10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Disadvantages of Today’s Systems • Time consuming balancing effort

• Rebalancing required when adding to system or remodeling • Poor valve authority at average or low load

• Balancing procedure dictates quality

• Low ΔT at the coils yields overfl ow and increases pumping costs • Potential spreading of control problems can occur when one or more

loops are instable, due to interactive nature of circuits

• Low ΔT at the coil yields overfl ow and increases pumping costs.

Advantages of the PICCV

• Easy selection, no Cv calculation required

• Hydronic balancing is simplifi ed, as the circuits are not interactive • Flexible commissioning

• One piece installation saves 50% of labor costs, installation space, and investment for balancing valve

• Reduces pumping costs by maintain fl ow regardless of pressure fl uctuations • Visualizes fl ow in a BMS system and provides accurate fl ow for each

degree of opening

• Prevents overfl ow or underfl ow for fast start-up

Options

• Belimo PC-Tool/ZTH-GEN US for commissioning

Pressure Independent Characterized

Control Valves

(PICCV)

Integral PT ports on ½” I

and ¾” models. External a

union with PT ports on 1” u

through 2” PICCV models. t

Optional PT ports O

Features

• Automatic dynamic system balancing Perpendicular mounting ISO fl ange and square drive head eliminate lateral forces on the stem.

Easy direct coupling of actuator with a single screw.

Blow-out proof stem with

thrust-bearing Tefl on® disc

offering sturdy construction.

Self cleaning ball seat design increases life and longevity of the valve.

Vent holes reduce condensation build-up.

Equal percentage character-izing disc provides excellent control and reliability.

Forged brass valve body.

Dynamic pressure regulator assembly with stainless steel, brass, components and resilient polymer diaphragm.

Downstream low pressure PT port.

Upstream high pressure PT port. Double EPDM O-Ring

design for long service life.

Nickle plated body reduces corrosion and stress concentration.

Regulator helps maintain constant differential pressure across ball.

Regulator assembly built to last.

(2)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Set-up

Pressure Independent Characterized Control Valves (PICCV)

INSTALLATION

PICCVs should be installed with fl ow in the direction of the arrow on the valve body. If installed backwards, there could be damage da age to either the diaphragm or the regulator.

The valve assembly can be installed in a vertical or horizontal arrangement, as long as the actuator is positioned to avoid condensation from dripping on the actuator.

SET-UP

2-WAY VALVE SPECIFY UPON ORDERING

NON-SPRING RETURN

Stays in Last Position

LRB24-3, KRB24-3

Floating type actuators

NC: Normally Closed-Factory default with the directional switch in the 1 positon. Power to pin 2 will drive valve CW. Power to pin 3 will drive valve CCW.

NO: Normally Open-

LRB Only- Change directional switch from default “1” position to the “0” postion.

LRX24-MFT

ARX24-MFT MFT type actuators*

NC: Normally Closed-valve will open as voltage increases.

Actuator switch on Y2.

NO: Normally Open-valve will close as voltage increases.

Actuator switch on Y1.

LRB24-SA NC ONLY: Normally Closed-valve will open as voltage increases. Actuator switch on Y2

SPRING RETURN

Note Fail Position

LF24-MFT US AFRX24-MFT

MFT type actuators†

NC/FO Valve: Normally Closed-valve will open as voltage increases. Actuator switch on CW. Spring Action: Will fail open upon power loss.

NC/FC Valve: Normally Closed-valve will open as voltage increases. Actuator switch on CW. Spring Action: Will fail closed upon power loss.

NO/FC Valve: Normally Open-valve will close as voltage increases. Actuator switch on CCW. Spring Action: Will fail closed upon power loss.

NO/FO Valve: Normally Open-valve will close as voltage increases. Actuator switch on CCW. Spring Action: Will fail open upon power loss.

TFRX24-MFT NC/FO Valve: Normally Closed-valve will open as voltage increases. Switch on (arrow setting) Spring Action: Will fail open upon power loss.

NC/FC Valve: Normally Closed-valve will open as voltage increases. Switch on (arrow setting) Spring Action: Will fail closed upon power loss.

NO/FC Valve: Normally Open-valve will close as voltage increases. Switch on (arrow setting) Spring Action: Will fail closed upon power loss.

NO/FO Valve: Normally Open-valve will close as voltage increases. Switch on (arrow setting) Spring Action: Will fail open upon power loss.

*The design fl ow rate of PICCVs with MFT actuators are dependent on their Minimum and Maximum Percentages of rotation. Actuators must be re-programmed for different Minimum and Maximum Settings if actuator set-ups must be changed. Please refer to PICCV online technical documentation, MFT Adjustment Tables, for re-programming the settings.

(3)

P 10410 - 09/13 - S ubject to change. © Belimo Air controls (U S A), Inc .

Operation / Installation

Pressure Independent Characterized Control Valves (PICCV)

Maintain design fl ow independent of pressure variations.

The PICCV is a two-way valve that will supply a specific flow for each degree of ball opening regardless of pressure variations in a system.

FLOW PATTERN

PICCV consists of a differential pressure regulator in series with a control valve.

The control valve is throttled to match the fl ow command of the control signal. The differential pressure regulator holds the pressure drop across the ball of the valve. As system pressures change, the differential pressure regulator moves in response to keep the fl ow stable.

Pressure P1 at the inlet of the PICCV is high and pressure P3 at the outlet is low. The differential pressure between P1 and P3 must be between 5-50 PSID to achieve pressure independent fl ow. When differential pressure increases the regulator opening is reduced. When differential pressure decreases the regulator opening is increased. This allows for the constant pressure differential across the ball of the valve.

Regulator Section

Control Valve Section

Water exits valve – pressure is P3 (low).

Low pressure pulls regulator down against the spring force. P1- Upstream pressure

entering valve.

P1

P3

P3

P3 is downstream of the ball as well as below diaphgram. P1 is upstream.

P3

THE BEST WAY TO CONTROL FLOW

P2

(4)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

TYPICAL PARALLEL PIPING IN RELATION TO THE INPUT AND OUTPUT

(SCALE: NONE)

BELIMO PICCV (TYP.)

UNION CONNECTION (TYP.) PT PORT PT PORT AIR VENT H/C–COIL PT PORT PT PORT PT PORT FLOW TEE (TYP.) SHUT–OFF VALVE SHUT–OFF VALVE PARALLEL PIPING

ARRANGEMENT FOR PICCV

FLOW FLOW FLOW FLOW STRAINER FLOW PT PORT DRAIN FLOW

TYPICAL PARALLEL PIPING IN RELATION

TO THE INPUT AND OUTPUT

(Optional)

TYPICAL PIPING IN RELATION TO THE INPUT AND OUTPUT

(SCALE: NONE)

FLOW H/C–COIL

AIR VENT

PT PORT PT PORT

BELIMO PICCV (TYP.)

FLOW

SHUT–OFF VALVE

UNION CONNECTION (TYP.)

Piping the PICCV to Achieve a Larger Flow Rate

The Pressure Independent Characterized Control Valves can be piped in a parallel orientation to achieve increased fl ow rates.

PICCVs are available in fl ow values from 0.5 to 100 GPM. To achieve higher fl ows, it is recommended to pipe the two valves in parallel. To correctly operate these valves, the Belimo Multi Function Technology (MFT) will be employed to utilize one common control signal.

This recommended confi guration provides the control of fl ows up to 200 GPM by using two valves. The top diagram details valves piped in a parallel arrangement. The bottom diagram features a typical single piping arrangement.

If more than three valves are piped in parallel, please call Belimo to discuss control options.

(5)

P10410 - 09/13 - Subject to change. © Belimo Air controls (USA ), Inc .

Nomenclature

Pressure Independent Characterized Control Valves (PICCV)

Ordering Example

2

1

Choose the valve actuator combination.

Specify preference or confi guration. Does order

require tagging?

4

For MFT Orders Only - Select Programming Code

Non-Spring Return Actuator Models

NO = Normally Open

NC = Normally Closed Spring Return Actuator Models

NO/FO = Normally Open/Fail Open

NO/FC = Normally Open/Fail Closed

NC/FO = Normally Closed/Fail Open

NC/FC = Normally Closed/Fail Closed

Set-Up

P-10019 (A19)

P-10019 (A19) 2 to 10 VDC P-10028 (A28) 0 to 10 VDC P-20031 (W31) 0.02 to 5.00 seconds PWM P-20032 (W32) 0.10 to 25.50 seconds PWM P-20034 (W34) 0.59 to 2.93 seconds PWM P-30003 (F03) Floating Point

3

Tagging: Valves may be tagged per customer specifi cation. ($10.00 charge per tag) Example: AHU-1 FCU-2

Part number for tagging:

+NC

P2050B005+LRX24-MFT

+Tagging (if needed)

P

2

050

B

005

LRX

24

-MFT

Valve Type

P= Pressure

Independent

Characterized

Control Valve

Porting

2 = Two

Way

Valve Body

Size

050 = ½”

075 = ¾”

Body Type

B = Chrome

Plated

Flow Rate

005 = .50 GPM

010 = 1 GPM

015 = 1.5 GPM

020 = 2 GPM

025 = 2.5 GPM

030 = 3 GPM

035 = 3.5 GPM

040 = 4 GPM

045 = 4.5 GPM

050 = 5 GPM

055 = 5.5 GPM

060 = 6 GPM

065 = 6.5 GPM

070 = 7 GPM

075 = 7.5 GPM

080 = 8 GPM

085 = 8.5 GPM

090 = 9 GPM

095 = 9.5 GPM

100 = 10 GPM

Options

-P = PT Port

-F = Flow

Orifi ce

Actuator Type

Non-Spring Return

LRB…

LRX…

KRB...

Spring Return

TF…

LF…

Power

Supply

24 = 24 VAC

/DC

120 = 120

VAC

Control

-3 = Floating Point

-MFT =

Multi-Function

Technology

-SA = Proportional

2-10VDC

(6)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Nomenclature

Pressure Independent Characterized Control Valves (PICCV)

Ordering Example

2

1

Choose the valve actuator combination.

+NC

PICCV-25-012+LRX24-MFT

+Tagging (if needed)

Specify preference or confi guration. Does order

require tagging?

4

For MFT orders only - select programming code

Non-Spring Models

NO = Normally Open

NC = Normally Closed Spring Return Models

NO/FO = Normally Open/Fail Open

NO/FC = Normally Open/Fail Closed

NC/FO = Normally Closed/Fail Open

NC/FC = Normally Closed/Fail Closed

Refers to valve ports from inlet to outlet, per fl ow arrow. Set-Up

P-10019 (A19)

P-10019 (A19) 2 to 10 VDC P-10028 (A28) 0 to 10 VDC P-20031 (W31) 0.02 to 5.00 seconds PWM P-20032 (W32) 0.10 to 25.50 seconds PWM P-20034 (W34) 0.59 to 2.93 seconds PWM P-30003 (F03) Floating Point P-10019 (A19) On/Off**

3

Tagging: Valves may be tagged per customer specifi cation. ($10.00 charge per tag) Example: AHU-1 FCU-2

Part number for tagging: 99981-00101

PICCV

25

-012

+LRX

24

-MFT

Pressure

Independent

Characterized

Control Valve

2-way Chrome

Plated Brass Ball

and Brass Stem

Valve Size

25 = 1”

32 = 1¼”

40 = 1½”

50 = 2”

Flow Rate

3 GPM

Refer to table

Options

-P = PT Port

-F = Flow

Orifi ce

Actuator Type

Non-Spring Return

LRB…

LRX…

ARX…

Spring Return

TF…

LF…

AF…

Power Supply

24 = 24 VAC/DC

120 = 120 VAC

Control

-3 = Floating Point

-MFT = Multi-Function

Technology

-SA = Proportional

2-10 VDC

S = Built-in

Auxiliary

Switch

(7)

P10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Factory Set Pressure Independent Characterized Control Valves (PICCV)

Product Range Overview – P2..., 2-way

PI

CCV

Characteristic Mode of Operation

The Pressure Independent Characterized Control Valve (PICCV) is a two-way valve which combines the functionality of a control valve and a pressure regulating valve, creating one precise product which is unaffected by pressure variations in a system.

Product Features

Constant fl ow regardless of pressure variations in the system at set degrees of ball opening. Maximizes chillerΔT, preventing energizing additional chillers due to lowΔT. Simplifi ed valve sizing and selection, no Cv calculations required.

(-P)ΔP verifi cation across valve using PT ports.

Actuator Specifi cations

Control type

-3 on/off, fl oating point

-MFT proportional, 2-10 VDC (confi gurable)

Manual override (LRB, LRX, AFRX, ARX)

Electrical connection 3 ft. [1m] cable with ½” conduit fi tting (additional cable lengths are available)

Valve Specifi cations

Service chilled or hot water, 60% glycol max

Flow characteristic equal percentage Controllable fl ow range 75°

Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”

End fi tting NPT female ends

Materials

Body brass, nickel plated

Ball chrome plated brass

Stem chrome plated brass

Seats

½” and ¾” Tefl on® PTFE 1” to 2” Tefl on® PTFE /Tefzel®

Seat o-rings Viton®

Characterizing disc

½” and ¾” brass

1” to 2” Tefzel®

O-rings EPDM (lubricated)

Diaphragm

½” and ¾” Nomex reinforced silicone 1” to 2” polyester reinforced silicone Regulator components stainless steel/brass/Nitrile

Spring stainless steel

Media temp range 0°F to 212°F [-18°C to +100°C]

PT Ports optional, ½” to ¾” internal

1” to 2” external (-P) Body pressure rating

600 psi ½”, ¾”, 1”

400 psi 1¼”, 1½”, 2”

Valve Nominal Size Type Suitable Actuators

GPM** Inches DN [mm] 2-way NPT Non-Spring Return Spring Return

Models with

(-P

) have integral PT ports

Forged Bod

y

0.5 ½ 15 P2050B005 (-P)

LRB24-3

LRX24-MFT LRX120-3

LRCB24-3 (Heat Pump Only)

TFRX24-MFT LF24-MFT US 1 ½ 15 P2050B010 (-P) 1.5 ½ 15 P2050B015 (-P) 2 ½ 15 P2050B020 (-P) 2.5 ½ 15 P2050B025 (-P) 3 ½ 15 P2050B030 (-P) 3.5 ½ 15 P2050B035 (-P) 4 ½ 15 P2050B040 (-P) 4.5 ½ 15 P2050B045 (-P) 5 ½ 15 P2050B050 (-P) 5.5 ½ 15 P2050B055 (-P) 6 ¾ 20 P2075B060 (-P) 6.5 ¾ 20 P2075B065 (-P) 7 ¾ 20 P2075B070 (-P) 7.5 ¾ 20 P2075B075 (-P) 8 ¾ 20 P2075B080 (-P) 8.5 ¾ 20 P2075B085 (-P) 9 ¾ 20 P2075B090 (-P) 9.5 ¾ 20 P2075B095 (-P) 10 ¾ 20 P2075B100 (-P) Models with (-P

) have external PT port

s 11 1 25 PICCV-25-011 (-P) 12 1 25 PICCV-25-012 (-P) 13 1 25 PICCV-25-013 (-P) 14 1 25 PICCV-25-014 (-P) 15 1 25 PICCV-25-015 (-P) 16 1 25 PICCV-25-016 (-P) 17 1 25 PICCV-25-017 (-P) 18 1 25 PICCV-25-018 (-P) 19 1 25 PICCV-25-019 (-P) C ast Bod y 18 1¼ 32 PICCV-32-018 (-P) ARX24-MFT AFRX24-MFT 19 1¼ 32 PICCV-32-019 (-P) 20 1¼ 32 PICCV-32-020 (-P) 21 1¼ 32 PICCV-32-021 (-P) 22 1¼ 32 PICCV-32-022 (-P) 23 1¼ 32 PICCV-32-023 (-P) 24 1¼ 32 PICCV-32-024 (-P) 25 1¼ 32 PICCV-32-025 (-P) 26 1¼ 32 PICCV-32-026 (-P) 26 1½ 40 PICCV-40-026 (-P) 27 1½ 40 PICCV-40-027 (-P) 28 1½ 40 PICCV-40-028 (-P) 29 1½ 40 PICCV-40-029 (-P) 30 1½ 40 PICCV-40-030 (-P) 31 1½ 40 PICCV-40-031 (-P) 32 1½ 40 PICCV-40-032 (-P) 33 1½ 40 PICCV-40-033 (-P) 33 2 50 PICCV-50-033 (-P) 34 2 50 PICCV-50-034 (-P) 35 2 50 PICCV-50-035 (-P) 36 2 50 PICCV-50-036 (-P) 37 2 50 PICCV-40-037 (-P) 38 2 50 PICCV-40-038 (-P) 39 2 50 PICCV-40-039 (-P) 40 2 50 PICCV-50-040 (-P) 44 2 50 PICCV-50-044 (-P) 48 2 50 PICCV-50-048 (-P)

(8)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Field Set

Pressure Independent Characterized Control Valves (PICCV)

Product Range Overview – P2..., 2-way

Mode of Operation

The Pressure Independent Characterized Control Valve (PICCV) is a two-way valve which combines the functionality of a control valve and a pressure regulating valve, creating one precise product which is unaffected by pressure variations in a system. Product Features

Once fi eld set the valve will provide constant fl ow regardless of pressure variations in the system at set degrees of ball opening. Maximizes chillerΔT, preventing energizing additional chillers due to lowΔT. Simplifi ed valve sizing and selection, no Cv calculations required.

(-P)ΔP verifi cation across valve using PT ports. (-F) Flow verifi cation usingΔP across orifi ce.

Valve is supplied at maximum fl ow in the full open position only. Field adjustment is necessary to achieve lower flow.

Actuator Specifi cations

Control type on/off, fl oating point

Manual override KRB, LRB...-SA

Electrical connection 3 ft. [1m] cable (no conduit on KR) ½” conduit fi tting on LR only

Valve Specifi cations

Service chilled or hot water, 60% glycol max

Flow characteristic equal percentage Controllable fl ow range 75°

Sizes ½”, ¾”, 1”

End fi tting NPT female ends

Materials

Body brass, nickel plated

Ball chrome plated brass

Stem chrome plated brass

Seats

½” and ¾” Tefl on®

PTFE

1” Tefl on®

PTFE /Tefzel®

Seat o-rings Viton®

Characterizing disc

½” and ¾” brass

1” Tefzel®

O-rings EPDM (lubricated)

Diaphragm

½” and ¾” Nomex reinforced silicone

1” polyester reinforced silicone

Regulator components stainless steel/brass/Nitrile

Spring stainless steel

Media temp range 0°F to 212°F [-18°C to +100°C] KR valve assembly 0°F to 176°F [-18°C to +80°C] Body pressure rating 600 psi

Valve Nominal Size Type Suitable Actuators

GPM Range Inches DN [mm] 2-way NPT Non-Spring Return

0...(0.5-1.5) ½ 15 P2050B010 KRB24-3 LRB24-SA 0...(1.6-3.0) ½ 15 P2050B025 0...(3.0-5.6) ½ 15 P2050B055 0...(5.7-10) ¾ 20 P2075B100 0...(11-16) 1 25 PICCV-25-016 0...(17-21) 1 25 PICCV-25-021

PI

CCV

Characteristic

ΔP verifi cation across valve using PT ports (-P)

Valve Nominal Size Type Suitable Actuators

GPM Range Inches DN [mm] 2-way NPT Non-Spring Return

0...(0.5-1.5) ½ 15 P2050B010-P KRB24-3 LRB24-SA 0...(1.6-3.0) ½ 15 P2050B025-P 0...(3.0-5.6) ½ 15 P2050B055-P 0...(5.7-10) ¾ 20 P2075B100-P 0...(11-16) 1 25 PICCV-25-016-P 0...(17-21) 1 25 PICCV-25-021-P

Flow verifi cation using ΔP across orifi ce (-F)

Valve Nominal Size Type Suitable Actuators

GPM Range Inches DN [mm] 2-way NPT Non-Spring Return

0...(0.5-1.5) ½ 15 P2050B010-F KRB24-3 LRB24-SA 0...(1.6-3.0) ½ 15 P2050B025-F 0...(3.0-5.6) ½ 15 P2050B055-F 0...(5.7-10) ¾ 20 P2075B100-F 0...(11-16) 1 25 PICCV-25-016-F 0...(17-21) 1 25 PICCV-25-021-F

(9)

P 10410 - 09/13 - S ubject to change. © Belimo Air controls (U S A), Inc .

Factory Set

P2... Series Pressure Independent Characterized Control Valves (PICCV)

Chrome Plated Brass Ball and Brass Stem, NPT Female Ends

Technical Data

Service chilled or hot water, 60% glycol

Flow characteristic equal percentage

Size ½”, ¾”, 1”

Type of end fi tting female, NPT Materials

Body forged brass, nickel plated

Ball chrome plated brass

Stem chrome plated brass

Seat O-rings Viton

Seat fi berglass reinforced Tefl on® PTFE

Characterizing disc ½” & ¾” Brass 1” TEFZEL®

Packing 2 EPDM O-rings, lubricated

Diaphragm ½” & ¾” silicone and Nomex 1” polyester reinforced silicone Regulator components stainless steel/brass/Nitrile

Spring stainless steel

Body pressure rating 600 PSI

Media temp. range 0°F to 212°F [-18°C to +100°C] Close off pressure 200 PSI

Leakage ANSI Class IV (0.01% of rated valve

capacity at 50 psi differential)

Rangeability 100 : 1

Differential pressure 5 to 50 PSI operating range

Valve accuracy ± 5%*

Weight of valve body ½” = 2.52 lbs ¾” = 2.52 lbs 1” = 4.98 lbs

½” body has three discs with different fl ow capbilities (.50 GPM to 1 GPM), (1.5 GPM to 2.5 GPM), (3 GPM to 5.5 GPM)

1” body has two discs with different fl ow capabilities (11 GPM to 16 GPM), (17 GPM to 19 GPM) Tefzel®® and Tefl on®® are registered trademarks of Dupont™

* See page 3 for more details.

Application

The Pressure Independent Characterized Control Valve is typically used in air handling units on heating and cooling coils, and fan coil unit heating or cooling coils. Some other common applications include unit ventilators and VAV re-heat coils. This valve is suitable for use in a hydronic system with constant or variable fl ow.

This valve is designed with MFT functionality which facilitates the use of various control input.

Flow Rate

Valve

Nominal Size Suitable Actuators

Valve Model GPM

Liter/sec Inches DN mm Close-off

PSI ReturnSpring Non-Spring Return

P2050B005(-P) 0.5 0.03 ½ 15 200

TFR24-MFT US

LF24-MFT US LRB(X)24-3 LRX24-MFT

LRCB24-3 Heat Pump Only

P2050B010(-P) 1 0.06 ½ 15 200 P2050B015(-P) 1.5 0.09 ½ 15 200 P2050B020(-P) 2 0.13 ½ 15 200 P2050B025(-P) 2.5 0.16 ½ 15 200 P2050B030(-P) 3 0.19 ½ 15 200 P2050B035(-P) 3.5 0.22 ½ 15 200 P2050B040(-P) 4 0.25 ½ 15 200 P2050B045(-P) 4.5 0.28 ½ 15 200 P2050B050(-P) 5 0.32 ½ 15 200 P2050B055(-P) 5.5 0.35 ½ 15 200 P2075B060(-P) 6 0.38 ¾ 20 200 P2075B065(-P) 6.5 0.41 ¾ 20 200 P2075B070(-P) 7 0.44 ¾ 20 200 P2075B075(-P) 7.5 0.47 ¾ 20 200 P2075B080(-P) 8 0.50 ¾ 20 200 P2075B085(-P) 8.5 0.54 ¾ 20 200 P2075B090(-P) 9 0.57 ¾ 20 200 P2075B095(-P) 9.5 0.60 ¾ 20 200 P2075B100(-P) 10 0.63 ¾ 20 200 PICCV-25-011(-P) 11 0.69 1 25 200 PICCV-25-012(-P) 12 0.76 1 25 200 PICCV-25-013(-P) 13 0.82 1 25 200 PICCV-25-014(-P) 14 0.88 1 25 200 PICCV-25-015(-P) 15 0.95 1 25 200 PICCV-25-016(-P) 16 1.01 1 25 200 PICCV-25-017(-P) 17 1.07 1 25 200 PICCV-25-018(-P) 18 1.14 1 25 200 PICCV-25-019(-P) 19 1.20 1 25 200 (-P) optional,ΔP verifi cation across valve using PT ports

(10)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Field Set

P2... Series Pressure Independent Characterized Control Valves

Chrome Plated Brass Ball and Brass Stem, NPT Female Ends

Technical Data

Service chilled or hot water, 60% glycol Flow characteristic equal percentage

Size ½”, ¾”, 1” Type of end fi tting female, NPT Materials

Body forged brass, nickel plated Ball chrome plated brass Stem chrome plated brass Seat O-rings Viton

Seat fi berglass reinforced Tefl on® PTFE

Characterizing disc ½” & ¾” brass 1” TEFZEL®

Packing 2 EPDM O-rings, lubricated Diaphragm ½” & ¾” silicone and Nomex

1” polyester reinforced silicone Regulator components stainless steel/brass/Nitrile Spring stainless steel

Body pressure rating 600 PSI Media temp. range

LRB24-SA 0°F to 212°F [-18°C to +100°C] KRB24-3 0°F to 176°F [-18°C to +80°C] Close off pressure 200 PSI

Leakage ANSI Class IV (0.01% of rated valve capacity at 50 psi differential) Rangeability 100 : 1

Differential pressure 5 to 50 psi operating range Valve accuracy ± 5%*

Weight of valve body ½” = 2.52 lbs [1.14 kg] ¾” = 2.52 lbs [1.14 kg] 1” = 4.98 lbs [2.26 kg]

Tefzel®® and Tefl on®® are registered trademarks of Dupont™. *See page 3 for more details.

Valve is supplied at maximum fl ow in the full open position

only. Field adjustment is necessary to ach

ie

ve lower flow.

Application

The Pressure Independent Characterized Control Valve is typically used in air handling units on heating and cooling coils, and fan coil unit heating or cooling coils. Some other common applications include unit ventilators and VAV re-heat coils. This valve is suitable for use in a hydronic system with constant or variable fl ow. Valve Nominal Size Suitable Actuators Valve Model GPM Range Inches DN mm Close-off

PSI Non-Spring Return

P2050B010 0...(0.5-1.5) ½ 15 200 KRB24-3 LRB24-SA P2050B025 0...(1.6-3.0) ½ 15 200 P2050B055 0...(3.0-5.6) ½ 15 200 P2075B100 0...(5.7-10) ¾ 20 200 PICCV-25-016 0...(11-16) 1 25 200 PICCV-25-021 0...(17-21) 1 25 200 PT Ports Valve Nominal Size Suitable Actuators Valve Model GPM Range Inches DN mm Close-off

PSI Non-Spring Return

P2050B010-P 0...(0.5-1.5) ½ 15 200 KRB24-3 LRB24-SA P2050B025-P 0...(1.6-3.0) ½ 15 200 P2050B055-P 0...(3.0-5.6) ½ 15 200 P2075B100-P 0...(5.7-10) ¾ 20 200 PICCV-25-016-P 0...(11-16) 1 25 200 PICCV-25-021-P 0...(17-21) 1 25 200

(-P) optional, ΔP verifi cation across valve using PT ports.

Flow Verifi cation Orifi ce

Valve Nominal Size Suitable Actuators Valve Model GPM Range Inches DN mm Close-off

PSI Non-Spring Return

P2050B010-F 0...(0.5-1.5) ½ 15 200 KRB24-3 LRB24-SA P2050B025-F 0...(1.6-3.0) ½ 15 200 P2050B055-F 0...(3.0-5.6) ½ 15 200 P2075B100-F 0...(5.7-10) ¾ 20 200 PICCV-25-016-F 0...(11-16) 1 25 200 PICCV-25-021-F 0...(17-21) 1 25 200

(11)

P10410 - 09/13 - Subject to change. © Belimo Air controls (USA ), Inc .

Factory Set

P2... Series Pressure Independent Characterized Control Valves (PICCV)

Chrome Plated Brass Ball and Brass Stem, NPT Female Ends

Technical Data

Service chilled or hot water, 60% glycol

Flow characteristic equal percentage

Size 1¼”, 1½”, 2”

Type of end fi tting female, NPT Materials

Body forged brass, nickel plated

Ball chrome plated brass

Stem chrome plated brass

Seat O-rings Viton

Seat fi berglass reinforced Tefl on® PTFE Characterizing disc TEFZEL®

Packing 2 EPDM O-rings, lubricated

Diaphragm polyester reinforced silicone Regulator components stainless steel/brass/Nitrile

Spring stainless steel

Body pressure rating 400 PSI

Media temp. range 0°F to 212°F [-18°C to 100°C] Close-off pressure 200 PSI

Leakage ANSI Class IV (0.01% of rated valve

capacity at 50 psi differential)

Rangeability 100 : 1

Differential pressure 5 to 50 PSI operating range

Valve accuracy ± 5%*

Weight of valve body 1¼” = 8.31 lbs 1½” = 7.70 lbs 2” = 9.38 lbs 2” large = 29.10 lbs

2” body has two different fl ow capacities (44 GPM to 80 GPM) (90 GPM & 100 GPM) Tefzel®and Tefl on® are registered trademarks of Dupont™.

*See page 3 for more details.

Application

The Pressure Independent Characterized Control Valve is typically used in air handling units on heating and cooling coils, and fan coil unit heating or cooling coils. Some other common applications include unit ventilators and VAV re-heat coils. This valve is suitable for use in a hydronic system with constant or variable fl ow.

This valve is designed with MFT functionality which facilitates the use of various control input.

Flow Rate Valve Nominal

Size Suitable Actuators

Valve Model

GPM

Liter/sec Inches DN mm Close-off

PSI Spring Return Non-Spring Return

PICCV-32-018(-P) 18 1.14 1¼ 32 200 AFRX24-MFT US ARX24-MFT PICCV-32-019(-P) 19 1.20 1¼ 32 200 PICCV-32-020(-P) 20 1.26 1¼ 32 200 PICCV-32-021(-P) 21 1.32 1¼ 32 200 PICCV-32-022(-P) 22 1.39 1¼ 32 200 PICCV-32-023(-P) 23 1.45 1¼ 32 200 PICCV-32-024(-P) 24 1.51 1¼ 32 200 PICCV-32-025(-P) 25 1.58 1¼ 32 200 PICCV-32-026(-P) 26 1.64 1¼ 32 200 PICCV-40-026(-P) 26 1.64 1½ 40 200 PICCV-40-027(-P) 27 1.70 1½ 40 200 PICCV-40-028(-P) 28 1.77 1½ 40 200 PICCV-40-029(-P) 29 1.83 1½ 40 200 PICCV-40-030(-P) 30 1.89 1½ 40 200 PICCV-40-031(-P) 31 1.96 1½ 40 200 PICCV-40-032(-P) 32 2.01 1½ 40 200 PICCV-40-033(-P) 33 2.08 1½ 40 200 PICCV-50-033(-P) 33 2.08 2 50 200 PICCV-50-034(-P) 34 2.15 2 50 200 PICCV-50-035(-P) 35 2.21 2 50 200 PICCV-50-036(-P) 36 2.27 2 50 200 PICCV-50-037(-P) 37 2.33 2 50 200 PICCV-50-038(-P) 38 2.40 2 50 200 PICCV-50-039(-P) 39 2.46 2 50 200 PICCV-50-040(-P) 40 2.52 2 50 200 PICCV-50-044(-P) 44 2.78 2 50 200 PICCV-50-048(-P) 48 3.03 2 50 200 PICCV-50-052(-P) 52 3.28 2 50 200 PICCV-50-056(-P) 56 3.53 2 50 200 PICCV-50-060(-P) 60 3.79 2 50 200 PICCV-50-065(-P) 65 4.10 2 50 200 PICCV-50-070(-P) 70 4.42 2 50 200 PICCV-50-075(-P) 75 4.73 2 50 200 PICCV-50-080(-P) 80 5.05 2 50 200 PICCV-50-090(-P) 90 5.68 2 50 200 PICCV-50-100(-P) 100 6.31 2 50 200 (-P) optional,ΔP verifi cation across valve using PT ports

(12)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Field Set KRB24-3 Actuator, On/Off, Floating Point

Technical Data

Power supply 24 VAC ± 20% 50/60 Hz 24 VDC ± 20% Power consumption 1.0 W (0.2 W resting) Transformer sizing 1.5 VA (Class 2 power source) Electrical connection 3 ft., 18 GA appliance rated cable

protected NEMA 2 (IP54) Overload protection electronic throughout rotation Control on/off, fl oating point Angle of rotation without end stop; limitless

with end stop; 315° fi x 287.5° max. with two end stops Torque 18 in-lbs [2 Nm]

Direction of rotation by electrical installation

Position indication reflective visual indicator (snap-on), with magnet Manual override disengage with magnet

Running time 75 seconds, constant independent of load Humidity 5 to 95% RH non condensing (EN 60730-1) Ambient temperature -22°F to +122°F [-30°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA 2, IP54

Noise level <45dB(A) Servicing maintenance free Quality standard ISO 9001 Weight 0.4 lbs [0.18 kg]

† Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.

Dimensions(Inches [mm]) D1 3 1 8 1.35” [34.2] 6.30” [160] C A B D 2.47” [62.8] E F Valve

Nominal Size Dimensions (Inches [mm])

In. DN

[mm] A B C D E F

½” 15 6.56" [167] 4.47" [114] 5.09" [129] 2.34" [59] 1.35" [34] 1.25" [32] ¾” 20 6.8" [173] 5.4" [137] 5.09" [129] 2.34" [59] 1.35" [34] 1.25" [32]

Dimensions with PT Port(Inches [mm])

D1 30 1 1.35” [34.2] 6.30” [160] D A B C Valve

Nominal Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F ½” 15 6.56" [167] 4.47" [114] 6.43" [163] 3.54" [90] 1.35" [34] 2.4" [61] ¾” 20 6.8" [173] 5.4" [137] 6.43" [163] 3.54" [90] 1.35" [34] 2.4" [61] 2.47” [62.8] E F

Models

KRB24-3

Valve is supplied at maximum flow in the full open

position

only. Field adjustment is necessary to

ach

ie

ve lower flow.

(13)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls (USA), Inc

.

Field Set KRB24-3 Actuator, On/Off, Floating Point

Wiring Diagrams

1 Provide overload protection and disconnect as required.

2

CAUTION Equipment Damage!

Actuators may be connected in parallel.

Power consumption and input impedance must be observed.

3 Actuators may also be powered by 24 VDC.

WARNING Live Electrical Components!

G

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-nents could result in death or serious injury.

W

536_08

On/Off Control

W

537_08

Floating Point or On/Off Control Typical Specification

Actuators shall have brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have manual override on the cover. Run time shall be constant and independent of torque. Actuators shall have a 5-year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo.

SAFETY NOTES

The actuator is not allowed to be used outside the specifi ed fi eld application. Assembly must be carried out by trained personnel. Any legal regulations or regulations issued by authorities must be observed during assembly. The device may only be opened at the manufacturer’s site. It does not contain any parts that can be replaced or repaired by the user.

The cable must not be removed from the device.

The device contains electrical and electronic components and is not allowed to be disposed of as household refuse. All locally valid regulations and requirements must be observed.

Dimensions with Orifice*(Inches [mm])

D 130 2 1.35” [34.2] 6.30” [160] A,B C D Valve

Nominal Size Dimensions (Inches [mm]) In. DN [mm] A B C D E F ½” 15 7.6" [193] 7.6" [193] 5.09" [129] 2.34" [59] 1.35" [34] 1.25" [32] ¾” 20 8.53" [217] 8.53" [217] 5.09" [129] 2.34" [59] 1.35" [34] 1.25" [32] 2.47” [62.8] E F

(14)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

LRB24-SA Actuator, Proportional

Model

LRB24-SA

Technical Data

Power supply 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% Power consumption running 1.5 W

holding 0.2 W

Transformer sizing 2 VA (class 2 power source) Electrical connection 3 ft., 18 GA, plenum rated cable

½” conduit connector

Overload protection electronic throughout 0° to 95° rotation Control proportional (2-10 VDC)

Angle of rotation 90°, adjustable with mechanical stop Position indication handle

Manual override external push button

Running time 90 seconds, constant independent of load Humidity 5 to 95% RH, non-condensing (EN 60730-1) Ambient temperature -22°F to +122°F [-30°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C] Housing type NEMA 2/IP54

Housing material UL94-5VA

Agency listings† cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC

Noise level less than 35 dB (A) Quality standard ISO 9001

† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1 (1.B for -S models)

Dimensions (inches [mm]) C A B D E F 2.6" [66] 6.5" [165] 1.69" [42] 3.22" [82] 2.34" [59.4] D1 3 1 9 Valve

Nominal Size Dimensions (Inches [mm])

In. DN

[mm] A B C D E F

½” 15 7.68" [195] 4.47" [114] 7.13" [181] 2.34" [59] 1.48" [38] 1.48" [38] ¾” 20 7.98" [203] 5.4" [137] 7.13" [181] 2.34" [59] 1.48" [38] 1.48" [38] 1” 25 8.9" [226] 6.85" [174] 8.02" [204] 3.23" [82] 1.6" [41] 1.6" [41]

Dimensions with PT Port(Inches [mm])

D1 309 6.5" [165] 1.69" [42] 3.22" [82] 2.34" [59.4] D A B C Valve

Nominal Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F ½” 15 7.68" [195] 4.47" [114] 8.47" [215] 3.54" [90] 1.48" [38] 2.4" [61] ¾” 20 7.98" [203] 5.4" [137] 8.47" [215] 3.54" [90] 1.48" [38] 2.4" [61] 2.6" [66] E F

Valve is supplied at maximum flow in the full open

position

only. Field adjustment is necessary to

ach

ie

ve lower flow.

(15)

P 10410 - 09/13 - S ubject to change. © Belimo Air controls (U S A), Inc .

LRB24-SA Actuator, Proportional

2 3 24 VAC Transformer Blk (1) Common Red (2) + Hot Wht (3) + Input a Line Volts 18 Function 100% Max a W 123 On/Off Blk (1) Common Red (2) + Hot Wht (3) Y Input, 2 to 10V Org (5) U Output, 2 to 10V 24 VAC Transformer 5 7 Control Signal (+) VDC/mA (–) Feedback Signal (+)2 to 10 VDC (–) Ω 500 Ω Line Volts 3 18 VDC/4-20 mA Wiring Diagrams 2

CAUTION

Equipment damage!

Actuators may be connected in parallel. Power consumption and

q p

q p

g

g

input impedance must be observed.

3 Actuators may also be powered by 24 VDC.

5 Only connect common to neg. (-) leg of control circuits. 7 A 500 VDC.  resistor converts the 4 to 20 mA control signal to 2 to 10

18 Actuators with plenum rated cable do not have numbers on wires;use color codes instead.

Meets cULus requirements without the need of an electrical ground connection

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

Dimensions with PT Port(Inches [mm])

D131 0 6.5" [165] 1.69" [42] 3.22" [82] 2.34" [59.4] A,B C D Valve

Nominal Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F 1” 25 12.6" [320] 12.6" [320] 8.02" [204] 2.95" [75] 1.6" [41] 1.6" [41] 2.6" [66] E F

Dimensions with Orifice*(Inches [mm])

D

1

3

11

Valve

Nominal Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F ½” 15 7.6" [193] 7.6" [193] 4.05" [103] 2.34" [59] 1.25" [32] 1.25" [32] ¾” 20 8.53" [217] 8.53" [217] 4.05" [103] 2.34" [59] 1.25" [32] 1.25" [32] 1” 25 8.9" [226] 8.9" [226] 8.02" [204] 3.23" [82] 1.6" [41] 1.6" [41] 2.6" [66] E F 6.5" [165] 1.69" [42] 3.22" [82] 2.34" [59.4] A, B C D

(16)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

LRB24-3, LRB24-3-S, LRX24-3 Actuators, On/Off, Floating Point

Models

LRB24-3

LRB24-3-S w/built-in Aux. Switch LRX24-3

Technical Data

Power supply 24 VAC ± 20% 50/60 Hz

24 VDC ± 10% Power consumption running 1.5 W

holding 0.2 W

Transformer sizing 2 VA (class 2 power source) Electrical connection 3 ft., 18 GA, plenum rated cable

½” conduit connector

Overload protection electronic throughout 0° to 95° rotation

Control on/off, fl oating point

Input impedance 600 Ω

Angle of rotation 90°, adjustable with mechanical stop Direction of rotation reversible with protected

Position indication handle

Manual override external push button

Running time 95 seconds, constant independent of load Humidity 5 to 95% RH, non-condensing (EN 60730-1) Ambient temperature -22°F to +122°F [-30°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C]

Housing type NEMA 2/IP54

Housing material UL94-5VA

Agency listings† cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC

Noise level less than 35 dB (A)

Quality standard ISO 9001

LRB24-3-S

Auxiliary switch 1 SPDT, 3A (0.5A) @ 250 VAC, UL Listed, adjustable 0° to 100°

† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1 (1.B for -S models)

Dimensions (inches [mm]) C A B D E F 2.6" [66] 6.5" [165] 1.69" [42] 0.78" [20] 3.22" [82] 2.34" [59.4] FlowSetR™ Dimensions D1 3 2 0 Valve

Nominal Size Dimensions (Inches [mm]) In. DN

[mm] A B C D E F

½” 15 7.68" [195] 4.47" [114] 7.91" [201] 2.34" [59] 1.48" [38] 1.48" [38] ¾” 20 7.98" [203] 5.4" [137] 7.91" [201] 2.34" [59] 1.48" [38] 1.48" [38] 1” 25 8.9" [226] 6.85" [174] 8.8" [224] 3.23" [82] 1.6" [41] 1.6" [41]

Dimensions with PT Port (Inches [mm])

D1 303 6.5" [165] 1.69" [42] 0.78" [20] 3.22" [82] 2.34" [59.4] FlowSetR™ Dimensions D A B C Valve

Nominal Size Dimensions (Inches [mm]) In. DN

[mm] A B C D E F

2.6" [66]

(17)

P 10410 - 09/13 - S ubject to change. © Belimo Air controls (U S A), Inc . Wiring Diagrams

2

CAUTION

Equipment damage!

Actuators may be connected in parallel.

Power consumption and input impedance must be observed.

3 Actuators are provided with color coded wires.Wire numbers are provided for reference. 4 Actuators may also be powered by 24 VDC.

Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

3 4 24 VAC Transformer

a open a closed

The indication of direction is valid for switch position 1.

Blk (1) Common Red (2) + Wht (3) + LRB24-3 1 0 a Line Volts On/Off Control 24 VAC Transformer

The indication of direction is valid for switch position 1.

Blk (1) Common Red (2) + Wht (3) + LRB24-3 Line Volts 1 0 3 4 W 123

Floating Point Control

LRB24-3-S S1 S2 S3 NC NO 0° to 95° W 169 Auxiliary Switch

LRB24-3, LRB24-3-S, LRX24-3 Actuators, On/Off, Floating Point

Dimensions with PT Port (Inches [mm])

D130 4 6.5" [165] 1.69" [42] 0.78" [20] 3.22" [82] 2.34" [59.4] FlowSetR™ Dimensions A, B C D Valve

Nominal Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F 1” 25 12.6" [320] 12.6" [320] 8.02" [204] 2.95" [75] 1.6" [41] 1.6" [41] 2.6" [66] E F

(18)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

LRX120-3 Actuators, On/Off, Floating Point

Models

LRX120-3

Technical Data

Control on/off, fl oating point

Power supply 100 to 240 VAC, 50/60 Hz (nominal) 85 to 265 VAC, 50/60 Hz (tolerance) Power consumption running 2 W

holding 0.5 W

Transformer sizing 4 VA (class 2 power source) Electrical connection ½” conduit connector

18 GA, plenum rated cable 3 ft. [1m] 10 ft. [3m] 16 ft. [5m] Overload protection electronic throughout 0° to 95° rotation

Input impedance 600 Ω

Angle of rotation 90°, adjustable with mechanical stop Direction of rotation reversible with protected

Position indication handle

Manual override external push button Running time 150, 95, 60, 45, 35 seconds,

constant independent of load

Humidity 5 to 95% RH non-condensing

(EN 60730-1)

Ambient temperature -22°F to +122°F [-30°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C]

Housing NEMA 2/IP54

Housing material UL94-5VA

Agency listings† cULus acc. to UL 60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC (and 2006/95/EC for line voltage and/or -S versions)

Noise level <35 dB(A)

Quality standard ISO 9001

† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1

Dimensions (Inches [mm]) C A B D E F D1 3 21 Valve

Nominal Size Dimensions (Inches [mm]) In. DN

[mm] A B C D E F

½” 15 7.68" [195] 4.47" [114] 7.91" [201] 2.34" [59] 1.48" [38] 1.48" [38] ¾” 20 7.98" [203] 5.4" [137] 7.91" [201] 2.34" [59] 1.48" [38] 1.48" [38] 1” 25 8.9" [226] 6.85" [174] 8.8" [224] 3.23" [82] 1.6" [41] 1.6" [41]

Dimensions with PT Port(Inches [mm])

D1 305 D A B C Valve

Nominal Size Dimensions (Inches [mm]) In. DN

[mm] A B C D E F

½” 15 7.68" [195] 4.47" [114] 9.25" [235] 3.54" [90] 1.48" [38] 2.4" [61] ¾” 20 7.98" [203] 5.4" [137] 9.25" [235] 3.54" [90] 1.48" [38] 2.4" [61]

(19)

P 10410 - 09/13 - S ubject to change. © Belimo Air controls (U S A), Inc . Wiring Diagrams

2

CAUTION

Equipment damage!

Actuators may be connected in parallel.

Power consumption and input impedance must be observed.

Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

W4

05

On/Off

W4

06

Floating Point or On/Off Control

LRX120-3 Actuators, On/Off, Floating Point

Dimensions with PT Port (Inches [mm])

D130 6 A,B C D Valve

Nominal Size Dimensions (Inches [mm]) In. DN

[mm] A B C D E F

1” 25 12.6" [320] 12.6" [320] 8.02" [204] 2.95" [75] 1.6" [41] 1.6" [41]

(20)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls (USA ), Inc .

Model

LRX24-MFT Technical Data

Power supply 24 VAC ± 20% 50/60 Hz

24 VDC ± 10% Power consumption running 2 W

holding 1.2 W

Transformer sizing 5 VA (class 2 power source) Electrical connection 18 GA plenum rated cable

1/2” conduit connector 3 ft. [1m] 10 ft. [3m] 16 ft. [5m] Overload protection electronic throughout 0° to 95° rotation Operating range Y 2 to 10 VDC, 4 to 20 mA (default)

variable (VDC, PWM, fl oating point, on/off) Input impedance 100 kΩ (0.1 mA), 500 Ω

1500 Ω (PWM, fl oating point, on/off) Feedback output U 2 to 10 VDC, 0.5mA max

VDC variable

Angle of rotation max. 95°, adjust. with mechanical stop electronically variable

Torque 45 in-lbs [5 Nm]

Direction of rotation reversible with protected Position indication handle

Manual override external push button

Running time 100 seconds

variable (35 to 150 seconds)

Humidity 5 to 95% RH non condensing

(EN 60730-1)

Ambient temperature -22°F to +122°F [-30°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C]

Housing NEMA 2/IP54

Housing material UL94-5VA

Agency listings† cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC

Noise level <35dB(A)

Quality standard ISO 9001

Weight 1.5 lbs [0.7 kg]

† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1 (1.B for -S models)

LRX24-MFT Actuators, Multi-Function Technology

Dimensions (inches [mm]) C A B D E F 7.5" [191] 1.69" [42] 3.22" [82] 2.34" [59.4] 2.6" [66] D1 3 22 Valve

Nominal Size Dimensions (Inches [mm]) In. DN

[mm] A B C D E F

½” 15 8.68" [220] 4.47" [114] 7.13" [181] 2.34" [59] 1.48" [38] 1.48" [38] ¾” 20 8.98" [228] 5.4" [137] 7.13" [181] 2.34" [59] 1.48" [38] 1.48" [38] 1” 25 9.9" [251] 6.85" [174] 8.02" [204] 3.23" [82] 1.6" [41] 1.6" [41]

Dimensions with PT Port (Inches [mm])

D1 307 7.5" [191] 1.69" [42] 3.22" [82] 2.34" [59.4] D A B C Valve

Nominal Size Dimensions (Inches [mm]) In. DN [mm] A B C D E F ½” 15 8.68" [220] 4.47" [114] 8.47" [215] 3.54" [90] 1.48" [38] 2.4" [61] ¾” 20 8.98" [228] 5.4" [137] 8.47" [215] 3.54" [90] 1.48" [38] 2.4" [61] E F 2.6" [66]

(21)

P 10410 - 09/13 - S ubject to change. © Belimo Air controls (U S A), Inc .

LRX24-MFT Actuators, Multi-Function Technology

Wiring Diagrams

2

CAUTION

Equipment damage!

Actuators may be connected in parallel.

Power consumption and input impedance must be observed. 3 Actuators may also be powered by 24 VDC.

4 Position feedback cannot be used with Triac sink controller.The actuator internal common reference is not compatible.

6 Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.

8 Contact closures A & B also can be triacs.A& B should both be closed for triac source and open for triac sink.

9 For triac sink the common connection from the actuatormust be connected to the hot connection.

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

Dimensions with PT Port(Inches [mm])

D130 8 7.5" [191] 1.69" [42] 3.22" [82] 2.34" [59.4] A,B C D Valve

Nominal Size Dimensions (Inches [mm]) In. DN [mm] A B C D E F 1” 25 12.6" [320] 12.6" [320] 8.02" [204] 2.95" [75] 1.6" [41] 1.6" [41] 2.6" [66] E F Blk (1) Common Red (2) Hot Wht (3) Y Input Org (5) U Output Line Volts 24 VAC/DC Transformer …MFT a Position Feedback VDC (+) (–) 2 3 W 53 8 On/Off Control …MFT Line Volts 2 to 10 VDC Feedback Signal 24 VAC Transformer Blk (1) Common – Red (2) Hot + Wht (3) Y1 Input Pnk (4) Y2 Input Org (5) U Output 2 to 10V 3 6 4 2 A B 8 9 W 538 Floating Point Blk (1) Common Red (2) + Hot Wht (3) Y1Input, 2 to 10V Org (5) U Output, 2 to 10V 4 to 20 mA or 2 to 10 VDC Control Signal Line Volts 24 VAC Transformer 2 3 (+) (–) Ω1/4 watt500Ω …MFT W 53 8 VDC/4-20 mA Blk (1) Common Red (2) + Hot Wht (3) Y Input Org (5) U Output Line Volts

24 VAC Transformer (AC only)

(+) (–) 6 2 …MFT Position Feedback VDC W 538 PWM

(22)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls (USA ), Inc .

Models

ARX24-MFT Technical Data

Power supply 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% Power

consumption

running 4 W holding 1.25 W

Transformer sizing 6 VA (class 2 power source) Electrical connection ½” conduit connector

18 GA plenum rated cable 3 ft. [1m] 10 ft. [3m] 16 ft. [5m] Overload protection electronic throughout 0° to 95° rotation Operating range Y 2 to 10 VDC, 4 to 20 mA (default)

variable (VDC, PWM, fl oating point, on/off) Input impedance 100 kΩ (0.1 mA), 500 Ω

1500 Ω (PWM, fl oating point, on/off) Feedback output U 2 to 10 VDC, 0.5 mA max

VDC variable

Angle of rotation 95° electronically variable Direction of rotation reversible with protected Position indication handle

Manual override external push button Running time 100 seconds

Humidity 5 to 95% RH non-condensing (EN 60730-1)

Ambient temperature -22°F to +122°F [-30°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA 2/IP54

Housing material UL94-5VA

Agency listings† cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC

Noise level <45 dB(A) Quality standard ISO 9001

† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1

ARX24-MFT Actuators, Multi-Function Technology

Dimensions (inches [mm]) D1 3 2 3 Valve Nominal

Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F 1¼” 32 9.05" [230] 8.19" [208] 8.73" [222] 3.5" [89] 1.85" [47] 1.85" [47] 1½” 40 9.09" [231] 8.03" [204] 8.73" [222] 3.5" [89] 1.85" [47] 1.85" [47] 2” 50 9.47" [241] 8.50" [216] 8.97" [228] 3.5" [89] 1.85" [47] 1.85" [47] 2” NPT with fl ows to 40 GPM. Dimensions (inches [mm]) D C A B BELIMODN 50 2 E F 3.3" [84] 2.49" [63.4] 8.0" [203] 1.35" [35] 2.5" [64] 3.46" [88] D1 3 24 Valve Nominal

Size Dimensions (Inches [mm])

In. DN

[mm] A B C D E F

2” 50 18.91" [480] 15.60 [396] 12.83" [326] 5.83" [148] 2.6" [66] 2.6" [66]

(23)

P10410 - 09/13 - Subject to change. © Belimo Air controls (USA ), Inc . Wiring Diagrams

ARX24-MFT Actuators, Multi-Function Technology

6 Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.

8 Contact closures A & B also can be triacs.A& B should both be closed for triac source and open for triac sink.

9 For triac sink the common connection from the actuatormust be connected to the hot connection.

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

W 538 On/Off Control W 538 Floating Point W 53 8 VDC/4-20 mA W 538

Dimensions with PT Port (Inches [mm])

D1313 D A, B C 3.3" [84] 2.49" [63.4] 8.0" [203] 1.35" [35] Valve

Nominal Size Dimensions (Inches [mm]) In. DN [mm] A B C D E F 2” 50 23.48" [596] 23.25" [591] 12.83" [326] 5.83" [148] 2.6" [66] 2.6" [66] E F 2.5" [64] 3.46" [88]

Dimensions with PT Port(Inches [mm])

D 1 3 1 0 6.5" [165] 1.69" [42] 3.22" [82] 2.34" [59.4] A,B C D Valve

Nominal Size Dimensions (Inches [mm]) In. DN [mm] A B C D E F 1¼” 32 15.9" [403] 15.9" [403] 8.73" [222] 3.5" [89] 1.85" [47] 1.85" [47] 1½” 40 15.43" [392] 15.43" [392] 8.73" [222] 3.5" [89] 1.85" [47] 1.85" [47] 2” 50 16.13" [410] 16.13" [410] 8.97" [228] 3.5" [89] 1.85" [47] 1.85" [47] 2.6" [66] E F

(24)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

TFRX24-MFT US Actuators, Multi-Function Technology

Dimensions (Inches [mm]) 6.28" [159.55] 3.0" [76.2] 2.93" [74.5] 2.40" [61] C A B D E F D1 3 2 5 Valve Nominal

Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F ½” 15 7.1" [180] 4.47" [114] 6.98" [177] 2.34" [60] 1.5" [38] 1.5" [38]

Models

TFRX24-MFT US Technical Data Control MFT

Power supply 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% Power consumption running 2.5 W

holding 1.0 W

Transformer sizing 4 VA (class 2 power source) Electrical connection 3 ft., 18 GA plenum rated cable

½” conduit connector

Overload protection electronic throughout 0° to 95° rotation Operating range Y* 2 to 10 VDC

4 to 20 mA

(with 500 Ω, ¼ W resistor) ZG-R01 Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)

500 Ω for 4 to 20 mA

1500 Ω for PWM, fl oating point and on/off control

Feedback output U* 2 to 10 VDC, 0.5 mA max Direction of rotation spring reversible with CW/CCW mounting

motor reversible with built-in Mechanical angle of rotation* 95°

Running time motor* 100 seconds

spring <25 sec @ -4°F to +122°F [-20°C to +50°C] <60 sec @ -22°F [-30°C]

Angle of rotation adaptation* off (default)

Override control* min. (min position) = 0% - ZS (mid. position) = 50% - max. (max. position) = 100% Position indication visual indicator, 0° to 95° Humidity 5 to 95% RH, non-condensing Ambient temperature -22°F to +122°F (-30°C to +50°C) Storage temperature -40°F to +176°F (-40°C to +80°C) Housing NEMA 2/IP42

Housing material UL 94-5VA Noise level (max) running <35 dB (A)

spring return <65 dB (A)

Dimensions with PT Port(Inches [mm])

D1 3 14 6.28" [159.55] 2.93" [74.5] 2.40" [61] D A B C Valve

Nominal Size Dimensions (Inches [mm])

In. DN [mm] A B C D E F ½” 15 7.1" [180] 4.47" [114] 8.01" [203] 3.54" [90] 1.5" [38] 2.4" [61] 3.0" [76.2] E F

(25)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls (USA), Inc

.

TFRX24-MFT US Actuators, Multi-Function Technology

Wiring Diagrams

1 Provide overload protection and disconnect as required.

2

CAUTION

Equipment damage!

Actuators may be connected in parallel.

Power consumption and input impedance must be observed. 3 Actuators may also be powered by 24 VDC.

4 ZG-R01 may be used.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

W02 5 4 to 20 mA Control Signal W 0 24 2 to 10 VDC Control Signal

(26)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls (USA ), Inc .

Models

LF24-MFT

LF24-MFT-S w/built-in aux. switch

Technical Data

Control MFT

Control signal 2 to 10 VDC

Power consumption running 2.5 W holding 1 W

Transformer sizing 5 VA (class 2 power source) Electrical connection 3 ft., 18 GA appliance cables

(-S model has 2 cables) ½” conduit connector

Overload protection electronic throughout 0° to 95° rotation Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)

500 Ω for 4 to 20mA 750 Ω for PWM

500 Ω for on/off and fl oating point

Feedback 2 to 10 VDC, 0.5 mA max

Angle of rotation 95°

Direction of rotation spring reversible with CW/CCW mounting motor reversible with built-in

Position indication visual indicator

Running time <40 to 75 seconds (on-off) 100 seconds

spring <25 sec. @-4°F to +122°F [-20°C to +50°C] <60 sec. @-22°F [-30°C]

Ambient temperature -22°F to +122°F [-30°C to +50°C]

Housing NEMA 2

Agency listings UL 873, CSA C22.2 No. 24 certifi ed, CE

Noise level max. 62 dB(A)

Quality standard ISO 9001

LF24-MFT-S US

Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed, adjustable 0° to 95° (double insulated)

LF24-MFT Actuators, Multi-Function Technology

Dimensions (Inches [mm]) C A B D 7.64" [194] 4.49" [114] 2.28" [58] 3.78" [96] E F D1 3 2 6 Valve

Nominal Size Dimensions (Inches [mm]) In. DN

[mm] A B C D E F

½” 15 8.1" [206] 4.47" [114] 8.54" [217] 2.34" [59] 1.89" [48] 1.89" [48] ¾” 20 8.3" [211] 5.4" [137] 8.54" [217] 2.34" [59] 1.89" [48] 1.89" [48] 1” 25 9.1" [231] 6.85"[174] 9.29" [236] 3.23" [82] 1.89" [48] 1.89" [48]

Dimensions with PT Port(Inches [mm])

D1 3 1 5 D A B C 7.64" [194] 4.49" [114] 2.28" [58] Valve

Nominal Size Dimensions (Inches [mm]) In. DN [mm] A B C D E F ½” 15 8.1" [206] 4.47" [114] 9.57" [243] 3.54" [90] 1.89" [48] 2.4" [61] ¾” 20 8.3" [211] 5.4" [137] 9.57" [243] 3.54" [90] 1.89" [48] 2.4" [61] E F 3.78" [96]

(27)

P

10410 - 09/13 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Wiring Diagrams

2

CAUTION

Equipment damage!

Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.

3 Actuators may also be powered by 24 VDC.

4 IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).

5 Triac A and B can also be contact closures.

6 Control signal may be pulsed from either the Hot (Source) orCommon (Sink) 24 VAC line.

7 Position feedback cannot be used with Triac sink controller.The actuators internal common reference is not compatible.

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

LF24-MFT Actuators, Multi-Function Technology

(1) Common (2) Hot (3) Y Input (5) U Output Line Volts 24 VAC/DC Transformer CCW CW …MFT a Position Feedback VDC (+) (–) W 04 3 On/Off Control (1) Common (2) + Hot (3) Y Input (5) U Output Line Volts

24 VAC Transformer (AC only)

CCW CW (+) (–) 6 7 …MFT Position Feedback VDC W 041

PWM, Triac Source and Sink

W

302

Floating Point Control

Proportional 2 to 10 or 4 to 20 mA Control Signal

Dimensions with PT Port(Inches [mm])

D131 6 A,B C D 7.64" [194] 4.49" [114] 2.28" [58] Valve

Nominal Size Dimensions (Inches [mm]) In. DN [mm] A B C D E F 1” 25 12.6" [320] 12.6" [320] 9.25" [235] 2.95" [75] 1.89" [48] 1.89" [48] 3.78" [96] E F

Figure

TABB - Testing Adjusting Balancing Bureau, http://www.tabbcertified.org/

References

Related documents

These pretend to be God’s message, but none of these can or will have the same effect as the True Gospel upon the heart of the believer!. None can produce the heart satisfaction

While every endeavour should be made to attend the incident scene as soon as possible in order to commence the investigation (or immediately as in the case of a

Service providers who are able to provide a broad range of services for PWID, such as acute health care, are particularly well placed to introduce information and access to

The improvement of sidewall angle of PSPI films offers yet further cost savings by consolidating the passivation and polyimide lithography steps into one process level.. This paper

As an indication of the value the Ministry of Children and Family Development places on its Family Care Resources, the Ministry and BCFFPA have contracted to pay for

New Contract Size = Old Contract Size + Implied market value of the Disbursed Security per original underlying equity security * Old Contract Size / Ex Date VWAP of original

Departing members for Group Salary Continuance must formally exercise their Continuation Option by notifying INPRO Australia and submitting the relevant OnePath

Disulfide-Stabilized NEMO Constructs Show Increased Binding Affinity for Ikkβ To determine whether the increased α-helix content observed by CD stabilizes the active