S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
FRONT MOUNTED EQUIPMENTS
GR1 Generator Differential Protn (87G) CT Sec: 5A, PT Sec:110V AC (PH-PH) SIEMENS 3 7UM62 1 0 0 0 0 1
Gen. B/U Impedence Protn - Stage-1(21G1) Aux. Supply : 220V DC
Gen. B/U Impedence Protn - Stage-2(21G1) 15B/I, 20B/O + 1 LIVE STATUS CONTACT Gen. Under Frequency Stage -1(81UF) Case Size : 1/1 19", IEC61850 PROTOCOL Gen. Under Frequency Stage -2(81UF) Time Stage-1&2 MLFB : 7UM6225-6EB92-3CB0-LOS Gen. Over Frequency Protn. (81OF)
Reverse Power Relay(32G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Time Stage-1 Reverse Power Relay(32G) +Time Stage-2 Low Power Relay(37G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Timer
Gen. Under Voltage Protn. (27G) Gen. Over Voltage Stage-1 & 2 (59G) Gen. Over Fluxing Stage-1 (99G)
Gen. Over Fluxing Stage-2 (99G) With GCB Open & Closed Gen. Pole Slipping (78G)
Gen. Loss of Excitation (40G)
Gen. Loss of Excitation With Under Voltage (27/40G) Gen. Negetive Phase Sequence (46) Stage-1 Gen. Neg. Phase Sequence (46) Stage-2 Time Stage-1&2 Gen. Stator Over load (50GS)
Gen. Stator earth fault 95% (64G2) GCB Local Breaker Backup (50LBB) Dead machine Protection (61B)
Voltage Balance Protection (60G21, 60G22, 60G23) Gen. Open delta earth Fault Protection (59N)
60G11,60G12 Voltage Balance Relay Aux. Supply : 220V DC, 2NO+4CO, S/R AREVA 3 MVAPM32 3 3 0 0 0 6
60G13,60G21 PT Sec:110V AC (PH-PH) , Case Size: Midos Case - 4 60G22,60G23 Wiring diagram: F1MVAPM32001
Model: MVAPM32D1AA2001A
186A1,186A2-1 High speed G roup-1 Class A//C 3 phase trip Aux. Supply : 220V DC AREVA 3 MVAJ20 5 0 0 0 0 5 186A2-2, 186A2-3 relay (Hand/Electrical Reset) Case: Midos size:4
186C-1, Contacts: 14NO+6NC (Hand/Electrical Reset) Flag: Yes, Mounting: Flush
Model: MVAJ205LA1006A
286A1, 286A2-1 High speed G roup-2 Class A//C 3 phase trip Aux. Supply : 220V DC AREVA 3 MVAJ20 0 5 0 0 0 5 286A2-2, 286A2-3 relay (Hand/Electrical Reset) Case: Midos size:4
286C-1, Contacts: 14NO+6NC (Hand/Electrical Reset) Flag: Yes, Mounting: Flush
Model: MVAJ205LA1006A
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name
ENGINEER : TCE CONSULTING ENGINEERS LIMITED
Date : 30.04.09
Description :- Equipment List
QTY / Panel
Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Sales Ref : 3001506934 Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT
PREP : MR CHKD : MS Circuit: GRP # UNIT10 APPD : MS SIEMENS SIEMENSSIEMENS SIEMENS Original/Replacement for/ (4)-G719EA-XG970-ER901-R4 Replaced by :-Page 1 of 8
S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
QTY / Panel
GR2 Generator Differential Protn (87G) CT Sec: 5A, PT Sec:110V AC (PH-PH) SIEMENS 3 7UM62 0 1 0 0 0 1
Gen. B/U Impedence Protn - Stage-1(21G1) Aux. Supply : 220V DC
Gen. B/U Impedence Protn - Stage-2(21G1) 15B/I, 20B/O + 1 LIVE STATUS CONTACT Gen. Under Frequency Stage -1(81UF) Case Size : 1/1 19", IEC61850 PROTOCOL Gen. Under Frequency Stage -2(81UF) Time Stage-1&2 MLFB : 7UM6225-6EB92-3CB0-LOS Gen. Over Frequency Protn. (81OF)
Reverse Power Relay(32G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Time Stage-1 Reverse Power Relay(32G) +Time Stage-2 Low Power Relay(37G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Timer
Gen. Under Voltage Protn. (27G) Gen. Over Voltage Stage-1 & 2 (59G) Gen. Over Fluxing Stage-1 (99G)
Gen. Over Fluxing Stage-2 (99G) With GCB Open & Closed Gen. Pole Slipping (78G)
Gen. Loss of Excitation (40G)
Gen. Loss of Excitation With Under Voltage (27/40G) Gen. Negetive Phase Sequence (46) Stage-1 Gen. Neg. Phase Sequence (46) Stage-2 Time Stage-1&2 Gen. Stator Over load (50GS)
Gen. Stator earth fault 95% (64G2) GCB Local Breaker Backup (50LBB) Dead machine Protection (61B)
Voltage Balance Protection (60G21, 60G22, 60G23) Gen. Open delta earth Fault Protection (59N)
95/186A1,95/186A2-1 Supervision relay for Trip Relay Supervision Relay AREVA 3 MVAXM21 7 0 0 2 1 10
95/186A2-2,95/186A2-3 High Speed Triping relay Aux. Supply: 220V DC, Contacts: 1NO+2NC S/R 95/186B,95/186C-1, Flag: Yes, Case:-Size 3 Midos: Mounting-Flush 95/186C-2,95/186DUT10A, Model no: MVAXM21C1CE3005A
95/186DUT10B, WDG: F1MVAXM21001
95/186DST1
95/286A1,95/286A2-1 Supervision relay for Trip Relay Supervision Relay AREVA 3 MVAXM21 0 7 0 2 1 10
95/286A2-2,95/286A2-3 High Speed Triping relay Aux. Supply: 220V DC, Contacts: 1NO+2NC S/R 95/286B, 95/286C-1, Flag: Yes, Case:-Size 3 Midos: Mounting-Flush 95/286C-2,95/286DUT10A, Model no: MVAXM21C1CE3005A
95/286DUT10B, WDG: F1MVAXM21001
95/286DST1
80A, 80B DC Supervision cum changeover Relay Aux. Volt:220V DC, 2N/O, 2C/O, Flag- NO, S/R AREVA 3 MVAAM11 1 1 0 0 2 Slug: 80+/-20ms on D/O Size:2 MIDOS,Flush
Model No:MVAAM11BIAG1030A WDG: Z1MVAAM11011
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name
Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Sales Ref : 3001506934 Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED
Date : 30.04.09
Description :- Equipment List PREP : MR CHKD : MS Circuit: GRP # UNIT10 APPD : MS SIEMENS SIEMENSSIEMENS SIEMENS Original/Replacement for/ (4)-G719EA-XG970-ER901-R4 Replaced by :-Page 2 of 8
S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
QTY / Panel
87GT/64GT/99GT, Numerical Generator Transformer Differential, CT Sec: 1A SIEMENS 3 7UT633 0 0 1 0 0 1
With inbuilt Over fluxing & High impedance REF Aux. Supply : 220V DC, 110V AC 21B/I, 24B/O + 1 LIVE STATUS CONTACT Case Size : 1 /1 x 19", IEC 61850 PROTOCOL, MLFB : 7UT6331-6EB92-1BB1-LOS
87/51UT-10A Numerical Unit Transformer for CT Sec: 1A SIEMENS 3 7UT633 0 0 0 2 0 2
87/51UT-10B Differential protection relay With Inbuilt O/C Relay Aux. Supply : 220V DC
21B/I, 24B/O + 1 LIVE STATUS CONTACT Case Size : 1 /1 x 19", IEC 61850 PROTOCOL, MLFB : 7UT6331-6EB92-1AA1-LOS
87/51ST1 Numerical station Transformer for CT Sec: 1A SIEMENS 3 7UT633 0 0 0 0 1 1
Differential protection relay With Inbuilt O/C Relay Aux. Supply : 220V DC
21B/I, 24B/O + 1 LIVE STATUS CONTACT Case Size : 1 /1 x 19", IEC 61850 PROTOCOL, FO DOUBLE, ST CONNECTOR
MLFB : 7UT6331-6EB92-1AA1-LOS
51NGT GT Backup earth fault protection Relay CT SEC:1A SIEMENS 3 7SJ80 0 0 1 0 0 1
Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL MLFB: 7SJ8011-5EB96-1FA0-LOS
50-UT10A Instantaneous over current CT SEC:1A SIEMENS 3 7SJ80 0 0 0 2 0 2
50-UT10B protection relay for unit transformers Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL MLFB: 7SJ8011-5EB96-1FA0-LOS
50-ST1 Instantaneous over current CT SEC:1A SIEMENS 3 7SJ80 0 0 0 0 1 1
protection relay for station transformer Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL MLFB: 7SJ8011-5EB96-1FA0-LOS
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name
Date : 30.04.09 Original/Replacement for/ PREP : MR SIEMENS SIEMENSSIEMENS SIEMENS CHKD : MS Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Sales Ref : 3001506934 Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT
Circuit: GRP # UNIT10 APPD : MS
(4)-G719EA-XG970-ER901-R4 Replaced by
:-Description :- Equipment List ENGINEER : TCE CONSULTING ENGINEERS LIMITED
S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
QTY / Panel
64-1-UT10A Restricted earth fault protection CT SEC:1A SIEMENS 3 7SJ80 0 0 0 4 0 4
64-2-UT10A relay for LV Side Unit transformer Auxiliary voltage: 220V DC 64-1-UT10B Size: 1/6 19"; Mounting: Flush 64-2-UT10B 3 BI; 5 BO +1 LIVE STATUS CONTACT
IEC 61850 PROTOCOL, FO DOUBLE, ST CONNECTOR MLFB: 7SJ8011-5EB96-1FA0-LOS
64-1-ST1 Restricted earth fault protection CT SEC:1A SIEMENS 3 7SJ80 0 0 0 0 2 2
64-2-ST1 relay for LV Side Station transformer Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL, FO DOUBLE, ST CONNECTOR MLFB: 7SJ8011-5EB96-1FA0-LOS
BLK - GR1A / 1B /1C Test Block 10 Terminal AREVA 3 MPG 3 3 2 6 3 17
BLK - GR2A / 2B /2C BLK - 87G1 / 87G2 / 87A
BLK - 50A / 64A / 87B BLK - 50B / 64B / 87 / 50
/64
G20Hz 20Hz Generator for 100% SEF Model No : 7XT33 in 7XP20 Case SIEMENS 3 7XT33 1 0 0 0 0 1
(For 100% Stator Earth Fault) MLFB NO: 7XT3300-0CA00
FGR1 Bandpass Filter for 100% SEF Model No : 7XT34 in 7XP20 Case SIEMENS 3 7XT34 1 0 0 0 0 1
(For 100% Stator Earth Fault) MLFB NO: 7XT3400-0CA00
SCUGRI Controlling Unit for Rotor Earth Fault MLFB NO: 7XT7100-0EA00 SIEMENS 3 7XT71 0 1 0 0 0 1
(For Rotor Earth Fault)
RCUGR Resistor for 1-3Hz Rotor Earth Fault Protection MLFB NO: 7XR6004-0CA00 SIEMENS 3 7X600 0 1 0 0 0 1 (For Rotor Earth Fault)
59N Neutral Displacement earth fault PT Sec , 110V AC SIEMENS 3 7SJ62 0 1 0 0 0 1
protection relay Aux. Supply : 220V DC 11B/I,6 B/O+1 LIVE STATUS CONTACT CASE SIZE:1/3x19", IEC 61850 PROTOCOL MLFB:7SJ6221-6EB92-1FE0-LOS
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name
CHKD : MS PREP : MR Circuit: GRP # UNIT10 APPD : MS SIEMENS SIEMENSSIEMENS SIEMENS Original/Replacement for/ Replaced by
:-Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Sales Ref : 3001506934 Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED
Date : 30.04.09
Description :- Equipment List
(4)-G719EA-XG970-ER901-R4
S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
QTY / Panel
195, 295 Trip Circuit Supervision relay 220V DC, 1N/O + 2N/C SR,Flag-Yes, AREVA 3 MVAXM31 0 0 2 0 0 2
for GCB Size:4 Midos: Mounting: Flush Model No:MVAXM31D1CE3005A WDG: F1MVAXM31001
GCB, GISOLA, Contact multiplication relay For Aux. Supply:220V DC AREVA 3 VAJC11 0 0 3 0 0 3
GISOLB GCB / Generator &I solator Case:1/2NV Contacts:4NO + 4N/C E/R Mounting:Flush, Flag: Yes WDG: BDZ075.6-9 MLFB NO: VAJC11ZF8305A(CH)
186B Trip Relay For UTA, UTB Trip Relay AREVA 3 MVAJ10 2 2 0 4 0 8
186C-2 Case : Midos case size :2
186D-UT10A Contacts : 8NO+2NC (Hand/Electrical Reset) 186D-UT10B Flag: Yes, Mounting: Flush
286B Aux supply : 220V DC
286C-2 Electrical Reset
286D-UT10A Model : MVAJ105JA1002A
286D-UT10B
186D-ST Trip Relay For ST Trip Relay AREVA 3 MVAJ10 0 0 0 0 2 2
286D-ST Case : Midos case size :2
Contacts : 8NO+2NC (Hand/Electrical Reset) Flag: Yes, Mounting: Flush
Aux supply : 220V DC Electrical Reset Model : MVAJ105JA1002A
ES-1, ES-2 Earthernet Swithes 10 Port Switch 10/100 MBPS RUGGED COM 3 RSG2100 0 0 1 1 0 2
Aus supply: 220V DC, Dual Supply 19" Rack Mounting Type 6 Optical Port (ST Connector) 4 RJ45 Port
RSG2100 -R-RM-HI-HI-FX01-FX01-FX01-XXXX-XXXX-XXXX--XXXX-XXXX-TX01-TX01
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name
Circuit: GRP # UNIT10 APPD : MS SIEMENS SIEMENSSIEMENS SIEMENS PREP : MR CHKD : MS Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Sales Ref : 3001506934 Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED
Date : 30.04.09
Description :- Equipment List
(4)-G719EA-XG970-ER901-R4 Replaced by
:-Original/Replacement for/
S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
QTY / Panel
2/186A1, 2/186A2 Wipe out Timer Aux. Volt:220V DC, Contact : 2N/O , 2C/O , S/R AREVA 3 MVTTM 4 4 0 0 0 8 2/186B, 2/186C Delay on Pick up : 0.01 - 9.99s
2/286A1, 2/286A2 Case : Midos case size :3 MIDOS 2/286B, 2/286C Model No:MVTTM14C1AA1002A
WDG: F10MVTTM14501
PB01,PB02,PB03,PB04 Push Buttton for Trip Relay Reset- GROUP A Normal actuator with plastic front ring and holder of black colour SIEMENS 3 3SB 4 0 0 0 0 4 3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A
PB05,PB06,PB07,PB08 Push Buttton for Trip Relay Reset- GROUP B contact block for rear connection SIEMENS 3 3SB 0 4 0 0 0 4 3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A
PB09,PB10,PB11,PB12 Pushbutton contact block for rear connection SIEMENS 3 3SB 0 0 0 4 0 4
3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A
PB13, PB14 Pushbutton contact block for rear connection SIEMENS 3 3SB 0 0 0 0 2 2
3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A
LBBSW1, LBBSW2 LBB In-Out Selector Handle: Pistol Grip, Black,8 Ways SWITRON 3 SPC32P 1 1 0 0 0 2
switch for LBB protn. Position: IN/OUT,Stayput , LOCKABLE in both position
SL01, SL02 Indicating lamp for Relay DC1/DC2 healthy White Holder with indicator - 3SB14052WZ3 SIEMENS 3 3SB 1 1 0 0 0 2 Lamp Holder with Rear Connection-3SB04012C
DCSS DC Supply Selector Switch Stay Put Non-Lockable With Pistol Grip Handle SWITRON 3 1 0 0 0 0 1
Position (1) DC1 (2) INDEPENDENT (3) DC2 Bezel size: 75 Sq.mm
No. of Ways : 8
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name SIEMENSSIEMENSSIEMENSSIEMENS
Circuit: GRP # UNIT10 Original/Replacement for/
CHKD : MS
(4)-G719EA-XG970-ER901-R4 Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED
Date : 30.04.09 PREP : MR
Sales Ref : 3001506934
Replaced by
:-APPD : MS
Description :- Equipment List
S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
QTY / Panel
INTERNALLY MOUNTED EQUIPMENTS
HT Space heater 100W,230V AC APT 3 1 1 1 1 1 5
CONTROL
HTS ON\OFF switch 15 A Anchor 1 1 1 1 1 1 5
PS Power socket 5/15A, 3Pin Anchor 1 1 1 1 1 1 5
TH Thermostat 30-90 deg cent APT 3 1 1 1 1 1 5
CONTROL
CILS Cubicle Door Operated Switch Limit Switch(1No+2Nc)-3SE30230A SIEMENS 1 1 1 1 1 1 5
CFL Compact Fluoroscent Lamp 240 V AC, 20W Philips 1 1 1 1 1 1 5
LK Link Base + Link and holder 3NW20NNSF+3NWNNSL SIEMENS 1 5 5 3 15 4 32
CT-1, CT-2 NCT for 100% SEF Protection 400/5A, 5VA SIEMENS 5 4NC5225 0 0 0 0 0 2
LOOSE SUPPLY Loose supply and same to be provided in Model No : 4NC 5225 NGT cubicle MLFB NO: 4NC5225-2CE20
SD1 Surge Divertor Model No.: C53207-A401-D77-1 SIEMENS 3 0 0 1 4 2 7
SR1 Stablizing Resistor Range : 0 - 1000 Ohms , 200Watts AREVA 3 0 0 1 4 2 7
DC MCB DC MCB 32A, 220VDC SIEMENS 3 1 1 0 0 0 2
Double Pole , Aux contact:1NC 10A, 220VDC SIEMENS 3 3 3 0 0 0 6
4A, 220VDC SIEMENS 3 1 1 10 4 2 18
AC MCB AC MCB 16A, 230VAC SIEMENS 3 1 1 1 1 1 5
Single Pole & Neutral , Aux contact:1NC
Test plug MPB Test Plug (LOOSE SUPPLY) AREVA 3 MPB 0 0 0 0 0 3
FO CABLE CABLE FO patch cable (ST-ST) 100BaseFX 1300nm, DLINK/ 5 MultiMode 62,5/125µm,2 core, Fibre Glass EQUIVALENT
a. 10m 0 0 0 0 0 1
b. 5m 0 0 0 0 0 6
c. 3m 0 0 0 0 0 13
D1 to D32 DIODE CDL4U(E)D3 CONNECTWELL 3 BY127 16 16 0 0 0 32
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name SIEMENSSIEMENSSIEMENSSIEMENS
CHKD : MS
Sales Ref : 3001506934
Description :- Equipment List
Original/Replacement for/
Circuit: GRP # UNIT10 APPD : MS
ENGINEER : TCE CONSULTING ENGINEERS LIMITED
Date : 30.04.09 PREP : MR Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT
(4)-G719EA-XG970-ER901-R4 Replaced by
S
Equipment List for Protn. for Generator Relay PanelFunc. Ref Description Specification Make Dis Type Total Qty.
10CHA00GH001 10CHA00GH002 10CHA00GH003 10CHA00GH004 10CHA00GH005
QTY / Panel
TM1703 CP-6014 Master Control Module MLFB: 6MF1113-0GA140-AA0BB SIEMENS 3 CP-6014 0 0 1 0 0 1
(For Transformer (4 - 20mA) Network interface Processor SM-2556 MLFB: 6MF1013-0CF56-0AA1 SIEMENS 3 SM-2556 0 0 2 0 0 2 Analog Input to Suitable for CM-2860 Patch Plug standard V28,ET,TR MLFB: 6MF1211-0CJ60-0AC0 SIEMENS 3 CM-2860 0 0 2 0 0 2 12AI) Mounted in DIN Channel PS-6630 Power Supply 24-60VDC EMC+ MLFB: 6MF1113-0GG30-0AA1 SIEMENS 3 PS-6630 0 0 3 0 0 3
AI-6300 Analog Input 2x2 ±20mA/±10V MLFB: 6MF1113-0GD00-0AA1 SIEMENS 3 AI-6300 0 0 6 0 0 6
DI-6102 Digital Input 2x8, 24-60VDC, Ims MLFB: 6MF1113-0GB002-0AA1 SIEMENS 3 DI-6102 0 0 12 0 0 12
PE-6410 Peripheral Contr. Ax-Bus electr. MLFB: 6MF1113-0GE100-AF0 SIEMENS 3 PE-6410 0 0 3 0 0 3
Flash Card 256MB MLFB: 6MF1213-1GA05-0AD0 SIEMENS 3 - 0 0 1 0 0 1
USB-Cable Type A-A AWG20/28 3m MLFB: 6MF1313-0GC01-0AA1 SIEMENS 3 - 0 0 3 0 0 3
TPP 3M TP Patch cable 3m Cat 5, grey MLFB: 6MF1304-0BC52-0AA1 3 - 0 0 3 0 0 3
Converter Input:220v DC Output:48V DC Phoenix 3 --- 0 0 1 0 0 1
CM-0843 Bus Interfaces Module Electrical MLFB: 6MF11110AJ430AH0 SIEMENS 3 CM-0843 0 0 1 0 0 1
PT MCB AC MCB 2A, 110VAC SIEMENS 3 3 3 3 0 0 9
Four Pole Aux contact:1 NC
3PP13 Resistor for under excitation protection MLFB NO: 3PP1326-OBZ-K2Y SIEMENS 3 3PP13 0 1 0 0 0 1
(Voltage divider, 20:1), group 012009
CAPACITOR Capacitor for Excitation circuit 10µF,250V Reputed 3 1 1
Item No : Qty : 1
R4 QT CORRECTED 09.06.10 KRK
R3 REVISED AS PER COMMENTS DT. 22.12.09 23.12.09 KRK
R2 REVISED AS PER COMMENTS DT. 25.09.09 11.11.09 KRK
Issue Remarks Date Name
ENGINEER : TCE CONSULTING ENGINEERS LIMITED
Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply
Sales Ref : 3001506934 Client : COASTAL GUJARAT POWER LIMITED
Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT
Original/Replacement for/
(4)-G719EA-XG970-ER901-R4 Replaced by
:-Date : 30.04.09
Description :- Equipment List PREP : MR CHKD : MS Circuit: GRP # UNIT10 APPD : MS SIEMENS SIEMENSSIEMENS SIEMENS Page 8 of 8
SIEMENS
TCE.5146A-704-0009
SITE1
MARKED THUS CORRECTION / MODIFICATION TO BE DONE AT SITE
BY COMMISIONING ENGINEER
DT 10.03.11
SHEET
DRAWING DESCRIPTION
00 LIST OF DRAWINGS
01 LIST OF DRAWINGS
02 LIST OF REFERENCE DRAWINGS
03 LIST OF DRAWINGS
04 PROTECTION TRIP LOGIC - GROUP-1 05 PROTECTION TRIP INITIATION - GROUP-1 06 PROTECTION TRIP INITIATION - GROUP-1 07 PROTECTION TRIP INITIATION - GROUP-1 08 PROTECTION TRIP LOGIC - GROUP-2 09 PROTECTION TRIP INITIATION - GROUP-2 10 PROTECTION TRIP INITIATION - GROUP-2 11 PROTECTION TRIP INITIATION - GROUP-2
12 PROTECTION TRIP INITIATION - GROUP-2 & 4-20mA INPUTS TO RTU 13 DIGITAL INPUTS TO RTU
14 SYSTEM SINGLE LINE DIAGRAM 15 PROTECTION SINGLE LINE DIAGRAM 16 PROTECTION SINGLE LINE DIAGRAM 17 GEN. LINE SIDE CT CORE DISTRIBUTION 18 GEN. NEUTRAL SIDE CT CORE DISTRIBUTION 19 UT-10A CT CORE DISTRIBUTION
20 UT-10B CT CORE DISTRIBUTION 21 ST-1 CT CORE DISTRIBUTION 22 VT-1 CORE DISTRIBUTION 23 VT-2 CORE DISTRIBUTION 24 VT-3 CORE DISTRIBUTION 25 AC SUPPLY DISTRIBUTION 26 DC SUPPLY DISTRIBUTION CIRCUIT
27 VOLTAGE SUPVN. (60G11) RELAY CKT 28 VOLTAGE SUPVN. (60G12) RELAY CKT 29 VOLTAGE SUPVN. (60G13) RELAY CKT 30 VOLTAGE SUPVN. (60G21) RELAY CKT
31 VOLTAGE SUPVN. (60G22) RELAY CKT 32 VOLTAGE SUPVN. (60G23) RELAY CKT 33 GEN. PROTN. RELAY (GR-1) AC CKT 34 GEN. PROTN. RELAY (GR-1) B/I CKT 35 GEN. PROTN. RELAY (GR-1) B/I CKT
37 GEN. PROTN. RELAY (GR-1) B/O CKT 38 GEN. PROTN. RELAY (GR-2) AC CKT 39 GEN.- PROTN. RELAY (GR-2) B/I CKT 40 GEN. PROTN. RELAY (GR-2) B/I CKT 41 GEN. PROTN. RELAY (GR-2) B/O CKT 42 GEN. PROTN. RELAY (GR-2) B/O CKT 43 GEN. OPEN DELTA E/F PROTN. AC CKT 44 GEN. OPEN DELTA E/F PROTN. BI CKT 45 GEN. OPEN DELTA PROTN. BO CKT 46 GEN. GROUP-1 CLASS-A1 TRIP RELAY CKT 47 GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT
48 GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT 49 GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT 50 GEN. GROUP-1 CLASS-B TRIP RELAY CKT 51 GEN. GROUP-1 CLASS-C TRIP RELAY CKT 52 GEN. GROUP-1 CLASS-C TRIP RELAY CKT 53 GEN. GROUP-2 CLASS-A1 TRIP RELAY CKT 54 GEN. GROUP-2 CLASS-A2 TRIP RELAY CKT
55 GEN. GROUP-2 CLASS A2 TRIP RELAY CKT 56 GEN. GROUP-2 CLASS A2 TRIP RELAY CKT 57 GEN. GROUP-2 CLASS B TRIP RELAY CKT 58 GEN. GROUP-2 CLASS C TRIP RELAY CKT 59 GEN. GROUP-2 CLASS C TRIP RELAY CKT 60 GT DIFF. PROTN. AC CIRCUIT
61 GT DIFF. PROTN. AC CIRCUIT 62 GT DIFF. PROTN. B/I CIRCUIT 63 GT DIFF. PROTN. B/I CIRCUIT 64 GT DIFF. PROTN. B/I CIRCUIT
√
REV-0
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
REV-1 REV-2
SHEET
DRAWING DESCRIPTION
REV-0
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
REV-1 REV-2
36 GEN. PROTN. RELAY (GR-1) B/O CKT
√
47A GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT
√
54A GEN. GROUP-2 CLASS-A2 TRIP RELAY CKT
√
26A DC SUPPLY DISTRIBUTION CIRCUIT
√
01A LIST OF DRAWINGS
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
13A DIGITAL INPUTS TO RTU
√
NOTE:-TB NOS & WIRE NOS MAY CHANGE DURING MANUFACTURING
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
REV-3
REV-3
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
REV-4
REV-4
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
DRAWING DESCRIPTION
DRAWING DESCRIPTION
72 RTU DC DISTRIBUTION CIRCUIT
73 RTU ANALOG INPUT CARD-1 (4-20mA) CIRCUIT 74 RTU ANALOG INPUT CARD-2 (4-20mA) CIRCUIT 75 RTU ANALOG INPUT CARD-3 (4-20mA) CIRCUIT 76 RTU ANALOG INPUT CARD-4 (4-20mA) CIRCUIT
77 UT-A DIFF. PROTN. AC CIRCUIT 78 UT-A DIFF. PROTN. AC CIRCUIT 79 UT-A DIFF. PROTN. B/I CIRCUIT 80 UT-A DIFF. PROTN. B/I CIRCUIT 81 UT-A DIFF. PROTN. B/I CIRCUIT 82 UT-A DIFF. PROTN. B/O CIRCUIT 83 UT-A DIFF. PROTN. B/O CIRCUIT 84 UT-A HV SIDE O/C PROTN. AC CIRCUIT 85 UT-A HV O/C PROTN. B/I & B/O CIRCUIT
86 UNIT-10A SWGR-A LV REF PROTN. AC CIRCUIT 87 UNIT-10A SWGR-A LV REF. PROTN. B/I & B/O CIRCUIT 88 UNIT-10A SWGR-B LV REF PROTN. AC CIRCUIT 89 UNIT-10A SWGR-B REF. LV PROTN. B/I & B/O CIRCUIT 90 UNIT-10A GROUP-1 TRIP RELAY CKT
91 UNIT-10A GROUP-2 TRIP RELAY CKT
92 BLANK SHEET
93 UT-B DIFF. PROTN. AC CIRCUIT 94 UT-B DIFF. PROTN. AC CIRCUIT 95 UT-B DIFF. PROTN. B/I CIRCUIT 96 UT-B DIFF. PROTN. B/I CIRCUIT 97 UT-B DIFF. PROTN. B/I CIRCUIT 98 UT-A DIFF. PROTN. B/O CIRCUIT 99 UT-A DIFF. PROTN. B/O CIRCUIT 100 UT-B HV SIDE O/C PROTN. AC CIRCUIT 101 UT-B HV O/C PROTN. B/I & B/O CIRCUIT 102 UNIT-10B SWGR-A LV REF PROTN. AC CIRCUIT 103 UNIT-10B SWGR-A LV REF. PROTN. B/I & B/O CIRCUIT 104 UNIT-10B SWGR-B LV REF PROTN. AC CIRCUIT 105 UNIT-10B SWGR-B LV REF. PROTN. B/I & B/O CIRCUIT 106 UNIT-10B GROUP-1 TRIP RELAY CKT
107 UNIT-10B GROUP-2 TRIP RELAY CKT 108 ST DIFF. PROTN. AC CIRCUIT 109 ST DIFF. PROTN. AC CIRCUIT 110 ST DIFF. PROTN. B/I CIRCUIT 111 ST DIFF. PROTN. B/I CIRCUIT 112 ST-1 DIFF. PROTN. B/I CIRCUIT 113 ST DIFF. PROTN. B/O CIRCUIT 114 ST DIFF. PROTN. B/O CIRCUIT 115 ST HV SIDE O/C PROTN. AC CIRCUIT 116 ST HV O/C PROTN. B/I & B/O CIRCUIT 117 ST SWGR-A LV REF PROTN. AC CIRCUIT 118 ST SWGR-A LV REF. PROTN. B/I & B/O CIRCUIT 119 ST SWGR-B LV REF PROTN. AC CIRCUIT
SHEET
SHEET
√
REV-0
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
REV-1 REV-2
√
REV-0
√
√
√
√
√
√
√
√
√
√
REV-1 REV-2
65 GT DIFF. PROTN. B/O CIRCUIT66 GT DIFF. PROTN. B/O CIRCUIT 67 GT STAND BY E/F PROTN. AC CIRCUIT 68 GT STANDBY E/F PROTN B/I & B/O CIRCUIT 69 GCB CLOSING & TRIP COIL-1 CIRCUIT
70 ISOLATOR CONTACT MULTI. CIRCUIT 71 BREAKER CONTACT MULTI. CIRCUIT
√
√
√
√
√
√
69A TRIP COIL-2 CIRCUIT√
√
√
76A RTU ANALOG INPUT CARD-5 (4-20mA) CIRCUIT76B RTU ANALOG INPUT CARD-6 (4-20mA) CIRCUIT 76C RTU DIGTAL INPUT CARD-1 CIRCUIT 76D RTU DIGTAL INPUT CARD-2 CIRCUIT 76E RTU DIGTAL INPUT CARD-3 CIRCUIT 76F RTU DIGTAL INPUT CARD-4 CIRCUIT 76G RTU DIGTAL INPUT CARD-5 CIRCUIT 76H RTU DIGTAL INPUT CARD-6 CIRCUIT 76J RTU DIGTAL INPUT CARD-7 CIRCUIT 76K RTU DIGTAL INPUT CARD-8 CIRCUIT 76L RTU DIGTAL INPUT CARD-9 CIRCUIT 76M RTU DIGTAL INPUT CARD-10 CIRCUIT
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
76N RTU DIGTAL INPUT CARD-11 CIRCUIT76P RTU DIGTAL INPUT CARD-12 CIRCUIT
REV-3
REV-3
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
REV-4
REV-4
√
√
√
√
√
√
√
√
√
√
√
√
DRAWING DESCRIPTION
120 ST SWGR-B LV REF. PROTN. B/I & B/O CIRCUIT125 400KV MAIN CB & TIE CB LBB & CLOSING INTERLOCK CIRCUIT 121 ST GROUP-1 TRIP RELAY CKT
122 ST GROUP-2 TRIP RELAY CKT
123 BLANK SHEET
124 400KV MAIN CB & TIE CB TRIPPING CKT
126 STEAM TURBINE INTERLOCK CIRCUIT 127 FIELD EXCITATION INTERLOCK CIRCUIT 128 UNIT-10A SWGR. INTERLOCK CIRCUIT 129 UNIT-10 SWGR. INTERLOCK CIRCUIT 130 ST-1 SWGR INTERLOCK CIRCUIT
131 BLOCK CONTACT DISTRIBUTION
132 BLOCK CONTACT DISTRIBUTION
133 BLOCK CONTACT DISTRIBUTION
134 SWITCH CONTACT DISTRIBUTION
135 DCS CIRCUIT
SHEET
REV-0 REV-1 REV-2
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
136 STAND ALONE DISTURBANCE RECORDER
√
137 COMMUNICATION DIAGRAM
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
REV-3
√
REV-4
√
√
√
√
√
AREVA 1. 26KV BREKAER
LIST OF REFERENCE DRAWINGS/DOCUMENTS
DRAWING REF.
TCE.5146A-739-AU-3001 - SHEET 1 & 2 MAIN ONE LINE DIAGRAMDESCRIPTION
2. 26KV ISOLATOR TCEMAKE
2. 26KV CVT 310MVA ,400KV/26KV GENERATOR 63/31.5/31.5 MVA,,26/11.5/11.5KV UNIT TRANSFORMER 63/31.5/31.5MVA,26/11.5/11.5KV NEUTRAL GROUNDING TRANSFORMER DCDB DRAWINGACDB DRAWING STATION TRANSFORMER 960MVA,26KV GENERATOR
TRANSFORMER
34566250672 - COOLER CONTROL GEAR BHEL,
JHANSI INDIVIDUAL KIOSK-34526200113
COMMON KIOSK-34526200112
BHEL
CONTROL ROOM LAYOUT TCE.5146A-580-GA-1701A TCE
TOSHIBA GCB ENCLOSURE
LEGEND
DESCRIPTOIN
CT TERMINATIONS
BAY MARSHALLING BOX TERMINATIONS ISOLATOR TERMINATIONS
PT TERMINATIONS CB TERMINATIONS
SYMBOLS
RELAY PANEL TERMINAL BLOCK OTHER SUPPLIER'S PANEL TB DISCONNECTING TERMINAL BLOCK
TO EXCITER, AVR, TURBINE CIRCUITS
X51A X11A X13A
TERMINAL
SPARE PT CIRCUIT CT CIRCUITDESCRIPTOIN-10CHA00GH001
X43A X41A TO SRP X91A TO ALARMDESCRIPTOIN-10CHA00GH002
DESCRIPTOIN-10CHA00GH003
DESCRIPTOIN-10CHA00GH004
WIRE CROSS REFERENCE STANDARDS
K101 FERRULE NUMBER
12 SHEET NUMBER
W951-03 DRAWING NO. WITH SHEET NO.
DESCRIPTOIN
REPRESENTATION
X61 TO ACDB
X62 TO DCDB-1
X63 TO DCDB-2
STRIP
TERMINAL
STRIP
TERMINAL
STRIP
TERMINAL
STRIP
X2A TO BREAKER (GCB) X3A TO ISOLATOR X42A TO GT, UT, STTO EXCITER, AVR, TURBINE CIRCUITS
X51B X11B X13B SPARE PT CIRCUIT CT CIRCUIT X43B X41B TO SRP X91B TO ALARM X61 TO ACDB X62 TO DCDB-1 X63 TO DCDB-2 X2B TO BREAKER (GCB) X3B TO ISOLATOR X42B TO GT, UT, ST
TO EXCITER, AVR, TURBINE CIRCUITS
X51C X44C X11C X13C SPARE TO RTU PT CIRCUIT CT CIRCUIT X43C X41C TO SRP X2C TO BREAKER (GCB) X3C TO ISOLATOR X42C TO GT, UT, ST
TO EXCITER, AVR, TURBINE CIRCUITS X51DA X11DA X13DA SPARE PT CIRCUIT CT CIRCUIT X43DA X41DA TO SRP X2DA TO BREAKER (GCB) X3DA TO ISOLATOR X42DA TO GT, UT, ST
DESCRIPTOIN-10CHA00GH005
TERMINAL
STRIP
TO EXCITER, AVR, TURBINE CIRCUITS X51E X11E X13E SPARE PT CIRCUIT CT CIRCUIT X43E X41E TO SRP X2E TO BREAKER (GCB) X3E TO ISOLATOR X42E TO GT, UT, ST TO 11kV UNIT-10A SWGR-A,B X45A
X79 AC SUPPLY BUS WIRE
X71
X77 DC SUPPLY BUS WIRE
DIODE TERRMINAL BLOCK
X50A X50B DIODE TERRMINAL BLOCK
X79 AC SUPPLY BUS WIRE
X71
X77 DC SUPPLY BUS WIRE
X79 AC SUPPLY BUS WIRE
X71
X77 DC SUPPLY BUS WIRE
X79 AC SUPPLY BUS WIRE
X71
X77 DC SUPPLY BUS WIRE
X79 AC SUPPLY BUS WIRE
X71
X77 DC SUPPLY BUS WIRE
TO 11kV UNIT-10B SWGR-A,B X46A TO 11kV STATION SWGR-A,B X47A TO 11kV UNIT-10A SWGR-A,B X45A TO 11kV UNIT-10B SWGR-A,B X46A TO 11kV STATION SWGR-A,B X47A
TRIP BUS WIRE NUMBER
CLASS-A1
CLASS-A2
CLASS-B
CLASS-C
CLASS-D-UT10A
GROUP-1
GROUP-2
K103
K303
K503
K703
K903
CLASS-D-UT10B
K1103
CLASS-D-ST
K1303
K203
K403
K603
K803
K1003
K1203
K1403
X81C GCP CIRCUIT X82C GCP CIRCUITTO EXCITER, AVR, TURBINE CIRCUITS X51DB X11DB X13DB SPARE PT CIRCUIT CT CIRCUIT X43DB X41DB TO SRP X2DB TO BREAKER (GCB) X3DB TO ISOLATOR X42DB TO GT, UT, ST X83D TO DCS X84D TO DISTURBANCE RECORDER
186A1 186A2 186B 186C 186D-UT1A 186D-UT1B 186D-ST G C B 5 0 L B B ,G R -1 G T H V M A IN C B , 5 0 L B B G T H V M ID D L E C B , 5 0 L B B G C B T R IP C O IL -1 G C B T R IP C O IL -2 G T H V M A IN C B , T R IP C O IL -1 G T H V M A IN C B , T R IP C O IL -2 1 1 K V U N IT -A , S W IT C H G E A R -A I N C O M E R T R IP C O IL G T H V M ID D L E C B , T R IP C O IL -1 G T H V M ID D L E C B , T R IP C O IL -2 1 1 K V U N IT -A , S W IT C H G E A R -B I N C O M E R T R IP C O IL 1 1 K V U N IT -B , S W IT C H G E A R -A I N C O M E R T R IP C O IL 1 1 K V U N IT -B , S W IT C H G E A R -B I N C O M E R T R IP C O IL 1 1 K V S T A T IO N , S W IT C H G E A R -A I N C O M E R T R IP C O IL 1 1 K V S T A T IO N , S W IT C H G E A R -B I N C O M E R T R IP C O IL F IE L D C B T R IP C O IL T U R B IN E T R IP C H A N N E L -1 T U R B IN E T R IP C H A N N E L -2 1 1 K V U N IT -A , S W IT C H G E A R -A I N C O M E R L B B 1 1 K V U N IT -A ,S W IT C H G E A R -B I N C O M E R L B B 1 1 K V U N IT -B ,S W IT C H G E A R -A I N C O M E R L B B 1 1 K V U N IT -B ,S W IT C H G E A R -B I N C O M E R L B B 1 1 K V S T A T IO N ,, S W IT C H G E A R -A I N C O M E R L B B 1 1 K V S T A T IO N , S W IT C H G E A R -B I N C O M E R L B B W IP E O U T T IM E R 2 /2 8 6 A 1 W IP E O U T T IM E R 2 /2 8 6 A 2 W IP E O U T T IM E R 2 /2 8 6 B W IP E O U T T IM E R 2 /2 8 6 C GROUP-1 PROTECTIONS X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
LEGEND OF TRIP RELAYS - GROUP-1
186A1 GROUP-1 CLASS A1 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS
186A2 GROUP-1 CLASS A2 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST
186B GROUP-1 CLASS B MASTER TRIP RELAY FOR NON CRITICAL GENERATOR FAULTS
186C GROUP-1 CLASS C MASTER TRIP RELAY FOR FAULTS EXTERNAL TO THE PLANT
186D-UT GROUP-1 UT CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF UT 186D-ST GROUP-1 ST CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF ST
286A1 GROUP-2 CLASS A1 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS
286A2 GROUP-2 CLASS A2 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST
286B GROUP-2 CLASS B MASTER TRIP RELAY FOR NON CRITICAL GENERATOR FAULTS
286C GROUP-2 CLASS C MASTER TRIP RELAY FOR FAULTS EXTERNAL TO THE PLANT
286D-UT GROUP-2 UT CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF UT 286D-ST GROUP-2 ST CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF ST
LEGEND OF TRIP RELAYS - GROUP-2
PROTECTION TRIP LOGIC - GROUP-1
GENERATOR DIFFERENTIAL PROTECTION(87G) GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -1
GENERATOR UNDER FREQUENCY STAGE-1 (81UF)
GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-1
GENERATOR OVER FREQUENCY (81OF)
GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -2
GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-2
REVERSE POWER RELAY(32G) + TIMER STAGE -2
GENERATOR UNDER VOLTAGE (27G) GENERATOR OVER VOLTAGE STAGE-1 (59G) GENERATOR OVER VOLATGE STAGE-2 (59G) GENERATOR OVER EXCITATION STAGE-1 (99G)
GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB CLOSED GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB OPEN GENERATOR POLE SLIPPING (78G)
GENERATOR LOSS OF EXCITATION (40G)
GENERATOR LOSS OF EXCITATION WITH UNDER VOLTAGE(27/40G) GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-1
GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-1
GROUP-1 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES
GROUP-1 PROTECTIONS
1
SL. NO.
186A1
186A2
186B
186C
186D-UT1A186D-UT1B 186D-ST
286A2
ALARM
GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-2 GENERATOR STATOR OVER LOAD (50GS)
GENERATOR STATOR EARTH FAULT 95% (64G3) GENERATOR STATOR EARTH FAULT 100% (64G1) GENERATOR ROTOR EARTH FAULT (64F2) - STAGE-1
GCB LOCAL BREAKER BACKUP (50LBB) DEAD MACHINE PROTECTION (61B)
VOLATGE BALANCE PROTECTION (60G11) VOLATGE BALANCE PROTECTION (60G12) VOLATGE BALANCE PROTECTION (60G13)
X
X
X
X
X
X
X
X
X
2 3 4 5 6 7 8 9 10 12 11 13 14 15 16 17 18 19 20 21 22 23 24 25 26 28 29 29 30 31X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
RELAY TYPE
I. GENERATOR PROTECTION
RELAY REF.
7UM62 GR1 MVAPM32 60G11 MVAPM32 60G12 MVAPM32 60G13X
X
GENERATOR ROTOR EARTH FAULT (64F2) - STAGE-227
GENERATOR ROTOR EARTH FAULT (64F1) 30
TOSHIBA TOSHIBA
X
SITE1
EXCITATION TRANSFORMER VERY HIGH
X
32
SITE1
GT STANDBY EARTH FAULT (51NGT) WITHOUT TIMER GT STANDBY EARTH FAULT WITH TIMER
GT PRESSURE RELIEF VALVE-A OPTD. GT OIL TEMPERATURE TRIP GT BUCHHOLZ TRIP (63T)
GT FIRE PROTECTION TRIP (63FT)
GROUP-1 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES
GROUP-1 PROTECTIONS
1
SL. NO.
186A1
186A2
186B
186C
186D-UT1A186D-UT1B 186D-ST
286A2
ALARM
X
X
X
X
2 3 4 5 6RELAY TYPE
X
II. GENERATOR TRANSFORMER PROTECTION
RELAY REF.
7SJ80 51NGT
BI OF 7UT633
X
III. UNIT TRANSFORMER-10A PROTECTIONS
UT INSTANTANEOUS OVER CURRENT (50UT) UT HV SIDE IDMT OVER CURRENT (51UT) UT LV SIDE IDMT EARTH FAULT (51NUT-LV1 & LV2) UT BUCHHOLZ TRIP (63T)UT OIL TEMPERATURE TRIP (49OT) 1 2 3 4 5 6 7 8
X
X
X
X
X
7SJ80 50-UT10A BI OF 7UT633 87/51-UT10A UT OIL TEMPERATURE ALARM (OTA)UT BUCHHOLZ ALARM(63A)
UT PUMP OIL FLOW LOW ALARM GROUP-1
X
X
X
IV. UNIT TRANSFORMER-10B PROTECTIONS
UT INSTANTANEOUS OVER CURRENT (50UT) UT HV SIDE IDMT OVER CURRENT (51UT) UT LV SIDE IDMT EARTH FAULT (51NUT-LV1 & LV2) UT BUCHHOLZ TRIP (63T)
UT OIL TEMPERATURE TRIP (49OT) 1 2 3 4 5 6 7 8
X
X
X
X
X
7SJ80 50-UT10B BI OF 7UT633 87/51-UT10B UT OIL TEMPERATURE ALARM (OTA)UT BUCHHOLZ ALARM(63A)
UT PUMP OIL FLOW LOW ALARM GROUP-1
X
X
X
SITE1V. STATION TRANSFORMER PROTECTIONS
ST INSTANTANEOUS OVER CURRENT (50ST) ST HV SIDE IDMT OVER CURRENT (51ST) ST LV SIDE IDMT EARTH FAULT (51NST-LV1 & LV2) ST BUCHHOLZ TRIP (63T)ST OIL TEMPERATURE TRIP (49OT) 1 2 3 4 5 6 7 8
X
X
X
X
X
7SJ80 50-ST1 BI OF 7UT633 87/51-ST1 ST OIL TEMPERATURE ALARM (OTA)ST BUCHHOLZ ALARM(63A)
ST PUMP OIL FLOW LOW ALARM GROUP-1
X
X
X
GROUP-1 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES
EXCITATION SYSTEM FAULTS - NON CRITICAL EXCITATION SYSTEM FAULTS - CRITICAL
OVERALL DIFFERENTIAL (87OA)
11KV UNIT A, SWITCHGEAR-A INCOMER LBB 11KV UNIT A, SWITCHGEAR-B INCOMER LBB 11KV UNIT B, SWITCHGEAR-A INCOMER LBB 11KV UNIT B, SWITCHGEAR-B INCOMER LBB 11KV STATION, SWITCHGEAR-A INCOMER LBB
VI. AVR
111KV STATION, SWITCHGEAR-B INCOMER LBB 2 1 2 3 4 5 6 7 8 9 11 12 13
X
X
GT HV MAIN CB LBB GT HV MIDDLE CB LBBWIPE OUT TIMER 2/186A2 WIPE OUT TIMER 2/186B WIPE OUT TIMER 2/186C
VII. OVERALL PROTECTIONS
X
X
X
X
X
X
X
X
X
10 WIPE OUT TIMER 2/186A1
X
X
X
X
AVR -FROM SRP 87OA - -AVR -UNIT-A -FROM SRP FROM SRP SWITCHGEAR-A UNIT-A SWITCHGEAR-B UNIT-B SWITCHGEAR-A UNIT-B SWITCHGEAR-B -STATION SWITCHGEAR-A -STATION SWITCHGEAR-B-286A1 286A2 286B 286C 286D-UT1A 286D-UT1B 286D-ST G C B 5 0 L B B ,G R -2 G T H V M A IN C B , 5 0 L B B G T H V M ID D L E C B , 5 0 L B B G C B T R IP C O IL -1 G C B T R IP C O IL -2 G T H V M A IN C B , T R IP C O IL -1 G T H V M A IN C B , T R IP C O IL -2 1 1 K V U N IT -A , S W IT C H G E A R -A I N C O M E R T R IP C O IL G T H V M ID D L E C B , T R IP C O IL -1 G T H V M ID D L E C B , T R IP C O IL -2 1 1 K V U N IT -A , S W IT C H G E A R -B I N C O M E R T R IP C O IL 1 1 K V U N IT -B , S W IT C H G E A R -A I N C O M E R T R IP C O IL 1 1 K V U N IT -B , S W IT C H G E A R -B I N C O M E R T R IP C O IL 1 1 K V S T A T IO N , S W IT C H G E A R -A I N C O M E R T R IP C O IL 1 1 K V S T A T IO N , S W IT C H G E A R -B I N C O M E R T R IP C O IL F IE L D C B T R IP C O IL T U R B IN E T R IP C H A N N E L -1 T U R B IN E T R IP C H A N N E L -2 1 1 K V U N IT -A , S W IT C H G E A R -A I N C O M E R L B B 1 1 K V U N IT -A ,S W IT C H G E A R -B I N C O M E R L B B 1 1 K V U N IT -B ,S W IT C H G E A R -A I N C O M E R L B B 1 1 K V U N IT -B ,S W IT C H G E A R -B I N C O M E R L B B 1 1 K V S T A T IO N ,, S W IT C H G E A R -A I N C O M E R L B B 1 1 K V S T A T IO N , S W IT C H G E A R -B I N C O M E R L B B W IP E O U T T IM E R 2 /2 8 6 A 1 W IP E O U T T IM E R 2 /1 8 6 A 2 W IP E O U T T IM E R 2 /1 8 6 B W IP E O U T T IM E R 2 /1 8 6 C GROUP-2 PROTECTIONS X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
LEGEND OF TRIP RELAYS - GROUP-1
186A1 GROUP-1 CLASS A1 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS
186A2 GROUP-1 CLASS A2 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST
186B GROUP-1 CLASS B MASTER TRIP RELAY FOR NON CRITICAL GENERATOR FAULTS
186C GROUP-1 CLASS C MASTER TRIP RELAY FOR FAULLTS EXTERNAL TO THE PLANT
186D-UT GROUP-1 UT CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF UT 186D-ST GROUP-1 ST CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF ST
286A1 GROUP-2 CLASS A1 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS
286A2 GROUP-2 CLASS A2 MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST
286B GROUP-2 CLASS B MASTER TRIP RELAY FOR NON CRITICAL GENERATOR FAULTS
286C GROUP-2 CLASS C MASTER TRIP RELAY FOR FAULLTS EXTERNAL TO THE PLANT
286D-UT GROUP-2 UT CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF UT 286D-ST GROUP-2 ST CLASS D MASTER TRIP RELAY FOR THERMAL OVER LOAD PROTECTIONS OF ST
LEGEND OF TRIP RELAYS - GROUP-2
GENERATOR DIFFERENTIAL PROTECTION(87G) GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -1
GENERATOR UNDER FREQUENCY STAGE-1 (81UF)
GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-1
GENERATOR OVER FREQUENCY (81OF)
GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -2
GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-2
REVERSE POWER RELAY(32G)+TURBINE TRIP RELAY OPERATED/ TIME STAGE-1 +TURBINE TRIP CH- 1/2
REVERSE POWER RELAY(32G) + TIME STAGE -2
LOW POWER RELAY(37G)+TURBINE TRIP RELAY OPERATED/ TIMER + TURBINE TRIP CH- 1/2
GENERATOR UNDER VOLTAGE (27G) GENERATOR OVER VOLTAGE STAGE-1 (59G) GENERATOR OVER VOLATGE STAGE-2 (59G) GENERATOR OVER EXCITATION STAGE-1 (24G)
GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB CLOSED GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB OPEN GENERATOR POLE SLIPPING (78G)
GENERATOR LOSS OF EXCITATION (40G)
GENERATOR LOSS OF EXCITATION WITH UNDER VOLTAGE(27/40G) GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-1
GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-1
GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES
GROUP-2 PROTECTIONS
1
SL. NO.
286A1
286A2
286B
286C
286D-UT1A286D-UT1B 286D-ST
186A2
ALARM
GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-2 GENERATOR STATOR OVER LOAD (50GS)
GENERATOR STATOR EARTH FAULT 95% (64G3) GCB LOCAL BREAKER BACKUP (50LBB) DEAD MACHINE PROTECTION (61B)
VOLATGE BALANCE PROTECTION (60G21) VOLATGE BALANCE PROTECTION (60G22) VOLATGE BALANCE PROTECTION (60G23)
X
X
X
X
X
X
X
X
X
2 3 4 5 6 7 8 9 10 12 11 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
RELAY TYPE
I. GENERATOR PROTECTION
RELAY REF.
7UM62 GR2 MVAPM32 60G21 MVAPM32 60G22 MVAPM32 60G23X
GENERATOR OPEN DELTA EARTH FAULT PROTECTION (59N)
30 7SJ62 59N
X
GENERATOR ROTOR EARTH FAULT (64F2) STAGE-1 26
X
X
GENERATOR ROTOR EARTH FAULT (64F2) STAGE-227
GENERATOR ROTOR EARTH FAULT (64F1)
27 TOSHIBA TOSHIBA
X
SITE1 SITE1
GT OVERHEAD LINE DIFFERENTIAL PROTECTION (87OH) GT SUDDEN PRESSURE RELAY TRIP
GT DIFFERENTIAL (87GT)
GT OVER FLUXING PROTECTION (99GT) STAGE-1
GT PRESSURE RELIEF VALVE-B TRIP GT RESTRICTED EARTH FAULT (64GT)
GT OVER FLUXING PROTECTION (99GT) STAGE-2
III. UNIT TRANSFORMER-10A PROTECTIONS
GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES
GROUP-2 PROTECTIONS
1
SL. NO.
286A1
286A2
286B
286C
286D-UT1A286D-UT1B 286D-ST
186A2
ALARM
X
X
X
X
X
2 3 4 5 6 910 GT OLTC OIL SURGE TRIP
RELAY TYPE
X
II. GENERATOR TRANSFORMER PROTECTION
RELAY REF.
7UT633 FROM SRP 87OHX
BI OF 59NX
UT DIFFERENTIAL PROTECTION (87UT) UT RESTRICTED EARTH FAULT (64UT) - LV1 & LV2 UT FIRE PROTECTION TRIP (63FT)
UT PRESSURE RELIEF DEVICE TRIP (63PRD)
UT LV1 WINDING TEMPERATURE TRIP (49WT) 1 2 3 4 5 6
X
X
X
X
7UT633 87/51-UT10A BI OF 7UT633 87/51-UT10AX
7SJ80 64-1-UT10A 64-2-UT10AUT HV WINDING TEMPERATURE TRIP (49WT)
X
UT LV2 WINDING TEMPERATURE TRIP (49WT)
7
X
UT OFF CIRCUIT TRIP SWITCH ABNORMAL POSITION TRIP
8
X
UT HV WINDING TERMPERATURE ALARM 9
UT LV1 WINDING TERMPERATURE ALARM 10
UT LV2 WINDING TERMPERATURE ALARM 11
PUMP OIL FLOW LOW GROUP-2 ALARM 12
X
X
X
X
GT HV WINDING TEMPERATURE TRIPGT LV WINDING TEMPERATURE TRIP 7
8
X
X
SITE1IV. UNIT TRANSFORMER-10B PROTECTIONS
GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES
GROUP-2 PROTECTIONS
SL. NO.
RELAY TYPE RELAY REF.
286A1
286A2
286B
286C
286D-UT1A286D-UT1B 286D-ST
186A2
ALARM
UT DIFFERENTIAL PROTECTION (87UT) UT RESTRICTED EARTH FAULT (64UT) - LV1 & LV2 UT FIRE PROTECTION TRIP (63FT)
UT PRESSURE RELIEF DEVICE TRIP (63PRD)
UT LV1 WINDING TEMPERATURE TRIP (49WT) 1 2 3 4 5 6
X
X
X
X
7UT633 87/51-UT10B BI OF 7UT633 87/51-UT10BX
7SJ80 64-1-UT10B64-2-UT10BUT HV WINDING TEMPERATURE TRIP (49WT)
X
UT LV2 WINDING TEMPERATURE TRIP (49WT)
7
X
UT OFF CIRCUIT TRIP SWITCH ABNORMAL POSITION TRIP
8
X
UT HV WINDING TERMPERATURE ALARM 9
UT LV1 WINDING TERMPERATURE ALARM 10
UT LV2 WINDING TERMPERATURE ALARM 11
PUMP OIL FLOW LOW GROUP-2 ALARM 12
X
X
X
X
V. STATION TRANDFORMER PROTECTIONS
ST DIFFERENTIAL PROTECTION (87ST) ST RESTRICTED EARTH FAULT (64ST) - LV1 & LV2 ST FIRE PROTECTION TRIP (63FT)
ST PRESSURE RELIEF DEVICE TRIP (63PRD)
ST LV1 WINDING TEMPERATURE TRIP (49WT) 1 2 3 4 5 6
X
X
X
X
7UT633 87/51-ST1 BI OF 7UT633 87/51-ST1X
7SJ80 64-1-ST1 64-2-ST1ST HV WINDING TEMPERATURE TRIP (49WT)
X
ST LV2 WINDING TEMPERATURE TRIP (49WT)
7
X
ST OFF CIRCUIT TRIP SWITCH ABNORMAL POSITION TRIP
8
X
ST HV WINDING TERMPERATURE ALARM 9
ST LV1 WINDING TERMPERATURE ALARM 10
ST LV2 WINDING TERMPERATURE ALARM 11
PUMP OIL FLOW LOW GROUP-2 ALARM 12
X
X
X
X
11KV UNIT A, SWITCHGEAR-A INCOMER LBB 11KV UNIT A, SWITCHGEAR-B INCOMER LBB 11KV UNIT B, SWITCHGEAR-A INCOMER LBB 11KV UNIT B, SWITCHGEAR-B INCOMER LBB 11KV STATION, SWITCHGEAR-A INCOMER LBB
GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES
SL. NO.
286A1
286A2
286B
286C
286D-UT1A286D-UT1B 286D-ST
186A2
ALARM
11KV STATION, SWITCHGEAR-B INCOMER LBB 1 2 3 4 5 6 7 8 9 11 12
FROM
GT HV MAIN CB LBB GT HV MIDDLE CB LBBWIPE OUT TIMER 2/286A2 WIPE OUT TIMER 2/286B WIPE OUT TIMER 2/286C
VI. OVERALL PROTECTIONS
X
X
X
X
X
X
X
X
10WIPE OUT TIMER 2/286A1
X
X
X
X
GROUP-2 PROTECTIONS
RELAY REF.
UNIT-A -FROM SRP FROM SRP SWITCHGEAR-A UNIT-A SWITCHGEAR-B UNIT-B SWITCHGEAR-A UNIT-B SWITCHGEAR-B -STATION SWITCHGEAR-A -STATION SWITCHGEAR-B
-GT-1 HV R-Ph WINDING TEMPERATURE INDICATION GT-1 LV R-Ph WINDING TEMPERATURE INDICATION
4-20mA INPUTS TO ANALOG CARD - AI1
PAGE
1 2 3 4FUNCTIONS
GT-1 HV Y-Ph WINDING TEMPERATURE INDICATION GT-1 LV Y-Ph WINDING TEMPERATURE INDICATION
73
GT-1 HV B-Ph WINDING TEMPERATURE INDICATION GT-1 LV B-Ph WINDING TEMPERATURE INDICATION
4-20mA INPUTS TO ANALOG CARD - AI2
PAGE
1 2 3 4FUNCTIONS
GT-1 B-Ph OIL TEMPERATURE INDICATION UT-10A HV WINDING TERMPERATURE INDICATION
74
UT-10A LV1 WINDING TEMPERATURE INDICATION UT-10A LV2 WINDING TEMPERATURE INDICATION
4-20mA INPUTS TO ANALOG CARD - AI3
PAGE
1 2 3 4FUNCTIONS
UT-10A OIL TEMPERATURE INDICATION UT-10B HV WINDING TERMPERATURE INDICATION
75
4-20mA INPUTS TO ANALOG CARD - AI4
PAGE
1 2 3 4FUNCTIONS
76
4-20mA INPUTS TO ANALOG CARD - AI5
PAGE
1 2 3 4FUNCTIONS
76A
GT-1 R-PH OLTC TAP POSITION GT-1 Y-PH OLTC TAP POSITION
4-20mA INPUTS TO ANALOG CARD - AI6
PAGE
1 2 3 4FUNCTIONS
GT-1 B-PH OLTC TAP POSITION GT-1 Y-Ph OIL TEMPERATURE INDICATION
76B
UT-10B LV1 WINDING TEMPERATURE INDICATIONUT-10B LV2 WINDING TEMPERATURE INDICATION UT-10B OIL TEMPERATURE INDICATION ST-1 HV WINDING TERMPERATURE INDICATION
ST-1 LV1 WINDING TEMPERATURE INDICATION ST-1 LV2 WINDING TEMPERATURE INDICATION ST-1 OIL TEMPERATURE INDICATION GT-1 R-Ph OIL TEMPERATURE INDICATION
INPUT
INPUT
INPUT
INPUT
INPUT
INPUT
UT-10A BANK-1 FANS ON UT-10A BANK-2 FANS ON UT-10A BANK-1 PUMPS ON UT-10A BANK-2 PUMPS ON UT-10A 415V AC SUPPLY-1 ON
INPUTS TO RTU DIGITAL CARD - DI1
INPUT
UT-10A 415V AC SUPPLY-2 ON 1 2 3 4 5 6 7 8 9PAGE
UT-10A FAN CONTROL ON - MANUAL UT-10A FAN CONTROL ON - AUTO
UT-10A PUMPS CONTROL ON -AUTO 10
UT-10A PUMPS CONTROL ON -MANUAL
FUNCTIONS
76C
UT-10A BANK-1 FAN FAIL 11
UT-10A BANK-2 FAN FAIL 12
UT-10A BANK-1 PUMP FAIL 13
UT-10A BANK-2 PUMP FAIL 14
UT-10A COOLER POWER SUPPLY AUTO CHANGEOVER FAIL 15
UT-10A CONTROL SUPPLY FAIL 16
UT-10B BANK-1 FANS ON UT-10B BANK-2 FANS ON UT-10B BANK-1 PUMPS ON UT-10B BANK-2 PUMPS ON UT-10B 415V AC SUPPLY-1 ON
INPUTS TO RTU DIGITAL CARD - DI2
INPUT
UT-10B 415V AC SUPPLY-2 ON 1 2 3 4 5 6 7 8 9PAGE
UT-10B FAN CONTROL ON - MANUAL UT-10B FAN CONTROL ON - AUTO
UT-10B PUMPS CONTROL ON -AUTO 10
UT-10B PUMPS CONTROL ON -MANUAL
FUNCTIONS
76D
UT-10B BANK-1 FAN FAIL 11
UT-10B BANK-2 FAN FAIL 12
UT-10B BANK-1 PUMP FAIL 13
UT-10B BANK-2 PUMP FAIL 14
UT-10B COOLER POWER SUPPLY AUTO CHANGEOVER FAIL 15
UT-10B CONTROL SUPPLY FAIL 16
GT-1 R-Ph NORMAL COOLER FAIL GT-1 R-Ph STANDBY COOLER FAIL GT-1 R-Ph COOLER CONTROL SUPPLY FAIL GT-1 R-Ph OIL FLOW LOW COOLER-A GT-1 R-Ph OIL FLOW LOW COOLER-B
INPUTS TO RTU DIGITAL CARD - DI3
INPUT
GT-1 R-Ph OIL FLOW LOW COOLER-C 1 2 3 4 5 6 7 8 9
PAGE
GT-1 R-Ph OIL FLOW LOW COOLER-D GT-1 R-Ph OIL FLOW LOW COOLER-E
GT-1 R-Ph LOW OIL LEVEL ALARM 10
GT-1 R-Ph OIL FLOW LOW COOLER-F
FUNCTIONS
76E GT-1 R-Ph HV WTI ALARM 11 GT-1 R-Ph LV WTI ALARM 12GT-1 R-Ph HOTSPOT WDG. TEMP. ALARM THROUGH FOTS 13 GT-1 R-Ph OTI ALARM 14 GT-1 R-Ph BUCHHOLZ ALARM 15 SPARE 16
GT-1 Y-Ph NORMAL COOLER FAIL GT-1 Y-Ph STANDBY COOLER FAIL GT-1 Y-Ph COOLER CONTROL SUPPLY FAIL GT-1 Y-Ph OIL FLOW LOW COOLER-A GT-1 Y-Ph OIL FLOW LOW COOLER-B
INPUTS TO RTU DIGITAL CARD - DI4
INPUT
GT-1 Y-Ph OIL FLOW LOW COOLER-C 1 2 3 4 5 6 7 8 9
PAGE
GT-1 Y-Ph OIL FLOW LOW COOLER-D GT-1 Y-Ph OIL FLOW LOW COOLER-E
GT-1 Y-Ph LOW OIL LEVEL ALARM 10
GT-1 Y-Ph OIL FLOW LOW COOLER-F
FUNCTIONS
76F
GT-1 Y-Ph HV WTI ALARM 11
GT-1 Y-Ph LV WTI ALARM 12
GT-1 Y-Ph HOTSPOT WDG. TEMP. ALARM THROUGH FOTS 13
GT-1 Y-Ph OTI ALARM 14
GT-1 Y-Ph BUCHHOLZ ALARM 15
SPARE 16
GT-1 B-Ph NORMAL COOLER FAIL GT-1 B-Ph STANDBY COOLER FAIL GT-1 B-Ph COOLER CONTROL SUPPLY FAIL GT-1 B-Ph OIL FLOW LOW COOLER-A GT-1 B-Ph OIL FLOW LOW COOLER-B
INPUTS TO RTU DIGITAL CARD - DI5
INPUT
GT-1 B-Ph OIL FLOW LOW COOLER-C 1 2 3 4 5 6 7 8 9
PAGE
GT-1 B-Ph OIL FLOW LOW COOLER-D GT-1 B-Ph OIL FLOW LOW COOLER-E
GT-1 B-Ph LOW OIL LEVEL ALARM 10
GT-1 B-Ph OIL FLOW LOW COOLER-F
FUNCTIONS
76G GT-1 B-Ph HV WTI ALARM 11 GT-1 B-Ph LV WTI ALARM 12GT-1 B-Ph HOTSPOT WDG. TEMP. ALARM THROUGH FOTS 13 GT-1 B-Ph OTI ALARM 14 GT-1 B-Ph BUCHHOLZ ALARM 15 SPARE 16
GT-1 R-Ph THERMAL OVERLOAD RELAY TRIP GT-1 R-Ph COOLER DIRECT ON
GT-1 R-Ph COOLER COOLER ON THRO. WTI/FOTS/ GT-1 R-Ph COOLER FAIL
GT-1 R-Ph DRIVE MOTOR AUTO TRIP/TAP CHANGE DELAYED
INPUTS TO RTU DIGITAL CARD - DI6
INPUT
COMMON KIOSK COOLER SUPPLY-A FAIL 1 2 3 4 5 6 7 8 9
PAGE
COMMON KIOSK COOLER SUPPLY-B FAIL COMMON KIOSK 10
FUNCTIONS
76H 11 12 13 14 15 SPARE 16GEN.FAS HV CB ON/FIELD CB ON/GCB ON
COOLER POWER SUPPLY AUTO CHANGEOVER FAIL GT-1 Y-Ph THERMAL OVERLOAD RELAY TRIP GT-1 Y-Ph COOLER DIRECT ON
GT-1 Y-Ph COOLER COOLER ON THRO. WTI/FOTS/ GT-1 Y-Ph COOLER FAIL
GT-1 Y-Ph DRIVE MOTOR AUTO TRIP/TAP CHANGE DELAYED GEN.FAS HV CB ON/FIELD CB ON/GCB ON
COMMON KIOSK OUT OF STEP IN 3-1 PHASE TAP POSITION COMMON KIOSK FOTS FAULTY
INPUTS TO RTU DIGITAL CARD - DI7
INPUT
1 2 3 4 5 6 7 8 9PAGE
10FUNCTIONS
76J 11 12 13 14 15 16GT-1 R-Ph HYDRAN SYSTEM FAIL ALARM SPARE
SPARE
GT-1 Y-Ph HYDRAN SYSTEM FAIL ALARM SPARE
INPUTS TO RTU DIGITAL CARD - DI8
INPUT
GT-1 R-Ph TAP CHANGE SUPPLY FAIL 1 2 3 4 5 6 7 8 9
PAGE
GT-1 Y-Ph TAP CHANGE SUPPLY FAIL GT-1 B-Ph TAP CHANGE SUPPLY FAIL
SPARE 10
GT-1 B-Ph HYDRAN SYSTEM FAIL ALARM
FUNCTIONS
76K SPARE 11 GCB TC-1 UNHEALTHY 12 GCB TC-2 UNHEALTHY 13 GMP DC SUPPLY UNHEALTHY 14 GRP DC-2 SUPPLY UNHEALTHY 15 SPARE 16GEN. GROUP-1 CLASS-A1 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-B TRIP RELAY UNHEALTHY
INPUTS TO RTU DIGITAL CARD - DI9
INPUT
GEN. GROUP-1 CLASS-C TRIP RELAY UNHEALTHY 1 2 3 4 5 6 7 8 9
PAGE
GEN. GROUP-1 CLASS-C TRIP RELAY UNHEALTHY SPARE 10
FUNCTIONS
76L 11 12 13 14 15 SPARE 16INPUTS TO RTU DIGITAL CARD - DI10
INPUT
1 2 3 4 5 6 7 8 9PAGE
10FUNCTIONS
76M 11 12 13 14 15 16FOR GT-1 R-Ph COOLER LOGIC - K42 FOR GT-1 R-Ph COOLER LOGIC - K1 FOR GT-1 R-Ph COOLER LOGIC - K2 FOR GT-1 R-Ph COOLER LOGIC - K3 FOR GT-1 R-Ph COOLER LOGIC - K4
INPUTS TO RTU DIGITAL CARD - DI11
INPUT
FOR GT-1 R-Ph COOLER LOGIC - K5 1 2 3 4 5 6 7 8 9
PAGE
FOR GT-1 R-Ph COOLER LOGIC - K6
10
FUNCTIONS
76N 11 12 13 14 15 16INPUTS TO RTU DIGITAL CARD - DI12
INPUT
1 2 3 4 5 6 7 8 9PAGE
10FUNCTIONS
76P 11 12 13 14 15 SPARE 16 VT-1 WDG-1 UNHEALTHY VT-2 WDG-1 UNHEALTHY VT-3 WDG-1 UNHEALTHY VT-3 WDG-2 UNHEALTHY SPARE SPARE GT-1 B-Ph THERMAL OVERLOAD RELAY TRIPGT-1 B-Ph COOLER DIRECT ON
GT-1 B-Ph COOLER COOLER ON THRO. WTI/FOTS/ GT-1 B-Ph COOLER FAIL
GT-1 B-Ph DRIVE MOTOR AUTO TRIP/TAP CHANGE DELAYED GEN.FAS HV CB ON/FIELD CB ON/GCB ON
SPARE SPARE
GRP DC-1 SUPPLY MCB UNHEALTHY UT-10A 415V AC SUPPLY-1 FAIL UT-10A 415V AC SUPPLY-2 FAIL
ST-1 415V AC SUPPLY-1 FAIL ST-1 415V AC SUPPLY-2 FAIL UT-10B 415V AC SUPPLY-1 FAIL UT-10B 415V AC SUPPLY-2 FAIL
SPARE SPARE
GEN. GROUP-2 CLASS-A1 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-B TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-C TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-C TRIP RELAY UNHEALTHY
ST-1 BANK-1 FANS ON ST-1 BANK-2 FANS ON ST-1 BANK-1 PUMPS ON ST-1 BANK-2 PUMPS ON ST-1 415V AC SUPPLY-1 ON ST-1 415V AC SUPPLY-2 ON ST-1 FAN CONTROL ON - MANUAL ST-1 FAN CONTROL ON - AUTO
ST-1 PUMPS CONTROL ON -AUTO ST-1 PUMPS CONTROL ON -MANUAL
ST-1 BANK-1 FAN FAIL ST-1 BANK-2 FAN FAIL ST-1 BANK-1 PUMP FAIL ST-1 BANK-2 PUMP FAIL
ST-1 COOLER POWER SUPPLY AUTO CHANGEOVER FAIL ST-1 CONTROL SUPPLY FAIL
SPARE
FOR GT-1 Y-Ph COOLER LOGIC - K42 FOR GT-1 Y-Ph COOLER LOGIC - K1 FOR GT-1 Y-Ph COOLER LOGIC - K2 FOR GT-1 Y-Ph COOLER LOGIC - K3 FOR GT-1 Y-Ph COOLER LOGIC - K4 FOR GT-1 Y-Ph COOLER LOGIC - K5 FOR GT-1 Y-Ph COOLER LOGIC - K6 SPARE
FOR GT-1 B-Ph COOLER LOGIC - K42 FOR GT-1 B-Ph COOLER LOGIC - K1 FOR GT-1 B-Ph COOLER LOGIC - K2 FOR GT-1 B-Ph COOLER LOGIC - K3 FOR GT-1 B-Ph COOLER LOGIC - K4 FOR GT-1 B-Ph COOLER LOGIC - K5 FOR GT-1 B-Ph COOLER LOGIC - K6 SPARE
2 5 0 0 A 2 5 0 0 A 2 5 0 0 A 2500A BUS-1 BPT2 2500A BUS-2 2500A P2 CORE-4 CORE-3 CORE-2 CORE-1 P1 2500A 2500A 400 KV, 3PH, 2000A, 40KA, FOR 1 SEC
C O R E -1 C O R E -2 C O R E -3 C O R E -4 P1 P2 GENERATOR TRANSFORMER-1 310MVA,420KV / 26kV BPT1 P1 P2 GENERATOR # 1 P2 864MW, 960MVA, 26kV 0.9 PF, 3000RPM, ~ G P2 P1 P1 CORE-N2 CORE-N3 CORE-N4 CORE-L3 CORE-L2 CORE-L1 SA 30kV,20kA UNIT TRF-10A Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV P2 P1 CORE-4 CORE-3 CORE-2 CORE-1 P1 P2 CORE-1 UT10A CORE-2 UT10A CORE-3 UT10A P1 P2 NGT 26kV/240V √3 √3 CORE-N1 11kV, 2000A, 40kA, 1Sec
P2 P1 CORE-4 CORE-3 CORE-2 CORE-1 UNIT-10A, SWGR-A
11kV, 2000A, 40kA, 1Sec UNIT-10A, SWGR-B TAPS IN THE RANGE OF ± IN STEPS OF 2.5%
UNIT TRF-10B Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV P2 P1 CORE-4 CORE-3 CORE-2 CORE-1 P1 P2 CORE-1 UT10B CORE-2 UT10B CORE-3 UT10B
11kV, 2000A, 40kA, 1Sec
P2 P1 CORE-4 CORE-3 CORE-2 CORE-1 UNIT-10B, SWGR-A
11kV, 2000A, 40kA, 1Sec UNIT-10B, SWGR-B
TAPS IN THE RANGE OF ± IN STEPS OF 2.5% VT-3
VT-2 VT-1
98.94% EFFICIENCY
50Hz, 400kVA FOR 10 Sec.
STATION TRF-1 Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV P2 P1 CORE-4 CORE-3 CORE-2 CORE-1 P1 P2 CORE-1 ST1 CORE-2 ST1 CORE-3 ST1
11kV, 2000A, 40kA, 1Sec
P2 P1 CORE-4 CORE-3 CORE-2 CORE-1 STATION, SWGR-A
11kV, 2000A, 40kA, 1Sec STATION, SWGR-B
TAPS IN THE RANGE OF ± IN STEPS OF 2.5% P1 P2 P1 P2 P2 P1 P1 P2 P2 P1 P1 P2 STATIC EXCITATION GCB EXCITATION TRAFO. (TOSHIBA)
G T G T P 2 P 1 O H L IN E