NetSure 701 A41, NetSure 501 A41, NetSure 501 A91
Subrack Power system User Manual
Version
V1.0
Revision date
August 29, 2012
BOM
31012653
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Copyright © 2012 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
Safety Precautions
To reduce the chance of accident, please read the safety precautions very carefully before operation. The "Caution, Notice, Warning, Danger" in this book do not represent all the safety points to be observed, and are only supplement to various safety points. Therefore, the installation and operation personnel must be strictly trained and master the correct operations and all the safety points before actual operation.
When operating Emerson products, the safety rules in the industry, the general safety points and special safety instructions specified in this book must be strictly observed.
Electrical Safety
I. Hazardous voltageDanger
Some components of the power system carry hazardous voltage in operation. Direct contact or indirect contact through moist objects with these components will result in fatal injury.
Safety rules in the industry must be observed when installing the power system. The installation personnel must be licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets, bangles, rings.
When water or moisture is found on the Subrack, turn off the power immediately. In moist environment, precautions must be taken to keep moisture out of the power system.
"Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during installation.
Danger
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high voltage operations.
II. Tools
Warning
In high voltage and AC operation, special tools must be used. No common or self-carried tools should be used.
III. Thunderstorm
Danger
Never operate on high voltage, AC, iron tower or mast in the thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be well earthed in time to avoid damage by lightning strikes.
IV. ESD
Notice
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.
V. Short circuit
Danger
During operation, never short the positive and negative poles of the DC distribution unit of the system or the non-grounding pole and the earth. The power system is a constant voltage DC power equipment, short circuit will result in equipment burning and endanger human safety.
Check carefully the polarity of the cable and connection terminal when performing DC live operations. As the operation space in the DC distribution unit is very tight, please carefully select the operation space. Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.
Insulated tools must be used.
In live operation, keep the arm muscle tense, so that when tool connection is loosened, the free movement of the human body and tool is reduced to a minimum.
VI. Dangerous energy
Warning
240VA, hazardous energy, keep off, no bridge connection. This converter contains outputs exceed 240VA, when installing into end system care must be taken that the output and appropriate wire may not be touched.
Battery
Danger
Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery connection method.
Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs, thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points:
Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist. Use special insulated tools.
Use eye protection device, and take preventive measures.
Wear rubber gloves and apron to guard against electrolyte overflow.
In battery transportation, the electrode of the battery should always be kept facing upward. Never put the battery upside down or slanted.
BLVD
The system has battery low voltage disconnection (BLVD) function. BLVD means when the mains fail and batteries supply power, the monitoring module cuts the load off when the battery voltage drops down to below 43.2V to prevent over-discharge. The BLVD voltage is settable. Refer to 4.2.3 Battery Selection for setting method.
The factory setting is enabling BLVD, which means that if power outage lasts for a long time or the power system fails, there might be BLVD. Users should classify the loads and connect the priority loads to BLVD routes. For vital loads, users can disable BLVD of these loads to insure reliability of the power supply.
The method of disabling BLVD is:
Set “BLVD Enable” item of the monitoring module to “N”. Refer to 4.2.3 错误错误错误错误 !!!! 未找到引用源未找到引用源未找到引用源 。未找到引用源。。。 for setting method.
Notice
The advantage of enabling BLVD is protecting the batteries from over-discharge when the battery voltage is low. The disadvantage of enabling BLVD is that when the battery voltage drops down to a certain value, all the loads (including non-priority loads and priority loads) will be cut off due to battery disconnection.
The advantage of software disabling BLVD is prolonging the power supply of priority loads. The disadvantage is that software disabling cannot prevent unwanted power failure due to misoperation or power system failure.
Others
I. Sharp object
Warning
When moving equipment by hand, protective gloves should be worn to avoid injury by sharp object.
II. Cable connection
Notice
Please verify the compliance of the cable and cable label with the actual installation prior to cable connection.
III. Binding the signal lines
Notice
The signal lines should be bound separately from heavy current and high voltage lines, with binding interval of at least 150mm.
Contents
Chapter 1 Overview ... 1
1.1 Model Information ... 1
1.2 Composition And Configuration ... 1
1.3 Features ... 4
Chapter 2 Installation Instruction ... 5
2.1 Safety Regulations ... 5
2.2 Preparation ... 5
2.3 Mechanical Installation ... 6
2.4 Electrical Installation ... 9
2.4.1 Power System Cabling Method ... 9
2.4.2 Connecting AC Input Cables ... 10
2.4.3 Connecting Load Cables ... 11
2.4.4 Connecting Battery Cables ... 11
2.4.5 Connecting Signal Cables ... 12
Chapter 3 Installation Testing ... 16
3.1 Installation Check And Startup ... 16
3.2 Basic Settings ... 16
3.3 Alarm Check And System Operation Status Check ... 17
3.4 Final Steps ... 18
Chapter 4 Use Of Monitoring Module M221S、M221S ... 19
4.1 Control Keypad And Indicator ... 19
4.1.1 Front Panel ... 19
4.1.2 Indicator Function ... 19
4.1.3 Control Keypad Function ... 19
4.2 LCD Menu Tree ... 20 4.2.1 Status ... 20 4.2.2 Settings... 21 4.2.3 Manual ... 28 4.2.4 ECO ... 28 4.2.5 Quick Setting ... 28 4.2.6 Controller Setting ... 29
4.3 WEB Interface Operation ... 30
4.3.1 Setting Up The Internet Explorer Web Browser ... 30
4.3.2 Logging Into The Controller ... 31
4.3.3 Homepage Introduction ... 32
4.4 WEB Bootloader Interface Operation ... 36
Chapter 5 Use Of Monitoring Module M820B ... 41
5.1 Operation Panel ... 41
5.2 First Screen... 42
5.3 Default Main Screen ... 42
5.4 Overall Menu Structure ... 43
5.5 Main Menu ... 43
5.6 Status ... 44
5.7 Manual ... 46
5.7.1 Settings... 47
5.7.2 Power System Setting ... 55
5.7.3 Rectifier Setting ... 57
5.7.4 Battery Setting ... 57
5.7.5 Parameter Settings Of BattFuseUnit ... 59
5.7.6 Parameter Settings Of DC ... 59
5.7.7 Parameter Setting Of LVD ... 59
5.7.8 AC Parameter Settings ... 60
5.7.9 Communication Parameter Settings ... 60
5.7.10 Controller Parameter Settings ... 60
5.8 Energy Saving Setting ... 60
5.9 Quick Settings ... 61
5.10 Access M820B Through Web ... 61
5.10.1 Login ... 62
5.10.2 Homepage Introduction ... 63
5.10.3 Device Information ... 64
5.10.4 Data Browse, Control And Parameter Setting Of Rectifier ... 64
5.10.5 Data Browse, Control And Parameter Setting Of Battery ... 67
5.10.6 Alarms ... 69
5.10.7 Maintenance ... 70
5.10.8 Configurations ... 78
5.10.9 Query ... 83
5.11 Access ACU+ Through NMS ... 85
5.11.1 NMS Supported By SNMP Agent ... 85
5.11.2 MIB Installation ... 85
5.11.3 Access ACU+ Through NMS ... 86
5.11.4 ESR Configure ... 87
Chapter 6 Alarm Handling ... 88
6.1 Handling Alarms ... 88
Appendix 1 Technical And Engineering Data ... 91
Appendix 2 Installation Instruction Of Battery Rack ... 95
1. Installation Instruction Of Two-Layer And Four-Layer Battery Rack ... 95
2. Installation Instruction Of Three-Layer Battery Rack ... 97
3. Fixing The Battery Rack ... 98
Appendix 3 Wiring Diagram ... 99
Appendix 4 Shematic Diagram ... 107
Chapter 1 Overview
This chapter introduces model description, composition and configuration, and features.
The “power system” in this manual refers to the NetSure NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 series 19 subrack power system.
1.1 Model Information
Take NetSure 501 A41-S1 power system as an example, the model description is given in Figure 1-1.
NetSure 501 A 4
Region. A: Asia-Pacific region
Output power of the rectifier. 501: 1740W
~
2000W. 701: 2900W~
5000WBrand name of the power supply system
1
Version
The number of the rectifier in the typical power supply system: 4. If the number ranges between 0 ~ 9, the character is represented by a number. If the number is larger than 9, the character isrepresented by a letter, for example, A represents the number 10, B represents the number 11,and so on
S 1
Cabinet type: Subrack Cabinet configuration
Figure 1-1Model information
1.2 Composition And Configuration
System composition
The system consists of power distribution parts, rectifiers and monitoring module. The rectifier model is R48-1800, R48-2900U or R48-3200 and the model of the monitoring module is M221S, M222S or M820B. The internal structures of the systems are shown in Figure 1-2 to Figure 1-6.
Dummy panel Load MCB Rectifier Monitoring module Battery MCB Positive terminals Controller AC input MCB
Figure 1-3 NetSure 501 A91-S1 system structure
Figure 1-4 NetSure 701 A41 –S2/S4 system structure
Figure 1-5 NetSure 701 A41-S1/S3/S5 system structure
Figure 1-6 NetSure 701 A41-S5 system structure
System configuration
Table 1-1 Configuration of fixed- configuration system
Item NetSure 501 A41-S1 NetSure 501 A41-S2 NetSure 501 A91-S1 NetSure 701 A41-S1 NetSure 701 A41-S2 NetSure 701 A41-S3 NetSure 701 A41-S4 NetSure 701 A41-S5
Contorller Model: M221S/M222S Model: M820B Model: M221S/M222S Model: M221S/M222S Model: M221S/M222S Model: M221S/M222S Model: M820B Model: M221S/M222S Rectifier Model: R48-1800A/R48-2000/ R48-2000e Standard configuration:4 pieces Model: R48-1800A/R48-2000/ R48-2000e Standard configuration:4 pieces Model: R48-1800A/R48-2000 /R48-2000e Standard configuration:5 pieces Model: R48-2900U/R48-300 0e/R48-3200/R48-35 00e/R48-4000e Standard configuration:3 pieces Model: R48-2900U/ R48-3000e R48- 3200 R48-3500e R48-4000e Standard configuration:4 pieces Model: R48-2900U/ R48-3000e R48- 3200 R48-3500e R48-4000e Standard configuration:4 pieces Model: R48-2900U/ R48-3000e R48- 3200 R48-3500e R48-4000e Standard configuration:4 pieces Model: R48-2900U/ R48-3000e R48- 3200 R48-3500e R48-4000e Standard configuration:4个 AC power distribution
L+N+PE/ 220Vac L+N+PE/220Vac 3P+N+PE/380Vac 3P+N+PE/380Vac L+N+PE/380Vac 3P+N+PE/ 220Vac 3P+N+PE/ 380Vac L+N+PE/ 220Vac
DC power distribution BLVD load route: 2 × 16A/1P, MCB LLVD load route: 2 × 63A/1P, 2 × 32A/1P MCB BLVD load route: 2 × 10A/1P, 2 × 32A/1PMCB LLVD load route: 2 × 63A/1P, 2 × 32A/1P MCB BLVD load route: 5 × 63A/1P, 5 × 32A/1P, 8 × 10A/1P MCB LLVD load route: Not configured BLVD load route: 1 × 10A/1P MCB LLVD load route: 4 × 40A/1P MCB BLVD load route: 4 × 63A/1P, 6 × 32A/1P, 2 × 10A/1P MCB LLVD load route: Not configured BLVD load route: 2 × 32A/1P, 2 × 16A/1P MCB LLVD load route: 2×63A/1P, 4×32A/1P, 2×16A/1P MCB BLVD load route: 2 × 63A/1P 4 × 32A/1P, 4 × 10A/1P MCB LLVD load route: 2×100A/1P 2×63A/1P, 2×32A/1P MCB BLVD load route: 2 × 32A/1P, 2 × 16A/1P MCB LLVD load route: 2×63A/1P, 4× 32A/1P MCB
Battery MCB 2 × 63A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P
AC SPD 1 piece Optional Optional Optional Optional 1 piece Optional 1 piece
DC SPD 1 piece Optional Optional Optional Optional 1 piece Optional 1 piece
Max.size (mm) 483 × 360 × 222 483 × 360 × 222 483 × 360 × 400 483 × 360 × 267 483 × 360 × 267 483 × 360 × 267 483 × 360 × 400 483 × 360 × 267
BLVD contorller mode
Contorller power-off Contorller power-on Contorller power-on Contorller power-on Contorller power-on Contorller power-off Contorller power-on Contorller power-off
Weight ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg
Notes:
1. Temperature sensor and connected cables, remote monitoring unit, battery rack.
1.3 Features
The rectifier uses the active Power Factor Compensation (PFC) technology, raising the power factor to 0.99. Wide AC input voltage range: 85V ~ 290V (NetSure 701 A41) or 85Vac ~ 300Vac (NetSure 501 A41 & NetSure
501 A91).
The rectifier uses soft switching technology, raising the system rated efficiency to 91%, and the efficient systems can be as high as 95%.
Ultra-low radiation. With advanced EMC design, the rectifier meets international standards such as CE and NEBS. Both the conducted and radiated interference reach Class B.
The rectifier safety design complies with UL, CE and NEBS standards. High power density.
Rectifiers are hot pluggable. It takes less than 1min to replace a rectifier.
Two over-voltage protection methods are optional: hardware protection and software protection. The latter one also has two optional modes: lock-out at the first over-voltage and lock-out at the second over-voltage. Perfect battery management: The management functions include the LLVD (optional), BLVD, temperature
compensation, auto voltage regulation, stepless current limiting, battery capacity calculation and on-line battery test, etc.
M221S and M222S support historical alarm record up to 200 and historical record up to 1000. And M820B supports historical alarm record up to 3000 and historical record up to 60000
10 sets of battery test data records.
Network design: Providing multiple communication ports (such as RS232, modem and dry contacts), which enables flexible networking and remote monitoring. M820B support the USB communication interface. Perfect lightning protection at AC side and DC side.
Complete fault protection and fault alarm functions.
NetSure 701 A41-S3, NetSure 701 A41-S5 and NetSure 501 A41-S1 adopt the way of outage for control, This way effectively prevents the storage battery from deeply discharging after system battery protection drops out and hence prevents the unattended outdoors and indoors server rooms from the damage due to the deep discharge.
Chapter 2 Installation Instruction
2.1 Safety Regulations
Certain components in this power system have hazardous voltage and current. Always follow the instructions below: 1. Only the adequately trained personnel with satisfactory knowledge of the power system can carry out the
installation. The most recent revision of these safety rules and local safety rules in force shall be adhered to during the installation.
2. All external circuits that are below 48V and connected to the power system must comply with the requirements of SELV as defined in IEC 60950.
3. Make sure that the power (mains and battery) to the system is cut off before any operations can be carried out within the system subrack.
4. The power subracks shall be kept locked and placed in a locked room. The key keeper should be the one responsible for the power system.
5. The wiring of the power distribution cables should be arranged carefully so that the cables are kept away from the maintenance personnel.
2.2 Preparation
Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done by representatives of both the user and Emerson Network Power Co., Ltd.To inspect the equipment, you should open the packing case, take out the packing list and check against the packing list that the equipment is correct and complete. Make sure that the equipment is delivered intact.
Cables
The cable design should meet relevant industry standards.
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least +70°C temperature durability. With cable length shorter than 30 meters, the Cross-Sectional Area (CSA) calculation should be based on the current density of 3.5A/mm2. The suggested CSA value is no less than the Table 2-1.
Table 2-1 Load cable CSA selection
AC MCB rated current Max. battery current Min. cable CSA Max. cable length
125A 105A 35mm2 50mm2
100A 80A 25mm2 50mm2
63A 50A 16mm2 25mm2
The CSA of DC cable depends on the current flowing through the cable and the allowable voltage drop. To select the battery cable CSA, see Table 2-2. Select the DC load cable CSA according to the Table 2-3.
Table 2-2 Battery cable CSA selection
Battery MCB rated current Max. battery current Min. cable CSA Max. cable length (volt drop: 0.5V, with max. CSA)
125A 105A 35mm2 6 m
63A 50A 16 mm2 5 m
Note:
1. The specs are applicable at ambient temperature of 25°C. If the temperature is higher or lower than this, the CSA of the cable should be increased.
2. The battery cable should reach at least +90°C he at durability. It is recommended to use double-insulated copper-core flame retardant cable as battery cable
Table 2-3 DC load cable selection Load route rated
current
Max. output current
Min. cable CSA
Max. cable length (volt drop:
0.5V, with min. CSA) Max. cable CSA
Max. cable length (volt drop: 0.5V, with max. CSA)
100A 80A 25mm2 14m 50mm2 20m
63A 50A 16mm2 9m 25mm2 14m
32A 25A 10mm2 11m 25mm2 29m
16A 12A 6mm2 14m 25mm2 48m
10A 8A 6mm2 23m 25mm2 98m
Note: The specs are applicable at ambient temperature of 25°C. If the temperature is higher than this, the CSA of the cable should be increased
To prevent the air switching capacity is too large, the load overload does not work. Recommended the capacity of the air switching is up to 1.5 ~ 2 times of the load peak.
The CSA of the system grounding cables should be consistent with the largest power distribution cables. The CSA value is no less than 25mm2.
AC and DC power distribution interface definition see Table 2-4.
Table 2-4 AC and DC power distribution interface definition
Connector name Connector specifications Wiring instructions
AC power
distribution
AC input MCB H type terminal, max. cable CSA 35mm
2 (Single-phase power input)
H type terminal, max. cable CSA 25mm2 (Three -phase power input) AC power line
Grounding
busbar One M8 bolt, OT type wiring terminal, max. cable CSA 35mm
2
Connected to the grounding bar of the equipment room
DC power distribution
Battery output MCB
H type terminal, max. cable CSA 25mm2 (63A and below)
H type terminal, max. cable CSA 50mm2 (capacity above 63A)
Connected to the battery port
Negative output MCB
H type terminal, max. cable CSA 25mm2 (63A and below)
H type terminal, max. cable CSA 50mm2 (capacity above 63A)
Connected to the users load port
Positive
busbar Terminal subrack terminal:cable CSA ≤ 50mm
2 Connected to the users load
port
2.3 Mechanical Installation
Note
1. The cabinet or rack the subrack power supply system installed in must provide fireproof and electric protection casing, or install in cement or other difficult to burn, at the same time and other combustible materials to keep enough distance. 2. For the convenience of maintenance, users should maintain a clearance of 800mm at the front of the power supply system. 3. Subrack cannot be installed against the wall, it must leave enough space for heat dissipation.
Installed on battery bracket
M6 screw Connector Subrack power system Battery bracket M6 screw Connector
Figure 2-1 Cabinet and rack installation
Installed in cabient
Insert the subrack power system to the matching cabinet, as shown in Figure 2-2.
电源插框 Subrack power
system
Figure 2-2 Installed in the cabinet system
Figure 2-3 Installation size of NetSure 501 A41 (unit: mm)
445
Figure 2-4 Installation size of NetSure 501 A91 (unit: mm)
Figure 2-5 Installation size of NetSure 701 A41-S1 (unit: mm)
Figure 2-7 Installation size of NetSure 701 A41- S4 (unit: mm)
265.0
438.5
482.6
Figure 2-8 Installation size of NetSure 701 A41-S5 (unit: mm)
Note
1. Tighten the captive screw of the MFU and DU Panel by the cross head screwdriver when there is no operation. 2. Also tighten the handle of the 501 modules by the cross head screwdriver.
3. Please plug in the new modules or installing a new panel after removing the rectifier module.
2.4 Electrical Installation
2.4.1 Power System Cabling Method
Cabling from the top of the power system
DU unit and MFU unit are available for the system top cover cabling.
For DU unit cabling: Cabling from the cable outlet area and then fixed to the cable-bundling plate and the top edge. As shown in Figure 2-9.
Cable outlet area
Cable-bundling plate
Cable outlet area
Figure 2-9 Cable entry Illustration of the DU unit
The MFU unit cabling is shown in 2-10.
Figure 2-10 Cable entry Illustration of the MFU unit
Cabling from side of the power system
Use a cross head screwdriver to remove two screws which fix the cabling panel at side of cabling area, then the cable can be led out from the cabling area, as shown in Figure 2-11.
出线板 (出线空间) 螺钉
Figure 2-11 Side cable cabling Illustration
2.4.2 Connecting AC Input Cables
Danger
1. Switch off all MCBs before the electrical connection.
2. Only the qualified personnel can do the mains cable connection.
Take the NetSure 701 A41 power supply system as an example, the position of the terminals are shown in Figure 2-12.
Figure 2-12 Illustration of the connection terminal 注意 注意注意 注意 若用户选用插框的交流输入采用的是端子形式,无过流和短路保护功能,则需要在插框前级配过流和接地保护器件,具 体保护器件规格的选择可以咨询艾默生网络能源有限公司当地的技术支持。
2.4.3 Connecting Load Cables
Connect the negative cable of the load to the upper terminal of load MCB. Connect the positive cable of the load to the DC positive busbar, as shown in Figure 2-13.
Figure 2-13 Illustration of the load cable connection terminal
2.4.4 Connecting Battery Cables
Note
1. The batteries may have dangerous current. Before connecting the battery cables, the corresponding battery input MCBs or the battery cell connector must be disconnected to avoid live state of the power system after installation.
2. Be careful not to reverse connect the battery. Otherwise, both the battery and the power system will be damaged!
1. Connect one end of the negative battery cable to the upper terminal of battery MCBs. Connect one end of the positive battery cable to the DC positive bus bar.
2. Connect copper lugs to the other end of the battery cables. Bind the connecting parts with insulating tape, and put them beside the battery. Connect the cables to the battery when the DC distribution unit is to be tested. As shown in Figure 2-14.
Battery MCB Positive terminal
2.4.5 Connecting Signal Cables
There are two user interface board of the power system can optional, respectively the W2453X1 user interface board and IB2 user interface board. The W2453X1 user interface board is used together with the M221S monitoring unit or M222S monitoring unit only; and the IB2 user interface board is used together with the M820B monitoring unit only. W2453X1 user interface board cable connection
Take the NetSure 501 A41 power supply system as an example, the position of the user connector board (W2453X1) is shown in Figure 2-15.
Figure 2-15 W2453X1 user interface board Illustration
At most two user connector boards are allowed in the power supply system. Standard cabinet is only configured with one user connector board.
With one user connector board configured, the power supply system provides three external digital signal input interfaces: DI2, DI3, DI4 (DI1 is used for DC SPD alarm. If no DC SPD is configured in the power supply system, DI1 is available) and four dry contact alarm output interfaces: DO1, DO2, DO3, DO4. With two user connector boards configured, the power supply system provides additional four dry contact alarm output interfaces: DO5, DO6, DO7, and DO8.
The functions of the interfaces are shown in Table 2-5.
Table 2-5 nterface functions
Type Default alarm Description
Dry contact 1 AC power failure /
Dry contact 2 DC overvoltage or DC undervoltage Four-level DC voltage alarms
Dry contact 3 Rectifier alarm Except rectifier lost and multi-rectifier alarm
Dry contact 4 Priority LLVD /
Dry contact 5 Non-priority LLVD /
Dry contact 6 / /
Dry contact 7 / /
Dry contact 8 / /
With default settings, when the preceding alarms are generated, the contactors of the corresponding dry contacts should change their status, that is, the normally-open contactors close, and the normally-closed contactors open. All the status changes should be verified by a multimeter. After the alarms are removed, the dry contacts should resume. The default settings of the dry contact alarms can be changed through the controller. The interfaces of the user connector board are shown in Figure 2-16.
Figure 2-16 W2453X1 user connector board interface
IB2 user interface board
The external input and output signals are all connected to the IB2 user interface board. For the ports on the IB2 user interface board, see Figure 2-17.
Figure 2-17 IB2 user interface board definition
Note
1. J11 and J12 are temperature sensor ports. They are not used here. 2. J2 is I2C interface, and provides the power.
See Table 2-6 for the dry contact terminal definition.
Table 2-6 Dry contact terminal definition
Name of double-layer port Pin No. Pin name Definition
J3
1 DI1- Digital input 1-
2 DI1+ Digital input 1+
3 DI2- Digital input 2-
4 DI2+ Digital input 2+
5 DI3- Digital input 3-
6 DI3+ Digital input 3+
J4
1 DI4- Digital input 4-
2 DI4+ Digital input 4+
3 DI5- Digital input 5-
4 DI5+ Digital input 5+
5 DI6- Digital input 6-
6 DI6+ Digital input 6+
J5
1 DI7- Digital input 7-
2 DI7+ Digital input 7+
3 DI8- Digital input 8-
4 DI8+ Digital input 8+
5 NA /
6 NA /
J6
1 DO1_NC NC contact of relay 1
2 DO2_NC NC contact of relay 2
3 DO1_COM Common contact of relay 1
4 DO2_COM Common contact of relay 2
5 DO1_NO NO contact of relay 1
6 DO2_NO NO contact of relay 2
J7
1 DO3_NC NC contact of relay 3
2 DO4_NC NC contact of relay 4
Name of double-layer port Pin No. Pin name Definition J7
4 DO4_COM Common contact of relay 4
5 DO3_NO NO contact of relay 3
6 DO4_NO NO contact of relay 4
J8
1 DO5_NC NC contact of relay 5
2 DO6_NC NC contact of relay 6
3 DO5_COM Common contact of relay 5
4 DO6_COM Common contact of relay 6
5 DO5_NO NO contact of relay 5
6 DO6_NO NO contact of relay 6
J9
1 DO7_NC NC contact of relay 7
2 DO8_NC NC contact of relay 8
3 DO7_COM Common contact of relay 7
4 DO8_COM Common contact of relay 8
5 DO7_NO NO contact of relay 7
6 DO8_NO NO contact of relay 8
The definition of dry contact function can be set through controller or WEB browser. The specifications of the dry contact ports are as follows:
Digital inputs: 8-route, opto-isolation, the alarm and high/low level are definable (high level: 20V ~ 60V, low level: less than 1V).
Digital output: 8-route, relay isolation, maximum: 30Vdc 1A, 125Vac 0.5A; 60W; minimum: 10uA @ 10Vdc, alarm is definable.
Connecting Communication Signal Cable
The communication port of the M221S controller is shown in Figure 2-18. The M222S only provides the RS232 communication serial port, whereas the Ethernet port is not provided.
Figure 2-18 M221S controller communication port
The communication port of the M820B controller is shown in Figure 2-19.
Chapter 3 Installation Testing
This chapter introduces procedures of installation testing. The corresponding safety rules shall be adhered to in the test.
3.1 Installation Check And Startup
Before the test, inform the chief manufacturer representative. Only trained electrical engineer can maintain and operate this equipment. In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets, bangles and rings.
During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries and property damage. Before the test, check the equipment to ensure the proper earthing. Installation check must be done before testing. Then the batteries can be charged for the first time.
Make sure that the AC input MCBs, battery MCBs and load MCBs are switched off. Make sure that all the devices are properly installed.
Installation check
OK Comments
Check all the MCBs and cables. Are their models correct?
Check the bus bar connections, input and output cable connection, and connection between the power system and the system grounding.
Check the if the number and connections of the batteris are correct. Check the polarity of the battery string with a voltmeter.
Make sure all the cable connections are firm and reliable.
Startup preparations
OK Comments
Make sure that all the MCB are switched off.
Measure the AC input voltage. Make sure the input voltage is within the allowable range. Umin=___V
Check that the communication and alarm cables are connected to the signal transfer board. Check that the temperature sensor, if any, has been installed.
Check that the battery string circuit is not closed.
Connect the disconnected batteries to the battery string circuit
Switch off unconnected battery MCBs. Check that the battery signal cables are connected to battery MCBs reliably, not loosened or suspended
Measure with a voltmeter across the connection points of each battery and make sure that the polarity is right. For a lead-acid battery with 24 cells, the voltmeter should read 2.0-2.1V/cell or 48-51V/battery. If the voltage of certain cell is lower than 2.0V, that cell must be replaced.
Umin=___V
Check with an ohmmeter that there is no short circuit between the positive & negative distribution bus bars, or between the positive & negative battery poles
(Note: Pull out all modules before the check and restore them after the check)
Startup
OK Comments
Switch on the system AC input MCB. The green LED on the rectifier will be on and the fan will start running after a certain delay. The monitoring module will show that the power supply voltage is 53.5V. Check the system voltage and busbar polarity with a voltmeter. The voltage difference between the measured value and displayed value should be less than ± 0.2V.
Start and stop each rectifier of the system by unplugging and inserting each rectifier. Check their output voltages.
3.2 Basic Settings
When the system is put into service for the first time, the parameters of monitoring module must be set based on the actual system configuration, such as battery number, capacity, user’s charge current limit and other functional requirements. Only after that can the monitoring module display system operation information and control the output.
OK Comments
The system model has been set correctly in factory before delivery, check that the setting agrees with
the actual system:
NetSure 701 A41-S1:48V/SET;Set the battery shunt coefficient for:175A/25mV;
NetSure 701 A41-S2~S5:48V/SET;Set the battery shunt coefficient for:300A/25mV;
NetSure 501 A41-S1:48V/SET;Set the battery shunt coefficient for:175A/25mV;
NetSure 501 A41-S2:48V/SET;Set the battery shunt coefficient for:300A/25mV;
NetSure 501 A91-S1:48V/SET;Set the battery shunt coefficient for:300A/25mV
The DC over-voltage alarm point has been set correctly in factory before delivery, check that the setting agrees with the actual system:
Set DC over-voltage alarm: 58V
Check that the parameter Setting→Alarm Settings→Alarm mode, check that the mode is set to “High”
The battery string number set at the monitoring module should be the same as the number actually connected. (By default: 2)
Set the battery capacity according to the actual capacity of the battery connected to the system. Default: 300Ah
Configure the temperature coefficient according to the battery manufacturer’s requirement. Setting range: 0-500mV/°C. By default: 72mV/°C. (if no temp erature sensor is installed, do not set this parameter)
Set the charge current limit according to your needs. Setting range: 0.1~0.25C10. (By default: 0.1C10)
Set the monitoring module according to the voltage suggested by the battery supplier. Floating Charge (FC) voltage range: 42V ~ Boost Charge (BC) voltage. Default: 53.5V. BC voltage range: FC voltage ~ 58V. By default: 56.4V.
For batteries that do not need BC, set the BC voltage to FC voltage plus 0.1V Put through the battery MCBs and connect the batteries
3.3 Alarm Check And System Operation Status Check
Alarm check
Check that all functional units can trigger alarms that can be displayed on the monitoring module.
OK Comments
Pull out one rectifier. The “Rect N Com Failure” alarm should be triggered. Insert the rectifier in. The alarm should disappear. Repeat the same procedures on other rectifiers.
Remove battery MCB 1. The “Batt1 Failure” alarm should be triggered. Put on the MCB. The alarm should be cleared. Repeat the same on battery MCB 2.
Switch off a load MCB connected to a load route. The alarm “Load N Failure” should be triggered. Switch on the MCB, and the alarm should be cleared. Repeat the same on the other load MCBs. Remove all the battery input MCBs. Keep only one rectifier in operation. Through the monitoring module, adjust the rectifier FC voltage to make it lower than the alarm point. The alarm “DC Voltage Low” should be triggered.
Keep the rectifiers in operation. Set through the monitoring module the battery management parameter to “Manual”. Enter the maintenance menu at the monitoring module. Select “Disconnect” and confirm it. The battery protection contactor should be open, and the “BLVD” alarm should be displayed at the monitoring module.
Note: when the preceding alarms are generated, the monitoring module will give alarms after approximately 3s.
System operation status check
There should be no alarms during normal system operation. The system operation status check can be conducted through the monitoring module.
OK Comments
Check that the system type agrees with the actual system when the system operates The monitoring module should display the correct AC voltage.
The monitoring module should be able to display the DC voltage. The difference between the displayed voltage and that measured at the bus bar should be less than 1%.
The monitoring module should display the battery current. The difference between the displayed and measured battery current should be less than 1%.
Check the number of the rectifier through the monitoring module. The number should be consistent with the actual number.
OK Comments
should agree with the actual parameters.
For the system configured with temperature sensor, the monitoring module should be able to display the battery ambient temperature. Hold the probe of the temperature sensor with hand and watch the monitoring module, which should diplay the change of temperature.
3.4 Final Steps
OK Comments
Disconnect all test equipment from the system and make sure that materials irrelevant to the equipment have been all removed.
Restore the equipment to its original condition and close the cabinet door. Check and handover the equipment that the user has purchased.
Note down all the operations taken, including time of the operation and name of the operator.
If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the repairing center for fault analysis.
Chapter 4 Use Of Monitoring Module M221S
、
、
、
、
M221S
This chapter introduces the front panel and functional keys briefly, and expounds screen contents, access method, system controlling, information querying and parameter setting.
After the monitoring module is powered on, the language selection screen will pop up, and the monitoring module is initialized. The default language is Chinese. After the initialization, the first system information page will appear.
4.1 Control Keypad And Indicator
4.1.1 Front Panel
There are backlit LCD display, functional keypad, indicators and positioning pin on the front panel of M500D monitoring module, as shown in figure 4-1.
Figure 4-1 Front panel of M500D monitoring module
4.1.2 Indicator Function
The function of the indicators is shown in table 4-1.
Table 4-1 Functions of Indicators
Indicator Normal State Fault State Fault Cause
Status (green) On Off If this LED is on, this means the system is operating normally
Observation Alarm
(yellow) Off On
The power system has one or more active observation alarms. Alarm conditions are programmable. Refer to Table 3-3 for defaults
Major Alarm (red)* Off On
The power system has one or more active major alarms (Major and Critical Alarms). Alarm conditions are programmable. Refer to Table 3-3 for defaults
Note: A Major Alarm initiates an alarm report if alarm report is enabled
4.1.3 Control Keypad Function
The function of the control keypad is shown in table 4-2.
Table 4-2 Function of Keys on the Panel
Key Symbol Key Name Function
ENT Enter Confirm or Execute
▲ Up Move Up Cursor or Select the Previous Screen
▼ Down Move Down Cursor or Select the Next Screen
4.2 LCD Menu Tree
The overall menu structure is shown in Figure 3-5. 09:20:20 Float 53.4V 404A Manual Normal 08-11-03 Float 53.4V 404A Manual Normal
ENT MAIN MENU Status Settings ECO Manual Quick Settings ENT STATUS Active Alarm Rectifiers History Alarm SETTINGS Alarm Rectifier Battery AC DC Controller Communication Disable CycPeriod: 168h RectWork: 80% MANUAL
Sys Mode: Auto In Manual ▼ System Type: 48V / set Capacity: 300Ah ECO ▼ Rect Limit: 1 LCD Rotation: On Figure 4-2 Main menu screen
4.2.1 Status
In the screen of MAINMENU, when cursor is at ‘Status’, press ‘ENT’ to go to the status screen:
Active Alarm Rectifiers History Alarm ENT ALARM: 1/2 Batt Discharge Observation Alarm Start Time: 081104 15:52:53 RECTIFIER 1/3 ID: 02070801232 R48800B00 DC Volt: 53.4V DC Curr Curr Limit: 109% AC Volt: 201V AC Status: On DC Status: On AC Derated : N Temp Derated : N ALARM 001 SPD Fault 08-07-10 11:35:22 08-07-10 12:35:22 ENT ALARM: 2/2 Batt Volt Low Critical Alarm Start Time: 081104 15:52:55 ALARM 002 DC Volt Low 08-07-10 11:35:25 08-07-10 12:35:25 ENT Status : 0.0A
In the status screen, you can move the cursor to ‘Active Alarm’, ‘Rectifiers’, and ‘History Alarm’ respectively and press ‘ENT’ to check the information of active alarm, rectifiers, and history alarm. The rectifier screen shows the information of first rectifier, if you want see the information of next rectifier, just press ‘ENT’. In screen of ‘Active Alarm’, ‘Alarm 1/2’, ‘1/2’ means there are 2 active alarms and this screen is displaying the first active alarm. The alarm level and alarm start time are displayed in the screen
In the screen of ‘History Alarm’, the ‘ALARM 001’ means this screen is displaying the first history alarm. The alarm start time and end time are displayed in the screen.
4.2.2 Settings
In the Main Menu screen, move the cursor to the item of ‘Setting’ and press ‘ENT’ to enter the Setting menus. Before you access the Setting menu, the system will require you to enter the password first. Method of entering password: For example, to enter the password of ‘640275’: Press ‘ENT’, and the bit will be highlighted, now you can press ▲ or
▼ continuously to enter the numbers from 0 to 9, or enter the letters from ‘a’ to ‘z’ or from capital letter ‘A’ to ‘Z’. After entering ‘6’, press ‘ENT’ and the cursor will move to the next bit, and in the same way, press ▲ or ▼ continuously to enter ‘4’, and you can enter the rest bits ‘0275’ in the same way.
SETTINGS Alarm Rectifier Battery AC DC Controller Communication ALARM Alarm Level Alarm Control DI Setting COMMUNICATION Address: 1 CommMode : RS232 Protocol: YDN23 BaudRate: 9600 IP/Subnet/Gate: 10.163.210.91 255.255.255.0 10.163.210.1 CallbackTime: 3 PhoneNumber: 86010677 86010808 RECTIFIER Position: Disabl R -Posi: 1-1 HVSD: 59.0V Default V: 53.5V Walk-in On: N Walk-in T: 8s Interval T: 0s AC OverV On: N ACCurrLim : 30A BATTERY Basic Charge Test Temp Comp AC Over Volt: 280V Under Volt: 180V PH Fail: 80V AC Input: N AC PH: 3 -PH DC Over Volt2: 58.2V Over Volt1: 58.5V Under V1: 45.0V Under V2: 45.0V Amb High: 40C Amb Low: - 5C CONTROLLER Lang: English Tzone: GMT + 08:00 Date: 2009-03 -23 Time: 22:17:18 System Type: 48V/1000A DownloadMode:N Reset PWD: N Reset Para: N Oper1PWD: ****** Oper2PWD: ****** AdminPWD: ****** LVD
In the Setting menu, there are 7 items that are ‘Alarm’, ‘Rectifier’, ‘LVD’, ‘AC’, ‘DC’, ‘Controller’ and ‘Communication’ respectively.
Move the cursor to ‘Rectifier’ and press ENT, you can configure the following rectifier parameters: Position: Enable or disable the shelf setting.
R-Posi: rectifier position in shelf.
HVSD: high voltage shut down, rectifier will shut down when its output voltage exceeds this HVSD point. Default V: rectifier default output voltage.
Walk-in ON: rectifier walk-in function (soft start) is enabled. Walk-in T: rectifier walk-in time (soft start time).
Interval T: rectifier sequential startup interval.
AC OverV on: rectifier will shutdown when AC input exceeds AC over voltage point. ACCurrLim: rectifier current limiting value during startup process.
Move the cursor to ‘AC’ and press ENT, you can configure the following AC parameters: Over Volt: set the over voltage protection point.
Under Volt: set the under voltage protection point. PH Fail: set the phase failure voltage point.
AC PH: can set the AC input to 3-phase or single phase (‘1-PH’).
Move the cursor to ‘DC’ and press ENT, you can configure the following DC parameters: Over Volt2: set the over voltage protection point2.
Over Volt1: set the over voltage protection point1. Under V1: set the DC output under voltage point 1. Under V2: set the DC output under voltage point 2. AmbHigh: set the high ambient temperature. AmbLow: set the low ambient temperature.
Move the cursor to ‘Controller’ and press ENT, you can configure the following controller parameters: Lang: set the display language of LCD, you can select English or your local language.
Tzone: set the time zone. Date: set the current date. Time: set the current time. System Type: set the system type.
DownloadMode: enter the download mode through serial port. Reset PWD: Reset the password to default.
Reset Para: Reset parameters to default. Oper1PWD: set the password of operator 1. Oper2PWD: set the password of operator 2. AdminPWD: set the password of administrator.
There are three levels password. Default passwords: 1 for operator1, 2 for operator2, and 640275 for administrator. Only administrator can transfer to serial and web download mode and reset the password. Operator2 can change the system type and reset the parameters.
Alarm Alarm Level Alarm Control DI Setting ALARM LEVEL Alarm Block Severity: Observation Alarm Out Relay: 0 ALARM LEVEL SPD fault Severity: Major Alarm Out Relay: 0 ALARM LEVEL LFuse Alarm Severity: Critical Alarm Out Relay: 6
ENT ENT ENT
ALARM CONTROL Alm Voice: Open Clear: History
DI SETTINGS DI NO.: 1 Digital1 Alarm Active: High
Figure 4-5 Alarm screen
Alarm level setting
In the submenu of alarm level setting, move cursor before ‘Alarm Block’, press ‘ENT’, then you can set the alarm levels of other alarms such as ‘SPD fault’, ‘LFuse Alarm’, ‘Digital3 Alarm’, etc.
In the submenu of alarm level setting, you can set the alarm level of each alarm to observe alarm, major alarm, or critical alarm. You can also set the output relay number that outputs the alarm signal.
The characteristics of 4 alarm categories are given in the following table:
Table 4-3 characteristics of 4 alarm categories
Alarm levels Red alarm indicator of controller and system Yellow alarm indicator of controller and system
Alarm buzzer Alarm report Remark
CA (critical alarm) On On Yes Alarm report is enabled MA (major alarm) On On Yes Alarm report is enabled OA (observation alarm) On Off No
No alarm Off Off Off No
Note:
1. The alarm levels of temperature sensor disconnected alarm and temperature sensor failure alarm, and the corresponding relay output cannot be set through the LCD. The alarm levels of these two alarms and the corresponding relay are the same with those of the high temperature alarm setting.
2. If the analog alarm has two levels of alarm thresholds, and if these two alarm thresholds are set to the same value, then the second level will be cancelled and the first level of the alarm will be displayed in LCD. For example: If the alarm threshold of ‘high temperature 1’ is set to the same with the threshold of ‘high temperature 2’, and if this threshold is set to 40 deg C, then when the temperature exceeds 40 deg C, the system will only issue ‘high temperature 1 alarm’, and will not issue the ‘high temperature 2 alarm’.
In the alarm level setting submenu, you can also set the output relay no. for the corresponding alarm. Alarm control menu
For the submenu of ‘AlmVoice’ of alarm control menu, you can set it to ‘Open’(audible alarm is enabled) or ‘Close’ (no audible alarm), and you can also set the time of audible alarm and the time can be ‘3min’, ‘10min’, ‘1h’ and ‘4h’. For the submenu of ‘Block Alarm’, you can set ‘Y’ or ‘N’ to select whether the alarm should be blocked or not. For the submenu of ‘Clear’, you can select ‘History’, ‘ECOFail’, ‘Maintain’, ‘ShortTest’, ‘TestFail’ ,’Rect Lost’ ‘Rect Commb’ and ‘Rect Not respond’ to clear corresponding alarm.
DI SETTINGS
All the alarms can be configured with No.1 to No.8 alarm contacts. ‘0’ means no alarm dry contacts. All the alarm dry contacts provide NC (normally closed) or NO (normally opened) output and the default alarm dry contacts are given in the following table.
Table 4-4 Default alarm dry contact setting
Dry contact No. Default alarm
Dry contact 1 Mains Failure
Dry contact 2 DC Under Volt or DC Over Volt
Dry contact 3 Rectifier alarm
Dry contact 4 LVD2
Dry contact 5 LVD1
Dry contact 6 None
Dry contact 7 None
Dry contact 8 None
Table 3-5 lists the alarms that you can scroll through in the ALARM SETTINGS/ALARM LEVEL menu, and also shows their factory default ‘Alarm Level’ and ‘Mapped Output Relay’ settings.
Table 4-5 Controller Alarms and Factory Default Settings
Alarm name Alarm description Condition Default alarm level Default mapped
output relay
Alarm Block Alarm Block Alarms are blocked by the LCU+ Observation
Batt
Imbalance Batt Imbalance
Battery middle voltage out of the range of ( bus
voltage /2) ± 0.6 Major
SavePowerF
ault SavePowerFault
Into and out of save power status for 5 times in one
hour Major
Save Power Save Power Function System is in save power status Observation
AC High AC Voltage High Input phase voltage higher than AC High point Observation
AC Low AC Voltage Low Input phase voltage lower than AC Low point Observation
AC PH Fail AC Phase Fail Input phase fails Observation
Temp High2 Temperature High 2 Ambient/ Battery temperature higher than
Temperature High 2 Major
Temp High1 Temperature High1 Ambient/ Battery temperature higher than normal
operation range Major
Temp Low Temperature Low Ambient/ Battery temperature lower than normal
operation range Observation
Batt Over
Chg Battery Over Charge The charging current over the maximum value Observation
DC Volt
High+ DC Voltage High+
System output voltage much higher than float
charge voltage Critical 2
DC Volt High DC Voltage High System output voltage higher than float charge
voltage Critical 2
DC Volt Low DC Voltage Low System output voltage slightly lower than float
charge voltage Critical 2
DC Volt Low- DC Voltage Low- System output voltage is much lower than float
charge voltage Critical 2
Rect HVSD Rectifier HVSD Rectifier HVSD circuit activated Major 3
Rect
LoadShare Rectifier LoadShare
The difference between rectifier output current and average output current larger than 8A (+/-4A), and the load of the rectifier greater than 10% of its capacity
Observation 3
Rect Derated Rectifier Derated The output power of at least one rectifier is derated
because of AC undervoltage or overtemperature Observation 3
Rect Fan
Fails Rectifier Fan Fails Fan of at least one rectifier fails Major 3
Rect Protect Rectifier Protect AC input voltage out of the range of 85Vac to
Alarm name Alarm description Condition Default alarm level Default mapped output relay
Rect Failure Rectifier Failure
Serious load sharing alarm (the output current of the rectifier is lower than 1A, and the average load is greater than 10% of the total rectifier capacity)
Critical 3
Rect TempHigh
Rectifier
Temperature High
High temperature protection activated in at least one
rectifier Major 3
Rect AC Fail Rectifier AC Fail AC input voltage lower than 80Vac Major 3
Rect Comm Fail
Rectifier
Communication Fail Rectifier(s) unable to communicate with LCU+ Major 3
MultiRect
Alarm Multi rectifier Alarm Two or more rectifiers have alarms Critical
System
Maintain System Maintain
System has not been maintained within preset
maintenance time None
Rect Lost Rectifier Lost Rectifier reduction detected Critical
Rect
OverLoad Rectifier OverLoad Total load current greater than the High Load value Observation
Mains
Failure Mains Failure AC input voltage lower than 80Vac Major 1
LVD2 LVD2 LVD contactor 2 open due to low battery voltage Critical 4
LVD1 LVD1 LVD contactor 1 open due to low battery voltage Critical 5
Batt Test Fail Battery Test Fail Battery discharge test failure (battery voltage is
lower than setting value before test time is reached) Observation
DC Volt Fail DC Voltage Fail The difference between bus voltage and the set
output voltage larger than the set value Observation
Curr
Imbalance Current Imbalance
The total output current not equal to the sum of the
battery current and the load current Observation
Batt
Discharge Battery Discharge Batteries are discharging Observation
Batt Test Battery Test The batteries are testing None
Boost
Charge Boost Charge The batteries are in boost charge state None
Manual
Mode Manual Mode The system is in manual mode Observation
SelfDetect
Fail SelfDetect Fail LCU+ detects error in hardware self test Observation
LVD2Ctrl Fail LVD2 Control Fail
After battery disconnection/ connection signal is sent out, the feedback signal of the contactor is false
Critical BattFuse
Fail Battery Fuse Fail Battery fuse(s) or circuit breaker(s) open Critical
LoadFuse
Fail Load Fuse Fail Distribution (load) fuse(s) or circuit breaker(s) open Critical
Digital4 Digital4 User programmable Major
Digital3 Digital3 User programmable Major
Digital2 Digital2 User programmable Major
Digital1 Digital1 User programmable Major
Move the cursor to ‘Battery’ to set the battery parameters: BATTERY Basic Charge Test Temp Comp
Sys Mode: Auto BattFuse : 2 Capacity: 600Ah ENT Float: 51.8V Boost: 57.6V Limit: 0.100C Over: 0.300C Auto Boost: - Enable -Current: 0.060C - Capacity: 80.0% Const Boost: - Curr: 0.01C - Time: 180min Cyc Boost: - Enable - Period: 2400h -Time: 720min
Boost Limit Time: 1080min
End Test - Volt: 45.2V - Time: 300min - Capacity: 0.70C Cyc Test: Disabl Cyc Test Time:
01 - 01 00:00 04 - 01 00:00 Short Test: - Alarm 10A - Period: 1h - Time: 1min ConCurr Test: - Enable: No - Current: 9999A Temp1: N Temp2: N Batt T H2: 50C Batt T H1: 50C Batt T L1: 0C LVD1: Enbl LVD2: Enbl LVD1 Volt: 44.0V LVD2 Volt: 43.2V LVD Bat. Shunt: Y Shunt Coeff -Current: 500A -Volt: 25mV Center Temp: 25C Coeff : 72mV / C - Enable: No 07 - 01 00:00 10 - 01 00:00
Figure 4-6 Battery screen
Move cursor to ‘Basic’, you can configure the following parameters:
Sys Mode: set the system mode from ‘Auto’ to ‘Manual’ or from ‘Manual’ to ‘Auto’. Method of changing ‘Auto’ to ‘Manual’:
As shown in screen of ‘Basic’, in the item of ‘Sys Mode’, press ‘ENT’ to highlight ‘Auto’, and then press ▲ or ▼ to change it into ‘Manual’, and then press ‘ENT’ again to validate the change.
BattFuse: set the number of battery fuses. Capacity: Set the battery capacities.
Bat. Shunt: set if battery shunt is configured. Shunt Coeff: set current and voltage coefficients.
Move cursor to ‘LVD’, you can configure the following parameters: LVD1: Enable or disable LVD1.
LVD2: Enable or disable LVD2.
LVD1 Volt: set the voltage point at which the LVD1 contactor disconnects. LVD2 Volt: set the voltage point at which the LVD2 contactor disconnects. Move cursor to ‘Charge’, you can configure the following parameters: Float: set the float charging voltage.
Limit: set the charging current limit. This is the maximum charging current that should be allowed into the battery at any time, as regards to the nominal capacity of the battery. For example, a value of 0.150C10 means that the charging current is limited to 15% of the battery’s nominal capacity.
Over: set the over boost charging current. This is the charging current, as regards to the nominal capacity of the battery, at which an over current alarm will be initiated if this current is reached. For example, a value of 0.300C10 means that when the charging current reaches 30% of the battery’s nominal capacity, an alarm will be extended. AutoBoost: An Automatic Boost is started when one of the following conditions is reached.
-Enable: Use this submenu to enable or disable auto boost charging.
-Curr: This is the battery discharge current, as regards to the nominal capacity of the battery, above which an Automatic Boost is started, when the Automatic Boost function is enabled. For example, a value of 0.060C10 means that an Automatic Boost is started if the battery current is greater than 6% of the battery’s nominal capacity.
-Cap: This is the remaining battery capacity under which (less than) an Automatic Boost is started when the Automatic Boost function is enabled.
CycBoost
-Enable: Use this submenu to enable or disable cyclic boost charging.
-Period: Use this submenu to set cyclic boost charging period. This is the interval, in hours, between the boost cycles.
-Time: Use this submenu to set cyclic boost charging time. This is the duration of each cycle for the Cyclic Boost when this function is enabled.
Const Boost
-Curr: Use this submenu to set constant boost charging current. -Time: Use this submenu to set constant boost charging time.
BoostLimitTime: Use this submenu to set boost charging time limit beyond which boost charge will be stopped. Move cursor to ‘Test’, you can configure the following parameters:
End Test: A Battery Test is interrupted when one of the following conditions is reached. -Volt: This is the ‘end of test voltage level’ for each battery test.
-Time: This is the maximum duration, in minutes, for each battery test.
-Cap: This is the remaining battery capacity, as regards to the nominal capacity of the battery, at which a Battery Test will be interrupted. For example, a value of 0.700C10 means that when the charging current reaches 70% of the battery’s nominal capacity, the battery test is interrupted.
Cyc Test: Displays whether the time (on specific dates) battery test function is enabled (Y) or not (N). During a Timed Battery Test, the output voltage of the rectifiers is reduced so that the batteries power the load. If the batteries fail, the rectifiers power the load.
Short Test: A short test is a short duration battery discharge test used to verify that parallel batteries are discharging equally. If the discharge current difference between the two batteries exceeds a preset level (default is 10 A), a Short Test Fault alarm is generated.
-Enable: Displays whether the short (at specific intervals) battery test function is enabled (Y) or not (N). -Alarm: Displays the battery current difference at which an alarm will be extended.
-Time: Displays the interval, in hours, between short battery tests. -Duration: Displays the duration, in minutes, of each short battery test.
ConCurr Test: A Constant Current test is a battery discharge test done at constant current. The controller will automatically adjust the rectifiers to maintain the battery discharge current at the preset value.
-Enable: Displays whether the constant current battery test function is enabled (Y) or not (N). -Current: Displays the stable test current.
Move cursor to ‘TEMP COMP’, you can configure the following parameters:
Center Temp: Displays the temperature, in °C, at which the syst em operates at normal voltage levels.
Temp 1: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None) in position No. 1, and if there is one, whether it is used for battery or ambient temperature measurements.
Temp 2: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None) in position No. 2, and if there is one, whether it is used for battery or ambient temperature measurements.
Coeff: Displays the temperature compensation slope or rate of change per °C above or below the normal operat ion level selected in the second line. This value is expressed in millivolt per °C per string (mV/°C/str). For example, for a rate of change of 72mV/°C/str in a 24-cell, 48 V nom inal, battery string, the rate of change is 3 mV per cell.
4.2.3 Manual
In the Main Menu, move the cursor to ‘Manual’ and press ENT to enter Manual control menu:
MAIN MENU Status Settings ECO Manual Quick Settings ENT MANUAL Start: Float LVD1: Reconn LVD2: Reconn RectTrim : 53.5V RectLimit : 121% MANUAL
Sys Mode: Auto In Manual
Change to 'Manual' from 'Auto'
▼
Figure 4-7 Manual screen
In the manual screen, you can perform the following manual control operations: Start: To start float or boost charging or battery test.
LVD1: To reconnect or disconnect LVD1 contactor. LVD2: To reconnect or disconnect LVD2 contactor. RectTrim: To adjust the rectifier output voltage. RectLimit: To adjust the rectifier current limiting point.
4.2.4 ECO
In the Main Menu, move the cursor to ‘ECO’ and press ENT to enter ECO menu:
MAIN MENU Status Settings ECO Manual Quick Settings ENT ECO Disable Cyc Period: 168h Rect Work: 80% Rect Limit: 1 Figure 4-8 ECO screen
The following parameters can be configured: ECO: To disable or enable ECO function. Cyc Period: Rectifier redundancy cycle.
Rect Work: Optimum operating load point of rectifier.
Rect Limit: In ECO mode, the minimum number of rectifiers required.
4.2.5 Quick Setting
In the Main Menu, move the cursor to ‘Quick Setting’ and press ENT to enter Quick Setting menu:
MAIN MENU Status Settings ECO Manual Quick Settings
ENT System Type:
48V / 1000A Capacity: 300Ah LCD Rotation: On
Figure 4-9 Quick Settings screen
In the Quick Setting screen, you set the system type and system capacity, as well as the parameters (current, voltage) of load shunts and battery shunts.
4.2.6 Controller Setting
Table 3-7 summarizes all the settings of the controller.
Table 4-6 Controller Settings
Components Name Available Settings Default setting Unit
Low limit High limit
Alarm DI alarm mode High / low High /
Rectifier
HVSD point 56 59 59 V
Default voltage 48 58 53.5
Restart time upon over voltage 0 300 300 s
Soft-start time with load 8 128 8 s
Soft-start with load enabled Enabled/Disabled Disabled /
Startup upon AC over voltage Enabled/Disabled Disabled /
System ECO enabled Enabled/Disabled Disabled /
Sequencial start interval 0 10 0 s
Input current limiting 1 50 30
Rectifier slot setting enabled Enabled/Disabled Disabled /
Rectifier slot setting 1 30 1-1/2-2… /
B a tt e ry Basic battery parameters Number of fuses 0 5 2 Nominal capacity 20 5000 600 Ah Shunt Yes / No
Shunt current 1 2000 According to system
type A
Shunt voltage 1 500 25 mV
Temperature 1 None/Battery/Ambient Disabled /
Temperature 2 None/Battery/Ambient Disabled /
Battery charge parameters
Float charging voltage 42 58 53.5 V
Boost charging voltage 42 58 56.4 V
Charging current limiting 0.1 0.25 0.1 C10
Auto boost charging enabled Yes / No Yes /
Constant charging current 0.002 0.02 0.01 C10
Battery charge parameters
Constant current charging time 5 1440 180 Min
To boost charging current 0.04 0.08 0.06 C10
To boost charging capacity 10 99 80 %
Scheduled boost charging enabled Yes / No Yes /
Boost charging protection time 60 2880 1080 H
Scheduled boost charging cycle 2 8760 2400 h
Scheduled boost charging time 30 2880 720 Min
Battery test parameters
Battery test end time 5 1440 300 Min
Battery test end voltage 43.1 57.9 45.2 Min
Battery test end capacity 0 1 0.7 C10
Scheduled test enabled Yes No /
Constant current test enabled Yes / No No /
Constant battery test current 1 9999 9999 A
Short test enabled Yes / No No /
Short test alarm point 1 100 10 A
Short test cycle 24 8760 720 h
Short test time 1 60 5 min
Battery temp compensation coefficient
Temperature compensation central
point 10 40 25 deg.C
Battery compensation coefficient 0 500 72 mv/deg.C
Battery over temperature point 10 100 50 deg.C
Battery high temperature point 10 100 50 deg.C
Battery low temperature point -40 10 0 deg.C
DC unit
Over voltage 1 40 60 58.5 V
Under voltage 1 40 60 45 V
Under voltage 2 40 60 45 V
High ambient temperature 10 100 40 deg.C
Components Name Available Settings Default setting Unit
Low limit High limit
Load shunt Yes / No No /
LVD
LVD1 Enabled Disabled / Enabled Disabled /
LVD2 enabled Disabled
/Enabled Disabled /
LVD1 voltage 40 60 43.2 V
LVD2 voltage 40 60 43.2 V
AC unit
Over voltage alarm point 0 500(866) 280(485) V
Under voltage alarm point 0 500(866) 180(304) V
Phase failure alarm point 0 500(866) 80(255) %
Communication parameters IP address 0-255 192.168.1.2 / Subnet code 0-255 255.255.255.0 / Default gateway 0-255 192.168.1.1 / Local address 1 255 1 /
Port type RS232/Modem/ETH RS232 /
Baud rate 1200/2400/4800/9600 9600
Protocol YDN23/EEM/RSOC/SOCTPE YDN23 /
Alarm call-back enabled Yes / No No /
Call back times 0 10 3
Call back number 1 Call back number 2 Call back number 3
Controller parameters
Language English / Chinese English
Display time zone GMT+08:00
System date System time
Restore default configurations Yes / No No
Set rotating screens Horizontal/Vertical Horizontal
System type
48V/set, 48V/1000A, 48V/500A, 48V/300A, 48V/100A, 24V/set, 24V/1000A, 24V/500A, 24V/300A and 24V/100A
48V/set
4.3 WEB Interface Operation
Through the WEB Interface, a remote user can: View real-time operating information. Send control commands.
Set programmable parameters.
Set which new alarms are displayed in a pop-up WEB window. Download and upload configuration files.
4.3.1 Setting Up The Internet Explorer Web Browser
Procedure
Note
This procedure needs to be performed only when the controller is connected to an Internet and the User has set that the access to the Internet needs to be made through proxy. If the controller is connected Internet and the user computer is connected to the Internet, the user cannot disable the proxy, otherwise he will have no access to the controller.