EXERCISE
REB500 - CONFIGURATION
► Configure the REB500 In- and Outputs according to
the following I/O list.
► Used the correct Database
► Check the Application accordingly
STATION
Exercise20
OBJECT/EQUIPMENT
BUSBAR- & STATION PROTECTION
SYSTEM REB500SYS
ENGINEERING DATE
ENGINEER
COMPANY
Total number of pages 9 (incl. this page)
Date: Signature:
Client
Date: Signature:
General datas
Nominal voltage of the protected station ... kV
Type of installation (double busbar, 1½ system...) ...
Air insulated (AIS) not applicable
Gas insulated (GIS) not applicable
Software version V.7.xx: Exercise20.MDB
... ...
Used drawings not applicable
(designation, No. and modification index) ...
... ... ...
Check of power supply
Type of battery grounding not applicable
(Negative grounded, floating, not applicable
symmetrically grounded at high impedance, …)
Measured voltages: not applicable
First battery: Second battery: not applicable
Plus to minus ... V Plus to minus ... V Plus to ground ... V Plus to ground ... V Ground to minus ... V Ground to minus ... V
Check of auxiliary contacts
Isolator fully “OPEN” Isolator fully "CLOSED"
Auxiliary contact must be closed Auxiliary contact ideally closed Auxiliary contact must be open “Closed” auxiliary
contact (N/O)
Isolation gap
“Open” auxiliary contact (N/C)
Condition of isolator switching sequence fulfilled: Yes No not applicable
Remarks: ... ... ... ... ... ... ...
Date: Signature:
Client
Date: Signature:
Central unit Slot no.
Binary inputs Function/Remarks Checked
OC01 OC02 OC03 OC04 OC05 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 OC06 OC07 OC08 OC09 OC10 OC11 OC12
OC01 External Reset
OC02 Accept bus image alarm
OC03 Block Output Relays
OC04 Block BBP
OC05 Block BFP
OC06 Block EFP
OC07 ... OC08 ... OC09 ... OC10 ... OC11 ... OC12 ...
Tripping and signalling contacts
CR01 1 2 3 4 5 7 6 CR05 8 9 10 CR06 11 12 13 CR07 14 15 16 17 18 CR02 CR03 CR08 CR09 CR04
CR01 Differential current alarm
CR02 Isolator alarm
CR03 Switching inhibited
CR04 Blocked (functions and / outputs)
CR05 General alarm (sum of all possible remaining alarms)
CR06 In service
CR07 EFP trip
CR08 BFP trip
Date: Signature:
Client
Date: Signature: Feeder OHL 10
Binary inputs Function/Remarks Checked
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 OC01 OC02 OC03 OC04 OC05 OC06 OC07 OC08 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 OC10 OC11 OC12 OC13 OC14 OC15 OC16 A B 16 17 18 OC09 OC17 OC18 OC19 OC20 16 17 18 OC01 QB1 OPEN OC02 QB1 CLOSED OC03 QB2 OPEN OC04 QB2 CLOSED
OC05 not used
OC06 not used
OC07 QA1 OPEN
OC08 QA1 CLOSED
OC09 QA1 CLOSING COMMAND
OC10 START BFP PHASE R
OC11 START BFP PHASE S
OC12 START BFP PHASE T
OC13 not used
OC14 not used
OC15 not used
OC16 not used
OC17 not used
OC18 RESET
OC19 START BFP PHASE RST (1)
Date: Signature:
Client
Date: Signature: Feeder OHL 10
Tripping and signalling contacts
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 CR01 CR02 CR03 CR04 CR05 CR06 CR07 CR08 CR09 CR10 CR11 CR12 CR13 CR14 CR15 CR16 C D CR01 not used CR02 not used CR03 not used
CR04 BFP REMOTE TRIP / EFP REMOTE TRIP (1)
CR05 BFP REMOTE TRIP / EFP REMOTE TRIP (2)
CR06 BBP / BFP TRIP CB PHASE R
CR07 BBP / BFP TRIP CB PHASE S
CR08 not used
CR09 not used
CR10 not used
CR11 BBP / BFP TRIP SIGNAL PHASE R
CR12 BBP / BFP TRIP SIGNAL PHASE S
CR13 BBP / BFP TRIP SIGNAL PHASE T
CR14 not used
CR15 not used
Date: Signature:
Client
Date: Signature: Feeder TRAFO 2
Binary inputs Function/Remarks Checked
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 OC01 OC02 OC03 OC04 OC05 OC06 OC07 OC08 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 OC10 OC11 OC12 OC13 OC14 OC15 OC16 A B 16 17 18 OC09 OC17 OC18 OC19 OC20 16 17 18 OC01 QB1 OPEN OC02 QB1 CLOSED OC03 QB2 OPEN OC04 QB2 CLOSED
OC05 not used
OC06 not used
OC07 QA1 OPEN
OC08 QA1 CLOSED
OC09 QA1 CLOSING COMMAND
OC10 START BFP PHASE R
OC11 START BFP PHASE S
OC12 START BFP PHASE T
OC13 not used
OC14 not used
OC15 not used
OC16 not used
OC17 not used
OC18 RESET
OC19 START BFP PHASE RST (1)
Date: Signature:
Client
Date: Signature: Feeder TRAFO 2
Tripping and signalling contacts
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 CR01 CR02 CR03 CR04 CR05 CR06 CR07 CR08 CR09 CR10 CR11 CR12 CR13 CR14 CR15 CR16 C D CR01 not used CR02 not used CR03 not used
CR04 EFP REMOTE TRIP (1)
CR05 EFP REMOTE TRIP (2)
CR06 BBP / BFP TRIP CB PHASE R
CR07 BBP / BFP TRIP CB PHASE S
CR08 not used
CR09 not used
CR10 not used
CR11 BBP / BFP TRIP SIGNAL PHASE R
CR12 BBP / BFP TRIP SIGNAL PHASE S
CR13 BBP / BFP TRIP SIGNAL PHASE T
CR14 not used
CR15 not used
CR16 BBP / BFP TRIP CB PHASE T
Date: Signature:
Client
Date: Signature: Feeder COUPLER
Binary inputs Function/Remarks Checked
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 OC01 OC02 OC03 OC04 OC05 OC06 OC07 OC08 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 OC10 OC11 OC12 OC13 OC14 OC15 OC16 A B 16 17 18 OC09 OC17 OC18 OC19 OC20 16 17 18 OC01 QB1 OPEN OC02 QB1 CLOSED OC03 QB2 OPEN OC04 QB2 CLOSED
OC05 not used
OC06 not used
OC07 QA1 OPEN
OC08 QA1 CLOSED
OC09 QA1 CLOSING COMMAND
OC10 QB10 OPEN OC11 QB10 CLOSED OC12 QB20 OPEN OC13 QB20 CLOSED OC14 QB11 OPEN OC15 QB11 CLOSED OC16 QB21 OPEN OC17 QB21 CLOSED OC18 RESET
OC19 START BFP PHASE RST (1)
Date: Signature:
Client
Date: Signature: Feeder COUPLER
Tripping and signalling contacts
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 CR01 CR02 CR03 CR04 CR05 CR06 CR07 CR08 CR09 CR10 CR11 CR12 CR13 CR14 CR15 CR16 C D CR01 not used CR02 not used CR03 not used CR04 not used CR05 not used CR06 not used CR07 not used CR08 not used CR09 not used CR10 not used
CR11 BBP / BFP TRIP SIGNAL PHASE R
CR12 BBP / BFP TRIP SIGNAL PHASE S
CR13 BBP / BFP TRIP SIGNAL PHASE T
CR14 not used
CR15 not used