REV.NO RO R1 ISSUE
INITIALS SIGN INITIALS SIGN INITIALS SIGN INITIALS SIGN
PPD.BY PVD Sd/- DB
Sd/-CKD.BY CPS Sd/- SJH Sd/- R1
PROTECTION OF TRANSFORMERS
TATA CONSULTING ENGINEERS
73/1, ST. MARK’S ROAD
BANGALORE 560 001
FLOPPY NO : TCE.M6-EL-FP-DOC-005 FILE NAME : M6-6508.DOC
CLAUSE NO.
DESCRIPTION
SHEET NO.
1.0
SCOPE
1
2.0
RECOMMENDED PRACTICE
1
3.0
DISCUSSIONS
18
TABLES
TABLE-1
PROTECTION OF TWO WINDING
TRANSFORMERS OF 500 TO 5000 KVA
RATING
2
TABLE-2
PROTECTION OF TWO WINDING
TRANSFORMERS OF 5000 TO 10,000 KVA
RATING
6
TABLE-3
PROTECTION OF TWO WINDING
TRANSFORMERS OF MORE THAN 10,000 KVA
RATING
10
TABLE-4
PROTECTION OF THREE WINDING
TRANSFORMERS
14
TABLE-5
PROTECTION OF AUTO TRANSFORMERS
16
TABLE-6
PROTECTION OF EARTHING TRANSFORMERS
18
APPENDIX
APPENDIX-1
TRANSFORMERS OF 500 KVA AND BELOW
PROVIDED WITH FUSES ON H.V. SIDE
REVISION STATUS SHEET
REV NO.
DATE
DESCRIPTION
winding transformers, auto transformers and earthing transformers
which are controlled by circuit breakers and protected by relays.
Protection of transformers provided with fuses on HV side is
covered separately in Appendix-1.
2.0
RECOMMENDED PRACTICE
Transformers are classified into the following groups for the
purpose of defining their protection requirements (which are given
in the tables to follow)
2.1
Two winding transformers
(a) Transformers of rating 500 to 5000 kVA – Table-1
(b)
Transformers of rating 5000 to 10000 kVA – Table-2
(c) Transformers of rating 10,000 kVA and above – Table-3
2.2
Three winding transformers of all ratings – Table-4.
Generally such transformers do not have ratings below 10,000 kVA
in practical applications.
2.3
Auto-transformers of all ratings – Table-5.
These are generally used as interconnecting transformers between
two system voltages such as 220 kV to 110 kV.
2.4
Earthing transformers of all ratings – Table-6
Ratings of earthing transformers are decided by desired ground
fault level of the system to which they are connected.
TABLE – 1
PROTECTION OF TWO WINDING TRANSFORMERS OF
500 TO 5000 kVA RATING
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 1.1 Instantaneoushigh set over current protection for phase faults on HV side (source side) ‘50’ Instantaneous over current relay should be provided on all three phases, o/c relay should have low transient over-reach of less than 5% and high drop off to pick up ratio
Range 500 to 2000%
In case of low ratio CTs – say 200/1A & less in a high fault level system of say 40 kA, (i.e. CT sec. side fault current ≥200 XIs) a separate protection CT core with higher ratio to be used for ‘50’ to avoid CT saturation Alternatively inst. over current relays may be connected directly to the main CT whose ratio is selected with due regard to sensitivity to terminal faults. Time delayed over current relays may be connected to sec. side of an aux. CT of suitable ratio & knee point. The pry of aux. CT will be in services with the instantaneous overcurrent relays 1.2 Backup overcurrent protection for phase faults on HV side ‘51’ Relay should be provided on all three phases. Relay should have very inverse normal time characteristics Range 50 to 200%
Though very inverse time characteristic is preferred, for proper coordination, normal inverse curve may have to be used if the same has been used on the LV side incomer.
In genral the characteristic of the relays should be selected to give fast & selective tripp-ing through proper gradation. As far as possible use relays with similar characteristic on both sides of the transformers
1.3 Ground fault protection on HV side
‘50N’ Applicable only for delta connected winding on HV side Instantaneous overcurrent relay connected in residual mode should have series stabilising resistor to ensure stability for magnetising inrush currents and LV through fault currents. For high impedance earthed system the relay shall be with adjustable time delay of 01. – 1 sec. and shall be connected to core balance C.T. Range 20-80% for effectively earthed system. 10-40% for system with ground fault current limited to rated current / impedance earthed system
Consider 3 phase fault on secondary terminals of transformer for selection of stabilising resistor 1.4 Backup ground fault protection on HV side
‘51N’ Applicable for star connected HV winding. Normal inverse time characteristic relay connected in residual mode is recommended Range 20-80% for effectively earthed system and 10-40% for system with ground fault current limited to rated current
TABLE – 1 (cont’d)
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 1.5 Backup over current protection on LV side for phase faults ‘51’ Protection should be provided on all three phases. Very inverse time characteristics recommended for co-ordination with relay protected out-going feeders and extremely inverse time characteristics to be used when co-ordination with fuse protected feeders is required50-200% See discussions for use of breaker series trips in place of these relays in case of 415V systems 1.6 Backup ground fault protection for LV systems with neutral directly earthed ‘51N’ Protection to be connected to CT in the transformer neutral connection. Normal inverse time characteristic relay is recommended. This protection is required even where all the outgoing feeders are fuse protected.
20-80% Neutral CT ratio shall be same as that of phase CTs
See discussion for 415V systems where outgoing feeders are provided with fuses and LV circuit breaker is provided with series trip device 1.7 Standby ground fault protection for LV system with neutral earthed through low resistances ‘515N’ Relay to be connected to neutral CT. Long inverse time characteristic relay is recommended. (Relay 51N above may either be deleted or connected to residual connection of phase CTs if Ig < IR 10-40% CT ratio same as phase CTs if Ig ≥ Irated In other cases select CT ratio based on ground fault current value Range 10 to 40%
Relay time setting should be co-ordinated with short time rating of grounding resistance
1.8 Gas protection ‘63G’ Two stages buchholz relay with one alarm stage and one tripping stage. This is supplied along with the transformer. Each stage will actuate an auxiliary relay with four pairs of self reset contacts (Alarm) or Hand reset contacts (Trip)
For transformers protected by fuse, trip stage without any switching device cannot be used as tripping device is not available. Only alarm stage may be used.
1.9 Transformer oil temperature trip
‘OTI’ Oil temperature indicators are usually provided with two contacts, one for alarm on “Oil temperature high” and other for trip on “Oil temperature very high”
These are optional items depending on transfomer rating and applications
1.10 Transformer winding
temperature trip
WTI Winding temp. indicators are provided with two stages, one for alarm on ‘winding temp. high’ and the other for trip on ‘winding temperature very high’
DO
-1.11 Oil pressure trip PRD Pressure relief device supplied with the transformer shall be provided with auxiliary relay with four pairs of hand reset contacts for tripping
This will be provided for transformers above 2500 kVA.
TABLE – 2
PROTECTION OF TWO WINDING TRANSFORMERS OF
5000 TO 10,000 kVA RATING
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 2.1 Differential protection ‘87T’ Relay should be connected on all three phases. Relay should incorporate(a) Adjustable
percentage biasing for through fault stability and tap changing
conditions.
(b) Harmonic restraint / zero current sensing to provide stability against magnetising inrush currents. (c) Auxiliary CTs on
both sides for ratio matching and compensation of mismatch of line CTs Refer discussions regarding harmonic restraints for magnetic inrush currents. 2.2 Instantaneous short circuit protection for phase faults on HV side
‘50’ Same as item 1.1 Range 500-2000% Same as in 1.1 2.3 Backup over current protection for phase faults on HV side
51 Same as item 1.2 Range 50-200%
2.4 Earth fault protection on HV side
50N Applicable only for delta connected HV. Protection same as item 1.3 20-80% for effectively earthed systems and 10-40% for low resistance earthed system 2.5 Backup earth fault protection on HV side
51N Applicable only for star connected HV side. Same as item 1.4 20-80% for effectively earthed system and 10-40% for system with low resistance earthing 2.6 Backup overcurrent protection on LV side for phase faults 51 Same as item 1.5 50-200% 2.7 Backup ground fault protection for LV side 51N Relay to be connected to neutral CT. CT ratio same as phase CTs when Ig ≥IR 20-80% for effectively earthed system and 10-40% for system with low resistance earthing 2.8 Restricted earth fault protection of LV side when LV neutral is grounded through low resistance
‘64’ CT ratio for phase and neutral CTs should be same 10-40% range, Stand. values of stabilising resistor are 50 ohm for 5 A CT and 200 ohm for 1 A CT Design stabilising resistance value on the basis of 3 phase through fault. RCT should be kept low to limit value of Vk & stabilising
resistor.
Recommended setting is 10%.
TABLE – 2 (cont’d)
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 2.9 Standby earth fault protection for LV side when neutral is grounded through low resistance ‘515N’ Relay connected to neutral CT. Long inverse time characteristic relay is recommended. (Relay ‘51N’ in 2.8 above should be connected to residual connection of phase CTs in this case)CT ratio same as phase CTs if Ig ≥ IR. In other cases select CT ratio based on designed ground fault current value. Range 10-40% Relay time setting should be co-ordinated with short time rating of grounding resistance
2.10 Gas protection 63G Same as 1.8 2.11 Winding
temperature trip WTI Same as item 1.10 2.12 Transformer oil
temperature high
DTI Same as item 1.9 2.13 Oil pressure trip PRD Same as item 1.11
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 3.1 Differential protection ‘87T’ Relay should be connected on all three phases. Relay shall be high speed type incorporating
(a) 2nd & 5th harmonic restraint / zero current sensing for magnetising inrush currents (b) Adjustable percentage bias for through fault stability
(c) Auxiliary CT on both sides for ratio matching and compensation for line CT mismatch (d) High set instantaneous unit in differential circuit 3.2 Instantaneous short circuit protection for phase faults on HV side
‘50’ Same as item 1.1 Range 500-2000%
(i) This
protection shall not provided for generator transfor-mers
TABLE – 3 (cont’d)
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 3.3 Backup overcurrent protection for phase faults on HV side‘51’ Same as item 1.2 Range 50-200%
3.4 Instantaneous ground fault protection on HV side
‘50N’ Applicable only when HV is delta connected Same as item 1.3 Range 20-80% for effectively earthed system and 10-40% for system with ground fault currents limited to rated current/ impedance earthed systems 3.5 Backup ground fault protection on HV side
51N Applicable for star connected HV winding Same as item 1.4 Range 20-80% for effectively earthed system and 10-40% for systems with limited ground fault current 3.6 Backup phase overcurrent protection for phase faults on LV side
‘51’ Same as item 1.5 Range 50-200%
3.7 Backup overcurrent protection for ground fault on LV side
‘51N’ Same as item 2.7 Range 20-80% for effectively earthed system and 10-40% for system with low resistance earthing 3.8 Restricted earth fault protection of LV side when LV neutral is grounded through low resistance ‘64’ Same as item 2.8 10-40% range 3.9 Standby earth fault protection of LV side when LV neutral is grounded through low resistance
‘51SN’ Same as item 2.9 Relay time setting to be co-ordinated with short time rating of resistor
3.10 Gas protection 63G Same as 1.8 3.11 Winding
temperature trip
WTI Same as item 1.10 3.12 Transformer oil
temperature trip
DTI Same as item 1.9 3.13 Oil pressure trip PRD Same as item 1.11
TABLE – 4
PROTECTION OF THREE WINDING TRANSFORMERS
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 4.1 Differential protection 87T Relay should be connected to all three phases. Relay shall have bias from all the three windings. If tertiary is not loaded and brought out, then the bias shall be taken from HV & LV sides only. Other requirements same as 3.1 4.2 Short circuit protection with instantaneous o/c relays on HV side (source side)
‘50’ Same as item 1.1 Range 500-2000% 4.3 Backup overcurrent protection for phase faults on HV side
‘51’ Same as item 1.2 Range 50-200%
4.4 Instantaneous ground fault protection on HV side
‘50N’ Applicable only for delta connected HV winding Same as item 1.3 Range 20-80% for effectively earthed system and 10-40% for systems with restricted ground fault current
NO. NO. RANGE 4.5 Backup ground
fault protection on HV side
51N Applicable for star connected HV winding Same as item 1.4 Range 20-80% for effectively earthed system and 10-40% for systems with limited ground fault current 4.6 Backup o/c protection on LV side, for phase faults
‘51’ Same as item 1.5 Range 50-200% Both LV windings shall have separate protections 4.7 Backup o/c protections for ground fault on LV side
‘51N’ Same as item 2.7 Range 20-80% or 10-40% depending on available fault current do -4.8 Restricted E/F protection of LV side when LV is grounded through a resistance ‘64’
Same as item 2.8 10-40% range
do -4.9 Standby E/F protection when LV is grounded through a resistance ‘51SN’ Same as item 2.9 do
-4.10 Gas protections 63G Two stage Buchholz
protection is part of transformer
Same as 1.8 4.11 Winding
temperature trip WTI Same as item 1.10 4.12 Oil temperature
trip OTI Same as item 1.9 4.13 Oil pressure trip PRD Same as item 1.11
TABLE – 5
PROTECTION OF AUTO-TRANSFORMERS
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 5.1 Differential protection ‘87T’ Relay to be connected on all three phases. High speed, harmonic restraint, percentage bias differential relays are to be used.If tertiary winding is brought out for loading, additional bias from this side also to be provided 5.2 Restricted E/F
protection ‘64’
Alt:1 7CT method – See fig.1
All CT ratios should be identical
Alt-2 9CT method – See fig.2
All CT ratios should be equal. One CT is required on each phase at neutral end of common winding. This alternative also covers phase faults inside transformers Single phase instantaneo us current operated relay. Range 20-80% Three phase instantaneo us current operated relay Range 20-80% Specify value of stabilising resistor taking RCT into account 5.3 Backup overcurrent protection for phase faults (Directional) on HV side 67/51-50 Protection shall be provided on all phases. Directionalisation is required as power flow can be both ways. Additional high set instantaneous unit can be provided to clear internal faults
3 relays – one per phase. Range 50-200% for inverse current element and 500-2000% for high set unit
5.4 Backup o/c protection for ground faults (Directional) on HV side 67/51N Directionalisation is required as current flow can be in both directions. Adopt potential polarisation Directional o/c relay Range 20-80% 5.5 Backup o/c protection for phase faults on LV side (Directional) 67/51-50 Similar to 5.3 above Directional o/c relay - 3 relays Range 50-200% for inverse time o/c & 500-2000% for high set unit 5.6 Backup o/c protection for ground faults (Directional) 67/51N Same as item 5.4 Range 20-80%
5.7 Overload relay (for alarm) for HT winding 50/OL To be connected to HT line CTs to monitor HT winding current Definite time o/c relay. Range 50-200% Time 1-10 sec. High DO/Pu ratio
5.8 Overload relay (for alarm) for common winding
50/OL
To be connected to CTs at the neutral end of phase winding
do -5.9 Gas protection
63G
Two stage Buchholz protection is part of transformer
TABLE – 5 (cont’d)
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 5.10 Windingtemperature trip WTI Same as item 1.10 5.11 Oil temperature trip OTI Same as item 1.9 5.12 Oil pressure trip PRD Same as item 1.11 5.13 For very large
transformer (above 100 MVA) compre-hensive numerical protection in one group & conventional protection in another group shall be provided 5.14 Over fluxing protection (for grid transformers)
5.15 In cases where trans-formers are continuously
operated at full load, and in addition, are likely to be subjected to short time overloads, (which may raise the winding temp. to more than 100°C temp. time integrators should be provided to enable estimation of degree of aging.
SR. NO. DESCRIPTION DEVICE NO. DETAILS SETTING RANGE REMARKS 6.1 Instantaneous o/c protection ‘50’ Relay should be provided on all three phases of the earthing transformer Instantaneous o/c relay Range 20-80% The CTs should be connected in Delta
6.2 Gas protections ‘63G’ Two stage gas protection is a part of transformer.