Building Inspection Report
3645 Sample RD. Riecken Home Inspections, IN 47730
Inspection Date:
04-19-2013
Prepared For:
Home Buyer
Prepared By:
Riecken Home
Inspections
345 N.
2nd St
Elberfeld IN,
47613
812.760.2960
812.774.0804
[email protected]
Report Number:
04192013
Inspector:
Brandon L. Riecken
This confidential report is prepared exclusively for the Home Buyer
Report Overview
THE HOUSE IN PERSPECTIVE
This is a well built home that has been lacking maintenance somewhat. Apart from the short term need to deal with this lacking maintenance, the improvements that are recommended in this report are not considered unusual for a home of this age and location. Please remember that there is no such thing as a perfect home.
CONVENTIONS USED IN THIS REPORT
For your convenience, the following conventions have been used in this report.
Major Concern: a system or component which is considered significantly deficient or is unsafe. Significant deficiencies need to be corrected and, except for some safety items, are likely to involve significant expense. Safety Issue: denotes a condition that is unsafe and in need of prompt attention.
Repair:denotes a system or component which is missing or which needs corrective action to assure proper and reliable function.
Improve: denotes improvements which are recommended but not required.
Monitor: denotes a system or component needing further investigation and/or monitoring in order to determine if repairs are necessary.
Deferred Cost: denotes items that have reached or are reaching their normal life expectancy or show indications that they may require repair or replacement anytime during the next five (5) years.
Please note that those observations listed under “Discretionary Improvements” are not essential repairs, but represent logical long term improvements.
For the purpose of this report, it is assumed that the house faces west.
IMPROVEMENT RECOMMENDATION HIGHLIGHTS / SUMMARY
The following is a synopsis of the potentially significant improvements that should be budgeted for over the short term. Other significant improvements, outside the scope of this inspection, may also be necessary. Please refer to the body of this report for further details on these and other recommendations.
SAFETY ISSUES Outlets
Safety Issue: The ground fault circuit interrupter (GFCI) outlet did not respond correctly to testing during the inspection. This receptacle should be replaced. (Just right of electric panel in detached garage)
REPAIR ITEMS Chimneys
Repair: The cap of the masonry chimney should have a preservative applied to it. (Both Chimneys)
Gutters & Downspouts
Repair: The gutters require cleaning to avoid spilling roof runoff around the building – a potential source of water entry or water damage. (Around Home)
Porch
• Repair: The porch columns show evidence of rotting. Recomend Repiar of rotten areas or replacement. (Bases of columns on Front Porch)
Landscaping
Repair: Vines growing on exterior walls should be kept trimmed away from siding, window trims, and the eaves to reduce risk of insect and water damage. (NE corner of home)
This confidential report is prepared exclusively for the Home Buyer
Wall / Ceiling Finishes
Repair: Water damage was noted. (Top of stairs coming from garage. 48% moisture)
Windows
• Repair: Window has rotten areas and should be repaired or replaced. (Second floor front windows both bedrooms) Repair: Window has lost its seal and should be repaired or replaced. (Over master bed)
Stairways
Repair: Loose stairway handrails should be better secured. (Main stair rail)
Crawl Space
Repair: All wood debris and/or trash should be removed from the crawl space. Organic debris around a property increases risk of insect or rot damage.
Repair: All potential vermin entry points to the crawl space should be sealed to reduce risk of pest activity or damage. (NE corner hole)
Repair: There is evidence of vermin activity in the crawl space. A pest control specialist should be consulted for treatment and control advice. (Termite Tubes, Mice Feces)
Repair: Damaged ductwork in the crawl space should be repaired. Improper duct work increases heating/cooling costs and can also cause building damage. (Insulation has fallen off main trunk in crawl)
Repair: Standing water was observed in the crawl space. Wet crawl spaces risk building damage from rot and insects and can cause interior mold or mildew. Roof and lot drainage repairs or improvements should be addressed as a first step to controlling water in the crawl space (see “Exterior”). This condition should then be monitored to determine if
additional, potentially costly measures are necessary. (North end of home)
Roof
Repair: Substantial evidence of roof leaks was observed. Please refer to the Roofing section of the report for
recommendations. (Three valleys on the SE corner of home show evidence of cracked shingles and water stain and wood rot on decking in attic.)
Flashings
Repair: The flashing is old and should be replaced to avoid leaks. (Boot is missing rubber section to keep water tight on east side of roof)
Main Panel
Repair: Circuits within the main distribution panel that are doubled up (referred to as “double taps”) should be separated. Each circuit should be served by a separate fuse or breaker. (GFCI breaker in panel)
Outlets
Repair: An outlet is loose. It should be replaced. (Outlet off bathroom on 2nd floor in hallway.)
Switches
Repair: The inoperative light switch should be repaired. (Couldn’t find what two switches in closet with key rack operated.)
Lights
Repair: The light is inoperative. If the bulbs are not blown, the circuit should be repaired. (A few bulbs around home)
Furnace
Repair: The heating system requires service. This should be a regular maintenance item to assure safe, reliable heat. (Central Air Unit off master bedroom shows sign of condensation problems. The wood below that unit is wet and possible fungi growing in crawlspace)
Gas Piping
Repair, Safety Issue: A gas leak was detected. This is a serious safety concern.(On/Off valve to gas fireplace in living Rm. This pipe does not leak if shut off but when turned on the valve catches fire Shown in picture.)
Supply Plumbing
Improve, Repair: The water piping lacks adequate support, recommend a qualified contractor for further evaluation. (Several clips are breaking in crawl space that supports water pipes. Recommend replacing clips)
This confidential report is prepared exclusively for the Home Buyer bath)
• Repair: The toilet tank mechanism is leaking water around the seal and ideally should be replaced (Master Bathroom) Repair: The faucet drain mechanism is leaking. (2nd floor north bathroom sink)
Doors
Repair: Doors should be trimmed or adjusted as necessary to work properly. (Door knob latch needs adjusted to close properly in laundry Rm.)
Waste / Vent
Repair: The waste piping does not have sufficient slope for proper drainage. (Kitchen sink off garbage disposal)
Central Air Conditioning
Repair: The outdoor unit of the air conditioning system requires cleaning. (Leaved inside units)
Attic / Roof
Repair: Exhaust vent pipes from the bathroom(s) should be vented to the building exterior. (All of them)
Crawl Space
• Repair: Vents at or bellow ground level should have a well dug out infront of it filled with gravel. (East side of home just around the corner of AC units.)
Supply Plumbing
Repair: A supply valve handle is missing to main shut off. (Next to water heater)
IMPROVEMENT ITEMS Crawl Space
Improve: The moisture (vapor) barrier in the crawl space floor should be adjusted to cover all areas of exposed soil.
ITEMS TO MONITOR Exterior Walls Porch
Monitor: The porch has settled relative to the house proper. This is a common condition that should be monitored.
Driveway
Monitor: The soil below the driveway has settled and/or heaved. Persisting movement may result in the need for resurfacing. (Looks to be associated with tree in driveway.)
Wall / Ceiling Finishes
Monitor: Damage to the interior finish was observed. (Nail pops, minor cracks)
Foundation
Monitor: Minor settlement cracks were observed in the foundation walls. This implies that some structural movement of the building has occurred. Cracks of this type should be watched for any sign of additional movement. In the absence of any sign of ongoing movement, repair should not be necessary. (Front porch, next to chimney at front of home)
Foundation
• Monitor: There does not appear to be a footer under foundation wall. (Footer was poured but seemed to have gotten off track. Just a small corner of concrete block over hanging footer.
Roof
Monitor: Evidence of condensation was observed on the underside of the roof sheathing. This can weaken the sheathing and ultimately necessitate replacement. Improved roof and attic ventilation (see Insulation and Ventilation) can reduce condensation. During re-roofing, the sheathing should be investigated to determine if replacement is needed. (Three valleys on SE side of roof)
This confidential report is prepared exclusively for the Home Buyer
Wood Boring Insects
Monitor: Evidence of wood destroying insect activity was observed and there is risk of additional hidden damage. If the property has not already been treated, a licensed pest control specialist should be engaged. Wood destroying insect can do a substantial amount of damage to the wood structural components of a home.
DEFERRED COST ITEMS
Deferred Cost Item: The roofing is near the end of its life. Minor repairs might be possible to extend the roof life and to defer leaks. Damaged or missing roofing material should be repaired. All roof penetrations should be examined and sealed as necessary. Expect to replace the roof soon. Recommend roofing contractor for further evaluation.
THE SCOPE OF THE INSPECTION
All components designated for inspection in the ASHI Standards of Practice are inspected, except as may be noted in the “Limitations of Inspection” sections within this report.
It is the goal of the inspection to put a home buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered a guarantee or warranty of any kind.
This inspection is visual only. A representative sample of building components are viewed in areas that are accessible at the time of the inspection. No destructive testing or dismantling of building components is performed.
Please refer to the pre-inspection contract for a full explanation of the scope of the inspection.
WEATHER CONDITIONS
Wet weather conditions prevailed at the time of the inspection. The estimated outside temperature was 45 degrees F.
RECENT WEATHER CONDITIONS
This confidential report is prepared exclusively for the Home Buyer
Structure
DESCRIPTION OF STRUCTURE
Foundation: Concrete Block Brick
Columns: Concrete Block
Floor Structure: Wood Joist
Wall Structure: Wood Frame
Ceiling Structure: Joist
Roof Structure: Rafters •Oriented Strand Board (OSB)
STRUCTURE OBSERVATIONS
Positive Attributes
The construction of the home is good quality. The materials and workmanship, where visible, are good. The visible joist spans appear to be within typical construction practices. The inspection did not discover evidence of substantial structural movement.
RECOMMENDATIONS / OBSERVATIONS Foundation
Monitor: Minor settlement cracks were observed in the foundation walls. This implies that some structural movement of the building has occurred. Cracks of this type should be watched for any sign of additional movement. In the absence of any sign of ongoing movement, repair should not be necessary.
• Repair: There does not appear to be a footer under foundation wall. Recommend repair.
Crawl Space
Repair: All wood debris and/or trash should be removed from the crawl space. Organic debris around a property increases risk of insect or rot damage.
Repair: All potential vermin entry points to the crawl space should be sealed to reduce risk of pest activity or damage. Repair: There is evidence of vermin activity in the crawl space. A pest control specialist should be consulted for
treatment and control advice.
Repair: Damaged ductwork in the crawl space should be repaired. Improper duct work increases heating/cooling costs and can also cause building damage.
Repair: Standing water was observed in the crawl space. Wet crawl spaces risk building damage from rot and insects and can cause interior mold or mildew. Roof and lot drainage repairs or improvements should be addressed as a first step to controlling water in the crawl space (see “Exterior”). This condition should then be monitored to determine if
additional, potentially costly measures are necessary.
Roof
Monitor: Evidence of condensation was observed on the underside of the roof sheathing. This can weaken the sheathing and ultimately necessitate replacement. Improved roof and attic ventilation (see Insulation and Ventilation) can reduce condensation. During re-roofing, the sheathing should be investigated to determine if replacement is needed.
Repair: Substantial evidence of roof leaks were observed. Please refer to the Roofing section of the report for recommendations.
Wood Boring Insects
Monitor: Evidence of wood destroying insect activity was observed and there is risk of additional hidden damage. If the property has not already been treated, a licensed pest control specialist should be engaged. Wood destroying insect can do a substantial amount of damage to the wood structural components of a home.
LIMITATIONS OF STRUCTURE INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
This confidential report is prepared exclusively for the Home Buyer Structural components concealed behind finished surfaces could not be inspected.
Only a representative sampling of visible structural components were inspected. Furniture and/or storage restricted access to some structural components.
Engineering or architectural services such as calculation of structural capacities, adequacy, or integrity are not part of a home inspection.
Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.
Standing water in crawl
Termite tubes in crawl Plastic that needs spread
out over dirt.
Insulation that has fallen off ducting.
Corner that is not over footer.
Hole that should be sealed in crawl space.
This confidential report is prepared exclusively for the Home Buyer
Roofing
DESCRIPTION OF ROOFING
Roof Covering: Asphalt Shingle
Roof Flashings: Metal
Chimneys: Masonry
Roof Drainage System: Aluminum Downspouts discharge below grade
Method of Inspection: Walked on roof Viewed from ladder at eave
ROOFING OBSERVATIONS
Positive Attributes
Better than average quality materials have been employed as roof coverings. The steep pitch of the roof should result in a longer than normal life expectancy for roof coverings. Roof flashing details appear to be in good order.
General Comments
In all, the roof coverings show evidence of normal wear and tear for a home of this age. The roof coverings are old and are at or near the end of its useful life.
RECOMMENDATIONS / OBSERVATIONS
Deferred Cost Item: The roofing is near the end of its life. Minor repairs might be possible to extend the roof life and to defer leaks. Damaged or missing roofing material should be repaired. All roof penetrations should be examined and sealed as necessary. Expect to replace the roof soon.
Chimneys
Repair: The cap of the masonry chimney should have a preservative applied to it.
Gutters & Downspouts
Repair: The gutters require cleaning to avoid spilling roof runoff around the building – a potential source of water entry or water damage.
Flashings
Repair: The flashing is old and should be replaced to avoid leaks.
LIMITATIONS OF ROOFING INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
Not all of the underside of the roof sheathing is inspected for evidence of leaks. Evidence of prior leaks may be disguised by interior finishes.
Estimates of remaining roof life are approximations only and do not preclude the possibility of leakage. Leakage can develop at any time and may depend on rain intensity, wind direction, ice build up, and other factors.
Antennae, chimney/flue interiors which are not readily accessible are not inspected and could require repair. Roof inspection may be limited by access, condition, weather, or other safety concerns.
This confidential report is prepared exclusively for the Home Buyer
Hole in boot allowing water in.
Chimney caps need to be resealed. Some minor spalling on chimney
This confidential report is prepared exclusively for the Home Buyer
Painting needed Moisture showing through on decking of roof
This confidential report is prepared exclusively for the Home Buyer
Exterior
DESCRIPTION OF EXTERIOR
Wall Covering: Metal Siding
Eaves, Soffits, And Fascias: Aluminum
Exterior Doors: Metal
Window/Door Frames and Trim: Wood Metal-Covered
Entry Driveways: Asphalt Concrete
Entry Walkways And Patios: Concrete Brick
Porches, Decks, Steps, Railings: Brick
Overhead Garage Door(s): Steel Automatic Opener Installed
Surface Drainage: Level Grade
EXTERIOR OBSERVATIONS
Positive Attributes
The aluminum soffits and fascia are a low-maintenance feature of the exterior of the home. There is no significant wood/soil contact around the perimeter of the house, thereby reducing the risk of insect infestation or rot. The auto reverse mechanism on the overhead garage door responded properly to testing. This safety feature should be tested regularly as a door that doesn’t reverse can injure someone or fall from the ceiling. Refer to the owner’s manual or contact the manufacturer for more information. The garage appears to be fully insulated. The garage completely finished. Freeze resistant hose bibs (exterior faucets) have been installed.
General Comments
The exterior of the home shows normal wear and tear for a home of this age.
RECOMMENDATIONS / OBSERVATIONS Exterior Walls
Porch
Monitor: The porch has settled relative to the house proper. This is a common condition that should be monitored. If the porch supports have not already been repaired, replacement may be needed.
• Repair: The porch columns show evidence of rotting. Recommend repair of rotten areas or replacement.
Driveway
Monitor: The soil below the driveway has settled and/or heaved. Persisting movement may result in the need for resurfacing.
Landscaping
Repair: Vines growing on exterior walls should be kept trimmed away from siding, window trims, and the eaves to reduce risk of insect and water damage.
Discretionary Improvements
• It is recommended that there be 4 to 6 inches of clearance from the siding to finish grade. This will enable owner to check for visible sign of vermin and or insects.
LIMITATIONS OF EXTERIOR INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
A representative sample of exterior components was inspected rather than every occurrence of components.
The inspection does not include an assessment of geological, geotechnical, or hydrological conditions, or environmental hazards.
This confidential report is prepared exclusively for the Home Buyer documented in this report.
Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.
Siding cracked on detached garage Vines on home
This confidential report is prepared exclusively for the Home Buyer
Electrical
DESCRIPTION OF ELECTRICAL
Size of Electrical Service: 120/240 Volt Second Service - Service Size: 200 Amps
Service Drop: Underground
Service Entrance Conductors: Aluminum
Service Equipment &
Main Disconnects: Main Service Rating 200 Amps Located: East side of garage
Service Grounding: Copper
Service Panel &
Overcurrent Protection: Panel Rating: 200 Amp Breakers Located: Main Garage
Sub-Panel(s): Panel Rating: 30 Amp Breakers Located: Detached Garage
Distribution Wiring: Copper
Wiring Method: Non-Metallic Cable "Romex"
Switches & Receptacles: Grounded
Ground Fault Circuit Interrupters: Bathroom(s) Exterior Garage Kitchen
Smoke Detectors: Present
ELECTRICAL OBSERVATIONS
Positive Attributes
The size of the electrical service is sufficient for typical single family needs. Generally speaking, the electrical system is in good order. The distribution of electricity within the home is good. All 3-prong outlets that were tested were appropriately grounded.
General Comments
Inspection of the electrical system revealed the need for typical, minor repairs. Although these are not costly to repair, they should be high priority for safety reasons. Unsafe electrical conditions represent a shock hazard. A licensed electrician should be consulted to undertake the repairs recommended below.
RECOMMENDATIONS / OBSERVATIONS Main Panel
Repair: Circuits within the main distribution panel that are doubled up (referred to as “double taps”) should be
separated. Each circuit should be served by a separate fuse or breaker.
Outlets
Repair: An outlet is loose. It should be replaced.
Safety Issue: The ground fault circuit interrupter (GFCI) outlet did not respond correctly to testing during the inspection. This receptacle should be replaced.
Switches
Repair: The inoperative light switch should be repaired.
Lights
Repair: The light is inoperative. If the bulbs are not blown, the circuit should be repaired.
LIMITATIONS OF ELECTRICAL INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
Electrical components concealed behind finished surfaces are not inspected. Only a representative sampling of outlets and light fixtures were tested.
This confidential report is prepared exclusively for the Home Buyer distribution system.
Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.
Switches unknown GFCI does not trip
Loose receptacle
This confidential report is prepared exclusively for the Home Buyer
Heating
DESCRIPTION OF HEATING
Energy Source: Gas
Heating System Type: Forced Air Furnace 2nd Floor over garage Manufacturer: Carrier 6-1991
Serial Number: 2791A02797 •Modal Number: 58SXA040-GG •Filter Size: 16x25x1
Heating System Type: Forced Air Furnace 2nd floor over kitchen Manufacturer: Carrier 10-2010
Serial Number: 4110A00659 •Modal Number: 58MEC060-12 •Filter Size: 16x25x1
Heating System Type: Forced Air Furnace Main floor
Manufacturer: Carrier 9-1991 Serial Number: 3691A06682 •Modal Number: 58DXA080-JG
Vents, Flues, Chimneys: Plastic
Heat Distribution Methods: Ductwork
HEATING OBSERVATIONS
Positive Attributes
This is a high efficiency heating system. Adequate heating capacity is provided by the system. Heat distribution within the home is adequate. The heating system is controlled by a “set back” thermostat. This type of thermostat, if set up correctly, helps reduce heating costs.
General Comments
The heating system shows no visible evidence of major defects.
RECOMMENDATIONS / OBSERVATIONS Furnace
Repair: The heating system requires service. This should be a regular maintenance item to assure safe, reliable heat.
LIMITATIONS OF HEATING INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
The adequacy of heat supply or distribution balance is not inspected.
The interior of flues or chimneys which are not readily accessible are not inspected.
The furnace heat exchanger, humidifier, or dehumidifier, and electronic air filters are not inspected. Solar space heating equipment/systems are not inspected.
This confidential report is prepared exclusively for the Home Buyer
Moisture under central unit off master bedroom
This confidential report is prepared exclusively for the Home Buyer
Cooling / Heat Pumps
DESCRIPTION OF COOLING / HEAT PUMPS
Energy Source: Electricity
Central System Type: Air Cooled Central Air Conditioning
Manufacturer: Carrier 2-2010 Serial Number: 0810E20063 •Modal Number: 24APA524A310
Central System Type: Air Cooled Central Air Conditioning
Manufacturer: Carrier 9-1991 Serial Number: 3791E14681 •Modal Number: 38TR036300
Central System Type: Air Cooled Central Air Conditioning
Manufacturer: Carrier 9-1991 Serial Number: 2491E15899 •Modal Number: 38TKB018300
Through-Wall Equipment: Present at SE side of home
COOLING / HEAT PUMPS OBSERVATIONS
RECOMMENDATIONS / OBSERVATIONS Central Air Conditioning
Repair: The outdoor unit of the air conditioning system requires cleaning.
LIMITATIONS OF COOLING / HEAT PUMPS INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
Window mounted air conditioning units are not inspected.
The cooling supply adequacy or distribution balance are not inspected.
The air conditioning system could not be tested as the outdoor temperature was at or below 65 degrees F. Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.
This confidential report is prepared exclusively for the Home Buyer
Insulation / Ventilation
DESCRIPTION OF INSULATION / VENTILATION
Attic Insulation: R30 Fiberglass in Main Attic
Exterior Wall Insulation: R12 Fiberglass in Original Walls
Crawl Space Insulation: R10 Exposed Polystyrene on walls
Vapor Retarders: Plastic
Roof Ventilation: Ridge Vents Gable Vents Soffit Vents
Crawl Space Ventilation: Exterior Wall Vents
Exhaust Fan/vent Locations: Bathroom Kitchen Dryer
INSULATION / VENTILATION OBSERVATIONS
Positive Attributes
Insulation levels are typical for a home of this age and construction.
RECOMMENDATIONS / ENERGY SAVING SUGGESTIONS Attic / Roof
Repair: Exhaust vent pipes from the bathroom(s) should be vented to the building exterior.
Crawl Space
• Repair: Vents at or bellow ground level should have a well dug out in front of it filled with gravel.
Improve: The moisture (vapor) barrier in the crawl space floor should be adjusted to cover all areas of exposed soil.
LIMITATIONS OF INSULATION / VENTILATION INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
Insulation/ventilation type and levels in concealed areas are not inspected. Insulation and vapor barriers are not disturbed and no destructive tests (such as cutting openings in walls to look for insulation) are performed.
Potentially hazardous materials such as Asbestos and Urea Formaldehyde Foam Insulation (UFFI) cannot be positively identified without a detailed inspection and laboratory analysis. This is beyond the scope of the inspection.
An analysis of indoor air quality is not part of our inspection unless explicitly contracted-for and discussed in this or a separate report.
Any estimates of insulation R values or depths are rough average values.
Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.
Bathroom vents need to discharge to the exterior.
This confidential report is prepared exclusively for the Home Buyer
Plumbing
DESCRIPTION OF PLUMBING
Water Supply Source: Public Water Supply
Service Pipe to House: Plastic
Main Water Valve Location: Beside Water Heater
Interior Supply Piping: Copper
Waste System: Public Sewer System
Drain, Waste, & Vent Piping: Plastic
Water Heater: Gas Approximate Capacity (in gallons): 50
Manufacturer: Whirlpool 7-2011 Serial Number: 1128T471530 •Modal Number: N50T61-403
Fuel Shut-Off Valves: Natural Gas Main Valve at meter
PLUMBING OBSERVATIONS
Positive Attributes
The piping system within the home, for both supply and waste, is a good quality system. The water pressure supplied to the fixtures is above average. Only a slight drop in flow was experienced when two fixtures were operated simultaneously. The water heater is a relatively new unit. As the typical life expectancy of water heaters is 7 to 12 years, this unit should have several years of remaining life.
General Comments
The plumbing system requires some typical minor improvements.
RECOMMENDATIONS / OBSERVATIONS Gas Piping
Repair: A gas leak was detected. This is a serious safety concern.
Supply Plumbing
Repair: The Water piping lacks adequate support, recommend a qualified contractor for further evaluation. Repair: A supply valve handle is missing.
Fixtures
• Repair: The sink drain does not work properly recommend fix or replace.
• Repair: The toilet tank mechanism is leaking water around the seal and ideally should be replaced Repair: The faucet drain mechanism is leaking.
Waste / Vent
Repair: The waste piping does not have sufficient slope for proper drainage.
LIMITATIONS OF PLUMBING INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions:
Portions of the plumbing system concealed by finishes and/or storage (below sinks, etc.), below the structure, or beneath the ground surface are not inspected.
Water quantity and water quality are not tested unless explicitly contracted-for and discussed in this or a separate report. Clothes washing machine connections are not inspected.
Interiors of flues or chimneys which are not readily accessible are not inspected.
Water conditioning systems, solar water heaters, fire and lawn sprinkler systems, and private waste disposal systems are not inspected unless explicitly contracted-for and discussed in this or a separate report.
This confidential report is prepared exclusively for the Home Buyer
toilet tank mechanism is leaking waste piping does not have sufficient slope
The sink drain does not work properly recommend fix or replace. faucet drain mechanism is leaking
Valve is on fire. Water piping lacks
This confidential report is prepared exclusively for the Home Buyer
Interior
DESCRIPTION OF INTERIOR
Wall And Ceiling Materials: Drywall
Floor Surfaces: Carpet Tile Wood
Doors: Wood-Hollow Core
Window Type(s) & Glazing: Casement Double/Single Hung
INTERIOR OBSERVATIONS
General Condition of Interior Finishes
On the whole, the interior finishes of the home are in average condition. Typical flaws were observed in some areas.
General Condition of Windows and Doors
The windows have been lacking maintenance.
General Condition of Floors
The floors of the home are relatively level and walls are relatively plumb.
RECOMMENDATIONS / OBSERVATIONS Wall / Ceiling Finishes
Monitor, Repair: Water damage was noted.
Monitor: Damage to the interior finish was observed.
Windows
• Repair: Window has rotten areas and should be repaired or replaced. Repair: Window has lost its seal and should be repaired or replaced.
Stairways
Repair: Loose stairway handrails should be better secured.
Doors
Repair: Doors should be trimmed or adjusted as necessary to work properly.
Discretionary Improvements
•It would be wise to replace all the batteries in the smoke detectors upon moving in the home.
LIMITATIONS OF INTERIOR INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions
Furniture, storage, appliances and/or wall hangings are not moved to permit inspection and may block defects. Carpeting, window treatments, central vacuum systems, household appliances, recreational facilities, paint, wallpaper,
and other finish treatments are not inspected.
This confidential report is prepared exclusively for the Home Buyer
Latch needs adjusted.
Windows show sign of rot and should be repaired. Insect damage to trim over
garage door. Seal Popped on this window. Dog scratching on windows
Water damage in this area.
This confidential report is prepared exclusively for the Home Buyer
Appliances
DESCRIPTION OF APPLIANCES
Appliances Tested: Built-in Electric Oven Gas Cooktop Dishwasher Refrigerator
Laundry Facility: 240 Volt Circuit for Dryer Dryer Vented to Building Exterior 120 Volt Circuit for Washer Hot and Cold Water Supply for Washer Waste Standpipe for Washer
Other Components Tested: Cooktop Exhaust Vent/Fan
APPLIANCES OBSERVATIONS
Positive Attributes
The appliances are to be in generally good condition. All appliances that were tested responded satisfactorily. The kitchen and laundry facilities are well organized. The fixtures employed in the kitchen are high quality. The appliances that have been installed in the kitchen are good quality.
RECOMMENDATIONS / OBSERVATIONS
None
LIMITATIONS OF APPLIANCES INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions
Thermostats, timers and other specialized features and controls are not tested.
The temperature calibration, functionality of timers, effectiveness, efficiency and overall performance of appliances is outside the scope of this inspection.
This confidential report is prepared exclusively for the Home Buyer
Fireplaces / Wood Stoves
DESCRIPTION OF FIREPLACES / WOOD STOVES
Fireplaces: Masonry Firebox Gas Fireplace Insert
Vents, Flues, Chimneys: Outside Combustion Air Provided Masonry Chimney-Lined
FIREPLACES / WOOD STOVES OBSERVATIONS
General Comments
On the whole, the fireplace and its components are in above average condition.
RECOMMENDATIONS / OBSERVATIONS
See Plumbing Section for repair item.
LIMITATIONS OF FIREPLACES / WOOD STOVES INSPECTION
As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions
The interiors of flues or chimneys are not inspected.
Firescreens, fireplace doors, appliance gaskets and seals, automatic fuel feed devices, mantles and fireplace surrounds, combustion make-up air devices, and heat distribution assists (gravity or fan-assisted) are not inspected.
The inspection does not involve igniting or extinguishing fires nor the determination of draft. Fireplace inserts, stoves, or firebox contents are not moved.