Basic Modules

Configuration

PCL

PCL

PCL

PCL

PACiS

PACiS

PACiS

PACiS Technical

Technical

Technical

Technical Training

Training

Training

Training Level

Level

Level

Level 2

2

2

2

CS&P

CS&P

CS&P

(2)

• Content

 Circuit Breaker

 Disconnector Switch

 Transformer

(3)

• Content

 Circuit Breaker

 Disconnector Switch

 Transformer

(4)

• Add / Configure a CB

1) Circuit Breaker can be added at

Bay

level in

Electric

hierarchy.

CB 3 phases (1 DPS for global position) / CB 1 phase (single phase acq.)

Short Name :

SCE Key + appears in viewers + printers

CB Type :

3-ph, 1-ph, other

2) CB attributes

Nodes definition :

(5)

• CB-1ph Configuration (1)

1) CB 1 phase basic configuration

1.1) Type 1

Typed Switch Ctrl DPC

:

DPC Open/Close

Typed CB Computed Position

DPS :

- Global CB Position, computed by C264 - is feedback of DPC command

- is animated on PACiS OI / C264 LCD

Typed Switchgear ph A,B,C

DPS :

CB single phase position, acquired by C264 (DI/CCU or IED)

1.2) Type 2

Position can be computed by :

- typed Switch ph A

DPS

- typed Phases Not Together

SPS

(6)

• CB-1ph Configuration (2)

2) CB enhanced configuration => possible sons

Typed Lock Control SPC

:

Operator lock

Typed Selection SPC

:

when SBO, activated at selection

Typed Sync CB Close

:

Synchrocheck

Typed Lock

SPS :

Lock status

Typed Phase Not Together

SPS :

- Indicates if all phases are in same position - holds a timer for CB trip

Typed withdrawn

SPS :

(7)

• CB-3ph Configuration

1) CB 3 phases basic configuration

1.1) Type 1

Typed Switch Ctrl DPC

:

DPC Open/Close

Typed CB Computed Position

DPS :

- Global CB Position, computed by C264 - is feedback of DPC command

- is animated on PACiS OI / C264 LCD

Typed Switchgear position

DPS :

CB Position, acquired by C264 (DI/CCU or IED)

1.2) Type 2

Typed Switch Ctrl DPC

can be replaced by :

- typed Switch Ctrl SPC

for

CLOSE

- typed Switch ph A SPC

for

OPEN

(8)

• Content

 Circuit Breaker

 Disconnector Switch

 Transformer

(9)

• Add / Configure a Disconnector Switch

1) Disconnector switch is a

Switchgear

, it can be added at

Bay

level in

Electric

hierarchy.

Short Name :

SCE Key + appears in viewers + printers

2) DS attributes

Nodes definition :

(10)

• Switchgear Configuration (1)

1) Switchgear basic configuration

Typed Switch Ctrl DPC

:

DPC Open/Close

Typed Switchgear position

DPS :

Switchgear Position, acquired by C264 (DI/CCU or IED)

(11)

• Switchgear Configuration (2)

2) Switchgear enhanced configuration => possible sons

Typed Lock Control SPC

:

Operator lock

Typed Selection SPC

:

when SBO, activated at selection

Typed Lock

SPS :

Lock status

Typed withdrawn

SPS :

(12)

• Content

 Circuit Breaker

 Disconnector Switch

 Transformer

(13)

• Add / Configure a Transformer

1) Transformer module can be added at

Transformer

or

Generic Bay

level in

Electric

hierarchy.

Short Name :

SCE Key + appears in viewers + printers

Transformer Type :

- Auto wound : no galvanic isolation between HV and LV sides, tap changer acts simultaneously in primary and secondary : TAP RAISE = LV LOWER - Double wound : galvanic isolation between HV and LV sides, tap changer acts in primary : TAP RAISE = LV RAISE

2) Transformer attributes

Nodes definition :

AVR

Power value / impedance :

(14)

• Transformer Configuration (1)

1) Transformer basic configuration

Tap Changer

built-in function:

cf. DATAPOINTS CONFIGURATION course

Typed Raise/Lower DPC

:

Tap Change control

Typed TPI

MV :

(15)

• Transformer Configuration (2)

2) Transformer enhanced configuration => possible sons

Typed Goto min/max DPC

:

DPC doing raise until max tap / lower until min tap

Typed MCB Open SPC

:

- AVR

- In case of invalid tap changing, it will stop supplying tap changer (power cutting)

Typed Higher Position / Lower Position

SPS :

- SET when max tap and min tap are reached

Typed TAP Select SPC

:

when SBO, activated at selection

Typed Tap in progress

SPS :

- physically acquired by C264 - impact on control sequence

(16)

• Content

 Circuit Breaker

 Disconnector Switch

 Transformer

(17)

• Features

1) Generic Modules are :

-

non typed

modules

- contains

generic datapoints

- huge range of use => non particular context

- ADVISE : DON’T USE GENERIC MODULES

for CB and disconnector if you

have :

- Built-in automation (AVR, Synchrocheck, Autorecloser)

- lock, hardware selection, withdrawn

References