.13010235 Eph = 622.7425899 < 28.8224976 V VR% = 622.7425899 – (555/ √3) (555/ √3) = 94.34627131 %
Solution: IL= 30 kVA /(√3) (550) = 31.49183286 A Vph= 550 / √3 = 317.5426481 V IRa= 4.72377493 V/phase Eph = Vph + IL ( Ra + j XL ) ; Vph + IRa < 36.86989765 Eph = 321.3341678 < 0.50537273 V ELL= 556.5671049 V If = 20<90.50537273 + 7<216.8698976 A = 16.82207726 < 110.0830856 A
:
Solution
(
1
19
)
18
8
144
to
slots
P
S
=
=
°
=
2
10
x
3
cos
pk
β
=
°
= 10
18
180
1. The following information is given in connection with an alternator: slots = 144; poles = 8; rpm = 900; conductors/slot = 6; flux per pole = 1.8 x 106 maxwells; coil span = slots
1 to 16; winding connection = star. Calculate: (a) the voltage per phase; (b) the voltage between terminals. 20 PTS
( )
conductors
Z
T=
6
144
=
864
288
864 =
=
phZ
1 pt965925826
.
0
=
pk
6
3
8
144
=
=
phase
poles
slots
m
°
=
2
10
sin
6
2
10
x
6
sin
dk
=
0
.
95614277
dk
288
3
=
=
phZ
phase
turns
T
144
/
2
288 =
=
( )
( )
(
6)
( )( )
(
8)
10
x
1
60
144
10
x
8
.
1
44
.
4
−=
d p gk
k
E
φV
E
gφ=
637
.
7283753
(
)
V
E
g LL577947
.
1104
7283753
.
637
3
=
=
1 pt 1 pt 1 pt 1 pt 8 pts 8 pts2. In a 3 phase, start connected alternator, there are 2 coil per slot and 16 turns per coil. Armature has 288 slots on its periphery. When driven at 250 rpm it produces 6600 V between the lines at 50 Hz. The pitch of the coil is 2 slots less than the full pitch. Calculate the flux per pole, total number of conductors and turns per phase. 20 PTS
:
Solution
V
E
LL=
6600
V
V
E
g3810
.
511777
3
6600
=
=
φ(
1
13
)
12
24
288
to
slots
P
S
=
=
β
=
°
= 15
180
3
4
24
288
=
=
phase
poles
slots
m
( )
poles
N
f
P
=
120
=
24
β
=
°
= 15
12
180
°
=
2
15
x
2
cos
pk
965925826
.
0
=
pk
1 pt
°
=
2
15
sin
4
2
15
x
4
sin
dk
=
0
.
957662196
dk
1 pt3 phase
slot
cond
slots
turns
coil
turns
x
slot
coils
16
32
64
.
2
=
=
(
)
conductors
Z
T=
64
288
=
18432
6144
3
18432 =
=
phZ
phase
turns
T
3072
/
2
6144 =
=
6 pts 6 pts:
2
.
Solution
no
of
on
continuati
( )
( )
( )(
3072
)( )
50
44
.
4
511777
.
3810
=
k
dk
pφ
mWb
040223388
.
6
=
φ
6 pts3. A 3-phase, 10-pole alternator has 90 slots, each containing 12 conductors. If the speed is 600 r.p.m. and the flux per pole is 0.1 Wb, calculate the line e.m.f. and voltage per phase when the phases are (i) star connected (ii) delta connected. Assume the winding factor to be 0.96 and the flux sinusoidally distributed.
20 PTS
:
Solution
(
)
Hz
f
50
120
600
10
=
=
( )
conductors
Z
T=
90
12
=
1080
360
3
1080 =
=
phZ
360
1 ptphase
turns
T
180
/
2
360 =
=
Wye:( )( )( )( )( )
1
0
.
1
50
180
44
.
4
d gk
E
φ=
V
E
gφ=
3836
.
16
6 pts 1 pt(
)
V
E
g LL424026
.
6644
16
.
3836
3
=
=
6 pts Delta:( )( )( )( )( )
1
0
.
1
50
180
44
.
4
d gk
E
φ=
LL gV
E
E
φ=
3836
.
16
=
6 pts1. Three non-inductive resistances, each of 100 Ω, are connected in star to 3-phase, 440 < 0O V supply. Three equal choking coils
each of reactance 100 Ω are also connected in delta to the same supply.
Calculate:
a) line current of each 3-phase load (in polar form)
b) the total line current (in polar form) c) power factor of the system
For Wye load:
:
Solution
100
30
3
440
1−
∠
=
=
I
φI
LA
I
I
L1=
φ=
2
.
540341184
∠
−
30
For Delta load: a) c) pf of the system
100
0
440
j
I
φ=
∠
A
I
φ=
4
.
4
∠
−
90
A
I
L2=
7
.
621023553
∠
−
120
b) total line current
A
I
I
I
T=
L1+
L2=
8
.
033264177
∠
−
101
.
5650512
( ) ( )
I
W
P
T=
L1 2100
=
645
.
3333331
c) pf of the system( ) ( )
I
Vars
Q
T=
L2 2100
=
1936
VA
U
T=
2040
.
723183
)
(
316227765
.
0
lagging
U
P
pf
T T=
=
2. A symmetrical 3-phase, 3-wire supply with a line voltage of 173 < 0O V supplies two balanced
3-phase loads; one Y-connected with each branch impedance equal to (6 + j8) ohm and the other Δ-connected with each branch impedance equal to (18 + j24) ohm. Calculate:
a) line current taken by each 3-phase load (in polar form)
b) the total line current (in polar form) c) power factor of the entire load circuit d) total real power and apparent power For Wye load:
8
6
30
3
173
1j
I
I
L+
−
∠
=
=
φA
I
I
L1=
φ=
9
.
9881
∠
−
30
a):
Solution
For Delta load:
24
18
j
I
φ=
+
A
I
φ=
5
.
766666667
∠
−
53
.
13010235
A
I
L2=
9
.
988159757
∠
−
83
.
13010235
b) total line current
A
I
I
Solution continuation No.2:
( ) ( )
I
W
P
L1=
L1 26
=
598
.
58
VA
U
L1=
997
.
6333333
( ) ( )
I
W
P
L2=
L2 26
=
598
.
5800001
VA
U
L2=
997
.
6333334
W
P
P
P
T=
L1+
L2=
1197
.
16
VA
U
U
U
T=
L1+
L2=
1995
.
266667
)
(
6
.
0
lagging
U
P
pf
T T=
=
pf
I
V
P
T=
3
L L°
=
31
.
78833062
θ
(
400
)( )(
55
0
.
85
)
3
=
TP
W
P
T=
35628
.
28511
3. A 440-V, 50-Hz induction motor takes a line current of 55 A at a power factor of 0.85 (lagging). Three Δ-connected capacitors are installed to improve the power factor to 0.9 (lagging). Calculate the kVA of the capacitor bank and the capacitance of each capacitor.
power factor of 0.85 (lagging).
T NEW
P
Q
=
tan(
β
)
°
=
25
.
8419327
β
VARS
Q
NEW=
17255
.
56604
T OLDP
Q
=
tan(
θ
)
VARS
Q
OLD=
22080
.
42799
NEW OLD
CAP