Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

N/A
N/A
Protected

Academic year: 2021

Share "Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates"

Copied!
37
0
0

Loading.... (view fulltext now)

Full text

(1)

Causes of High Relative

Humidity Inside Air

Conditioned Buildings

Roger G.Morse AIA, Paul Haas CSP, CIH

(2)

S. FLORIDA – AVE. AMBIENT 91 F dB / 78 F wB 16,000 HOURS ANNUALLY THAT wB > 66 F THIS INDICATES A SIGNIFICANT PROBLEM

WITH HIGH OUTDOOR HUMIDITY AND THEREFORE, HIGH INDOOR HUMIDITY

(3)
(4)
(5)

Cause of High Relative Humidity

Inside Air Conditioned Buildings

Study Included:

• HVAC Equipment Diagnosis • Heat Gain Calculations

• Field survey and logging of Temperature, RH and Occupant Interviews

(6)

Study Parameters

• Forty-One (41) Schools Investigated

– 228 Separate Air-Conditioned Buildings

– 28 Elementary (ES), 7 Middle (MS), 3 High Schools (HS) & 3 Vocational Centers (Ctr) – 1036 HVAC Systems:

631 Air Handling Units (AHU), 283 Fan Coil Units (FCU), 90 Unit Ventilators (UV) & 32 Heat Pumps (HP)

(7)

Study Results

• After occupant interview, data logging was performed using HOBO™ H8 loggers for RH/Temp for one week.

• The logging and occupant interviews were followed up with detailed maintenance and mechanical assessments.

• A summary report which analyzed findings included a detail of the cause(s) of high RH.

(8)

Causes of High Relative Humidity

Inside Air Conditioned Buildings

Controls Which Affected Relative Humidity

– 63 % had Malfunctioning or Misapplied Dehumidification Enhancements – Face & Bypass, Supply Bypass etc.

– 93 % had a potential for uncontrolled humidity entering spaces through the lack of Outside Air Controls – Building Pressurization, Manual

(9)

Age of Equipment and Maintenance

• HVAC Equipment Service Life (ASHRAE Recommendation ~ 20 years)

• 30 % - 20 years or the age was unknown • 13% - 15-20 years

• 53% - 5-15 years • 4% - 0-5 years

(10)

Commercial Dehumidification

• Commercial systems dehumidify by chilling air below the dew point

• Water condenses out on the fins of the cooling coil

• The leaving air has a reduced dew point and specific humidity

• The leaving air will be saturated and should have a relative humidity of about 100%

(11)

Chilled Water System

CHILLED WATER SYSTEM

Fan Conditioned Air Vapor Hot Vapor Liquid Heat Exchanger Heat Exchanger Cooling Tower Chilled Water Warmer Water 52° 50° Warm Water Cooled Water

(12)

Single Fan AC Unit

Condensate Drain Pan Coil 50° F Mixed Air Chamber Air Damper Return Fresh Air Damper Fresh Air Roof Or Wall 90° - 90% RH

Wet Side Dry Side Filter Bank

SINGLE FAN AC UNIT Supply Air

50° F 100%RH

Supply Fan

(13)
(14)

Causes of High Relative Humidity

More Outside Air Than Capacity of System • Negatively Pressurized Building and/or

Cavities – 140 cases (21.41%)

• Excessive or Uncontrolled Ventilation -129 cases (19.72%)

• Oversized Units – 118 cases (11.47%)

• Partial Load with High Relative Humidity --85 cases (8%)

(15)

Face and By-Pass

DAMPER BYPASS AIR RETURN DAMPER BYPASS AIR FRESH COIL COOLING

(16)
(17)
(18)

Coil Capacity Inadequate

• Coil Too Warm During Partial Load Conditions (14.53%)

– Coil inadequate for latent loads (too few rows) – Frequently due to excessive outside air

(19)
(20)

Temperature Controls That

Caused RH Problems

• Modulating Chilled Water Valve (11.93%)

– Constant Ventilation with Continuous Fan Operation and Cycling Cooling

(21)
(22)
(23)

Correct Lack of Coil Capacity

• Replace Coil

• Precondition outside air

• Eliminate Chilled Water Reset

• Replace modulated CW valves with on-off valves

(24)

Exhaust Fans On 24 Hrs

Building envelope

(25)
(26)

Condition Outside Air

Intentional opening

(27)
(28)

Positively Pressurize Building

• Precondition fresh air 10% greater than exhaust air

• Avoid plenum returns – use ducted returns • Avoid supply ducts in unconditioned attics • Seal wall cavities from ceiling plenum

(29)

Special Cases :

• Fan Coil Units with Filter Grille • Unit Ventilators

(30)
(31)
(32)

ASHRAE – Environmental and

Ventilation Requirements

• ASHRAE 55-1992 “Thermal

Environmental Conditions for Human Occupancy.”

• ANSI/ASHRAE 62-1999 “Ventilation for Acceptable Indoor Air Quality.”

(33)

Findings from Study

ASHRAE ‘Compliance’

• 25 of 41 schools studied had HVAC

equipment installed with a capacity of 5 CFM OA / person

• 3 of 41 schools had HVAC equipment installed with 15 CFM OA / person

• 13 schools had mixed capacity when new additions were made

(34)

Findings from Study

High Relative Humidity

• Analysis of Relative Humidity and Temperature Logs proved to be a powerful tool

• Misapplied or Malfunctioning Dehumidification Enhancement to HVAC Equipment often led to high Relative Humidity

• The lack of Outdoor Air Control appeared to be the most consistent cause of high RH either in conjunction with mechanical issues or separately

(35)

Recommendations for Future Study

• IEQ Conditions with ventilation for occupants at 5 CFM / person

• Maintenance and Retrofit of HVAC Equipment

• Building Envelope contribution to Relative Humidity

(36)

Acknowledgement

Acknowledgement

THANKS TO MR. LEE KENDRICK THANKS TO MR. LEE KENDRICK

WHO AT 86 YEARS OLD IS STILL AN

WHO AT 86 YEARS OLD IS STILL AN

IMPORTANT INFLUENCE FOR

IMPORTANT INFLUENCE FOR

INDUSTRIAL HYGIENISTS IN

INDUSTRIAL HYGIENISTS IN

UNDERSTANDING “THE CAUSE AND

UNDERSTANDING “THE CAUSE AND

CURE OF MOLD IN BUILDINGS”

(37)

Morse Zehnter Associates

Roger G. Morse AIA

504 Snake Hill Road Poestenkill, NY 12140

(518) 283-7671

rgmorse@morse-associates.com

Coauthor’s - Andrea Grdina, Paul Haas and Dean Zehnter 2240 Palm Beach Lakes Blvd., Suite 300

West Palm Beach, FL 33409 (561) 712-4777

References

Related documents

By considering smart city as an integrated enterprise, the results from dataset-3 will be compared with dataset-1, in order to apply tools, techniques, and approaches

As part of our assessment of the craft industry, Indecon has produced a number of rigorous new estimates on key economic indicators for the sector including

Taking the final causal relationship the beta value and error value corresponding to the relationship between Fan page participation and Psychological Motivation

5 working days 6 Business License 7 working days 7 Business License extension 7 working days 8 Business license merger 7 working days 9 Facilities for exemption duty

“The Academic and Athletic Experience of Division I Football Players.” Paper presented at the Annual Meeting of the American Educational Research Association, San Francisco, CA,

Unilateral ischemic sensorimotor cortical damage in female rats: Forelimb behavioral effects and dendritic structural plasticity in the contralateral homotopic cortex.. Training the

She received her DVM from Colorado State University and is trained in pain medicine, medical acupuncture, medical massage, and physical rehabilitation.. She has extensive

A large number of time-consuming logistics operations with a low level of labor productivity in this area presents the management of companies with a choice: to