Report Prepared For:
Jeffrey R Rexford
75-5681 Kuakini Highway 219
Report Prepared For: Jeffrey R Rexford
TABLE of CONTENTS
TABLE of CONTENTS ... 2
SUMMARY REPORT ... 3
GENERAL INFORMATION ... 5
INTRODUCTION AND STRUCTURAL OVERVIEW ... 5
PURPOSE AND SCOPE ... 6
GENERAL LIMITATIONS AND EXCLUSIONS ... 7
PLUMBING SYSTEM ... 8
ELECTRICAL SYSTEM ... 11
INTERIOR ... 14
SUMMARY REPORT
Note: This analysis is not meant to be technically exhaustive but rather to highlight areas where repairs are needed or areas of long-term future concern relating to maintenance and operation.
This summary lists items taken from the main report that we feel need immediate attention or consideration. It is entirely the customer's decision whether or not to include additional items from the main report that they may have concerns about.
Further, the Summary is not a substitute for reading and understanding the complete report .
PLUMBING SYSTEM
When reference is made to the type of plumbing, the comment relies on a visual observation, seller
statements, the presence or absence of a water bond, and what may be present in the way of notification
in the electrical service panel. There is no non-invasive way to determine what is behind a closed wall. For
example, when copper plumbing is identified, copper piping protrudes from the walls behind plumbing
fixtures. If client requires absolute knowledge as to the type of plumbing throughout the home, then a
consultation with a licensed plumbing contractor is recommended.
Please note: Inspectors are not required to determine the source of the water supply or operate any valve
except water closet flush valves, fixture faucets, and hose bibs. Solar systems, septic systems, wells, filters,
conditioners, yard watering systems and fire sprinkler systems are not part of this inspection.
Please note: Water stop valves and overflows are not checked for function during a home inspection.
Fixtures and trim are observed for function only and not for cosmetic value.
The drain assembly is inoperable at the bathtub. Recommendation: Replace the drain assembly.
ELECTRICAL SYSTEM
The smoke alarms were tested and found to be working in the manner intended at the time of the
inspection.
A representative number of switches and receptacles that are readily accessible are tested for function.
Determination of adequacy of electrical panels and current capacity are not within the scope of this
report. Low voltage systems, stereos, intercoms, vacuum systems, security systems or other low voltage
systems are not inspected and are not within the scope of a home inspection.
The left switch on the entry wall to the living room does not appear to control anything. Recommendaiotn:
Consult the seller for details.
Report Prepared For: Jeffrey R Rexford
INTERIOR
There are minor blemishes throughout the home that are of no real significance other than cosmetic.
APPLIANCES
GENERAL INFORMATION
Inspection Address
Street: 75-5681 Kuakini Hwy 219
City: Kailua Kona
State: Hawaii
Zip: 96740
INTRODUCTION AND STRUCTURAL OVERVIEW
Inspection Details
Inspection Date: June 21, 2021
Report Date: June 21, 2021
Report Delivered: by web site download
Weather Conditions: sunny
Temperature: 75 degrees
Present During Inspection: buyer and buyer's agent
Building Occupied: yes occupied
Inspection Limited to: plumbing, electrical, kitchen, and bathroom
Building Details
Date Built: 1974
Approximate Age: 47 years
Approximate Area: 754 Sq. Ft.
Legal Description
Lot: 3750040200041
Client Information
Name: Jeffrey R Rexford
Address: 565 Lori Drive 14
City: Bernicia
State: California
Zip: 94510
Cell: 925-899-1425
Report Prepared For: Jeffrey R Rexford
Buyer’s Agent Information
Name: Dayna Apilado
Company: Corcoran Pacific Properties
City: Kailua Kona
State: Hawaii
Zip: 96740
Cell: 808-895-6389
Email: [email protected]
Inspected By
Name: Warren d'Aquin
Company Information
Company: Kona Home Inspections
Address: PO Box 1508
City: Kealakekua
State: Hawaii
Zip: 96750
Phone: 808-769-0545
Email: [email protected]
Web Site: https://konahomeinspections.com
PURPOSE AND SCOPE
It should be noted that a standard pre-purchase inspection is a visual assessment of the condition of the residence at the time of inspection. The inspection and inspection report are offered as an opinion only. Although every reasonable effort is made to discover and correctly interpret indications of previous or ongoing defects that may be present, it must be understood that no guarantee is implied nor responsibility assumed by the inspector or inspection company, for the actual condition of the building or property being examined. Additional information as to inspection standards is included at the end of the report.
This firm endeavors to perform all inspections in substantial compliance with the standards of practice of the American Society of Home Inspectors (ASHI). As such, inspectors inspect the readily accessible and installed components and systems of a home as outlined below:
GENERAL LIMITATIONS AND EXCLUSIONS
The ASHI Standards of Practice are applicable to buildings with four or fewer dwelling units and their garages or carports. They are the bare minimum standard for a home inspection, are not technically exhaustive and do not identify concealed conditions or latent defects. Inspectors are NOT required to determine the condition of any system or component that is not readily accessible; the remaining service life of any system or component; the strength, adequacy, effectiveness or efficiency of any system or component; causes of any condition or deficiency; methods materials or cost of corrections; future conditions including but not limited to failure of systems and components; the suitability of the property for any specialized use; compliance with regulatory codes, regulations, laws or ordinances; the market value of the property or its marketability; the advisability of the purchase of the property; the presence of potentially hazardous plants or animals including but not limited to wood destroying organisms or diseases harmful to humans; the presence of any environmental hazards including, but not limited to toxins, carcinogens, noise, and contaminants in soil, water or air; the effectiveness of any system installed or methods utilized to control or remove suspected hazardous substances; the operating costs of any systems or components and the acoustical properties of any systems or components.
Inspectors are NOT required to operate any system or component that is shut down or otherwise inoperable; any system or component which does not respond to normal operating controls or any shut off valves.
Inspectors are NOT required to offer or perform any act or service contrary to law; offer or perform engineering services or work in any trade or professional service other than home inspection.
Inspectors DO NOT offer or provide warranties or guarantees of any kind unless clearly explained and agreed to by both parties in a formal pre-inspection agreement.
Inspectors are NOT required to inspect underground items including, but not limited to underground storage tanks or other underground indications of their presence, whether abandoned or active; systems or components that are not installed; decorative items; systems or components that are in areas not entered in accordance with the ASHI Standards of Practice; detached structures other than carports or garages; common elements or common areas in multi-unit housing, such as condominium properties or cooperative housing.
Inspectors are NOT required to perform any procedure or operation which will, in the opinion of the inspector, likely be dangerous to the inspector or others or damage the property, its systems or components; move suspended ceiling tiles, personal property, furniture, equipment, plants, soil, snow, ice or debris or dismantle any system or component, except as explicitly required by the ASHI Standards of Practice.
Report Prepared For: Jeffrey R Rexford
PLUMBING SYSTEM
In accordance with the ASHI © standard of practice pertaining to Plumbing Systems, this report describes the water supply, drain, waste and vent piping materials and the water heating equipment, energy source and location of the main water and main fuel shut-off valves, when readily viewable or known. Inspectors are required to inspect the interior water supply and distribution systems, all fixtures and faucets, the drain waste and vent systems (including all fixtures for conveying waste), the water heating equipment (vent systems, flues and chimneys of water heaters or boiler equipment), fuel storage and distributions systems for water heaters and/or boiler equipment and drainage sumps, sump pumps and associated piping.
COMPONENT DESCRIPTIONS
The inspection of the plumbing system includes checking all faucets and fixtures for cross-connection and
leaks. Cross-contamination issues are also included as well as pressure, functional flow and functional
drainage.
Supply and Piping
Supply and Waste System: municipal supply and waste system
Branch Piping Size: 1/2-inch and 3/4-inch
Branch Piping Type: copper, PEX, and galvanized steel
Fixtures/Faucets Condition: Good condition-no issues
Functional Flow: satisfactory
Function Drainage: satisfactory
Waste and Vent Piping: schedule 40 ABS plastic and cast iron/galvanized steel
Condition: no access-not inspected
1Water Heater
Water Heater Type: one conventional storage tank
Water Heater Energy Source: electricity
Capacity: 40 Gallons
Water Heater Location: interior closet
Condition: good condition-no issues
Automatic Safety Controls (TPR) Condition: satisfactory condition-no defects apparent
Water Controls and Drains
Main Water Shut Off Location: common system for entire complex
OBSERVATIONS
When reference is made to the type of plumbing, the comment relies on a visual observation, seller
statements, the presence or absence of a water bond, and what may be present in the way of notification
in the electrical service panel. There is no non-invasive way to determine what is behind a closed wall. For
example, when copper plumbing is identified, copper piping protrudes from the walls behind plumbing
fixtures. If client requires absolute knowledge as to the type of plumbing throughout the home, then a
consultation with a licensed plumbing contractor is recommended.
Please note: Inspectors are not required to determine the source of the water supply or operate any valve
except water closet flush valves, fixture faucets, and hose bibs. Solar systems, septic systems, wells, filters,
conditioners, yard watering systems and fire sprinkler systems are not part of this inspection.
Report Prepared For: Jeffrey R Rexford
The drain assembly is inoperable at the bathtub. Recommendation: Replace the drain assembly.
ELECTRICAL SYSTEM
In accordance with the ASHI© standard of practice pertaining to Electrical Systems, this report describes the amperage and voltage rating of the service, the location of the main disconnect and any sub panel(s), the presence of solid conductor aluminum branch circuit wiring and the absence of smoke detectors. Inspectors are required to inspect the viewable portions of the service drop from the utility to the house, the service entrance conductors, cables and raceways, the service equipment and main disconnects, the service grounding, the interior components of the service panels and sub panels, the conductors, the over-current protection devices (fuses or breakers), ground fault circuit interrupters and a representative number of installed lighting fixtures, switches and receptacles.
COMPONENT DESCRIPTIONS
Service Entry
Meter Location: in a mechanical room
Main Disconnect
Main Disconnect Type: breaker
Main Disconnect Rating: 100 amps
Main Disconnect Location: inside the service entrance panel
Main Panel
Service Entrance Panel Location: inside closet
Panel Style: breaker system
Report Prepared For: Jeffrey R Rexford
Distribution Wiring
Wiring Type: EMT
Wiring Conductors: copper
Condition: good condition
GFCI Locations: in the home
1Outlets & Switches Tested: inside the building
Polarity & Ground Tested: inside the building
Smoke Alarm Detectors
Smoke Alarms: Alarms Found
OBSERVATIONS
The smoke alarms were tested and found to be working in the manner intended at the time of the
inspection.
A representative number of switches and receptacles that are readily accessible are tested for function.
Determination of adequacy of electrical panels and current capacity are not within the scope of this
report. Low voltage systems, stereos, intercoms, vacuum systems, security systems or other low voltage
systems are not inspected and are not within the scope of a home inspection.
The left switch on the entry wall to the living room does not appear to control anything. Recommendation:
Consult the seller for details.
There is a label in the panel box saying to leave the breaker to the disposal off. Recommendation: Consult
the seller for details.
Report Prepared For: Jeffrey R Rexford
INTERIOR
In accordance with the ASHI© standard of practice pertaining to Interiors, there is NO requirement for the report to describe any interior components or finishes. Inspectors are required to inspect walls, ceilings and floors, steps, stairways and railings, countertops and a representative number of cabinets, a representative number of doors and windows and the garage doors and automatic garage operators.