Application of Non-Directional Overcurrent
and Earthfault Protection
Non-Directional Overcurrent and Earth
Fault Protection
Overcurrent Protection
Purpose of Protection
z Detect abnormal conditions
z Isolate faulty part of the system
z Speed
z Fast operation to minimise damage and danger
z Discrimination
z Isolate only the faulty section
z Dependability / reliability
z Security / stability
Overcurrent Protection
Co-ordination
z Co-ordinate protection so that relay nearest to fault operates first
z Minimise system disruption due to the fault
F1 F2
F3 F3 F2
Overcurrent Protection
Fuses
z Simple
z Can provide very fast fault clearance
z <10ms for large current
z Limit fault energy
Pre Arc Time
Arcing Time
Prospective Fault Current
Total
Operating Time
Overcurrent Protection
Fuses - disadvantages
z Problematic co-ordination
z IFA approx 2 x IFB
z Limited sensitivity to earth faults
z Single phasing
z Fixed characteristic
z Need replacing following fault clearance
Overcurrent Protection
Direct Acting AC Trip
z AC series trip
z common for electromechanical O/C relays
51
IF
Overcurrent Protection
Direct Acting AC Trip
z Capacitor discharge trip
z used with static relays where no secure DC supply is available IF' Sensitive Trip Coil IF 51 +
-Overcurrent Protection
DC Shunt Trip
z Requires secure DC auxiliary
z No trip if DC fails IF' IF DC BATTERY SHUNT TRIP COIL 51
Overcurrent Protection
Principles
z Operating Speed z Instantaneous z Time delayed z Discrimination z Current setting z Time settingz Current and time
z Cost
IF1
IF1
IF2
Overcurrent Protection
Instantaneous Relays
z Current settings chosen so that relay closest to fault operates
z Problem
z Relies on there being a difference in fault level between the two relay locations
z Cannot discriminate if IF1 = IF2 50 B 50 A IF1 IF2
Overcurrent Protection
Definite (Independent) Time Relays
TOP TIME
IS Applied Current
Overcurrent Protection
Definite (Independent) Time Relays
z Operating time is independent of current
z Relay closest to fault has shortest operating time
z Problem
z Longest operating time is at the source where fault level is highest
51
0.9 sec 0.5 sec
Overcurrent Protection
IDMT
z Inverse Definite Minimum Time characteristic
TIME
Applied Current (Relay Current Setting)
Overcurrent Protection
Disc Type O/C Relays
z Current setting via plug bridge
z Time multiplier setting via disc movement
z Single characteristic
z Consider 2 ph & EF or 3 ph plus additional EF relay
Overcurrent Protection
Static Relay
z Electronic, multi characteristic
z Fine settings, wide range
z Integral instantaneous elements
RESET A B C INST t I > Is INST t I > Is No Ph+ I n Vx V Hz 0.05 0 0 0 0 0 0 1 1 1 0.05 0.05 0.1 0.2 0.3 0.4 1 2 4 8 10 ∝ 0.05 0 0 0 0 0 0 1 1 1 0.05 0.05 0.1 0.2 0.3 0.4 1 2 4 8 10 ∝ 0.1 0.1 0.2 0.4 0.4 0.4 0.8 0 0 0 0.025 0 0 0 0 0 0 0 0 0 0 0 D LT1 S 1 V 1 E1 I t s I = Σ x I s s I = Σ x I s x t = Σ x t = Σ IINST = Σ x Is IINST= Σ x Is M CG G
Overcurrent Protection
Numerical Relay
z Multiple characteristics and stages
z Current settings in primary or secondary values
z Additional protection elements
Current Time I>1 I>2 I>3 I>4
Overcurrent Protection
Co-ordination Principle
z Relay closest to fault must operate first
z Other relays must have adequate additional
operating time to
prevent them operating
z Current setting chosen to allow FLC
z Consider worst case conditions, operating modes and current flows T IS1 IS2 Maximum Fault Level I R2 R1 IF1
Overcurrent Protection
Co-ordination Example
C B A 0.01 0.1 1 10 Operating time (s) Current (A) FLB FLC FLD E D C B D EOvercurrent Protection
IEC Characteristics
z SI t = 0.14 (I0.02 -1) z VI t = 13.5 (I2 -1) z EI t = 80 (I2 -1) z LTI t = 120 (I - 1)Current (Multiples of Is) 0.1 1 10 100 1000 1 10 100 Operating Time (s) VI EI SI LTI
Overcurrent Protection
Operating Time Setting - Terms Used
z Relay operating times can be calculated using relay
characteristic charts
z Published characteristcs are drawn against a multiple of current setting or Plug Setting
Multiplier
z Therefore characteristics can be used for any application
regardless of actual relay current setting
z e.g at 10x setting (or PSM of 10) SI curve op time is 3s
Current (Multiples of Is) 0.1 1 10 100 1000 1 10 100 Operating Time (s)
Overcurrent Protection
Current Setting
z Set just above full load current
z allow 10% tolerance
z Allow relay to reset if fault is cleared by downstream device
z consider pickup/drop off ratio (reset ratio)
z relay must fully reset with full load current flowing
z PU/DO for static/numerical = 95%
z PU/DO for EM relay = 90%
Overcurrent Protection
Current Setting
z
Current grading
z
ensure that if upstream relay has started
downstream relay has also started
z Set
upstream device current setting greater than
downstream relay
e.g. Is
R1= 1.1 x Is
R2Overcurrent Protection
Grading Margin
z Operating time difference between two devices to
ensure that downstream device will clear fault before upstream device trips
z Must include
z breaker opening time
z allowance for errors
z relay overshoot time
z safety margin
GRADING MARGIN
Overcurrent Protection
Grading Margin - between relays
z Traditional
z breaker op time - 0.1
z relay overshoot - 0.05
z allow. For errors - 0.15
z safety margin - 0.1
z Total 0.4s
z Calculate using formula
R2 R1
Overcurrent Protection
Grading Margin - between relays
z Formula
z t’ = (2Er + Ect) t/100 + tcb + to + ts
z Er = relay timing error
z Ect = CT measurement error
z t = op time of downstream relay
z tcb = CB interupting time
z to = relay overshoot time
z ts = safety margin
z Op time of Downstream Relay t = 0.5s
z 0.375s margin for EM relay, oil CB
Overcurrent Protection
Grading Margin - relay with fuse
z Grading Margin = 0.4Tf + 0.15s over whole characteristic
z Assume fuse minimum operating time = 0.01s
z Use EI or VI curve to grade with fuse
z Current setting of relay should be 3-4 x rating of fuse to ensure co-ordination
Overcurrent Protection
Grading Margin - relay with upstream fuse
z 1.175Tr + 0.1 + 0.1 = 0.6Tf
or
z Tf = 2Tr + 0.33s
Allowance for CT and relay error
CB Safety margin Allowance for fuse
error (fast)
Tf Tr
Overcurrent Protection
Time Multiplier Setting
z Used to adjust the operating time of an inverse
characteristic
z Not a time setting but a multiplier
z Calculate TMS to give
desired operating time in
accordance with the grading margin
Current (Multiples of Is) 0.1 1 10 100 1 10 100 Operating Time (s)
Overcurrent Protection
Time Multiplier Setting - Calculation
z Calculate relay operating time required, Treq
z consider grading margin
z fault level
z Calculate op time of inverse characteristic with TMS = 1, T1
Overcurrent Protection
Co-ordination - Procedure
z Calculate required operating current
z Calculate required grading margin
z Calculate required operating time
z Select characteristic
z Calculate required TMS
z Draw characteristic, check grading over whole curve
Grading curves should be drawn to a common voltage base to aid comparison
Overcurrent Protection
Co-ordination Example
z Grade relay B with relay A
z Co-ordinate at max fault level seen by both relays = 1400A
z Assume grading margin of 0.4s
Is = 5 Amp; TMS = 0.05, SI I FMAX = 1400 Amp B A 200/5 100/5 Is = 5 Amp
Overcurrent Protection
Co-ordination Example
z Relay B is set to 200A primary, 5A secondary
z Relay A set to 100A ∴ If (1400A) = PSM of 14
relay A OP time = t = 0.14 x TMS = 0.14 x 0.05 = 0.13 (I0.02 -1) (140.02 -1)
z Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s
z Relay A uses SI curve so relay B should also use SI curve
Is = 5 Amp; TMS = 0.05, SI IFMAX = 1400 Amp B A 200/5 100/5 Is = 5 Amp
Overcurrent Protection
Co-ordination Example
z Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s
z Relay A uses SI curve so relay B should also use SI curve
z Relay B set to 200A ∴ If (1400A) = PSM of 7
relay B OP time TMS = 1 = 0.14 x TMS = 0.14 = 3.52s
(I0.02 -1) (70.02 -1)
z Required TMS = Required Op time = 0.53 = 0.15
Op time TMS=1 3.52
z Set relay B to 200A, TMS = 0.15, SI
Is = 5 Amp; TMS = 0.05, SI I FMAX = 1400 Amp B A 200/5 100/5 Is = 5 Amp
Overcurrent Protection
LV Protection Co-ordination
ZA2118B Relay 1 Relay 2 Relay 3 Relay 4 Fuse 1 2 3 4 F 350MVA 4 4 3 3 2 F 11kV MCGG CB ACB CTZ61 (Open) CTZ61 ACB MCCB 27MVA 20MVA Load Fuse 2 x 1.5MVA 11kV/433V 5.1% K 1Overcurrent Protection
LV Protection Co-ordination
ZA2119 1000S 100S 10S 1.0S 0.1S 0.01S0. 1kA 10kA 1000kA
TX damage Very inverse M CCB (c o ld ) Relay 2 Relay 3 R e la y 4 F u s e
Overcurrent Protection
LV Protection Co-ordination
ZA2120C Relay 1 Relay 2 Relay 3 Relay 4 Fuse 1 2 3 4 F 350MVA 4 4 3 3 2 1 F 11kV KCGG 142 CB ACB (Open) KCEG 142 ACB MCCB 27MVA 20MVA Load Fuse 2 x 1.5MVA 11kV/433V 5.1% KOvercurrent Protection
LV Protection Co-ordination
ZA2121 1000S 100S 10S 1.0S 0.1S 0.01S0. 1kA 10kA 1000kA
TX damage Long time inverse M CCB (c o ld ) Relay 2 Relay 3 Relay 4 F u se
ZA2135 R3 R2 R1 Block t > I > Start IF2 IF1 M (Transient backfeed ?) Graded protection Blocked protection
Overcurrent Protection
Blocked OC Schemesz A phase-phase fault on one side of transformer
produces 2-1-1 distribution on other side
z Use an overcurrent element in each phase (cover the 2x phase)
z 2∅ & EF relays can be used
provided fault current > 4x setting Iline 0.866 If3∅ Turns Ratio = √3 :1 Idelta
Overcurrent Protection
z Istar = E∅-∅/2Xt = √3 E∅-n/2Xt z Istar = 0.866 E∅-n/Xt z Istar = 0.866 If3∅ z Idelta = Istar/√3 = If3∅ /2 z Iline = If3∅ Iline 0.866 If3∅ Turns Ratio = √3 :1 Idelta
Overcurrent Protection
z Grade HV relay with respect to 2-1-1 for
∅-∅ fault
z Not only at max fault level 51 HV Ø/Ø 51 LV If3∅ 86.6%If3∅
Overcurrent Protection
z Fast clearance of faults
z ensure good operation factor, If >> Is (5 x ?)
z Current setting must be co-ordinated to prevent overtripping
z Used to provide fast tripping on HV side of transformers
z Used on feeders with Auto Reclose, prevents transient faults becoming permanent
z AR ensures healthy feeders are re-energised
z Consider operation due to DC offset - transient overreach
Overcurrent Protection
z Set HV inst 130% IfLV
z Stable for inrush
z No operation for LV fault
z Fast operation for HV fault z Reduces op times required of upstream relays HV2 HV1 LV HV2 LV TIME CURRENT HV1 IF(LV) IF(HV) 1.3IF(LV)
Overcurrent Protection
z Earth fault current may be limited
z Sensitivity and speed requirements may not be met by overcurrent relays
z Use dedicated EF protection relays
z Connect to measure residual (zero sequence) current
z Can be set to values less than full load current
z Co-ordinate as for OC elements
z May not be possible to provide co-ordination with fuses
Overcurrent Protection
z Combined with OC relays
E/F OC OC OC E/F OC OC
z Economise using 2x OC relays
Overcurrent Protection
z EF relay setting must be greater than normal
neutral current
z Independent of neutral
current but must use 3 OC relays for phase to neutral faults
E/F OC OC OC E/F OC OC OC
Overcurrent Protection
z Solid earth
z 30% Ifull load adequate
z Resistance earth
z setting w.r.t earth fault level
z special considerations for impedance earthing - directional?
Overcurrent Protection
z Settings down to 0.2% possible
z Isolated/high
impedance earth networks
z For low settings cannot use residual connection, use dedicated CT
z Advisable to use core balance CT
z CT ratio related to earth fault current not line current
z Relays tuned to system frequency to reject 3rd harmonic B C E/F A
Overcurrent Protection
z Need to take care with core balance CT and armoured cables
z Sheath acts as earth return path
z Must account for earth current path in connections - insulate cable gland NO OPERATION OPERATION CABLE BOX CABLE GLAND CABLE GLAND/SHEATH EARTH CONNECTION E/F