MAINTENANCE SCHEDULE

Specification - Electrical Services

No. Detail Maintenance Frequency

D W M 3M/6M Y/2Y 1.0 1.1 1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 1.1.6 1.1.7 1.1.8 1.1.9 1.1.10

MAIN SWITCH BOARD AND LOW VOLTAGE COMPONENTS Switch Room Including Riser Room

Cleaning of switch room & riser rooms Cleaning of cable trench/condition of cable trench (ensure clean, water free and slab cover - ok)

Cleaning and repairing doors, locks and repainting (if necessary)

Check to ensure that "No Smoking", No Admittance" & "Danger Signs". Treatment Shock Card" & Schematic Drawing are in good condition and are visible/readable and replace if

necessary

Check to ensure fire-extinguisher and C02/halon system are in good working condition, expiry date not due and take the necessary action

Check rubber mat in front of the main switch board-replace if damaged

Ensure all electrical spares are sufficient and stored in order and maintenance in good condition

Check antivermin wire mesh - replace/ repair if necessary.

Check the roof/floor above to ensure no leakage/damage - repair if necessary Ensure no water flowing into Switch Room/Riser room X X X X X X X X X Y

(2)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 1.1.11 1.1.12 1.2 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 1.2.7 1.2.8 1.2.9 1.2.10 1.2.11

Check wiring and electrical fittings, power points, light fittings, and exhaust fans. Check duct seals

Main switch Board/Sub-switch boards

Check all indicator light, selector switches, voltmeter, ammeter, power factor meter etc – replace if faulty

Check and retighten all screws, contactors, termination etc.

Check condition of cables for burn marks, insulation leakage and other abnormal conditions

Record readings for maximum current, voltage, power factor, etc into the log book and take necessary action

Test cable insulation, cable box cable terminations and other related connections Test earthing system and all terminations, connections etc.

Testing, calibration and resetting, all earth fault and overcurrent relays inclusive of current transformers, voltage transformers etc.

Check copper busbars and ensure that is in good condition

Do load balancing Balance to + 5% of load

Check capacitor Bank conditions

Check contactors, capacitors etc. change when required X X X X X X X X 6M Y 2Y 2Y Y

(3)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 1.2.12 1.2.13 1.3 1.3.1 1.3.2 1.3.3 1.3.4 1.3.5 1.3.6 1.4 1.4.1 1.4.2 1.4.3 1.4.4 1.4.5 1.4.6

Check P.F. meter and ensure p.f is better than 0.85 lagging

Retighten all cables etc.

Air Circuit Breakers (ACB)

Clean arc chute and arc contacts and replace as necessary

Clean all insulating parts

Adjust & calibrate circuit breaker Grease all moving contacts and related components

Test tripping mechanism to ensure that it is in good working condition

Check and retighten all wiring and connections

Fuse switches/Switch fuses

Check cover for any damage – replace or repair as necessary

Check switch handle for any damage – repair/replace as necessary

Continuity test on fuses – replace with correct rating if damage/faulty

Retighten fuse carriers

Clean contacts with clean cloth to ensure good contact

Retighten all connections/termination to prevent from any sparking when loaded

X X X X 6M 6M 6M 2Y Y Y Y Y Y Y

(4)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 1.5 1.5.1 1.5.2 1.5.3 1.5.4 1.5.5 1.5.6 1.6 1.6.1 1.6.2 1.6.3 1.7 1.7.1 1.7.2 1.7.3 1.7.4 1.7.5 1.7.6 1.7.7

Residual Current Device (RCD) (including rccbs)

Retighten all connections, termination etc. Check and test switch handle

Tripping test on RCD – replace if faulty Test for earth continuity

Retighten all earth electrode terminations Test RCD tripping time and sensitivity

Moulded case Circuit Breaker (MCCB)

Check switch handle and ensure that it operates “ON” and “OFF”

Retighten all connections, terminations etc Check ELR functions/trippings

Distribution Board

Check condition of distribution board Ensure that “Danger” and schematic diagram are available and readable/visible Check and ensure spares ways available in the distribution board

Retighten fuse handle Test on continuity of fuses Check MCBs for tripping test

Retighten all connections, terminations etc. X X 3M 3M 3M 3M Y Y Y Y Y Y Y Y Y Y E

(5)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 1.7.8 1.8 1.8.1 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 2.1.7 2.1.8 2.2 2.2.1

Check and clean internal part of the distribution board

Surge Suppressors

Check all surge suppressors

LOW VOLTAGE DISTRIBUTION SYSTEM

Bare and insulated aluminium conductor (over head line) where applicable

Check condition of pole – to reinstate to upright position and replace if

damaged/unsafe

Ensure that no tree branches touching the live conductors

Retention of cables when found sagging Check insulation and replace if insulation is damage/unsafe

Check stay wires and retention as necessary

Check insulators for stay wires – replace when necessary

Check and test cable earthing Retighten all line taps

Paper or XLPE or PVC insulated armoured underground cables

Test cable insulation

X X Y Y Y Y Y Y Y Y Y

(6)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 2.3.7 2.3.8 2.3.9 2.4 2.4.1

Phasing out test

Retighten all connection, terminations etc. Check all cable route markers – replace if found missing / damaged

Check labeling

Check cable end terminations and cable end boxes

Busduct and submain risers in trunking/cable tray

Check and ensure that trunking is clean and in dry condition

Check and ensure that no condensation present in the trunking

Test for insulation and continuity Check busbar support – replace when necessary

Check busbar support – replace when necessary

Check fire barriers – replace if damaged Retighten all connections, terminations etc.

Ensure that trunking is mounted properly and safely

Ensure trunking covers intact

Mineral insulated type cable

Text for insulation and continuity

X X X X X Y Y Y Y Y Y Y Y Y Y

(7)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 2.5 2.5.1 2.5.2 2.5.3 2.5.4 2.5.5 2.5.6 2.5.7 2.5.8 2.5.9 3.0 3.1 3.1.1 3.1.2

XLPE/PVC insulated type cable on cable tray

Check and ensure that trunking is clean and dry condition

Check and ensure that no condensation present within the trunking

Test for cable insulation, between cables and continuity

Check trunking earth copper tape

Check cable supports – replace if damaged Check fire barriers – replace if damaged Retighten all connections, terminations etc Ensure that space factor of 45% is not exceeded

Ensure that trunking is mounted properly and safety

LUMINAIRES, SWITCHES AND SOCKETS OUTLETS, FANS, WATER HEATERS, P.A. SYSTEM, MOTORS AND WATER PUMPS AND

OUTDOOR LIGHTING Luminaires

Check components of light fittings eg. Cable, lamp holder, lamps, control gear etc.

Ensure that “KELUAR” sign is in good working condition X X X X X Y Y Y Y Y Y

(8)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 3.1.3 3.1.4 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 3.2.9 3.3 3.3.1 3.3.2 3.4 3.4.1

Test emergency light fittings

Replace KELUAR & Emergency light fittings.

Fluorescent Luminaires (Including SL & PL Type

Check and ensure that the tube is in good condition

Check and ensure that no black mark or oil trace

Check and ensure that no burnt marks at both ends of the tube

Check conditions of capacitor

Check conditions of whole luminaries and replace if necessary

Ensure that no noise generated from the ballasts – replace if necessary

Check starter to ensure in good working conditions

Retighten all connection, terminations etc. Check other luminaries (incandescent)

Switches and switch sockets outlets

Ensure no damage from visual inspection Open, clean and retighten all connections, termination etc.

Fans (Ventilating & Exhaust)

Check and clean fan

X X X X X X X X X X X X X 5Y

(9)

Specification - Electrical Services

No. Detail D Maintenance FrequencyW M 3M/6M Y/2Y 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 3.4.7 3.4.8 3.4.9 3.4.10 3.4.11 3.4.12 3.5 3.5.1 3.5.2 3.5.3 3.5.4 3.5.5

Ensure continuous rotation/functionality Ensure that no noise being generated – repair/replace if necessary

Check safety wire rope

Ensure that the exhaust fan is not blocked Ensure that all bolts and nuts, connections, suspension rod, rubber mounting are in good condition

Check condition of regulator Test for insulation – and earthing

Check regulator and ensure that no noise generated during operation

Retighten all connections, terminations etc. for the fan

Retighten all connections, terminations etc. to the regulator

Ensure auto louvers in working condition

Water Heater

Check and clean water heater

Check and ensure that no water leakage to the connecting pipe and tank

Check and record load

Check and retighten connections, earthing terminations etc.

Check temperature range as stated in manufacturer’s specifications X X X X X X X X X X X X X 6M 6M Y

(10)

Specification - Electrical Services

No. Detail D Maintenance FrequencyW M 3M/6M Y/2Y 3.5.6 3.5.7 3.5.8 3.5.9 3.5.10 3.6 3.6.1 3.6.2 3.6.3 3.6.4 3.7 3.7.1 3.7.2 3.7.3 3.7.4 3.7.5 3.7.6 3.7.7

Check condition of safety valve Check indicator light

Check and retighten connection and to the double pole switch

Check pressure control switch functional Check r.c.d. for function

Public Address (PA) System

Check functionality of complete PA system

Check and clean amplifier, loud speakers, microphone mixer, tuner, players and other related equipment

Check and retighten all connections Inspect & service battery/battery charger

Motor, protection equipment and water pump

Check and clean motor from dust

Check ventilation holes to prevent from blockage

Check motor noise level and ensure that there is no friction

Check motor mounting/alignment/vibration Check functionality of hand driers

Check and test for fuse

Check and test for emergency switch

X X X X X X X X X X X X X X X X

(11)

Specification - Electrical Services

No. Detail D Maintenance FrequencyW M 3M/6M Y/2Y 3.7.8 3.7.9 3.7.10 3.7.11 3.7.12 3.7.13 3.7.14 3.7.15 3.7.16 3.7.17 3.7.18 3.7.19 3.7.20 3.7.21 3.8 3.8.1 3.8.2 3.8.3

Check protection system and limit Check temperature oil dashpot relays Check short circuit protection

Check earth fault relay

Check anti condensation heater Check bearing temperature Check overload protection relay Check thermistor relay

Check and retighten all connections, terminations for protection equipment Check motor speed

Carry out insulation and continuity test Check slip rings and commutators Check motor couplings

Check and retighten all connections, termination etc. to motor

Outdoor Lighting – Compound and Street Lighting, Building Floodlighting & security Lightings.

Ensure light fittings functional

Check by visual inspection condition of poles and light fitting, lamp cover, control switch gear etc.

Check control components and retighten all connections and termination

X X X X X X X X X X X X 6M Y Y Y Y

(12)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 3.8.4 3.8.5 3.8.6 3.8.7 3.8.8 3.8.9 4.0 4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7

Check time switch Check isolator

Check condition of cable Check mounting and support Check and clean light fittings

Check for paint works/Rust and corrosion & repair as necessary

ELECTRICAL TESTING (TO ENSURE COMPLIANCE WITH B.S. 7671:1992-16TH EDITION IEE WIRING REGULATIONS; MS.IEC 60364-1996) General Testing

Check condition of electrical equipment by usual inspection to check for fault indication on switches, socket outlets, light points, light fittings etc.

Test and check accuracy of all meter (in switchboards and control panels) Check condition of main/sub switchboards Check conditions of distribution boards Check and test all circuit breakers and fuses

Retighten all connections, termination etc Record locations for each final circuit, check with record available at distribution board and update when necessary

X X X X X X X 6M Y Y Y Y Y

(13)

Specification - Electrical Services

No. Detail D Maintenance FrequencyW M 3M/6M Y/2Y

4.2 4.2.1 4.2.2 4.2.3 4.2.4 4.2.5 4.2.6 4.3 4.3.1 4.3.2 4.3.3 4.3.4 4.4 4.4.1 4.5 4.5.1

Final circuit continuity and protection circuit tests

Check condition of protective conductors Check condition of wiring

Check copper tape for trunking

Check and test protection system for conduits

Test for final circuit continuity Test for protective circuit continuity

Installation Impedance Measurement

Check and test all circuit breakers and fuses

Check, test and measure insulation

impedance between conductors and between conductors to earth

Record locations for each final circuit, check with record available at distribution board and update when necessary

Retighten all connections, terminations etc.

Identification of Polarity

Test electrical wiring polarity for light points, switches, power points etc.

Measurement or earth fault loop impedance

Test & record earth fault loop impedance

X X X X Y Y Y Y Y Y Y Y

(14)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 4.6 4.6.1 4.6.2 4.7 4.7.1 4.7.2 4.7.3 4.7.4

Testing of Residual Current Devices

Test operation of residual current circuit breaker by pressing the ‘trip’ button

Test & record for sensitivity of residual current circuit breaker

Measurement of earth electrode impedance

Test & record for earth conductor continuity Check and retighten connections, terminations for earth electrode

Check condition of concrete inspection box for earth electrode

Test measure & record electrode impedance

X X Y Y Y Y

(15)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 5.0 5.1 5.1.1 5.1.2 5.1.3 5.1.4 5.1.5 5.1.6 5.1.7 5.1.8 5.1.9 5.2.0 5.3 5.3.1 5.3.2 5.3.3 5.3.4 5.3.5 UPS(UNINTERRUPIBLE POWER SUPPLY) Batteries

Check battery type (Lead Acid or NiCD) and record voltage output of each cell

Check batteries electrolyte level – top up or replace when necessary

Check S.G of electrolyte (if lead acid type) Check and clean terminal from acid corrosion

Check cleanliness of cells

Check, clean, retighten vent plug Check connections between cells for

cleanliness, and lubricate with petroleum jelly Remeasure and record cell output voltage after maintenance

Check ventilation in battery room For nickel cadmium batteries release air bubbles trapped in the batteries to prolong battery life time

Battery charger

Check and record incoming voltmeter reading Check and record incoming ammeter reading Check and record battery voltmeter reading Check and record battery ammeter

reading X X X X X X X X X X X X X X

(16)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 5.3.6 5.3.7 5.3.8 5.3.9 5.4 5.4.1 5.4.2 5.4.3 5.4.4 5.4.5 5.4.6 5.4.7 Check ‘cubicles’

Check and retighten all connections Check indicators for protection system as follows

:-i) ‘thyristor’ fuse ii) A.T high voltage iii) Battery fuse

iv) Current control limit

v) thyristor choking fan failure vi) power failure

vii) battery voltage low viii) earth fault

ix) other (if any)

Check and clean all heatsink, capacitor and P.C.B’s (use dry brush or vacuum cleaner)

Invertor

Check and record voltmeter reading Check and record frequency reading Check and clean ‘cubicles’

Check and record volt-ampere reading Check accuracy of all meters (to Manufacture’s recommendation) Check connections

Check protection system:-- current control - fan failure

- voltage abnormal - high current - over current - other (if any)

X X X X X X X X X X X

(17)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 5.5 5.5.1 5.5.2 5.6 5.6.1 5.6.2 6.0 6.1 6.1.1 6.1.2 6.1.3 6.1.4 6.1.5 6.1.6 6.1.7 6.2 6.2.1 6.2.2 6.2.3 6.2.4 6.2.5

Static transfer switch

Check control circuit

Check completeness of switch functions

Maintenance by-pass switch

Check cleanliness of ‘cubicles’

Check completeness of switch functions

Generator set Lubrication System

Check engine oil level Change engine oil

Change oil full flow and bypass filters Check hydraulic governor oil

Change hydraulic governor oil

Lubricate tachometer drive and throttle control mechanism

Check and rectify external leaks

Fuel System

Change fuel system

Adjust injectors and valves

Recalibrate fuel pump and injectors Drain water and sediment from fuel tank, tighten all fuel line connections

Check fuel level X X X X X X X X X X Y Y Y Y Y Y

(18)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 6.3 6.3.1 6.3.2 6.3.3 6.3.4 6.3.5 6.3.6 6.3.7 6.3.8 6.3.9 6.3.10 6.4 6.4.1 6.4.2 6.4.3 6.4.4 6.4.5 6.4.6 6.4.7 Cooling System

Check cooling water system level Change water filter

Check and adjust water pump belts tension Check and adjust fan belts

Dismantle and service water pump fan hub and idler pulley assembly and the associated bearings

Check hoses for deterioration Check and rectify external leaks Check and clean radiator fins

Check coolant – change if necessary Change fan belt

Air System

Check and clean air cleaner element wet/dry Change air cleaner element if required Check and clean crankcase breather element Change crankcase breather element

Check and tighten all air hose connections from Air Filter to Air Manifold

Check and clean Turbo charger (if any) Check and adjust (if necessary) clearance of

X X X X X 6M 3M 3M 6M Y Y Y Y Y Y Y Y

(19)

Specification - Electrical Services

No. Detail D WMaintenance FrequencyM 3M/6M Y/2Y 6.4.8 6.5 6.5.1 6.5.2 6.5.3 6.5.4 6.5.5 6.5.6 6.6 6.6.1 6.6.2 6.6.3 6.6.4 6.6.5 6.7 6.7.1 6.7.2

Check and clean blower screen (if Necessary)

Electrical System (To comply with 5.1 & 5.2

Check battery type (Lead acid or NiCd) Check battery electrolyte level add if necessary. Check S.G if lead acid type Check battery charger

Check and test electrical connections

Check and clean battery, starter and terminal Check AVR

Alternator

Inspect alternator, clean and blow out dust Grease bearings

Insulation check on Main Stator, main rotor and excitor stator and excitor rotor

Check and retighten drive coupling bolts Change all carbon brushes (if applicable)

Generator set control panel

Check and service generator set control panel (AMF) including all relays wiring connections etc. and Automatic changeover contactor located in the Main Service Board Test safety indicating and alarm devices for normal functioning of over-speed, over temp, oil pressure, overload, low fuel etc.

X X X X X X X X X 6M 6M 6M Y

(20)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 6.8 6.8.1 6.8.2 6.8.3 6.8.4 6.9.1 6.9.2 6.9.3 7.0 7.1 7.1.1 7.1.2 7.1.3 7.1.4

Operations Testing and General Servicing

Test running condition (with no load ) for 30 minutes

Test running condition (with load) for 30 minutes

Simulation of supply utility power failure etc. On the essential Switch Board by switching off mains supply to the automatic Changeover Contactor

Perform engine turning up if necessary Check acoustic system (air intake, outlets, attenuators, acoustic door)

& measure and record noise level To clean & clear surrounding, drain and external compound of the room

To clear, clean and vacuum the interior Room window and door louvers etc.

HIGH VOLTAGE SYSTEM

High Voltage Switchborad (11kV and above)

Test insulation at 5kV and record in megaohms.

Check all connections, conductors, busbars, switch contacts, fuse contacts, etc. tighten & rectify if necessary.

Check all cable boxes.

Clean and vacuum inside switchboard.

X X X X X 3M Y Y Y Y Y

(21)

Specification - Electrical Services

No. Detail D WMaintenance FrequencyM 3M/6M Y/2Y

7.2 7.2.1 7.2.2 7.2.3 7.2.4 7.2.5 7.2.6 7.2.7 7.3 7.3.1 7.3.2 7.3.3 7.3.4

Oil Circuit Breaker

Inspect OCB, measure insulation at 5KV and record.

Recondition contacts, adjust stroke, wipe, Overshoot stop and latch, and operating

Mechanism, record closing and opening times of each pole to verify correct adjustment.

Check condition of tension rod & turbulator pod and flush breaker components and tank with clean oil.

Lubricate auxiliary contacts with copper grease and test conductivity of contacts, record results. Check and adjust trip operations, interlock integral earthing and report.

Test acidity and insulating oil for dielectric strength until it passes test of 30KV at 4mm gap for one minute or equivalent approved standard. Change insulating oil (if necessary)

Vacuum Circuit Breaker (VCB)

Inspect and clean VCB for contamination, moisture and corrosion.

Check the spring operating mechanism, condition of the lubrication on rotating and sliding bearing surfaces.

Check the breaker pole with vacuum interrupter for any suspect damage.

Check auxiliary switch, shunt releases/blocking magnets, charging motor and d.c. rectifier.

X Y Y Y Y Y Y Y Y Y Y

(22)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 7.4 7.4.1 7.4.2 7.4.3 7.4.4 7.4.5 7.4.6 7.5 7.5.1 7.5.2 7.5.3 7.5.4 7.5.5 7.5.6 SF6 Circuit breaker

Check pressure indication. Report if any low gas pressure.

Check, test auxiliary and solid-state relay circuits.

Inspect and clean external surface. Report if any defect.

Check all connections and cable boxes condition and report.

Check and adjust, if necessary all operation and interlocks against inadvertent erroneous

switching and report.

Check geared motor operating condition.

Ring Main Unit (Oil Type)

Inspect and clean external surface. Report if any defect.

Check all connections and cable boxes condition and report.

Inspect Ring Main Unit, (HFU switch fuse, OLU oil switch, Busbar & Isolater) measure insulation at 5kV and record.

Check and adjust, if necessary all operation and interlocks against inadvertent erroneous

switching and report.

Test insulating oil for dielectric strength until it passes test of 30kV at 4mm gap for one minute or equivalent approved standard.

Change insulating oil ( if necessary)

X X X 6M 6M 6M Y Y Y Y Y Y

(23)

No. Detail D WMaintenance FrequencyM 3M/6M Y/2Y 7.6 7.6.1 7.6.2 7.6.3 7.6.4 7.7 7.7.1 7.7.2 7.8 7.8.1 7.8.2 7.8.3 7.8.4 7.8.5 7.8.6 7.8.7

Metering (Voltmeter and Ammeter)

Check meters condition inclusive of glass covers

Ensure that the pointer is at zero when not in use

Ensure that the reading indicated by the meters is correct – recalibrate if necessary

Record voltmeter and ammeter maximum readings to ensure correct readings and no occurrence of overload

Protection relays

Recalibration of overcurrent and earth fault relays

Recalibration of transformer protection (for oil-filled transformer) Bucholtz relay

Direct Current (D.C) Supply

Check battery type (Lead Acid or NiCD) and record voltage output of each cell

Check batteries electrolyte level – top up or replace when necessary

Check S.G of electrolyte (if lead acid Type

Check and clean terminal from acid corrosion

Check cleanliness of cells

Check, clean, retighten vent plug

Check connection between cells for cleanliness, X X X X X X X X X X X 2Y 2Y

(24)

Specification - Electrical Services

No. Detail D WMaintenance FrequencyM 3M/6M Y/2Y 7.8.8 7.8.9 7.8.10 7.8.11 7.9 7.9.1 7.9.2 7.9.3 7.9.4 7.9.5 7.10 7.10.1 7.10.2 7.10.3

Remeasure and record cell output voltage after maintenance

Check ventilation in battery room Check all meters functional

For nickel cadmium batteries release air bubbles trapped in the batteries to prolong battery life time

Transformer (oil-filled type)

External surface to be cleaned and to touch up with paint if necessary, oil leakage to

Be arrested, if necessary.

Check oil level, max. Temperature, silicagel condition to be recorded. If necessary top up oil, replaces silicagel and determine

Check all connection and cable boxes condition and report

Test acidity and insulating oil for dielectric strength until it passes test of 30Kv at 4mm gap for one minute or equivalent

standard

Oil conditions, refilter or change when necessary

Transformer (Resin/dry Type)

Check the winding temperature and instrumentation circuits.

Check the cooling fan operation.

Check visual inspection of coils, wiring and monitoring equipment for any suspected damage X X X X X X X X Y Y Y Y

(25)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 7.10.4 7.10.5 7.10.6 7.10.7 7.10.8 7.11 7.11.1 7.11.2 7.11.3 7.11.4 7.12 7.12.1 7.12.2 7.12.3 7.13 7.13.1 7.13.2

Check all connections for correct degree of tightness.

Test and measure insulation resistance. Record all measurement.

Clean and remove dust/contamination from transformer.

Check and rectified for any abnormally high temperature/noise level and rectify.

External surface to be cleaned and to touch up with paint if necessary.

11kV Cable (& Cables>1kV)

Check compound in cable box (if PILCDSTAS cable) for any abnormal condition.

Ensure that no digging being done near underground cable route

Test cable insulation Checked cable makers

Earthing System

Retighten all connections, terminations, earthing.

Retighten all earth electrode terminations and ensure corrosion free

Test and measure earth electrode impedance

H.T. Switch Room

Cleaning of switch room

Cleaning of cable trench/condition of cable

X X X X X X X X X Y Y Y Y Y

(26)

No. Detail D WMaintenance FrequencyM 3M/6M Y/2Y 7.13.3 7.13.4 7.13.5 7.13.6 7.13.7 7.13.8 7.13.9 7.13.1 0 7.13.1 1

Cleaning and repairing doors, locks and repainting (if necessary)

Check to ensure that “No Smoking”, No Admittance” & “Danger Sings”. Treatment Shock Card” & Schematic Drawing are in good condition and are visible/readable and replace if necessary

Check to ensure fire-extinguisher and CO²/halon-free system are in good working condition, expiry date not due and take the necessary action

Check rubber mat in front of the main switch board-replace if damaged

Check antivermin wire mesh – replace/repair if necessary

Check the roof/floor above to ensure no leakage/damage – repair if necessary Ensure no water flowing into Switch Room/Riser room

Check wiring and electrical and fittings, power points, light fittings, and exhaust fans

Check duct seals

X X X X X X X Y Y

(27)

No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 8.0 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8

LIGHTING PROTECTION SYSTEM

Visual inspection of all components of lightning protection system e.g. air termination, downdrop, connections, test connections, etc. to ensure that they are in good working condition – replace/repair when necessary. Proprietary type lightning

protection systems included.

Make sure that all final/copper tape in good condition – if damaged, replace/repair

Ensure structural support for system & check support saddles for copper tape- ensure securely fixed

Check all connections, termination points to down conductors are in good condition – replaced or repair when necessary

Check down conductors from test joints too earth chambers – ensure present and secured in place

Clean surface of connections, joints,

terminations of conductors from oxidation and test for continuity to earth

Test conductors for earth continuity and ensure that the overall earth impedance

does not exceed (10 ohms)

Check and record counter device reading

X X X X X X Y Y

(28)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 9.0 9.1 9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.1.6 9.1.7 9.1.8 9.1.9 9.1.10 9.1.11 9.1.12 10.0 10.1 10.2 10.3 TELECOMMUNICATION SYSTEM (VOICE COMMUNICATION)

Telephone /PABX System

Check PABX system – functional Check telephone sets/system

Check telephone cabling/wiring system Check telephone DP – Boxes

Check telephone Riser cable Check MDF & IDF system Check lighting/surge arrestors

Check battery system/charger (as per 5.1 & 5.2)

Check battery electrolyte level add/replace if necessary and check specific gravity

Check telephone earthing system – ensure connection/termination/inspection

chambers in good condition Test telephone earthing system Operator’s system

STRUCTURED CABLING SYSTEM

Check and inspect closets for structured cabling system & telecommunications systems.

Test all cables Other items:-X X X X X X X X X X X X X X X X Y Y X

(29)

Specification - Electrical Services No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 11.0 11.1 11.1.1 11.1.2 11.1.3 11.1.4 11.1.5 11.1.6 11.1.7 11.1.8 11.1.9 11.2 11.2.1 11.2.2 11.2.3 11.2.4

AUDIO AND VIDEO SYSTEM Video Screens & Projection Systems

Check to ensure monitor 100Hz functional Check to ensure screen unit functional. Check to ensure image controller functional Check metal base frame of monitor, screen, rollers for rust/corrosion, repair or paint as necessary.

Check and clean large screen PMMA for stain dirts.

Check and service video cassette player, laser vision player, caption camera, computers and related equipment.

Check master power supply.

Check and retighten all connections. Other

items:-(Manufacturer’s recommendation to be complied with)

Sound Reinforcement System

Check for functionality of complete sound reinforcement system.

Check and clean power amplifiers, speakers, paging and other audio related equipments. Check and retighten all connections. Other items:-(Manufacturer’s recommendation to be complied with) X X X X X X X X X X X X X X X X X X X X X

(30)

Specification - Electrical Services

No. Detail D W M 3M/6M Y/2Y

11.3 11.3.1 11.3.2 11.3.3 11.3.4 12.0 12.1 12.2 12.3 12.4 12.5 12.6 12.7 12.8 Conference System

Check for functionality of complete conference system

Check and clean amplifier, delegate

conference sets and other related equipment. Check and retighten all connections.

Other

items:-(Manufacturer’s recommendation to be complied with)

BUILDING MANAGEMENT/ AUTOMATION SYSTEM

Service the central processing unit, monitors, power instrumentation and PDC unit.

Check PIR scanner and miniature contactor. Check built-in control module in electrical switch board

Check AC to DC converter. Check UPS system.

Check and service the electrical contractor Check the data gathered and maintain hard copies. Other items:-(Manufacturer’s recommendation to be complied with) X X X X X X X X X X X X X X X X X X X X

(31)

Specification - Electrical Services

No. Detail D Maintenance FrequencyW M 3M/6M Y/2Y

14.0 14.1 14.2 14.3 14.4 16.0 16.1 16.2 17.0 17.1 17.2 18.0 18.1 18.2 19.0 19.1 19.2 COMPUTERISED MAINTENANCE MANAGEMENT SYSTEM

Updates all records

Updates As-Built Drawing Check and inspect system

Service System as per manufacture’s

RIGGING SYSTEMS

Check system functionality

Manufacturer’s recommendation to be complied with – all items

STAGE LIGHTING SYSTEM

Check system functionality

Manufacturer’s recommendation to be complied with – all items

PRODUCTION INTERCOM SYSTEM

Check system functionality

Manufacturer’s recommendation to be complied with – all items

GRAPHIC USER INTERFACE SYSTEM

Check system functionality

Manufacturer’s recommendation to be complied with – all items

X X X X X X X X X X X X X X X X X X X X X X X X X X Y X X X X X

(32)

Specification - Electrical Services

Note: Maintenance Frequency Letter Codes

D – Daily W – Weekly

M – Monthly 3M – Three monthly

6M – Six Monthly Y – Yearly

2Y – 2 yearly Notes:

1. The above maintenance schedule shall be read in conjuction with the manufacturer’s recommended maintenance schedule, with the more stringent requirements/portions taking precedence. Any manufacturer’s requirements not listed in this scehdule shall be complied with. No. Detail Maintenance Frequency D W M 3M/6M Y/2Y 20.0 20.1 20.2 21.0 21.1 21.2 21.3 21.4 21.5 22.2

VIDEO CONFERENCE SYSTEM

Check system functionality

Manufacturer’s recommendation to be complied with – all items

CHANDELLIER LIGHTING

Check system functionality

Check and ensure that all the entire bulb is in good condition, replace if necessary.

Check conditions of whole luminaries and replace if necessary

Retighten all connection, termination etc. Manufacturer’s recommendation to be complied with – all items including cleaning

SPECIAL EVENT

Temporary decoration lighting for official function, Ramadhan and Syawal month.

Supply and install temporary decoration lighting in compound and trees in complex’s area X X X X X X X X X X X 6M X X X

(33)

2. The battery and battery charger maintenance scehdule of 5.1 and 5.2 shall be complied with for all battery and battery chargers.

3. The work for the Y and 2Y maintenance schedule shall be carried out at the 6th and 18th month respectively.

References

Related documents

Moreover, lesion studies have previously been used to understand the effects of local structural organization on network dynamics, demonstrating the integrative role of “connector”

Ensure roof and plumbing leaks are repaired and replace water-damaged ceiling tiles.. Repair other water-damaged building materials (e.g.,

Before using the compressor again, check the safety devices or any slightly damaged parts to ensure that they are in good working order.. Check that the moving parts are

Err-01 U-Phase IGBT1 overcurrent fault IGBT Phase U is damaged Check and replace IGBT Err-02 U-Phase IGBT2 overcurrent fault IGBT Phase U is damaged Check and replace IGBT

This paper gives sufficient conditions for an integrable operator to be the square of a Hankel operator, and applies the condition to the Airy, associated Laguerre, modified Bessel

Check the power cable before use and if you find that the cable is damaged, be sure to unplug the compressor and replace the cable.. Do not use

Chemical composition of carbon supports (Table S1), relative content of nitrogen forms (Table S2), comparison of experimental and theoretical binding energies for N 1s (Table

31 In 1907 a retired RAMC Colonel had written a letter to The Times making claims for Captain Hughes to have found the bacteria in milk [Hughes was killed