Ref.
(4)-G77700-S0019-L061-A
Project:
Gilgel Gibe – II PROJECT
ETHIOPIA
Description:
400 kV SWITCHYARD
DESIGN
REPORT’s & CALCULATION’s
Subject:
Report on Calculations for Determination of
Cantilever Strength of Bus Post Insulators
Note:
This report establishes the sizing of bus post insulators for 400kV switchyard
on the basis of cantilever strength.
BPI Selection Design Report : Cantilever Strength Calculation
Page: 3 of 7
Handling:
Unrestricted
Siemens Power Engineering Pvt. Ltd.
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.(4)-G77700-S0019-L061-A
Contents
page
1.
Introduction ... 4
2.
System Data... 4
3.
Conductor Data ... 4
4.
Bus Post Insulator data ... 5
5.
Attachments ... 6
6.
Conclusion ... 6
BPI Selection Design Report : Cantilever Strength Calculation
Page: 4 of 7
Handling:
Unrestricted
Siemens Power Engineering Pvt. Ltd.
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.(4)-G77700-S0019-L061-A
1 Introduction
The rigid bus in out-door substation is primarily supported on Bus Post Insulators. These bus
post insulators are hence subjected to sustain all types of stresses on bus conductor owing to
electrically and mechanically originated forces.
The principal forces on the bus post insulator are as follows –
a. Short circuit current force on the bus conductor.
b. Wind force on the bus conductor.
c. Wind force on the insulator stack.
d. Weight of the bus conductor span supported by the bus post insulator.
Since the forces on the bus-conductors are transmitted to the bus post insulators, the strength of
the insulator must be considered. With various bus configurations, insulators may be required to
withstand cantilever, compressive, tensile and torsional forces. However, only the cantilever
force, which is a function of the effective conductor span length supported by the bus post
insulator, have been regarded significant and considered for design.
2 System data
400kV AC Switchyard
Nominal System Voltage
400 kV
System Frequency
50 Hz
Short Circuit Fault Current
31.5 kA
Duration of Fault Current
1 sec
Maximum Wind Pressure
700 N/m
2Altitude above sea level
>1500 m
3 Conductor Data
Rigid Conductor
i) 250/6mm Aluminum Tube (AlMgSi0.5F25)
Outer Diameter
250 mm
BPI Selection Design Report : Cantilever Strength Calculation
Page: 5 of 7
Handling:
Unrestricted
Siemens Power Engineering Pvt. Ltd.
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.(4)-G77700-S0019-L061-A
Weight
12.4 Kg/m
Weight of Damping Material (Twin 954 MCM Cardinal ACSR)
1829.8 Kg/kM
ii) 120/8mm Aluminum Tube (AlMgSi0.5F25)
Outer Diameter
120 mm
Wall thickness
8 mm
Weight
7.6 Kg/m
Weight of Damping Material (Single 954 MCM Cardinal ACSR)
1829.8 Kg/kM
iii) 120/6mm Aluminum Tube (AlMgSi0.5F25)
Outer Diameter
120 mm
Wall thickness
6 mm
Weight
5.8 Kg/m
Weight of Damping Material (Single 954 MCM Cardinal ACSR)
1829.8 Kg/kM
Common for all tubes specified above
Young’s Modulus
70000 N/mm
24 Bus Post Insulator data
i) C8-1550
Height of Insulator Stack
3350 mm
Maximum Width
310 mm
Minimum Width
140 mm
Weight of Insulator
349 Kg
Cantilever Strength (designated by manufacturer)
800 daN
i) C6-1550
Height of Insulator Stack
3350 mm
Maximum Width
290 mm
BPI Selection Design Report : Cantilever Strength Calculation
Page: 6 of 7
Handling:
Unrestricted
Siemens Power Engineering Pvt. Ltd.
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.(4)-G77700-S0019-L061-A
Weight of Insulator
291 Kg
Cantilever Strength (designated by manufacturer)
600 daN
i) C12.5-1550
Height of Insulator Stack
3350 mm
Maximum Width
360 mm
Minimum Width
160 mm
Weight of Insulator
400 Kg
Cantilever Strength (designated by manufacturer)
1250 daN
Busbar Selection
The following types of tubular busbar has been considered in the design :
x 250/6 mm AlMgSi0.5F25 Tubular Bus bar to serve as Main Bus Conductor.
x 120/8 mm AlMgSi0.5F25 Tubular Bus bar to serve as Equipment Bus Conductor at the
Bus Coupling feeder.
x 120/6 mm AlMgSi0.5F25 Tubular Bus bar to serve as Equipment Bus Conductor at the
Transformer & Line feeders.
5 Attachments
Attachment-1: Calculation of Cantilever Strength of Bus Post Insulator supporting the Main Bus
Attachment-2: Calculation of Cantilever Strength of Bus Post Insulator supporting the Equipment
Bus at Coupling Bay
Attachment-3: Calculation of Cantilever Strength of Bus Post Insulator supporting the Equipment
Bus at Transformer & OHL Feeders.
6 Conclusion
1. The required Cantilever Strength of the C12.5-1550 for supporting the maximum bus span(24 m)
of the Main Bus is 995.67 daN, whereas the cantilever strength published by the manufacturer is
1250 daN. Thus the design is safe and Bus Post Insulators of C12.5-1550 type may be used for
supporting the Main Bus conductor.
2. The required Cantilever Strength of the C6-1550 for supporting the maximum bus span(12 m) of
the Equipment Bus at Coupling Bay is 281.23 daN, whereas the cantilever strength published by
BPI Selection Design Report : Cantilever Strength Calculation
Page: 7 of 7
Handling:
Unrestricted
Siemens Power Engineering Pvt. Ltd.
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.(4)-G77700-S0019-L061-A
the manufacturer is 600 daN. Thus the design is safe and Bus Post Insulators of C6-1550 type
may be used for supporting the Equipment Bus conductor at the Coupling Bay.
3. The required Cantilever Strength of the C6-1550 for supporting the maximum bus span (12 m)
of the Equipment Bus at Transformer & OHL Feeders is 249.28 daN, whereas the cantilever
strength published by the manufacturer is 600 daN. Thus the design is safe and Bus Post
Insula-tors of C6-1550 type may be used for supporting the Equipment Bus conductor at Transformer &
OHL Feeders.
7 References
1. IEEE Std 605 : 1987 IEEE Guide for Design of Substation Rigid-Bus Structures.
2. Technical Data sheet for Aluminum Alloy Tubular Conductor: Manufacturer – Corus.
3. Technical Data sheet for Bus Post Insulator: Manufacturer – Porzellanfabrik Frauenthal
Insulators.
S
(4)-G77700-S0019-L062-AATTACHMENT-1
SYSTEM VOLTAGE ( IN KV. ): 400 FAULT LEVEL( IK3 ) ( IN KA.): 31.5
TUBULAR BUS CONDUCTOR :
a) Size : AlMgSi0.5F25 250 mm c) Thickness : 6 mm d) Weight 12.4 Kg/m e) conductor Young's Modulus 7.00E+10 N/m2 f) Conductor spacing 6 m g) Max Allowable stress 115 N/mm2
11.72 Kg/mm2 h) Max. Span 24 m
i) Weight of Damper Material 3.66 Kg/m (Twin 954 CARDINAL ACSR Conductor)
INSULATOR DATA (Type:C12,5-1550):
a. Height 3.35 m b. Max. Width 0.36 m c. Min. Width 0.16 m d Bus Cen. Line
height above Insulator 0.215 m e. Weight 400 Kg
Max. Wind Pressure(Pmax) = 700 N/m 2
(as per technical specification) Ambient air density(d) = 0.613 Kg/m3
Wind Velocity(V) = (Pmax/d) 1/2
m/s = 33.79 m/s Now,
Coss sectional moment of inertia of the tube (J) = = (S/64 ).(Do 4
- Di 4
) where,
DO = Outer Diameter of Conductor = 250 mm
Di = Inner Diameter of Tube = 238 mm
Therefore, J = 34231262.64 mm4
= 82.24027953 in4 Sectional Modulus of the tube S = J/(DO/2) mm
3
= 273850.1011 mm3 = 16.71125822 in3
Conductor Wind Force (FW) = 2.132 x 10 -4
CDKZGFV 2
(DO+2r1) lbf/ft (Cl. 10. of IEEE:605)
Where
DO = Outer Diameter of Conductor 9.84 inch
r1 = Radial Ice thickness. = 0 inch
CD = Drag coefficient (Ref. Table 1 of IEEE:605) = 1
KZ = Height and exposure factor (Cl. 10.2 of IEEE:605) = 1
GF = Gust factor (Cl. 10.3 of IEEE:605) = 1.3
V =Wind speed at 30ft. above ground = 33.79 m/s = 75.59 mi/h Hence, FW = 15.59 lbf/ft
Short Circuit Current Unit Force (FSC) = 27.6* ISC2 /107(D) lbf/ft
CALCULATION OF CANTILEVER STRENGTH OF BUS POST INSULATOR SUPPORTING THE MAIN BUS
b) Outer dia.
Calculation for conductor Wind Force:
Calculation for Short Circuit Current Unit Force:
(For Round conductor)
Gilgel Gibe II Hydroelectric Project
Page 1 OF 3
S
(4)-G77700-S0019-L062-AATTACHMENT-1
ISC = Symmettrical short circuit current = 31500 A
D = Conductor spacing centre to centre = 236.22 inch * = Constant based on type of short circuit and = 0.866
conductor location (Ref. Table 2 of IEEE:605) Hence, FSC = 10.04 lbf/ft
Total bus unit weight (FG) = FC + FI+ FD lbf/ft
FC = Conductor unit weight = 8.33 lbf/ft
FD = Damping material unit weight = 2.46 lbf/ft
FI = Ice Unit weight = 0 lbf/ft
Hence, FG = 10.79 lbf/ft
Calculation for Insulator Strength
a. Calculation for Bus Short circuit Current Force: FSB = LE.FSC lbf
FSB = Bus Short Circuit Force transmitted to bus support fitting
LE = Effective Bus span length = 78.74 ft
FSC = Short Circuit Current Unit Force = 10.04 lbf/ft
Now, for a Rigid Bus Section of Equipment connection in a typical Line bay
across the Main Bus (as shown in the figure alongside) P P P LE = 1/2(L1+L2) (Refer Table 5 of IEEE-605)
= 78.74016 ft
Adjescent Bus Span (L1) = 24 m
= 78.74 ft Adjescent Bus Span (L2) = 24 m
= 78.74 ft 24m 24m Therefore FSB = 790.55 lbf
L1 L2
b. Calculation for Bus Wind Force : Fig 1
FWB = LE.FW lbf
Where,
FWB = Bus Wind force transmitted to bus support fitting
LE = Effective Bus span length = 78.74 ft
FW = Wind unit force on the bus = 15.59 lbf/ft
Therefore FWB = 1227.38 lbf
c. Calculation for Insulator wind force: FWI = 1.776 x 10 -5 CDKZGFV 2 (Di+2r1)Hi lbf Where,
FWI = Wind Force on Insulator
Hi = Insulator Height = 131.89 Inch
Di = Effective insulator diameter
= (D1+D2)/2 = 10.2362 inch
D1 = Max. Insulator Width = 14.1732 inch
D2 = Min. Insulator Width = 6.2992 inch
BPI BPI BPI
Calculation for Gravitational Force:
Gilgel Gibe II Hydroelectric Project
S
(4)-G77700-S0019-L062-AATTACHMENT-1
r1 = Radial Ice thickness = 0 inch
CD = Drag coefficient = 1 (For 'round conductor' as per Table 1 of IEEE:605)
KZ = Height and exposure factor = 1(as per Cl. 10.2 of IEEE:605)
GF = Gust factor = 1.3 (as per Cl. 10.3 of IEEE:605)
V =Wind speed at 30ft. above ground = 33.79 m/s = 75.59 mi/h Therefore FWI = 178.11 lbf
Calculation for Total Insulator Cantilever load
FIS = K1 [ FWI/2 + {(Hi+Hf)/Hi} FWB] + K2 [{(Hi+Hf)/Hi} FSB] lbf
FIS = Total Cantilever load acting at the end of Insulator
FWI = Wind force on the insulator in lbf = 178.11 lbf
FSB = Bus Short Circuit Force transmitted to bus support fitting = 790.55 lbf
FWB = Bus Wind force transmitted to bus support fitting = 1227.38 lbf
Hi = Insulator Height = 131.89 inch
Hf = Bus Cen. Height above Insulator = 8.46 inch
K1 = Overload Factor applied to wind force = 1
K2 = Overload Factor applied to short circuit force = 1
Therefore FIS = 2236.49 lbf
Now
Effective weight of bus transmitted to bus support fitting FGB = LE.FG lbf
where,
LE = Effective Bus span length = 78.74 ft
FG = Total Bus Unit Weight = 10.79 lbf/ft
Therefore FGB = 849.83 lbf
Natural Frequency of the Insulator with effective weight of the conductor span : fi = (1/2S) [Ki g / (0.226FGI + FGB)]
1/2
where,
Ki = Insulator cantilever Spring Constant = 1 lbf/inch
g = gravitional constant = 386 inch/s2 FGI = Weight of the insulator = 881.85 lbf
FGB = Effective weight of bus transmitted to bus support fitting = 849.83 lbf
Therefore fi = 0.10 Hz
As fi < 50Hz => K2 = 1 (Refer Cl. No. 13.2 of IEEE: 605)
Cantilever Load on the Support Insulator FIS (Eqp) = 1015.37 Kgf
(in the direction of the Equipment Connection)
=> Reqiured cantilever Strength of the Supporting Insulator = 995.67 daN
Gilgel Gibe II Hydroelectric Project
S
(4)-G77700-S0019-L061-AATTACHMENT-2
SYSTEM VOLTAGE ( IN KV. ): 400 FAULT LEVEL( IK3 ) ( IN KA.): 31.5
TUBULAR BUS CONDUCTOR :
a) Size : AlMgSi0.5F25 120 mm c) Thickness : 8 mm d) Weight 7.6 Kg/m e) conductor Young's Modulus 7.00E+10 N/m2 f) Conductor spacing 6.5 m g) Max Allowable stress 115 N/mm2
11.72 Kg/mm2 h) Max. Span 12 m
i) Weight of Damper Material 1.83 Kg/m (Single 954 CARDINAL ACSR Conductor)
INSULATOR DATA (Type:C6-1550):
a. Height 3.35 m b. Max. Width 0.29 m c. Min. Width 0.13 m d Bus Cen. Line
height above Insulator 0.15 m e. Weight 291 Kg
Max. Wind Pressure(Pmax) = 700 N/m 2
(as per technical specification) Ambient air density(d) = 0.613 Kg/m3
Wind Velocity(V) = (Pmax/d) 1/2
m/s = 33.79 m/s Now,
Coss sectional moment of inertia of the tube (J) = = (S/64 ).(Do4 - Di4)
where,
DO = Outer Diameter of Conductor = 120 mm
Di = Inner Diameter of Tube = 104 mm
Therefore, J = 4433981.44 mm4 = 10.6525978 in4 Sectional Modulus of the tube S = J/(DO/2) mm
3
= 73899.69067 mm3 = 4.509608754 in3
Conductor Wind Force (FW) = 2.132 x 10 -4
CDKZGFV 2
(DO+2r1) lbf/ft (Cl. 10. of IEEE:605)
Where
DO = Outer Diameter of Conductor 4.72 inch
r1 = Radial Ice thickness. = 0 inch
CD = Drag coefficient (Ref. Table 1 of IEEE:605) = 1
KZ = Height and exposure factor (Cl. 10.2 of IEEE:605) = 1
GF = Gust factor (Cl. 10.3 of IEEE:605) = 1.3
V =Wind speed at 30ft. above ground = 33.79 m/s = 75.59 mi/h Hence, FW = 7.48 lbf/ft
Short Circuit Current Unit Force (FSC) = 27.6* ISC2 /107(D) lbf/ft
CALCULATION OF CANTILEVER STRENGTH OF BUS POST INSULATOR SUPPORTING THE EQUIPMENT BUS
b) Outer dia.
Calculation for conductor Wind Force:
Calculation for Short Circuit Current Unit Force:
(For Round conductor)
AT COUPLING BAY
Gilgel Gibe II Hydroelectric Project
S
(4)-G77700-S0019-L061-AATTACHMENT-2
ISC = Symmettrical short circuit current = 31500 A
D = Conductor spacing centre to centre = 255.91 inch * = Constant based on type of short circuit and = 0.866
conductor location (Ref. Table 2 of IEEE:605) Hence, FSC = 9.27 lbf/ft
Total bus unit weight (FG) = FC + FI+ FD lbf/ft
FC = Conductor unit weight = 5.11 lbf/ft
FD = Damping material unit weight = 1.23 lbf/ft
FI = Ice Unit weight = 0 lbf/ft
Hence, FG = 6.34 lbf/ft
Calculation for Insulator Strength
a. Calculation for Bus Short circuit Current Force: FSB = LE.FSC lbf
FSB = Bus Short Circuit Force transmitted to bus support fitting
LE = Effective Bus span length = 31.99 ft
FSC = Short Circuit Current Unit Force = 9.27 lbf/ft
Now, for a Rigid Bus Section of Equipment connection in a typical Line bay
across the Equipment Bus in Coupling bay(as shown in the figure alongside) F P P LE = 1/8(3L1+4L2) (Refer Table 5 of IEEE-605)
= 31.98819 ft
Adjescent Bus Span (L1) = 12 m
= 39.37 ft Adjescent Bus Span (L2) = 10.5 m
= 34.45 ft 12m 10.5m Therefore FSB = 296.45 lbf
L1 L2
b. Calculation for Bus Wind Force : Fig 1
FWB = LE.FW lbf
Where,
FWB = Bus Wind force transmitted to bus support fitting
LE = Effective Bus span length = 31.99 ft
FW = Wind unit force on the bus = 7.48 lbf/ft
Therefore FWB = 239.34 lbf
c. Calculation for Insulator wind force: FWI = 1.776 x 10 -5 CDKZGFV 2 (Di+2r1)Hi lbf Where,
FWI = Wind Force on Insulator
Hi = Insulator Height = 131.89 Inch
Di = Effective insulator diameter
= (D1+D2)/2 = 8.2677 inch
D1 = Max. Insulator Width = 11.4173 inch
D2 = Min. Insulator Width = 5.1181 inch
ISO(Panto) BPI CT
Calculation for Gravitational Force:
Gilgel Gibe II Hydroelectric Project
S
(4)-G77700-S0019-L061-AATTACHMENT-2
r1 = Radial Ice thickness = 0 inch
CD = Drag coefficient = 1 (For 'round conductor' as per Table 1 of IEEE:605)
KZ = Height and exposure factor = 1(as per Cl. 10.2 of IEEE:605)
GF = Gust factor = 1.3 (as per Cl. 10.3 of IEEE:605)
V =Wind speed at 30ft. above ground = 33.79 m/s = 75.59 mi/h Therefore FWI = 143.86 lbf
Calculation for Total Insulator Cantilever load
FIS = K1 [ FWI/2 + {(Hi+Hf)/Hi} FWB] + K2 [{(Hi+Hf)/Hi} FSB] lbf
FIS = Total Cantilever load acting at the end of Insulator
FWI = Wind force on the insulator in lbf = 143.86 lbf
FSB = Bus Short Circuit Force transmitted to bus support fitting = 296.45 lbf
FWB = Bus Wind force transmitted to bus support fitting = 239.34 lbf
Hi = Insulator Height = 131.89 inch
Hf = Bus Cen. Height above Insulator = 5.91 inch
K1 = Overload Factor applied to wind force = 1
K2 = Overload Factor applied to short circuit force = 1
Therefore FIS = 631.71 lbf
Now
Effective weight of bus transmitted to bus support fitting FGB = LE.FG lbf
where,
LE = Effective Bus span length = 31.99 ft
FG = Total Bus Unit Weight = 6.34 lbf/ft
Therefore FGB = 202.72 lbf
Natural Frequency of the Insulator with effective weight of the conductor span : fi = (1/2S) [Ki g / (0.226FGI + FGB)]
1/2
where,
Ki = Insulator cantilever Spring Constant = 1 lbf/inch
g = gravitional constant = 386 inch/s2 FGI = Weight of the insulator = 641.54 lbf
FGB = Effective weight of bus transmitted to bus support fitting = 202.72 lbf
Therefore fi = 0.17 Hz
As fi < 50Hz => K2 = 1 (Refer Cl. No. 13.2 of IEEE: 605)
Cantilever Load on the Support Insulator FIS (Eqp) = 286.80 Kgf
(in the direction of the Equipment Connection)
=> Reqiured cantilever Strength of the Supporting Insulator = 281.23 daN
Gilgel Gibe II Hydroelectric Project
S
(4)-G77700-S0019-L061-AATTACHMENT-3
SYSTEM VOLTAGE ( IN KV. ): 400 FAULT LEVEL( IK3 ) ( IN KA.): 31.5
TUBULAR BUS CONDUCTOR :
a) Size : AlMgSi0.5F25 120 mm c) Thickness : 6 mm d) Weight 5.8 Kg/m e) conductor Young's Modulus 7.00E+10 N/m2 f) Conductor spacing 6.5 m g) Max Allowable stress 115 N/mm2
11.72 Kg/mm2 h) Max. Span 12 m
i) Weight of Damper Material 1.83 Kg/m (Single 954 CARDINAL ACSR Conductor)
INSULATOR DATA (Type:C6-1550):
a. Height 3.35 m b. Max. Width 0.29 m c. Min. Width 0.13 m d Bus Cen. Line
height above Insulator 0.15 m e. Weight 291 Kg
Max. Wind Pressure(Pmax) = 700 N/m 2
(as per technical specification) Ambient air density(d) = 0.613 Kg/m3
Wind Velocity(V) = (Pmax/d) 1/2
m/s = 33.79 m/s Now,
Coss sectional moment of inertia of the tube (J) = = (S/64 ).(Do4 - Di4)
where,
DO = Outer Diameter of Conductor = 120 mm
Di = Inner Diameter of Tube = 108 mm
Therefore, J = 3498701.04 mm4 = 8.405595626 in4 Sectional Modulus of the tube S = J/(DO/2) mm
3
= 58311.684 mm3 = 3.558375932 in3
Conductor Wind Force (FW) = 2.132 x 10 -4
CDKZGFV 2
(DO+2r1) lbf/ft (Cl. 10. of IEEE:605)
Where
DO = Outer Diameter of Conductor 4.72 inch
r1 = Radial Ice thickness. = 0 inch
CD = Drag coefficient (Ref. Table 1 of IEEE:605) = 1
KZ = Height and exposure factor (Cl. 10.2 of IEEE:605) = 1
GF = Gust factor (Cl. 10.3 of IEEE:605) = 1.3
V =Wind speed at 30ft. above ground = 33.79 m/s = 75.59 mi/h Hence, FW = 7.48 lbf/ft
Short Circuit Current Unit Force (FSC) = 27.6* ISC2 /107(D) lbf/ft
CALCULATION OF CANTILEVER STRENGTH OF BUS POST INSULATOR SUPPORTING THE EQUIPMENT BUS
b) Outer dia.
Calculation for conductor Wind Force:
Calculation for Short Circuit Current Unit Force:
(For Round conductor)
AT TRANSFORMER & OHL BAY
Gilgel Gibe II Hydroelectric Project
S
(4)-G77700-S0019-L061-AATTACHMENT-3
ISC = Symmettrical short circuit current = 31500 A
D = Conductor spacing centre to centre = 255.91 inch * = Constant based on type of short circuit and = 0.866
conductor location (Ref. Table 2 of IEEE:605) Hence, FSC = 9.27 lbf/ft
Total bus unit weight (FG) = FC + FI+ FD lbf/ft
FC = Conductor unit weight = 3.90 lbf/ft
FD = Damping material unit weight = 1.23 lbf/ft
FI = Ice Unit weight = 0 lbf/ft
Hence, FG = 5.13 lbf/ft
Calculation for Insulator Strength
a. Calculation for Bus Short circuit Current Force: FSB = LE.FSC lbf
FSB = Bus Short Circuit Force transmitted to bus support fitting
LE = Effective Bus span length = 27.89 ft
FSC = Short Circuit Current Unit Force = 9.27 lbf/ft
Now, for a Rigid Bus Section of Equipment connection in a typical Line bay across
the Equipment Bus in Transformer & OHL bay(as shown in the figure alongside) F P P P LE = 1/8(3L1+4L2) (Refer Table 5 of IEEE-605)
= 27.88714 ft 8m Adjescent Bus Span (L1) = 12 m
= 39.37 ft Adjescent Bus Span (L2) = 8 m
= 26.25 ft 12m 10.5m Therefore FSB = 258.45 lbf
L1 L2
b. Calculation for Bus Wind Force : Fig 1
FWB = LE.FW lbf
Where,
FWB = Bus Wind force transmitted to bus support fitting
LE = Effective Bus span length = 27.89 ft
FW = Wind unit force on the bus = 7.48 lbf/ft
Therefore FWB = 208.65 lbf
c. Calculation for Insulator wind force: FWI = 1.776 x 10 -5 CDKZGFV 2 (Di+2r1)Hi lbf Where,
FWI = Wind Force on Insulator
Hi = Insulator Height = 131.89 Inch
Di = Effective insulator diameter
= (D1+D2)/2 = 8.2677 inch
D1 = Max. Insulator Width = 11.4173 inch
D2 = Min. Insulator Width = 5.1181 inch
ISO(Panto) BPI CB
Calculation for Gravitational Force:
Gilgel Gibe II Hydroelectric Project
S
(4)-G77700-S0019-L061-AATTACHMENT-3
r1 = Radial Ice thickness = 0 inch
CD = Drag coefficient = 1 (For 'round conductor' as per Table 1 of IEEE:605)
KZ = Height and exposure factor = 1(As per Cl. 10.2 of IEEE:605)
GF = Gust factor = 1.3 (As per Cl. 10.3 of IEEE:605)
V =Wind speed at 30ft. above ground = 33.79 m/s = 75.59 mi/h Therefore FWI = 143.86 lbf
Calculation for Total Insulator Cantilever load
FIS = K1 [ FWI/2 + {(Hi+Hf)/Hi} FWB] + K2 [{(Hi+Hf)/Hi} FSB] lbf
FIS = Total Cantilever load acting at the end of Insulator
FWI = Wind force on the insulator in lbf = 143.86 lbf
FSB = Bus Short Circuit Force transmitted to bus support fitting = 258.45 lbf
FWB = Bus Wind force transmitted to bus support fitting = 208.65 lbf
Hi = Insulator Height = 131.89 inch
Hf = Bus Cen. Height above Insulator = 5.91 inch
K1 = Overload Factor applied to wind force = 1
K2 = Overload Factor applied to short circuit force = 1
Therefore FIS = 559.95 lbf
Now
Effective weight of bus transmitted to bus support fitting FGB = LE.FG lbf
where,
LE = Effective Bus span length = 27.89 ft
FG = Total Bus Unit Weight = 5.13 lbf/ft
Therefore FGB = 142.99 lbf
Natural Frequency of the Insulator with effective weight of the conductor span : fi = (1/2S) [Ki g / (0.226FGI + FGB)]
1/2
where,
Ki = Insulator cantilever Spring Constant = 1 lbf/inch
g = gravitional constant = 386 inch/s2 FGI = Weight of the insulator = 641.54 lbf
FGB = Effective weight of bus transmitted to bus support fitting = 142.99 lbf
Therefore fi = 0.18 Hz
As fi < 50Hz => K2 = 1 (Refer Cl. No. 13.2 of IEEE: 605)
Cantilever Load on the Support Insulator FIS (Eqp) = 254.22 Kgf
(in the direction of the Equipment Connection)
=> Reqiured cantilever Strength of the Supporting Insulator = 249.28 daN
Gilgel Gibe II Hydroelectric Project