Data Center
CH1
>
powerful/
efficient
/reliable
solutions
Committed to ultimate reliability, DFT’s philosophy is to design, build, operate and manage highly dependable and environmentally efficient data centers. Our goal is to maximize Power Usage Effectiveness ("PUE") in all aspects of data center operations. Dynamic electrical distribution and flexible floor plans provide optimal solutions for our tenants. DFT commissions proven technologies, such as rotary UPS and evaporative chilled water systems, in configurations that maximize utilization of the data center design and infrastructure. Our engineering track record and expertise enable us to shorten the duration of construction and minimize costs which directly benefit our clients.
PHILOSOPHY
Located in the western suburbs of Chicago, CH1 is one of the Midwest’s most sophisticated and efficient data centers. The facility is constructed in two phases of 18.2 MW of Critical Load each. Clients are able to lease one or multiple dedicated computer rooms each with independent redundancy and security. The property has multiple major fiber carriers on site and benefits from some of the country’s most competitive power rates. Customers requiring substantial office space can utilize the adjacent and exclusive 32,000 square foot office building.
OVERVIEW
DFT is a leading owner, developer, operator and manager of wholesale data centers. Our highly advanced and secure facilities power, cool, and protect the computer servers of numerous enterprise and technology
companies. In conjunction with our operational expertise, we deliver uninterrupted service and ultimate reliability to our customers’ mission critical business applications.
ABOUT
DUPONT FABROS
TECHOLOGY
(DFT)
>
Data Center CH1
>
Data Center CH1: Specifications
PROPERTY
BUILDING DESCRIPTION
Location: Elk Grove Village, IL Acreage: 22.8
Building Size: 485,000 sq ft
Nearest Airport: O'Hare International Airport Utility Power: 34.5 kV
Parking: 400+ Number of Stories: 1 Loading Docks: 4 Dock Bays
CRITICAL POWER
DATA CENTER AREA DESCRIPTION
Total Megawatts: 36.4
Redundancy: N+2, Each Phase, plus additional Swing UPS which offers additional redundancy to either electrical system Raised Floor Area: 121,000 sq ft (Phase I), 109,666 sq ft (Phase II)
Number of Computer Rooms: 16 (Phase I), 15 (Phase II) Raised Floor Height: 42" under raised floor plenums Raised Floor to Ceiling Height: 15-20+ft
SECURITY
STAGING/TENANT OFFICE SP ACE
Building and Perimeter: Ballistic glass enclosed security check-in, front window areas and loading dock Security Guards: Staffed 24/7
Access Control: Electronic Security features with card key access and dual authentication with biometric readers CCTV: 24/7 surveillance of the interior/exterior of the facility
Office: 9 internal suites and 32,000 sf of adjacent office space Staging: 6 staging rooms (Phase I), 2 staging rooms (Phase II)
UPS SYSTEMS GENERA
TORS
HEAT REJECTION SYSTEMS (HV AC) ON SITE FUEL CAP
ACITY
FIRE PROTECTION STS/PDUS COMMUNICA
TIONS
Description: 32 Rotary power systems with 1,300 kW of critical output each Redundancy: N+2, Each Phase
Description: 32 diesel-powered engine generators with 2,250 kW capacity each Redundancy: N+2, Each Phase
Description: 16 centrifugal chillers with 1,150 Ton capacity each Redundancy: N+2, Each Phase
Chilled Water Storage: Two 500,000 gallon storage tanks for 24 minutes of continuous full load operation Storage Tanks: Four 50,000 gallon underground diesel storage tanks
Number of Hours: Nominal 55 Hours
Description: Conventional smoke detector and laser based incipient smoke detection systems and double interlocked
pre-action sprinkler system
STS Description: Dual input Static Transfer Switches (STSs) PDU Description: 300 kVA Power Distribution Units (PDUs)
POE: 4 separate network Points of Entry (POE) with diverse underground duct banks providing multiple entry points into
the facility
Conduits: Dedicated underground conduits to each computer room from multiple and diverse POEs Multiple Carriers: Available
Meet-Me-Room: Available
COMPUTER ROOM SPECIFICA TIONS
Phase 1: Critical Load: 18.2 MW
Rooms 1-3: Critical Load: 0.433 MW, Approx. Gross SF: 2,700 Rooms 4-13: Critical Load: 1.3 MW, Approx. Gross SF: 8,400 Rooms 14-16: Critical Load: 1.3 MW, Approx. Gross SF: 9,900 Phase 2: Critical Load: 18.2 MW
Rooms 18A-18B: Critical Load: 0.650 MW, Approx. Gross SF: 5,000 Rooms 17, 19-26: Critical Load: 1.3 MW, Approx. Gross SF: 7,300-8,900
Electrical/Mechanical Computer R
oom
Public Circulation
SP ACE ALL OCA TIONS Data/T elco Suppor t Administration/Office
D
at
a C
en
te
r C
H
1: Ma
p
PHASE 2 PHASE 1DIESEL ENGINE GENERATOR (TYP
.)
AREA
WA
Y
UPS UNIT (TYP
.) SWITCHBOARD (TYP .) AREA WA Y MECH. RM. STOR .
CENTRIFUGAL CHILLER (TYP
.) TR ANSFORMER POE MECH. RM. MECH. RM. MECH. RM. BR . RM. BR . RM. BR . RM. COMP UTER ROOMS 1-16 COMP UTER ROOMS 17-28 STOR . SNOW MEL T FP/PL RM. LOADING DOCK OFFICE 6 19 7 1 2 3 4 8 5 10 11 12 14 15 16 13 17 18A 19 20 21 22 18B 23 24 25 26 28A 28B 27A 27B MECH RM. LOB. LOB. BR . RM. W. M. W. M. W. M. OFF . ELEV . OFF. OFF . MECH RM. OFF . OFF . SECOND FL OOR FIRST FL OOR MMR X X ELEV . OFFICE POE CORRIDOR SEC EQ CORRIDOR MECH RM. CORRIDOR POE AREA WA Y AREA WA Y STOR . POE TELE/COMM MECH RM. MECH. RM. MMR OFF . CON.