Impact of phase-locked loop on stability of active damped
LCL-filter-based grid-connected inverters with capacitor
voltage feedback
Xiaoqiang GUO1, Shichao LIU2, Xiaoyu WANG3
Abstract Active damped LCL-filter-based inverters have been widely used for grid-connected distributed generation (DG) systems. In weak grids, however, the phase-locked loop (PLL) dynamics may detrimentally affect the stability of grid-connected inverters due to interaction between the PLL and the controller. In order to solve the problem, the impact of PLL dynamics on small-signal stability is investigated for the active damped LCL-filtered grid-con-nected inverters with capacitor voltage feedback. The system closed-loop transfer function is established based on the Norton equivalent model by taking the PLL dynamics into account. Using an established model, the system stability boundary is identified from the viewpoint of PLL bandwidth and current regulator gain. The accuracy of the ranges of stability for the PLL bandwidth and current regulator gain is verified by both simulation and experi-mental results.
Keywords Phase-locked loop, Small-signal stability, Grid-connected inverter, Active damping, LCL filter, Transfer function
1 Introduction
LCL-filter-based grid-connected inverters have been widely discussed in [1–4]. One of the important issues is their stability. Ref. [5] proposed a robust passive damping method for LLCL-filter-based grid-connected inverters, so as to minimize the effect of harmonic voltages on the grid. Another interesting filter was proposed in [6] for optimiz-ing the system performance and stability. A recent review of passive filters for grid-connected converters was pre-sented in [7], and different passive damping methods were discussed. In order to avoid the losses resulting from pas-sive damping, capacitor-current feedback active damping was proposed in [8] to enhance the stability of LCL-type grid-connected inverters. Ref. [9] presented an interesting active damping method that can handle stability with only grid-current feedback control. In [10], a virtual RC damping method was presented with extended selective harmonic compensation. Note that these solutions are for voltage-source inverters. In practice, there are also current-source inverters [11–13]. An interesting active damping solution was presented in [14]. However, while the above methods are insightful for stability analysis, the impact of phase-locked loop (PLL) dynamics on the stability of grid-connected inverters has been neglected. The PLL is used to track the phase angle of the voltage at the point of common coupling (PCC) and thus to achieve grid synchronization for the inverter [15]. In case of high grid impedance, it has been found that the stability of a voltage source converter (VSC) can be affected by PLL parameters [16, 17]. In CrossCheck date: 23 May 2017
Received: 17 January 2017 / Accepted: 23 May 2017 / Published online: 8 July 2017
The Author(s) 2017. This article is an open access publication & Xiaoqiang GUO
[email protected] Shichao LIU [email protected] Xiaoyu WANG
1 Department of Electrical Engineering, Yanshan University,
Qinhuangdao, China
2 School of Mechanical, Electronic, and Control Engineering,
Beijing Jiaotong University, Beijing, China
3 Department of Electronics, Carleton University, Ottawa, ON
K1S 5B6, Canada
VSC-based high voltage direct current (HVDC) transmis-sion systems, the PLL parameters have been found to limit the maximum power transfer capability [18]. In [19], the impact of short-circuit ratio and phase-locked-loop parameters on small-signal behavior is investigated, However, it only takes L-filter-based inverters into account.
In summary, these early works have discussed the influence of PLL parameters on the system stability. However, they only focused on grid-connected inverter systems with L or LC filters. In fact, an LCL filter is pre-ferred in grid-connected inverters, due to its better higher frequency attenuation and reduced physical size of the inductor [20]. In practice, the LCL filter usually suffers from resonance problems, which result in system instabil-ity. In order to deal with the problem, active damping controllers have been used [21].
Under weak grid conditions, the current regulator and the PLL dynamics of the active damped inverter may interact as the grid current passes the grid impedance, especially in case of a high bandwidth PLL. In fact, fast grid synchronization and PLL is important for operating the grid-connected inverters. Increasing PLL bandwidth is helpful for the fast and accurate grid synchronization. The PLL bandwidth should be large enough for the fast grid synchronization, and this is why diverse PLL designs have been proposed, as shown in [22–28]. However, when the PLL bandwidth is increased beyond a certain limit, the system may become unstable due to resonance between the inverter and the weak grid. Therefore, the interaction between fast PLL dynamics and current regulation deserves further investigation.
The objective of this paper is to contribute both ana-lytical and experimental verification on the interaction of PLL dynamics and current regulation in three-phase grid-connected active damped inverters with LCL filters under weak grid conditions. Using the Norton Theorem, a closed-loop transfer function is established to model the whole grid-connected inverter system including the PLL dynam-ics. By analyzing the poles of the closed-loop transfer function, the ranges of stability of the PLL bandwidth and the current regulator gain are obtained. Both a simulation and experimental results from a three-phase grid-connected inverter are provided to verify the effectiveness of the proposed model. The remainder of this paper is organized as follows. In Sect.2, a small-signal model is established for the three-phase grid-connected LCL-filter-based inver-ter with capacitor voltage feedback and active damping. In Sect.3, the small-signal stability of the inverter is dis-cussed in terms of the PLL dynamics and the current reg-ulator. In Sect.4, the analytical results are verified through simulations and experimental tests. Finally, conclusions are presented in Sect.5.
2 Inverter system model
Figure1 shows the structure of a typical three-phase grid-connected inverter system. S1* S6are the switches; L1 is the inverter-side filter inductance; C is the filter capacitance; L2is the grid-side filter inductance; Lgis the grid line inductance; VCa, VCb, VCc are the capacitor volt-ages in the grid frame ‘abc’; Iga, Igb, Igcare the grid cur-rents in the grid frame ‘abc’.
In the grid dq frame, h1is the PLL output phase angle; x1is the angular frequency; VC, Ig, IL, VPCC, Vg are the voltage vector at the filter capacitors, grid current vector, inverter-side filter current vector, voltage vector at the point of common coupling, and voltage vector of the grid-side voltage sources, respectively. In the inverter dq frame, the PLL output phase angle is denoted as h, which is almost the same as h1 in steady-state conditions. Other variables in the inverter dq frame are labeled with a superscript c, when referred in the grid dq frame. As current references are constant, in both dq frames, they are denoted as Iref.
Let VCs denote the capacitance voltage in the ab frame. VC¼ ejh1Vs
C when it is in the grid dq frame, and
VCc = ejhVCs in the inverter dq frame. Then, the following relationship is obtained: Vc C¼ ejDhVC Dh¼ h h1 ð1Þ
where Dh is the phase angle difference in these two dq frames and is approximately equal to zero when the grid-connected inverter operates in steady state. The PLL dynamics, however, make Dh depart from zero. Conse-quently, it is important to investigate the impact of the PLL on the dynamic stability of the grid-connected inverter under weak grid conditions.
Iga DC power supply C θ + + + + + + IIgbgc VCa Iqref VCb VCc dq abc dq abc PI S1 PWM PCC PLL S3 S5 L1 F F + + + F Idref L2 S4 S6 S2 Lg ~ ~ ~
2.1 Current regulation with active damping
As shown in Fig.2, the current regulator for the inverter system includes a PI regulator and an active damping controller, whose transfer function is F(s).
Note that an active damped LCL filter increases the system complexity while increasing the stability of the inverter. Passive damping can also be used, but it incurs additional power losses. Therefore, in this paper, active damping is used due to avoid these power losses, and it is based on capacitor voltage feedback, where the capacitor voltage is differentiated by s and multiplied by a gain K before being fed back to the current regulator output. The transfer function F sð Þ is KCs.
In practice, the differential term may result in a high-frequency disturbance. To avoid this problem, a partially differentiation is used in the form s s
ssþ1, where s is a
time constant parameter. It is close to a differential element when s is very small. This gives the active damping con-troller a transfer function of the form F sð Þ ¼ K Cs
ssþ1.
The inverter output voltage is described as follows: VPWMð Þ ¼s Irefð Þ Is cgð Þs kpþ ki s þ F sð ÞVc Cð Þs V dc 2
From Fig.2, the system variable relationships can be described by the following open-loop transfer functions [29]:
ILcð Þ ¼ Hs 1ð ÞVs PWMð Þ þ Hs 2ð ÞVs cPCCð Þs
Igcð Þ ¼ Hs 3ð ÞVs PWMð Þ þ Hs 4ð ÞVs cPCCð Þs
VCcð Þ ¼ Hs 5ð ÞVs PWMð Þ þ Hs 6ð ÞVs cPCCð Þs
ð2Þ
where the transfer functions H1(s) * H6(s) are
H1ð Þ ¼s L2Cs2þ 1 L1L2Cs3þ Lð 1þ L2Þs ; H2ð Þ ¼ s 1 L1L2Cs3þ Lð 1þ L2Þs ; H3ð Þ ¼s 1 L1L2Cs3þ Lð 1þ L2Þs ; H4ð Þ ¼ s L1Cs2þ 1 L1L2Cs3þ Lð 1þ L2Þs ; H5ð Þ ¼s L2s L1L2Cs3þ Lð 1þ L2Þs ; H6ð Þ ¼s L1s L1L2Cs3þ Lð 1þ L2Þs :
Based on the above equations, the grid current can be obtained as:
Igcð Þ ¼ Gs Tð ÞIs refð Þ Ys ið ÞVs cCð Þs ð3Þ
which in vector matrix form is:
Icgð Þ ¼s gtð Þs 0 0 gtð Þs |fflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflffl} GTð Þs Irefð Þ s yið Þs 0 0 yið Þs |fflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflffl} Yið Þs VcCð Þs ð4Þ where gt(s) and yi(s) can be expressed as:
gt¼ VdckpþksiH3H6 VdckpþksiH4H5 2H6þ Vdc kpþksi H3H6 Vdc kpþksi H4H5 yi¼ VdcFðsÞH4H5 2H4 VdcFðsÞH3H6 2H6þ VdckpþksiH3H6 VdckpþksiH4H5 8 > > > < > > > : ð5Þ
The small-signal transfer function can be expressed as:
DIcg ¼ yið Þs 0 0 yið Þs |fflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflffl} Yið Þs DVcC ð6Þ
where DIcg is a grid current disturbance and DVcC is a capacitor voltage disturbance in the inverter dq frame.
2.2 Small-signal model of PLL dynamics
Figure3 illustrates the PLL closed-loop control system used in the three-phase grid-connected inverter. A PI reg-ulator is used to enable the q-axis element of the capacitor voltage to follow the zero input reference Vq*, while VCac ,VCbc ,VCcc are the PLL inputs; x0 is the base phase angular velocity; f and h are the PLL output frequency and phase angle, respectively. The output of the PI regulator is
Igref VPWM PI Gvc(s) F(s) + + + + + Vdc/2 c C V Ig(s) VC(s) c g I
Fig. 2 Structure of inverter current regulator
αβ abc αβ dq θ f Filter Oscillator PI + + * q 0 V = + + Cq c V Cd c V + 0 ω 1/2π 1 s Ca c V Cb c V c Cc V Fig. 3 PLL system VPCC(s) ZL1(s) GT(s)Iref (s) VC(s) Ig(s) + Zg(s) Vg(s) + Zeq(s)
the instantaneous angular velocity disturbance Dx in the following form: Dx¼ kpPLLþ kiPLL s |fflfflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflfflffl} FPLLð Þs Im V cC ð7Þ
where kpPLL and kiPLL are the proportional and integral gains of the PI regulator, respectively.
It can be interpreted from Fig.3 that, by integrating Dx ? x0, the following relationship is obtained, where FPLLð Þ is defined in (s 7): dh dt ¼ x0þ Dx ¼ x0þ FPLLð ÞIm Vs c C ð8Þ
Based on (1), the capacitor voltage can be written as
VcC¼ ejDhVC 1 jDhð Þ V C0þ DVC ¼ V0 Cþ DVC jDhVC0 ) Im Vc C ¼ Im DVf Cg DhVC0 ð9Þ
where VC0 is the steady-state capacitor voltage and DVCis the capacitor voltage disturbance. The capacitor voltage disturbance in the inverter dq frame DVCc is:
DVcC¼ DVC jDhVC0 ¼ DVC jVC0GPLLð ÞIm DVs f Cg
ð10Þ where GPLL(s) is given in the following equation:
Dh¼ FPLLð Þs sþ V0 CFPLLð Þs |fflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflffl} GPLLð Þs Im DVf Cg ð11Þ -2000 -1500 -1000 -500 0 500 -6000 -4000 -2000 0 2000 4000 6000 Real axis Imaginary axis Real axis -500 0 500 -1000 -500 0 500 1000 Imaginary axis 8000 -8000 1500 -1000
(a) Root locus
(b) Detail near the origin
Fig. 5 Root locus of the system as PLL bandwidth changes
Real axis Imaginary axis -2000 -1500 -1000 -500 0 -6000 -4000 -2000 0 2000 4000 6000 Real axis Imaginary axis -400 -300 -200 -100 0 100 200 -600 -400 -200 0 200 400 600 8000 500 -8000 800 -800
(a) Root locus
(b) Detail near the origin
The vector matrix form of DVcC is DVcC¼ 1 0 0 1 V0 CGPLLð Þs DVC ð12Þ
Similarly, the grid current disturbance DIgc can be expressed as follows:
DIcg¼ DIg jDhI0g ¼ DIg jIg0GPLLð ÞIm DVs f Cg ð13Þ
where Ig0 is the steady-state value of the grid current and DIg is the current disturbance in the grid dq frame. The vector matrix form of (13) can be written as:
DIc g¼ DIg 0 0 0 IrefGPLLð Þs DVC ð14Þ
With (12), (13) and (14), the inverter input impedance Zeqcan be obtained: Zeq¼ DVC DIg 1 ¼ 0 0 0 IrefGPLLð Þs þ yið Þs 0 0 yið Þs 1 0 0 1 V0 CGPLLð Þs ð15Þ
Then with (14) and (15), the grid current can be expressed as
Igð Þ ¼ Gs Tð ÞIs refð Þ Zs eqð Þs1VCð Þs ð16Þ
The equivalent Norton model of the inverter system is shown in Fig.4.
In Fig.4, ZL1(s) denotes the grid-side filter inductance and Zg(s) denotes the grid line impedance:
ZL1ð Þ ¼s 1=L2s 0 0 1=L2s Zgð Þ ¼s Lgs 0 0 Lgs 8 > > > < > > > : ð17Þ
The final transfer function of the closed-loop system can be obtained from Fig.4 as follows:
G sð Þ ¼ VPCCð Þ Is ½ refð Þs1 ¼ GT ZL1þ Zg Zeq Zeqþ ZL1þ Zg þ Zeq Zeqþ ZL1þ Zg VgðIrefÞ1 ð18Þ
3 Small signal stability analysis
In general, a weak grid condition means the grid has a high impedance. In this section, a small signal stability analysis is carried out for the grid-connected inverter sys-tem with high grid impedance. More specifically, the ran-ges of the PLL bandwidth and the current regulator gain kp required to keep the inverter system stable are investigated. It should be noted that optimized design of the current regulator and the PLL gains is beyond the scope of this paper.
3.1 Impact of PLL bandwidth
When the current regulator gain kp= 0.1 and the PLL regulator gain kpPLLis varied within the range from 2 to 22,
Table 1 System parameters
Variable Value Per unit Variable Value Per unit
Vdc 200 V 1 p.u. Vg 80 V 1 p.u.
L2 2.5 mH 0.05 Lg 6.5 mH 0.12
L1 3 mH 0.06 C 9.4 lF 21
Table 2 Control parameters
Variable Value Variable Value
f0 50 Hz fswitch 10 kHz Ts 50 ls Igref 5 A ki 10 K 0.11 s 10-5 kp 0.1 t (s) -50 0 50 Ig (A) 5 1 . 0 0 1 . 0 5 0 . 0 -50 0 50 Ig (A ) t (s) 5 1 . 0 0 1 . 0 5 0 . 0
(a) Introde the active damping function
(b) Remove the active damping function
Iga I gb
Igc
Iga Igb
Igc
Fig. 7 Simulated input current waveform in the grid-connected inverter
the root loci of the closed-loop transfer function (18) are shown in Fig.5. The arrows indicate the direction of increasing PLL bandwidth, and the intersection with the vertical axis is at kpPLL= 12. As can be seen from the root loci, the poles of the closed-loop system are all in the left half side of the complex plane, and the system is stable, when kpPLLis within the range from 2 to 12 (equally, the PLL bandwidth is less than 90 Hz). It should be noted that when the current regulator gain is fixed, the system tends to
become less stable as the PLL bandwidth increases. Therefore, under weak grid conditions, a relatively small PLL bandwidth should be chosen to ensure system stability for the inverter.
3.2 Impact of current regulator gain
When the PLL bandwidth is fixed at 50 Hz and the current regulator gain kpis varied within the range from 0 to 0.1, the root loci of the closed-loop transfer function (18) are shown in Fig.6. The arrows indicate the direction of decreasing gain, and the intersection with the vertical axis is at kp= 0.04. As can be seen from this figure, the poles of the closed-loop system are all in the left half side of the complex plane, and the system is stable when kpis greater than 0.04. It can be observed that, when the PLL bandwidth is constant, the system tends to be less stable as the current regulator gain decreases.
4 Simulation and experimental verifications
Based on the results of the small-signal stability analy-sis, it can be seen that the PLL dynamics may significantly affect the inverter system stability under weak grid con-ditions. In this section, time-domain simulations and experimental tests are conducted to verify the theoretical results.Parameters of a three-phase grid-connected inverter system with the structure shown in Fig.1 are listed in Tables1 and2.
4.1 Simulation results
In order to verify the effectiveness of the active damping controller, the following two test cases were simulated with sampling period Ts = 50 ls and with integral gain of the
PI-type current regulator ki= 10:
Case 1 The inverter is initially only equipped with a PI-type current regulator, then the active damping function is added at t = 0.05 s.
Case 2 The inverter is initially installed with a PI-type current regulator and the active damping function, then the damping function is removed at t = 0.1 s.
As shown in Fig.7, the system becomes stable as soon as the active damping function is added, and it becomes unstable after the active damping function is removed.
To evaluate the impact of the PLL bandwidth, with a fixed current regulator gain kp= 0.1, the simulations were conducted with PLL bandwidth of 30 Hz and 125 Hz. The Fig. 8 Simulated dynamics of Igand VPCCwhen PLL bandwidth is
30 Hz
Fig. 9 Simulated dynamics of Igand VPCCwhen PLL bandwidth is
resulting dynamics of grid current Igand voltage at PCC VPCC are shown in Figs.8 and 9 respectively. In Fig.8, when the PLL bandwidth is 30 Hz, the inverter is
stable and the oscillations of Ig and VPCC are small. However, in Fig.9, when the PLL bandwidth is increased to 125 Hz, the dynamics of both Igand VPCCdiverge and the system becomes unstable. Based on these simulation results, for a given current regulator gain, it can be seen that the stability margin of the inverter system is bigger when the PLL bandwidth is smaller. This conclusion ver-ifies the results of the small-signal analysis.
To evaluate the effect of the current regulator gain, keeping the PLL bandwidth fixed at 50 Hz, the simulations Fig. 10 Simulated dynamics of Igand VPCCwhen kp= 0.1
Fig. 11 Simulated dynamics of Igand VPCCwhen kp= 0.02
DC power supply C PCC L1 L2 Lg
Fig. 12 Schematic diagram of the experimental setup
i (5 A/div), V (100 V/div) Time (10 ms/div) PCC V La i ga i (a) Case 1 i (5 A /div) , V (100 V /div) Time (10 ms/div) PCC V La i ga i (b) Case 2
Fig. 13 Experimental waveforms for the grid-connected inverter
Fig. 14 Experimental waveforms when the PLL bandwidth is 30 Hz and the current regulator gain is kp= 0.1
were conducted with kp= 0.1 and kp= 0.02. The resulting dynamics of grid current Igand voltage at PCC VPCCare shown in Figs.10and11respectively. The grid-connected inverter system is stable when kp= 0.1, as shown in Fig.10. However, the dynamics of both Ig and VPCC diverge and the grid-connected inverter system becomes unstable when kp= 0.02, as shown in Fig.11. The con-clusion again verifies the results of the small-signal anal-ysis. These observations also indicate that the inverter system may become unstable when the PLL bandwidth is beyond its stable range, even when the current regulation gain is within its stable range. Therefore, it is important to take the PLL dynamics into account.
4.2 Experimental results
A 3 kVA experimental platform system was built to further verify the impacts of the PLL dynamics and the current regulator. The schematic diagram of the experi-mental setup is shown in Fig.12.
The inverter is controlled by a 32-bit fixed-point 150 MHz TMS320F2812 DSP. The system parameters are the same as those simulated above, listed in Tables1and2. The effectiveness of the active damping controller was verified using two test cases similar to those simulated, as follows:
Case 1 The inverter system is initially only equipped with a PI type current regulator, then the active damping function is added at t = 0.023 s.
Case 2 The inverter system is initially installed with a PI type current regulator and the active damping function, then the damping function is removed at t = 0.25 s.
As shown in Fig.13, the system becomes stable as soon as the active damping function is added, and it becomes unstable after the damping function is removed. These
results verify the effectiveness of active damping regarding the resonance which results from the LCL filters.
The interaction between the PLL dynamics and the current regulator was also experimentally tested. First of all, the current regulator gain was fixed as kp= 0.1, and experimental tests were carried out with the PLL band-width set to 30 Hz and 125 Hz. The results are shown in Figs. 14 and 15 respectively. It can be observed that the waveforms of VPCC, Ig, and iL are stable when the PLL bandwidth is 30 Hz. However, when the PLL bandwidth is
Fig. 15 Experimental waveforms when the PLL bandwidth is 125 Hz and the current regulator gain is kp= 0.1
Fig. 16 Experimental waveforms when changing the PLL bandwidth
Fig. 17 Experimental waveforms when the current regulator gain kp= 0.1 and the PLL bandwidth is 50 Hz
125 Hz, VPCC, Ig, and iL start diverging and operate unstably. This is consistent with the theoretical analysis and simulation results that, for a fixed current regulator gain, the system is more stable with a smaller PLL band-width. The same good agreement with theory was observed
when the PLL bandwidth was changed online, as shown in Fig.16.
Secondly, the PLL bandwidth was fixed at 50 Hz, and experimental tests were carried out with the current regu-lator gain set to kp= 0.1 and kp= 0.02. The results are shown in Figs.17and18respectively.
It can be observed from Fig. 17that the waveforms of VPCC, Ig, and iL are stable when kp= 0.1. However, the system becomes unstable when kp= 0.02, with VPCC, Ig, and iL diverging and showing irregular behavior. This is consistent with the theoretical analysis and simulation results that, when the PLL bandwidth is fixed, the system is more stable for a larger current regulator gain. When the current regulator gain was changed online, as shown in Fig.19, the same good agreement with theory was observed.
5 Conclusion
In this paper, the interaction of phase-locked loop (PLL) dynamics and the current regulator on system stability has been investigated for active damped LCL-filter-based grid-connected inverters with capacitor voltage feedback under weak grid conditions. To efficiently model the system including the PLL dynamics, an equivalent Norton model was applied to obtain the closed-loop transfer function of the whole system. By investigating the poles of the transfer function, it has been found that the system tends to be instable as the PLL bandwidth increases with a fixed cur-rent regulator gain. Also, when the PLL bandwidth is fixed, the system tends to be instable as the current regulator gain decreases. The ranges of stability of the PLL bandwidth and the current regulator gain have been identified. The effectiveness of the designed active damping control method has been verified by both simulations and experi-mental results using a three-phase grid-connected inverter system. Future research can include stability analysis with a low sampling frequency under different control and operating modes.
Acknowledgements This work was supported by Science Founda-tion for Distinguished Young Scholars of Hebei Province (No. E2016203133) and Hundred Excellent Innovation Talents Support Program of Hebei Province (No. SLRC2017059).
Open Access This article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http:// creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made. ga i La i PCC V i (5 A/div ), V (100 V/div) Time (10 ms/div)
Fig. 18 Experimental waveforms when the current regulator gain kp= 0.02 and the PLL bandwidth is 50 Hz
Fig. 19 Experimental waveforms when changing the current regula-tor gain kp
References
[1] Pan D, Ruan X, Bao C et al (2015) Optimized controller design for LCL-type grid-connected inverter to achieve high robustness against grid-impedance variation. IEEE Trans Ind Electron 62(3):1537–1547
[2] Guo X, Jia X (2016) Hardware-based cascaded topology and modulation strategy with leakage current reduction for trans-formerless PV systems. IEEE Trans Ind Electron 62(12): 7823–7832
[3] Shuai Z, Huang W, Shen C et al (2017) Characteristics and restraining method of fast transient inrush fault currents in synchronverters. IEEE Trans Ind Electron. doi:10.1109/TIE. 2017.2652362
[4] Guo X, Liu W, Zhang X et al (2015) Flexible control strategy for grid-connected inverter under unbalanced grid faults without PLL. IEEE Trans Power Electron 30(4):1773–1778
[5] Wu W, Sun Y, Huang M et al (2014) A robust passive damping method for LLCL-filter-based grid-tied inverters to minimize the effect of grid harmonic voltages. IEEE Trans Power Electron 29(7):3279–3289
[6] Li F, Zhang X, Zhu H et al (2015) An LCL-LC filter for grid connected converter: topology, parameter, and analysis. IEEE Trans Power Electron 30(9):5067–5077
[7] Beres RN, Wang X, Liserre M et al (2016) A review of passive power filters for three-phase grid-connected voltage-source converters. IEEE J Emerg Sel Top Power Electron 4(1):54–69 [8] Pan D, Ruan X, Bao C et al (2014) Capacitor-current feedback
active damping with reduced computation delay for improving robustness of LCL-type grid-connected inverter. IEEE Trans Power Electron 29(7):3414–3427
[9] Wang X, Blaabjerg F, Loh PC (2016) Grid-current-feedback active damping for LCL resonance in grid-connected voltage source converters. IEEE Trans Power Electron 31(1):213–223 [10] Wang X, Blaabjerg F, Loh PC (2015) Virtual RC damping of
LCL filtered voltage source converters with extended selective harmonic compensation. IEEE Trans Power Electron 30(9): 4726–4737
[11] Guo X (2017) Three phase CH7 inverter with a new space vector modulation to reduce leakage current for transformerless pho-tovoltaic systems. IEEE J Emerg Sel Top Power Electron 5(2):708–712
[12] Guo X, Xu D, Wu B (2016) Common-mode voltage mitigation for back-to-back current-source converter with optimal space-vector modulation. IEEE Trans Power Electron 31(1):688–697 [13] Guo X (2017) A novel CH5 inverter for single-phase
trans-formerless photovoltaic system applications. IEEE Trans Cir-cuits Syst II Express Br. doi:10.1109/TCSII.2017.2672779 [14] Liu F, Wu B, Zargari NR et al (2011) An active damping
method using inductor-current feedback control for high-power PWM current source rectifier. IEEE Trans Power Electron 26(9):2580–2587
[15] Cespedes M, Sun J (2014) Impedance modeling and analysis of grid-connected voltage-source converters. IEEE Trans Power Electron 29(3):1254–1261
[16] Shuai Z, Hu Y, Peng Y et al (2017) Dynamic stability analysis of synchronverter-dominated microgrid based on bifurcation the-ory. IEEE Trans Ind Electron. doi:10.1109/TIE.2017.2652387 [17] Zhang D, Wang Y, Hu J et al (2016) Impacts of PLL on the
DFIG-based WTG’s electromechanical response under transient conditions: analysis and modeling. CSEE J Power Energy Syst 2(2):30–39
[18] Zhang L, Harnefors L, Nee HP (2010) Power-synchronization control of grid-connected voltage-source converters. IEEE Trans Power Syst 25(2):809–820
[19] Zhou JZ, Ding H, Fan S et al (2014) Impact of short-circuit ratio and phase-locked-loop parameters on the small-signal behavior of a VSC-HVDC converter. IEEE Trans Power Del 29(5):2287–2296
[20] Guo X, Wu W, Gu H (2010) Modeling and simulation of direct output current control for LCL-interfaced grid-connected inverters with parallel passive damping. Simul Model Pract Theory 18(7):946–956
[21] Pan D, Ruan X, Wang X et al (2017) Analysis and design of current control schemes for LCL-type grid-connected inverter based on a general mathematical model. IEEE Trans Power Electron 32(6):4395–4410
[22] Zheng L, Geng H, Yang G (2016) Fast and robust phase esti-mation algorithm for heavily distorted grid conditions. IEEE Trans Ind Electron 63(11):6845–6855
[23] Liu H, Xing Y, Hu H (2016) Enhanced frequency-locked loop with a comb filter under adverse grid conditions. IEEE Trans Power Electron 31(12):8046–8051
[24] Guo X, Guerrero JM (2016) Abc-frame complex-coefficient filter and controller based current harmonic elimination strategy for three-phase grid connected inverter. J Mod Power Syst Clean Energy 4(1):87–93. doi:10.1007/s40565-016-0189-4
[25] Wu F, Zhang L, Duan J (2015) A new two-phase stationary-frame-based enhanced PLL for three-phase grid synchroniza-tion. IEEE Trans Circuits Syst II Express Br 62(3):251–255 [26] Guo X, Liu W, Lu Z (2017) Flexible power regulation and
current-limited control of grid-connected inverter under unbal-anced grid voltage faults. IEEE Trans Ind Electron. doi:10.1109/ TIE.2017.2669018
[27] Guan Q, Zhang Y, Kang Y et al (2017) Single-phase phase-locked loop based on derivative elements. IEEE Trans Power Electron 32(6):4411–4420
[28] Guo X, Wu W, Chen Z (2011) Multiple-complex-coefficient-filter- based phase-locked loop and synchronization technique for three-phase grid interfaced converters in distributed utility networks. IEEE Trans Ind Electron 58(4):1194–1204
[29] He J, Li YW, Bosnjak D et al (2013) Investigation and active damping of multiple resonances in a parallel-inverter-based microgrid. IEEE Trans Power Electron 28(1):234–246
Xiaoqiang GUOreceived the B.S. and Ph.D. degrees in Electrical Engineering from Yanshan University, Qinhuangdao, China, in 2003 and 2009, respectively. He has been a Postdoctoral Fellow with the Laboratory for Electrical Drive Applications and Research (LEDAR), Ryerson University, Toronto, ON, Canada. He is currently an associate professor with the Department of Electrical Engineering, Yanshan University, China. His current research interests include high-power converters and ac drives, electric vehicle charging station, and renewable energy power conversion systems.
Shichao LIU received the B.Sc. and M.Sc. degrees from Harbin Engineering University, Harbin, China, in 2007 and 2010, respec-tively, and the Ph.D. degree from Carleton University, Ottawa, ON, Canada, in 2014. His research interests include networked control systems, energy management, and optimization of microgrids. Xiaoyu WANGreceived the B.Sc. and M.Sc. degrees from Tsinghua University, Beijing, China, in 2000 and 2003, respectively, and the Ph.D. degree from the University of Alberta, Edmonton, AB, Canada, in 2008. He is currently an Associate Professor with the Department of Electronics, Faculty of Engineering and Design, Carleton Univer-sity, Ottawa, ON, Canada. His research interests include the integration of distributed energy resources and power quality.