• No results found

02-Non-Dir

N/A
N/A
Protected

Academic year: 2021

Share "02-Non-Dir"

Copied!
58
0
0

Loading.... (view fulltext now)

Full text

(1)
(2)

Application of Non-Directional Overcurrent

and Earthfault Protection

(3)

Non-Directional Overcurrent and Earth

Fault Protection

(4)

Overcurrent Protection

Purpose of Protection

z Detect abnormal conditions

z Isolate faulty part of the system

z Speed

z Fast operation to minimise damage and danger

z Discrimination

z Isolate only the faulty section

z Dependability / reliability

z Security / stability

(5)

Overcurrent Protection

Co-ordination

z Co-ordinate protection so that relay nearest to fault operates first

z Minimise system disruption due to the fault

F1 F2

F3 F3 F2

(6)
(7)

Overcurrent Protection

Fuses

z Simple

z Can provide very fast fault clearance

z <10ms for large current

z Limit fault energy

Pre Arc Time

Arcing Time

Prospective Fault Current

Total

Operating Time

(8)

Overcurrent Protection

Fuses - disadvantages

z Problematic co-ordination

z IFA approx 2 x IFB

z Limited sensitivity to earth faults

z Single phasing

z Fixed characteristic

z Need replacing following fault clearance

(9)
(10)

Overcurrent Protection

Direct Acting AC Trip

z AC series trip

z common for electromechanical O/C relays

51

IF

(11)

Overcurrent Protection

Direct Acting AC Trip

z Capacitor discharge trip

z used with static relays where no secure DC supply is available IF' Sensitive Trip Coil IF 51 +

(12)

-Overcurrent Protection

DC Shunt Trip

z Requires secure DC auxiliary

z No trip if DC fails IF' IF DC BATTERY SHUNT TRIP COIL 51

(13)
(14)

Overcurrent Protection

Principles

z Operating Speed z Instantaneous z Time delayed z Discrimination z Current setting z Time setting

z Current and time

z Cost

(15)

IF1

IF1

IF2

Overcurrent Protection

Instantaneous Relays

z Current settings chosen so that relay closest to fault operates

z Problem

z Relies on there being a difference in fault level between the two relay locations

z Cannot discriminate if IF1 = IF2 50 B 50 A IF1 IF2

(16)

Overcurrent Protection

Definite (Independent) Time Relays

TOP TIME

IS Applied Current

(17)

Overcurrent Protection

Definite (Independent) Time Relays

z Operating time is independent of current

z Relay closest to fault has shortest operating time

z Problem

z Longest operating time is at the source where fault level is highest

51

0.9 sec 0.5 sec

(18)

Overcurrent Protection

IDMT

z Inverse Definite Minimum Time characteristic

TIME

Applied Current (Relay Current Setting)

(19)

Overcurrent Protection

Disc Type O/C Relays

z Current setting via plug bridge

z Time multiplier setting via disc movement

z Single characteristic

z Consider 2 ph & EF or 3 ph plus additional EF relay

(20)

Overcurrent Protection

Static Relay

z Electronic, multi characteristic

z Fine settings, wide range

z Integral instantaneous elements

RESET A B C INST t I > Is INST t I > Is No Ph+ I n Vx V Hz 0.05 0 0 0 0 0 0 1 1 1 0.05 0.05 0.1 0.2 0.3 0.4 1 2 4 8 100.05 0 0 0 0 0 0 1 1 1 0.05 0.05 0.1 0.2 0.3 0.4 1 2 4 8 100.1 0.1 0.2 0.4 0.4 0.4 0.8 0 0 0 0.025 0 0 0 0 0 0 0 0 0 0 0 D LT1 S 1 V 1 E1 I t s I = Σ x I s s I = Σ x I s x t = Σ x t = Σ IINST = Σ x Is IINST= Σ x Is M CG G

(21)

Overcurrent Protection

Numerical Relay

z Multiple characteristics and stages

z Current settings in primary or secondary values

z Additional protection elements

Current Time I>1 I>2 I>3 I>4

(22)
(23)

Overcurrent Protection

Co-ordination Principle

z Relay closest to fault must operate first

z Other relays must have adequate additional

operating time to

prevent them operating

z Current setting chosen to allow FLC

z Consider worst case conditions, operating modes and current flows T IS1 IS2 Maximum Fault Level I R2 R1 IF1

(24)

Overcurrent Protection

Co-ordination Example

C B A 0.01 0.1 1 10 Operating time (s) Current (A) FLB FLC FLD E D C B D E

(25)

Overcurrent Protection

IEC Characteristics

z SI t = 0.14 (I0.02 -1) z VI t = 13.5 (I2 -1) z EI t = 80 (I2 -1) z LTI t = 120 (I - 1)

Current (Multiples of Is) 0.1 1 10 100 1000 1 10 100 Operating Time (s) VI EI SI LTI

(26)

Overcurrent Protection

Operating Time Setting - Terms Used

z Relay operating times can be calculated using relay

characteristic charts

z Published characteristcs are drawn against a multiple of current setting or Plug Setting

Multiplier

z Therefore characteristics can be used for any application

regardless of actual relay current setting

z e.g at 10x setting (or PSM of 10) SI curve op time is 3s

Current (Multiples of Is) 0.1 1 10 100 1000 1 10 100 Operating Time (s)

(27)

Overcurrent Protection

Current Setting

z Set just above full load current

z allow 10% tolerance

z Allow relay to reset if fault is cleared by downstream device

z consider pickup/drop off ratio (reset ratio)

z relay must fully reset with full load current flowing

z PU/DO for static/numerical = 95%

z PU/DO for EM relay = 90%

(28)

Overcurrent Protection

Current Setting

z

Current grading

z

ensure that if upstream relay has started

downstream relay has also started

z Set

upstream device current setting greater than

downstream relay

e.g. Is

R1

= 1.1 x Is

R2

(29)

Overcurrent Protection

Grading Margin

z Operating time difference between two devices to

ensure that downstream device will clear fault before upstream device trips

z Must include

z breaker opening time

z allowance for errors

z relay overshoot time

z safety margin

GRADING MARGIN

(30)

Overcurrent Protection

Grading Margin - between relays

z Traditional

z breaker op time - 0.1

z relay overshoot - 0.05

z allow. For errors - 0.15

z safety margin - 0.1

z Total 0.4s

z Calculate using formula

R2 R1

(31)

Overcurrent Protection

Grading Margin - between relays

z Formula

z t’ = (2Er + Ect) t/100 + tcb + to + ts

z Er = relay timing error

z Ect = CT measurement error

z t = op time of downstream relay

z tcb = CB interupting time

z to = relay overshoot time

z ts = safety margin

z Op time of Downstream Relay t = 0.5s

z 0.375s margin for EM relay, oil CB

(32)

Overcurrent Protection

Grading Margin - relay with fuse

z Grading Margin = 0.4Tf + 0.15s over whole characteristic

z Assume fuse minimum operating time = 0.01s

z Use EI or VI curve to grade with fuse

z Current setting of relay should be 3-4 x rating of fuse to ensure co-ordination

(33)

Overcurrent Protection

Grading Margin - relay with upstream fuse

z 1.175Tr + 0.1 + 0.1 = 0.6Tf

or

z Tf = 2Tr + 0.33s

Allowance for CT and relay error

CB Safety margin Allowance for fuse

error (fast)

Tf Tr

(34)

Overcurrent Protection

Time Multiplier Setting

z Used to adjust the operating time of an inverse

characteristic

z Not a time setting but a multiplier

z Calculate TMS to give

desired operating time in

accordance with the grading margin

Current (Multiples of Is) 0.1 1 10 100 1 10 100 Operating Time (s)

(35)

Overcurrent Protection

Time Multiplier Setting - Calculation

z Calculate relay operating time required, Treq

z consider grading margin

z fault level

z Calculate op time of inverse characteristic with TMS = 1, T1

(36)

Overcurrent Protection

Co-ordination - Procedure

z Calculate required operating current

z Calculate required grading margin

z Calculate required operating time

z Select characteristic

z Calculate required TMS

z Draw characteristic, check grading over whole curve

Grading curves should be drawn to a common voltage base to aid comparison

(37)

Overcurrent Protection

Co-ordination Example

z Grade relay B with relay A

z Co-ordinate at max fault level seen by both relays = 1400A

z Assume grading margin of 0.4s

Is = 5 Amp; TMS = 0.05, SI I FMAX = 1400 Amp B A 200/5 100/5 Is = 5 Amp

(38)

Overcurrent Protection

Co-ordination Example

z Relay B is set to 200A primary, 5A secondary

z Relay A set to 100A ∴ If (1400A) = PSM of 14

relay A OP time = t = 0.14 x TMS = 0.14 x 0.05 = 0.13 (I0.02 -1) (140.02 -1)

z Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s

z Relay A uses SI curve so relay B should also use SI curve

Is = 5 Amp; TMS = 0.05, SI IFMAX = 1400 Amp B A 200/5 100/5 Is = 5 Amp

(39)

Overcurrent Protection

Co-ordination Example

z Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s

z Relay A uses SI curve so relay B should also use SI curve

z Relay B set to 200A ∴ If (1400A) = PSM of 7

relay B OP time TMS = 1 = 0.14 x TMS = 0.14 = 3.52s

(I0.02 -1) (70.02 -1)

z Required TMS = Required Op time = 0.53 = 0.15

Op time TMS=1 3.52

z Set relay B to 200A, TMS = 0.15, SI

Is = 5 Amp; TMS = 0.05, SI I FMAX = 1400 Amp B A 200/5 100/5 Is = 5 Amp

(40)

Overcurrent Protection

LV Protection Co-ordination

ZA2118B Relay 1 Relay 2 Relay 3 Relay 4 Fuse 1 2 3 4 F 350MVA 4 4 3 3 2 F 11kV MCGG CB ACB CTZ61 (Open) CTZ61 ACB MCCB 27MVA 20MVA Load Fuse 2 x 1.5MVA 11kV/433V 5.1% K 1

(41)

Overcurrent Protection

LV Protection Co-ordination

ZA2119 1000S 100S 10S 1.0S 0.1S 0.01S

0. 1kA 10kA 1000kA

TX damage Very inverse M CCB (c o ld ) Relay 2 Relay 3 R e la y 4 F u s e

(42)

Overcurrent Protection

LV Protection Co-ordination

ZA2120C Relay 1 Relay 2 Relay 3 Relay 4 Fuse 1 2 3 4 F 350MVA 4 4 3 3 2 1 F 11kV KCGG 142 CB ACB (Open) KCEG 142 ACB MCCB 27MVA 20MVA Load Fuse 2 x 1.5MVA 11kV/433V 5.1% K

(43)

Overcurrent Protection

LV Protection Co-ordination

ZA2121 1000S 100S 10S 1.0S 0.1S 0.01S

0. 1kA 10kA 1000kA

TX damage Long time inverse M CCB (c o ld ) Relay 2 Relay 3 Relay 4 F u se

(44)

ZA2135 R3 R2 R1 Block t > I > Start IF2 IF1 M (Transient backfeed ?) Graded protection Blocked protection

Overcurrent Protection

Blocked OC Schemes

(45)
(46)

z A phase-phase fault on one side of transformer

produces 2-1-1 distribution on other side

z Use an overcurrent element in each phase (cover the 2x phase)

z 2∅ & EF relays can be used

provided fault current > 4x setting Iline 0.866 If3∅ Turns Ratio = √3 :1 Idelta

Overcurrent Protection

(47)

z Istar = E∅-∅/2Xt = √3 E∅-n/2Xt z Istar = 0.866 E∅-n/Xt z Istar = 0.866 If3 z Idelta = Istar/√3 = If3 /2 z Iline = If3 Iline 0.866 If3∅ Turns Ratio = √3 :1 Idelta

Overcurrent Protection

(48)

z Grade HV relay with respect to 2-1-1 for

∅-∅ fault

z Not only at max fault level 51 HV Ø/Ø 51 LV If3∅ 86.6%If3∅

Overcurrent Protection

(49)
(50)

z Fast clearance of faults

z ensure good operation factor, If >> Is (5 x ?)

z Current setting must be co-ordinated to prevent overtripping

z Used to provide fast tripping on HV side of transformers

z Used on feeders with Auto Reclose, prevents transient faults becoming permanent

z AR ensures healthy feeders are re-energised

z Consider operation due to DC offset - transient overreach

Overcurrent Protection

(51)

z Set HV inst 130% IfLV

z Stable for inrush

z No operation for LV fault

z Fast operation for HV fault z Reduces op times required of upstream relays HV2 HV1 LV HV2 LV TIME CURRENT HV1 IF(LV) IF(HV) 1.3IF(LV)

Overcurrent Protection

(52)
(53)

z Earth fault current may be limited

z Sensitivity and speed requirements may not be met by overcurrent relays

z Use dedicated EF protection relays

z Connect to measure residual (zero sequence) current

z Can be set to values less than full load current

z Co-ordinate as for OC elements

z May not be possible to provide co-ordination with fuses

Overcurrent Protection

(54)

z Combined with OC relays

E/F OC OC OC E/F OC OC

z Economise using 2x OC relays

Overcurrent Protection

(55)

z EF relay setting must be greater than normal

neutral current

z Independent of neutral

current but must use 3 OC relays for phase to neutral faults

E/F OC OC OC E/F OC OC OC

Overcurrent Protection

(56)

z Solid earth

z 30% Ifull load adequate

z Resistance earth

z setting w.r.t earth fault level

z special considerations for impedance earthing - directional?

Overcurrent Protection

(57)

z Settings down to 0.2% possible

z Isolated/high

impedance earth networks

z For low settings cannot use residual connection, use dedicated CT

z Advisable to use core balance CT

z CT ratio related to earth fault current not line current

z Relays tuned to system frequency to reject 3rd harmonic B C E/F A

Overcurrent Protection

(58)

z Need to take care with core balance CT and armoured cables

z Sheath acts as earth return path

z Must account for earth current path in connections - insulate cable gland NO OPERATION OPERATION CABLE BOX CABLE GLAND CABLE GLAND/SHEATH EARTH CONNECTION E/F

Overcurrent Protection

References

Related documents

For this type of culvert it is important to align the culvert with the natural river or stream, it is also necessary for the cross sectional area of the culvert to be the same size

On the initiative of the Danish Energy Agency, the REFU Advisory Body on Energy Research formulated in April 2006 a Strategy for energy research, development and trial based on

Tourism finance decisions are the processes involved in the responsible choices that relates to looking for potential investment alternatives that tourism organizations

Mortality surveillance incorporating verbal autopsy tool revealed a transition in cause of deaths from respiratory diseases to cardiovascular diseases over the decade.. Focus of

One might argue for government participation on slightly different grounds, however, relating to the observation that private reinsurers facing capacity constraints will

required, you must enter the correct Export Control Classification Number (ECCN) on the SED or AES record for all exports authorized under a license or License Exception, and

Paz A, Brown J, Cordeiro CLO, Aguirre-Santoro J, Bacci LF, Kaehler M, Assis C, Caddah MK, Reginato M, Lyra ML, Amaro RC, Amaral F, d’Horta F, Freitas AVL, Goldenberg R, Lohmann L

The Aboriginal sacred stories are stories about events of the Dreaming and how Ancestral (Spirit) Beings formed the land, and founded life on the land.. Dreaming is the unseen