Versatile Access Power

and Integration Enclosures

Installation Guide

Includes Models:

Trove1

(2)

Overview:

Trove accommodates various combinations of access controllers and accessories from the industry’s leading manufacturers with or without Altronix power supplies and accessories for access systems.

Specifications:

• 19 Gauge grey enclosure with ample knockouts for convenient access.

Trove Model Identification:

Series (H” x W” x D”)Enclosure Size Backplane Model Power Supply 1 Power Supply 2 Power SupplyFeature Set

Trove 2 M 1 3 F 1 = 18” x 14.5” x 4.625” 2 = 27.25” x 21.75” x 6.5” AM = AMAG C / CV = CDVI KA = Keyscan M = Mercury SH = Software House V = HID/Vertx 1 = 4A 3 = 6A 5 = 10A/12VDC 7 = 10A/24VDC 1 = 4A 3 = 6A 5 = 10A/12VDC 7 = 10A/24VDC Blank = Not installed

Blank = ULXB F = eFlow

Backplane Model Identification:

Backplane

Model Manufacturer Dimensions (H x W x D) EnclosureTrove

TC1 CDVI 16.65” x 12.5” x 0.3125” (422.9mm x 321.3mm x 7.9mm) Trove1 TM1 Mercury TV1 HID/Vertx TAM2 AMAG 25.4” x 19.4” x 0.3125” (645.16mm x 492.76mm x 7.9mm) Trove2 TCV2 CDVI TKA2 Keyscan TM2 Mercury TSH2 Software House TV2 HID/Vertx

TMV2 Mercury/Vertx door backplane (603.25mm x 460.4mm x 7.9mm)23.75” x 18.125” x 0.3125”

Installation Instructions:

1. Remove backplane from enclosure. Do not discard hardware.

2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding.

Place the enclosure’s upper keyholes over the two/three upper screws; level and secure. Mark the position of the lower three holes. Remove the enclosure.

Drill the lower holes and install the two/three fasteners. Place the enclosure’s upper keyholes over the two/three upper screws. Install the two/three lower screws and make sure to tighten all screws.

3. Mount included UL Listed tamper switch

(Ademco model 112 or equivalent) in desired location, opposite from hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.

To activate alarm signal open the door of the enclosure. 4. Mount boards to backplane, refer to individual backplane installation instructions.

Edge of Enclosure to Access Control Panel

(3)

Power Supply Specifications:

Power Supply

Model # Identification Code Input

Output Battery Size for

30 min. Backup

12VDC 24VDC

AL400ULXB2 1 115VAC, 60Hz, 3.5A 4A 3A 4AH

AL600ULXB 3 115VAC, 60Hz, 3.5A 6A 7AH

AL1012ULXB 5 115VAC, 60Hz, 2.6A 10A ---- 12AH

AL1024ULXB2 7 115VAC, 60Hz, 4.2A ---- 10A 12AH

eFlow4NB 1F 115VAC, 60Hz, 3.5A 4A 3A 4AH

eFlow6NB 3F 115VAC, 60Hz, 3.5A 6A 7AH

eFlow102NB 5F 115VAC, 60Hz, 3.5A 10A ---- 12AH

eFlow104NB 7F 115VAC, 60Hz, 4.5A ---- 10A 12AH

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.

1. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] on a single or both power supply boards. Use 14 AWG or larger for all power connections.

Keep power-limited wiring separate from non power-limited wiring. Minimum 0.25” spacing must be provided.

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

2. Select desired DC output voltage by setting SW1 to the appropriate position on the

AL400ULXB2, AL600ULXB, eFlow4NB and eFlow6NB power supply (Figs. 2 and 2a, pg. 4). AL1012ULXB and eFlow102NB power supplies are factory set at 12VDC.

AL1024ULXB2 and eFlow104NB power supplies are factory set at 24VDC.

3. Measure the output voltage of the unit before connecting any devices to ensure proper operation. Improper or high voltage will damage these devices.

4. Connect devices or Altronix sub-assembly modules to be powered to the terminals marked [-- DC +].

eFlow Power Supply: For auxiliary device connection, this output will not be affected by

Low Power Disconnect or Fire Alarm Interface. Connect device to the terminals marked [+ AUX -- ].

5. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to the terminals marked [-- BAT + ]. Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of an appropriate rating.

6. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL supervisory relay outputs.

7. eFlow Power Supply:

To delay AC reporting for 2 hrs., set dip switch [AC Delay] to OFF position. To delay AC reporting for 1 min., set dip switch [AC Delay] to ON position.

Note: Must be set to ON position for Burglar Alarm Applications.

8. eFlow Power Supply:

To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position. To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position. 9. eFlow Power Supply:

Trigger terminals are end of a line resistor supervised (10k Ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown.

10. eFlow Power Supply:

(4)

Power Supply Board Output Voltage Settings:

Fig. 2 + DC --- SW1 OFF - 24V ON - 12V ON ON

OFF - 24V

ON - 12V

--- DC + OFF - 24V ON - 12V ON AL400ULXB2/AL600ULXB

(5)
(6)
(7)
(8)

Trove2 Enclosure Dimensions (H x W x D):

27.25” x 21.75” x 6.5” (692.15mm x 552.45mm x 165.1mm) G 1.25” (31.75mm) 1.25” (31.75mm) 6.25” (158.75mm) 6.25” (158.75mm) 6.75” (171.45mm) 8.25” (209.54mm) 8.00” (203.2mm) 1.5” (38.1mm) 1.25” (31.75mm) 0.85” (21.59mm) 0.85” (21.59mm) 1.00” (25.4mm) 2.00” (50.8mm) 1.25” (31.75mm) 2.00” (50.8mm) 2.00” (50.8mm) (133.35mm)5.25” (177.79mm)7.00” (133.35mm)5.25” 2.00” (50.8mm) 2.00” (50.8mm) 27.00” (685.8mm) 3.50” (88.9mm) 0.5625” (14.29mm) 2.415” (61.34mm) 0.685” (17.399mm) 1.77” (44.96mm) 3.50” (88.9mm) 21.50” (546.1mm) 19.80” (502.92mm) 5.25” (133.35mm) 5.25” (133.35mm) 0.885” (22.479mm) 1.125” (28.32mm) Knockouts

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. 140 58th Street, Brooklyn New York 11220 USA, 718-567-8181, fax: 718-567-9056

References

Related documents

Four basic themes emerged from the analysis; social and cyber arrangements within the Dublin Chemsex scene; poly drug use and experiences of drug dependence; drug and sexual

Comparative study of various bomber aircrafts The first step in the design of aircraft is to collect data of existing aircraft of similar purpose i.e., bomber.. This step

For each pair, the same context photograph that accompanied it in the first study phase was later re-presented together with the cue on both cued-recall tests (see Fig. The

Amino acid sequence identities (%) of eleven proteins of a novel pigeon rotavirus to representatives of other rotavirus species (A-H) belonging to the genus Rotavirus.. *A major

Until 2012, the School of Architecture and Planning’s Timber Technology seminar course at the University of Auckland had focused each semester on the construction of

Uji statistik independent t test menunjukkan tidak adanya perbedaan secara signifikan SDNN dan RMSSD pada kelompok kontrol dan intervensi, sehingga bekam kering tidak

○ If BP elevated, think primary aldosteronism, Cushing’s, renal artery stenosis, ○ If BP normal, think hypomagnesemia, severe hypoK, Bartter’s, NaHCO3,

Dark septate and arbuscular mycorhizal colonization of Artemisia tridentata, seeds were planted in soil which contained different inoculum according to the indicated treatments.