Operating the DS9400 Fire Alarm

Operating the DS9400 Fire Alarm

(2)

Outline

Outline

I.

Description

II.

Features

III.

Installation

IV.

System Operation

V.

System Programming

VI.

UL Requirements

VII.

Fire Safety

(3)

What is the DS9400 AddressiFire

 255

Fire Alarm Control/Communicator?

(4)

I.

I.

Description

Description

• The DS9400 AddressiFire™ 255 Fire

Alarm Control/Communicator is a

four-zone panel (expandable to eight four-zones) that

can support up to 20 conventional

two-wire detectors per loop, or any number of

four-wire detectors (depending on

(5)

I.

I.

Description

Description

• Two Notification Appliance Circuits

(NACs) provide up to 4A of 24V power to

operate horns, strobes, bells and other

(6)

I.

I.

Description

Description

• By adding a DS9431 Multiplex Expansion

Module, the DS9400’s conventional system

features are enhanced by adding

addressable point capability, increasing the

number of relay outputs and allowing for

more system users.

(7)

II.

II.

Features

Features

BUILT-IN ALPHA KEYPAD SUPPORT:

• The keypad built into the Control/Communicator is

an alphanumeric keypad that provides a two-line,

16-character (per line) LCD display.

(8)

II.

II.

Features

Features

REMOTE ALPHA KEYPAD SUPPORT:

• The DS9447 Remote LCD Keypad functions like the

built-in keypad on the DS9400. It provides a two-line,

16-character (per line) LCD display. Text is freely

programmable for zone descriptions. Up to four

DS9447 Remote LCD Keypads are allowed per

system.

Maximum Wire Length per DS9447: 1,000 ft.

(9)

II.

II.

Features

Features

EASY USER INTERFACE:

• Nine labeled function keys allow the user to easily

silence bells/sirens, reset smoke detectors or view

history events. Menu-driven keypad programming

allows for customizing of the control panel.

(10)

II.

II.

Features

Features

16 PERSONAL ID NUMBERS (PINs):

• The system supports 16 4-digit PINs.

(11)

II.

II.

Features

Features

ZONES:

• The DS9400 accepts up to 4 (expandable to 8) input

zones. These zones are completely flexible and can be

programmed to provide several different functions.

Zone Inputs: 4 circuits, expandable to 8; 2.21K

End-of-Line resistor

Initiating Circuits: All zones work with two-wire or

four-wire smoke detectors. 20 two-wire detectors

(12)

II.

II.

Features

Features

SMOKE DETECTOR ALARM VERIFICATION:

• Should an alarm occur, the DS9400 may be

programmed to perform an automatic reset on the smoke

detectors.

(13)

II.

II.

Features

Features

100 EVENT HISTORY BUFFER:

(14)

II.

II.

Features

Features

FLEXIBLE DIGITAL COMMUNICATION:

• The communicator will work into most alarm receivers

that are in use today. The DS9400 supports these formats:

• SIA (100 or 300 Baud)

• Contact ID

• BFSK

(15)

II.

II.

Features

Features

THREE TELEPHONE NUMBERS:

• The system supports two 20-digit telephone numbers

with a three or four digit account code for each.

• Each phone number can be individually configured for

the type of communication format and choice of pulse or

tone dialing.

(16)

II.

II.

Features

Features

EE MEMORY:

• The panel uses EEPROM technology, thereby allowing

it to retain all program memory through a total power

failure.

(17)

II.

II.

Features

Features

ENCLOSURE:

• The standard enclosure is manufactured from 18 Ga.,

cold-rolled steel.

• A keyed lock is included, and the LEDs and display are

visible through the door.

• The transformer and backup batteries are housed inside

the enclosure.

(18)

II.

II.

Features

Features

POWER REQUIREMENTS:

Input Power: 120 VAC, 1.5 A

NAC Power: 20 - 30 VDC unfiltered, 4 A

Auxiliary Power: 20 - 30 VDC unfiltered, 1 A

Initiating Circuit (Smoke) Power: 20.4 - 28.2 VDC

filtered, 1A

Option Bus Power: 12 V

±

5%, 500 mA

(19)

II.

II.

Features

Features

ON-BOARD OUTPUTS AND RELAYS:

Outputs: There are two on-board NAC outputs (NAC

1 and NAC 2) on the DS9400 board. These are 24 V

outputs for notification appliances with up to 2.5 A

capacity (limited by overall 4.0 A capacity) on each

circuit. Both outputs are wired for standard Class B

operation.

(20)

II.

II.

Features

Features

REMOTE ANNUNCIATORS:

• The DS9400 supports a maximum of 8 DS9445 LCD

Annunciators. These annunciators can identify the

location of a fire alarm for up to eight zones.

Maximum Wire Length: 1,000 ft.

Wire Type: 4-conductor, unshielded #18 AWG quad

fire rated wire; can be home-run or daisy-chained

Maximum Wire Length Total: 4,000 ft. per bus

(21)

II.

II.

Features

Features

MULTIPLEX EXPANSION TECHNOLOGY:

• The addition of a DS9431 Multiplex Expansion Module

enhances the DS9400’s conventional system features:

• Expands the base system to 255 total points

• Increases the number of relay outputs to 58

• Adds an additional 400 events to the history buffer for a

total of 500 non-volatile events

(22)

II.

II.

Features

Features

LISTINGS:

• Commercial Fire Alarm

Type Service: Auxiliary, Local, Central Station and

Remote Station

Initiating: Automatic, Manual, Sprinkler Supervisory

and Waterflow

(23)

II.

II.

Features

Features

BOARD LAYOUT:

2 1 3 4 5 6 7 8 9 # Cmnd 0 Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm LCD Display Keypad DS9431 Muliplex Expansion Module Connector Pins Option Bus Terminal Strip

Telco Terminal Strip

Relay Terminal Strip

Zone Input Terminal Strip NAC Terminal Strip DS9434 Point Expander Connector Pins Auxiliary Power Terminal Strip DS9482 ENAC Module Connector Pins IMPORTANT! IMPORTANT!

(24)

III.

III.

Installation

Installation

When Installing the DS9400:

The control panel must be installed in accordance to the

National Electrical Code (NFPA 70), the National Fire

Alarm Code (NFPA 72) and the Authority Having

Jurisdiction.

The DS9400’s enclosure should be mounted in a

convenient location for servicing and maintenance.

Mount the DS9400’s enclosure to the desired wall and

the DS9400 board in the enclosure using the supplied

hardware in accordance to the installation guide.

Field wiring is routed into and out of the enclosure via

knockouts provided on the enclosure.

(25)

III.

III.

Installation

Installation

Terminal Connections: Power Supply

White Black Primary Red Brown To unswitched 120 V, 60 Hz circuit WARNING! WARNING!

(26)

III.

III.

Installation

Installation

Terminal Connections: Backup Batteries

Backup Batteries Battery # 1 Battery # 2 Red Black Battery # 1 Battery # 2 (+) (-) (+) Red Black (-)

Battery connection for 24V operation.

BATT 1 BATT 2

Battery

• 24V operation requires two 12V batteries connected in

series for a combined voltage of 24V.

IMPORTANT!

IMPORTANT!

(27)

III.

III.

Installation

Installation

Terminal Connections: Typical Fire Wiring

Smoke Power: 24V, 1.0A max. (filtered)

Refer to Technical Service Note P/N: 31142 for compatible devices.

Aux. Power: 24V, 1.0A max.

(unfiltered) Earth Ground supervised switched unsupervised unswitched Input Points 1-4:

(supervised) Points are intended for connection of Normally Open/ Normally Closed alarm contacts. They may also be used for compatible

2-wire smoke detectors. All EOL resistors are P/N: 25899,

UL listed.

Initiating devices are Class B, Style B. Two-Wire Compatibility Identifier “A”.

EOL Resistor Class B, Style B

(supervised)

• Two-wire Detector Wiring

See the System Option section for more details on detector wiring.

IMPORTANT!

IMPORTANT!

Only use UL Listed

compatible smoke detectors!

(28)

III.

III.

Installation

Installation

Terminal Connections: Typical Fire Wiring

• Four-wire Detector Wiring

Smoke Power: 24V, 1.0A max. (filtered)

Refer to Technical Service Note P/N: 31142 for compatible devices.

Aux. Power: 24V, 1.0A max.

(unfiltered) Earth Ground supervised switched unsupervised unswitched Input Points 1-4:

(supervised) Points are intended for connection of Normally Open/ Normally Closed alarm contacts. They may also be used for compatible

2-wire smoke detectors. All EOL resistors are P/N: 25899,

UL listed.

Initiating devices are Class B, Style B. Two-Wire Compatibility Identifier “A”.

Smoke

Detector RelayEOL

EOL Resistor Smoke Power+ Loop Power + Smoke Power Loop Power -IMPORTANT! IMPORTANT!

Only use UL Listed

compatible smoke detectors!

See the System Option section for more details on detector wiring.

NOTE:

(29)

III.

III.

Installation

Installation

Terminal Connections: NAC Wiring

EOL supervised F I R E F I R E F I R E F I R E EOL supervised F I R E F I R E F I R E F I R E

+24V while in alarm; ground while in standby.

Ground while in alarm; supervisory voltage while in standby.

NOTIFICATION APPLIANCE CIRCUIT:

BAT -BAT +

Requires two 12V batteries, in series, for a combined voltage of 24V. Charge current = 1.1A, max.

+24V while in alarm; ground while in standby.

Ground while in alarm; supervisory voltage while in standby.

NOTIFICATION APPLIANCE CIRCUIT:

Caution: Do not short terminals - explosion and burn hazard. BATTERIES: NAC 2+ NAC 2-NAC 1+ NAC 1-IMPORTANT! IMPORTANT!

Only use UL Listed

compatible NAC

devices!

Shared cable is not recommended for NAC wiring.

NOTE:

(30)

III.

III.

Installation

Installation

Terminal Connections: Option Bus

• All option bus devices must be connected to the same bus,

either Bus A or Bus B.

• Do not connect some devices to Bus A data terminals

(“YA”, “GA”) and some to Bus B data terminals (“BA”,

“BB”).

• Power (“RA”, “RB”) and ground (“BA”, “BB”) terminals

may be connected interchangeably to either set of terminals.

RA BA GA YA RB BB GB YB

Option Bus A Option Bus B Data

15mA max 15mA maxData Option Power (A + B) 500mA, max

Supervised, Style 4 +12 Com +12 Com 1 2 3 4 5 6 7 8 9 # Cmd 0 Prog * Clear Reset Drill Disabl e Test History Alarm Trouble Silenced Power Silence ®

Shared cable is not recommended for Option Bus wiring.

NOTE:

(31)

III.

III.

Installation

Installation

Terminal Connections: Relays

(32)

III.

III.

Installation

Installation

Terminal Connections: Phones

Phone Line 2 (Supervised) Phone Line 1 (Supervised) R2 HR2 HT2 T2 R1 RH1 TH1 T1

Shared cable is not recommended for telephone wiring.

NOTE:

(33)

IV.

IV.

System Operation

System Operation

Understanding the Built-in Keypad

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm SYSTEM NORMAL

SILENCED LED: the yellow Silenced

LED lights when an alarm or trouble condition has been manually silenced by the user. It turns off when the condition that was silenced is corrected.

ALARM LED: the red Alarm LED

lights whenever the system has registered an alarm and has not been reset.

TROUBLE LED: the yellow Trouble LED is lit

whenever the system has detected a problem with its wiring or internal circuitry. The Trouble LED flashes while programming mode is active, and whenever inputs are not active, as during smoke power reset or alarm verification.

POWER LED: the green Power LED

(34)

IV.

IV.

System Operation

System Operation

Understanding the Built-in Keypad

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm SYSTEM NORMAL

DRILL Key: The Drill key is used to

activate the NACs manually. It creates a history log entry and can optionally be reported to the central station.

DISABLEKey: The Disable Key

allows the system to disable or re-enable inputs, NACs or relays (outputs) and the dialer.

TEST Key: The Test Key allows

one of 7 special test modes to be selected.

HISTORY Key: The History

Key allows the record of system events to be viewed.

CLEAR Key: The Clear Key can be used to

(35)

IV.

IV.

System Operation

System Operation

Understanding the Built-in Keypad

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm SYSTEM NORMAL

RESET Key: The Reset Key briefly turns

off power to the detectors to reset them

and clears any off-normal conditions.

SILENCE Key: The Silence Key quiets the

bells/sirens for an alarm or trouble condition

if the system has been configured accordingly.

CMND Key: The Command Key

is used to accept data when in

the programming mode.

PROG Key: The Programming Key

(36)

IV.

IV.

System Operation

System Operation

Understanding the DS9447 Keypad

Reset Drill Disable Test History Alarm Silenced Power Silence ® Trouble Prog Cmd Clear

• The DS9447 Remote LCD Keypad is an alphanumeric LCD

keypad.

•Up to 4 of these keypads can be mounted apart from the main

control/communicator to provide additional locations for system

status and control.

(37)

IV.

IV.

System Operation

System Operation

Understanding the DS9447 Keypad

Reset Drill Disable Test History Alarm Silenced Power Silence ® Trouble Prog Cmd Clear

To adjust the volume, press and hold the [*] key. To decrease the volume,

(38)

IV.

IV.

System Operation

System Operation

Understanding the DS9447 Keypad

Reset Drill Disable Test History Alarm Silenced Power Silence ® Trouble Prog Cmd Clear

To adjust the display backlight intensity, press and hold the [*] key.

To increase the display backlight intensity, press the [3] key.

(39)

IV.

IV.

System Operation

System Operation

Understanding the DS9447 Keypad

• Any of special test modes can be selected using the Test Key

found on the built-in and DS9447 keypads: Walk Test,

Communicator Test, Call for Remote Programming, Test

Battery/NAC Circuits, Answer for Remote Programming,

Manually Activate Outputs, Read Zone Input Levels, Addressable

Point Test (MUX Test) and Sensitivity Test.

(40)

IV.

IV.

System Operation

System Operation

Modes of Operation

There are three modes of system operation for the

DS9400 Control/Communicator:

• ALARM

• TROUBLE

(41)

IV.

IV.

System Operation

System Operation

Modes of Operation: ALARM

When an alarm occurs, the top line of the display will show

“FIRE ALARM”, or a similar message depending on the type

of alarm. This display will override any other system display.

• The second line of the display will show the number of the

point that is in alarm, alternating with the programmed

description for that point.

• If more than one alarm (or other off-normal condition) is

active, they will be shown on the second line of the display

one after another.

• The built-in sounder turns on with a steady tone and outputs

programmed to activate with the current alarm condition(s)

will activate.

(42)

IV.

IV.

System Operation

System Operation

Modes of Operation: ALARM

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm

• If the system is configured to allow alarm silencing, the

[Silence] key turns off the horns/bells, but does not reset the

alarm status and does not return the tripped input to normal

service.

• Detectors that were tripped will stay in alarm and can be

checked (usually by means of an LED on the detector) to see

which one caused the alarm.

• Once the detector(s)

causing the alarm has been

identified, the system

(43)

IV.

IV.

System Operation

System Operation

Modes of Operation: ALARM

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm

• The [Reset] key clears the system alarm status and briefly

turns off the power to reset the detectors.

• This command is required after any fire alarm affecting a

point programmed for latching operation (the normal

configuration).

• This operation is also

required to reset a Class A,

Style 6 Multiplex

(44)

IV.

IV.

System Operation

System Operation

Modes of Operation: TROUBLE

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm SYSTEM TROUBLE

• When a trouble condition occurs (e.g. wiring for a point is cut,

AC power fails, etc.), the sounder will activate with a beep

every 10 seconds.

• The Trouble LED will light and the LCD will display

“SYSTEM TROUBLE”, followed by a description of the

trouble condition.

• The system can diagnose and

display a variety of trouble

conditions, including those

affecting the input points, NAC

circuits, power, battery, system

grounding and internal operations

of the fire panel.

IMPORTANT!

IMPORTANT!

(45)

IV.

IV.

System Operation

System Operation

Modes of Operation: TROUBLE

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm SYSTEM TROUBLE

• The system trouble beep can be silenced with the

[Silence]

key. After the problem has been fixed, press the

[Reset] key to

clear the “SYSTEM TROUBLE” display.

• To prevent intermittent system faults (such as ground fault or

initiating loop open fault) from interfering with central station

operations, the panel has a feature to limit reporting to 100

trouble reports in 24 hours.

• When this limit is

exceeded, the panel transmits

a “DATA LOST” report and

inhibits additional trouble

reports. Non-trouble reports

are not limited

(46)

IV.

IV.

System Operation

System Operation

Modes of Operation: TROUBLE

• Control panel alarms and problems are indicated by one of the

following messages on the top line of the display:

IMPORTANT!

IMPORTANT!

Contact the installing company if these problems persist.

OFF-NORMAL DISPLAYS DISPLAY DESCRIPTION FIRE ALARM SUP’VISORY ALARM SYSTEM TROUBLE POINT TROUBLE DISABLED DEVICE

One or more points is in alarm.

A supervisory condition exists (e.g. a shut-off valve is closed).

A trouble condition exists (e.g. wiring for a point is cut, AC power fails, etc.). One of the points is not responding to the control panel.

(47)

IV.

IV.

System Operation

System Operation

Modes of Operation: NORMAL

• When the system is operating normally, it displays “SYSTEM

NORMAL” on the top line of the display, the Power LED is on

steady and no other LEDs are lit.

• If the system is programmed to require a PIN, the second line

of the LCD screen will display “ENTER PIN”.

• If no PIN is needed, the control panel will show a rotating

menu of possible user actions.

(48)

IV.

IV.

System Operation

System Operation

Basic Use of System: Scrolling Menus

• Once a PIN number, if required, has been entered, the keypad

will display “SYSTEM NORMAL” on the top line and

“SELECT:” on the bottom line followed by these scrolling

menu items: PROG/0, CMND/#, TEST, HISTORY, DISABLE

and DRILL.

• The scrolling menu items will flash one at a time at 1-second

intervals through the list and then start over.

(49)

IV.

IV.

System Operation

System Operation

Basic Use of System: Selecting Menu Items

• Depending on what system level you are at (menu, sub menu,

sub-sub-menu, etc.), there are 3 ways to select an item:

1) In the Main Menu, TEST, HISTORY, DISABLE and

DRILL each have an exclusive button on the keypad. To select

one of these menu items, press the corresponding button.

(50)

IV.

IV.

System Operation

System Operation

Basic Use of System: Selecting Menu Items

2) As in the cases of Main Menu items PROG and CMND, the

PROG and CMND keys are

not exclusive - they are shared

with other characters. The character sharing the corresponding

key is displayed in the second line following a forward slash.

To select one of these items, press the corresponding key.

(51)

IV.

IV.

System Operation

System Operation

Basic Use of System: Selecting Menu Items

3) The corresponding key to a sub-menu item may be displayed

in the second line preceding a dash. Press the corresponding

key to select that item.

2

1

3

4 5 6

7 8 9

#

Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence

Trouble

Silenced

Power

Alarm

PROG MODES

1 - PROG TIMES

While a menu like this is active, you do not have to wait for the

desired menu item to appear before making your selection. Any

item on the current menu rotation can be selected at any time.

NOTE:

(52)

IV.

IV.

System Operation

System Operation

Basic Use of System: Other Functions

Once You Have Selected a Main Menu Item: When a Main

Menu item is selected, the keypad may prompt you to enter

your PIN. If so, enter your number and press the

[Cmnd/#]

key. The display will automatically go to the sub-menu display.

Backtracking Through a Menu: To return to a previous

screen at any time, press the

[Clear/*] key. To return to the

SYSTEM NORMAL display, press the

[Clear/*] key and

backtrack out of the menu until you reach SYSTEM

NORMAL.

Entering Data: When a sub-menu item prompts you to enter

data, do so followed by the

[#] key. If data already exists at a

particular location, it will be displayed. You can either accept

that data or enter new data over it. When the

[#] key is pressed

(53)

IV.

IV.

System Operation

System Operation

Basic Use of System: Other Functions

Drill: The drill command activates all NACs and no relays. It

creates a history log entry and can optionally be reported to the

central station.

Disable: The disable command is used to disable input points,

outputs or the dialer. When any device is disabled, the system

will show this condition on the LCD and on the system trouble

LED. The “disable all” inputs operation takes several seconds

to perform, during which time the system display remains

fixed.

History: The history option lists all the system events that

have occurred. This option can be selected from the Main Menu

by pressing the

[History] key. After pressing the [History] key,

(54)

IV.

IV.

System Operation

System Operation

Basic Use of System: Other Functions

History example: You have already started at the Main Menu

and pressed the

[History] key.

2

1

3

4 5 6

7 8 9

# Cmnd

0

Prog

*

Clear Disable Drill Test History Reset Silence Trouble Silenced Power Alarm 12/12 DRILL:OVER 08:13 102999 Event# Total # of stored events Event

Time Date (mm/dd/yy)

• Press

[7] to

backtrack

through the

history buffer.

• Press

[9] to

scroll to the next

event record.

In systems without a DS9431 Multiplex Expansion Module, all

history events will be cleared if the system loses all power.

IMPORTANT!

(55)

IV.

IV.

System Operation

System Operation

Point/Zone Mapping

• The panel supports a flexible system to map input points to

output points.

• The system is defaulted so that all NAC outputs are activated

by a fire alarm.

• By programming output zones, you can implement almost any

desired output activation scheme, such as “floor above/floor

below” activation or conditional elevator recall.

Input Points: Initiating devices such as smoke detectors, pull

stations, etc.

Zone: A group of input points (Zones 1-50 are configurable,

52-63 are activated automatically).

Output Points: NAC devices such as bells, strobes, etc.

Relays are also output points.

(56)

IV.

IV.

System Operation

System Operation

Point/Zone Mapping

IMPORTANT!

IMPORTANT!

Inputs activate zones; zones activate outputs.

(57)

IV.

IV.

System Operation

System Operation

Point/Zone Mapping

Zones 1-50 are available for the installer to program.

Each input may activate one zone, however, any number

of inputs may drive the same zone.

Zones above 50 are automatically activated by inputs.

For example, any input that is configured as a

“waterflow” type will activate Zone 61 when it is

alarmed. Any output driven by Zone 61 will activate

when any waterflow type point is alarmed.

(58)

IV.

IV.

System Operation

System Operation

Personal Identification Numbers

Your system may have up to 100 different PINs.

Each PIN is 4 digits long.

A PIN may be assigned to each User Number 00-15.

User codes 16-99 are available with the installation

of a DS9431 Multiplex Expansion Module.

There is one PIN for each User Number. Attempting to

assign the same PIN to multiple User Numbers will result

in the 3-beep error tone, and the change will not be made.

User Number 00 is designated as a

Master Code. It can be

(59)

IV.

IV.

System Operation

System Operation

PIN Authority Levels

Authority levels are assigned to PINs to determine which

functions each user will be able to perform.

PINs should never be programmed with common sequences such

as 1111, 1234 or 2468 because they are easily violated.

IMPORTANT!

IMPORTANT!

PIN AUTHORITY LEVELS PIN Authority Level Allowed Operations

Maximum (1) Medium (2) Minimum (3)

None (0)

All panel operations, including programming.

System test modes, fire drill, reset, disable, silence, view history. Silence, view history.

(60)

V.

V.

System Programming

System Programming

How to Program: Point Programming

• Each of the points in the system can be programmed with its

own characteristics.

Point functions simplify the programming of points by

allowing you to define a common set of characteristics for

similar points, and then assigning those characteristics to

selected points as a

point function.

• There are 16 point functions, each of which has these

programmable features:

• Configuration (fire, waterflow, etc.)

• Local Only Operation

• Silencing

• Loop Response

Function:

An action; it does something. 8 total.

Point Function:

(61)

V.

V.

System Programming

System Programming

How to Program: Point Programming

• Each point is assigned to use the characteristics of one point

function, and then is individually programmed for these

additional characteristics:

• Response to an Open Circuit

• Enabled Status

• Output Zone

• Verification

• Latching

(62)

V.

V.

System Programming

System Programming

How to Program: Point Programming

• Before programming the panel, it is best to first determine the

types of functions that are required, and then map the various

input points to the functions.

• For example, you may determine that you have the following

functions:

• 1 = pull station

5 = supervisory input

• 2 = smoke detector

6 = monitor input

• 3 = reset keyswitch

7 = local test

(63)

V.

V.

System Programming

System Programming

How to Program: Point Programming

• This table shows the characteristics that correlate with each

function:

Fire No No Fast

1. Pull Station

Fire No No Fast

2. Smoke Detector

Reset Yes No Fast

3. Reset Keyswitch

Silence Yes No Fast

4. Silence Keyswitch

Supervisory No Yes Fast

5. Supervisory Input

Monitor Yes Yes Fast

6. Monitor Input

Fire Yes Yes Fast

7. Local Test

Waterflow No No Programmed

8. Waterflow Sensor

Function Configuration Local Only? Silenceable? Loop Response

NOTE:

NOTE:

(64)

V.

V.

System Programming

System Programming

How to Program: Point Programming

• As shown above, a function can be assigned to a point function,

which can be assigned to several different zones.

(65)

V.

V.

System Programming

System Programming

How to Program: Alpha Programming

When programming the

Point Descriptions, the

numeric keys are used to

enter alphanumeric

information similar to the

way telephone buttons are

used to process

information over phone

lines - each key represents

4 or more letters or

symbols.

A different character will

be entered each time a

numeric key is pressed.

* Press [1] nine times to

reach this value.

** Press the listed key 4

times to reach this value.

B 1 2 3 4 5 6 7 8 9 0 SILENCE DISABLE CLEAR # CMND SPACE 1

,

& / # ! -* A C D E F G H I J K L M N O P Q R S T U V W X Y Z 2** 3** 4** 5** 6** 7** 8** 9** 0

Enters the description and returns to the programming menu.

Returns to the programming menu without entering changes.

Moves the cursor one space to the right. Moves the cursor one space to the left.

(66)

V.

V.

System Programming

System Programming

How to Program: Format Programming

4/2: When 4/2 format is used, reports generated by points

consist of an event type (1st digit) and a point number (2nd

digit). Digits may be programmed for fire alarm, fire restoral,

waterflow alarm, supervisory alarm, point trouble, trouble

restore, point disable, disable restoral and monitor alarm. The

same event type (1st digit) will be sent for any point. The point

number is the second digit. Each point may be programmed to a

different digit.

SIA: The report that is sent by the SIA format when the panel is

(67)

V.

V.

System Programming

System Programming

How to Program: Format Programming

BFSK: 5 system events may be programmed for two unique

digits each when the BFSK format is used.

Contact ID: The Contact ID reports are all fixed and do not

need to be programmed.

3/1: The 3/1 reporting codes are determined by the

programming of the 4/2 codes. Only Digit 1 (left digit of the

two-digit code) is transmitted. Also, only the first 3 two-digits of the

(68)

V.

V.

System Programming

System Programming

How to Program: Understanding Shortcuts

• Shortcuts provide speedy instructions to panel programming by

reducing repetition.

• Shortcuts list the buttons to push to get to the desired level.

• Three levels in programming shortcut:

Level 1: Main Menu. <PROG/0> is Main Menu choice

for all system programming. First number in shortcut is 0.

Level 2: Provides 8 options to choose from: PROG TIME,

SECURITY, PROG SYSTEM, PROG INPUTS, PROG

OUTPUTS, PROG ACCOUNTS, PROG FORMATS and

HISTORY DEFAULTS. Second shortcut number enters the

Level 2 option and brings you to Level 3. DS9431

Multiplex Expansion Module adds ninth option:

PROGRAM MUX.

Level 3: Third shortcut number represents Level 3

(69)

V.

V.

System Programming

System Programming

How to Program: Understanding Shortcuts

Shortcut = 0

1

2

Press “0” to select PROG from the Main Menu which scrolls at the System Normal display.

Press “1” to select PROG TIME

from Sub-Level 2.

Press “2” to select AUTO TEST from Sub-Level 3. At this point, you should follow the procedural description.

Lvl 1

Lvl 2

Lvl 3

LEVEL 1

(MAIN MENU)

LEVEL 2

LEVEL 3

LEVEL 4

PROG/0

1- PROG TIME 1- SYSTEM 2- AUTO TEST TEST FREQ TEST TIME First number in shortcut Second number

in shortcut Third numberin shortcut

The above example is the shortcut to TEST FREQ and TEST

TIME.

(70)

V.

V.

System Programming

System Programming

Programming: Menus

SYSTEM NORMAL

SELECT: PROG/0

SELECT: CMD/#

SELECT: TEST

SELECT: HISTORY

SELECT: DISABLE

SELECT: DRILL

Main Menu

PROG/0

1- PROG TIME

2- SECURITY

3- PROG SYSTEM

4- PROG INPUTS

5- PROG OUTPUTS

6- PROG ACC’NTS

Programming Menu

8- HISTORY DEFLTS

9- PROGRAM MUX

7- PROG FORMATS

In the Programming Menu, Option #9 is only possible with the

addition of a DS9431 Multiplex Expansion Module.

(71)

V.

V.

System Programming

System Programming

PROG TIME

Level 1

(Main Menu) Level 2 Level 3 Level 4 Level 5

1- SYSTEM 2 - AUTO TEST 3 - DAYLIGHT SAV 1- PROG TIME

PROG/0 1- TEST TIME

(72)

V.

V.

System Programming

System Programming

PROG TIME: System

PROG TIME 1- SYSTEM 2- AUTO TEST 3- DAYLIGHT SAV

PROG TIME Menu

System

Shortcut: 0- PROG, 1- PROG TIME, 1- SYSTEM

ENTER DATE

MMDDYY: ________ Enter the date followed by the [#] key.

ENTER TIME

(73)

V.

V.

System Programming

System Programming

PROG TIME: Auto Test

PROG TIME 1- SYSTEM 2- AUTO TEST 3- DAYLIGHT SAV

PROG TIME Menu

Automatic Test: Test Time

Shortcut: 0- PROG, 1- PROG TIME, 2- AUTO TEST, 1- TEST TIME

This feature allows you to program the time of day at which the automatic tests occur and uses a 24-hour clock (11:00 pm = 2300).

Enter the time followed by the [#] key. AUTO TEST TIME

(74)

V.

V.

System Programming

System Programming

PROG TIME: Auto Test

Automatic Test: Test Frequency

Shortcut: 0- PROG, 1- PROG TIME, 2- AUTO TEST, 2- TEST FREQNCY

This feature allows you to program how often the automatic test reports are sent. The first test will be sent when the programmed test time matches the system time. Subsequent reports will be sent according to the selected interval.

Scrolling Menu Current Setting

Press the number key that corrsponds to your selection. AUTO FREQNCY (_) 1- 6 HOURS 2- 12 HOURS 3- 24 HOURS 4- 7 DAYS 5- 28 DAYS PROG TIME 1- SYSTEM 2- AUTO TEST 3- DAYLIGHT SAV

(75)

V.

V.

System Programming

System Programming

PROG TIME: Daylight Savings

Daylight Savings

Shortcut: 0- PROG, 1- PROG TIME, 3- DAYLIGHT SAV

This feature enables automatic adjustment of system time for Daylight Savings. The dates for the adjustment are pre-programmed in the system.

Press [1] disable the Daylight Savings feature, or press [2] to enable it.

DAYLIGHT SAV 1- DISABLE 2- ENABLE PROG TIME 1- SYSTEM 2- AUTO TEST 3- DAYLIGHT SAV

(76)

V.

V.

System Programming

System Programming

SECURITY

Programming Tree for SECURITY functions:

Level 1

(Main Menu) Level 2 Level 3 Level 4 Level 5

(77)

V.

V.

System Programming

System Programming

SECURITY: PINs

PINs: Programmer PIN

Shortcut: 0- PROG, 2- SECURITY, 1- PINS, 1- PROGRAMR PIN

Press [1] for Programmer PIN. SECURITY

1- PINS

2- AUTHORITY

SECURITY Menu

The Programmer PIN is the code used by the installer to configure and operate the panel. Factory default code is 9876 and may be changed at any time.

PROGRAM PINS 1- PROGRAMR PIN 2- USER PINS

USER 0

ENTER PIN: _____ Enter the PIN and press [#].

(78)

V.

V.

System Programming

System Programming

SECURITY: PINs

PINs: User PINs

Shortcut: 0- PROG, 2- SECURITY, 1- PINS, 2- USER PINS

Press [2] for User PINS.

Up to 15 additional user codes (or up to 100 when the DS9431 is installed) can be programmed for the unit to protect the system from unauthorized operation and allow a record to be kept of actions by individual system users.

PROGRAM PINS 1- PROGRAMR PIN 2- USER PINS

Enter the user for which you want to program a PIN and press [#]. For example, for User 5, press [5]. PROGRAM PINS 1- PROGRAMR PIN 2- USER PINS

PIN Menu

USER 5 ENTER PIN: _____ OTHER PINS USER (01-15)

(79)

V.

V.

System Programming

System Programming

SECURITY: Authority

Authority

Shortcut: 0- PROG, 2- SECURITY, 2- AUTHORITY

Enter the user for which you want to program authority and press [#].

This feature determines which system actions a user can perform. SECURITY 1- PINS 2- AUTHORITY

SECURITY Menu

AUTHORITY USER (01-15)

Press the number key that corresponds to your selection. USER 1 ATHRY ( ) 0- NONE 1- MAXIMUM 2- MEDIUM 3- MINIMUM Current Setting

(80)

V.

V.

System Programming

System Programming

PROG SYSTEM

Programming Tree for PROG SYSTEM functions:

Level 1

(Main Menu) Level 2 Level 3 Level 4 Level 5

(81)

V.

V.

System Programming

System Programming

PROG SYSTEM: Program Timers

Program Timers

Shortcut: 0- PROG, 3- PROG SYSTEM, 2- TIMERS

Press [1] to program the Smoke Reset Timer.

From the PROG SYSTEM Menu, press [2] to reach the Program Timers Menu.

PROG SYSTEM Menu

(82)

V.

V.

System Programming

System Programming

PROG SYSTEM: Program Timers

Program Timers: Smoke Reset

Shortcut: 0- PROG, 3- PROG SYSTEM, 2- TIMERS, 1- SMOKE RESET

This feature designates the length of time that the smoke detector power is turned off after reset. No alarms are registered by the system for 5 seconds after the power is turned back on.

Program Timers Menu

TIMERS 1- SMOKE RESET 2- AC FAIL DLY 3- AUTO SILENCE 4- (reserved) 5- DISPLAY RATE SMOKE RESET ( ) (0-16 SECS): _____

From the Program Timers Menu, press [1] for Smoke Reset. Enter the value and press [#].

(83)

V.

V.

System Programming

System Programming

PROG SYSTEM: Program Timers

Program Timers: AC Fail Delay

Shortcut: 0- PROG, 3- PROG SYSTEM, 2- TIMERS, 2- AC FAIL DLY

This feature sets the number of hours the DS9400 will wait after an AC failure before sending an AC Failure report.

Program Timers Menu

TIMERS 1- SMOKE RESET 2- AC FAIL DLY 3- AUTO SILENCE 4- (reserved) 5- DISPLAY RATE

Option 1, Wait for DC, causes the AC fail report to be sent when the battery has been 25% depleted based on the measured voltage of the battery. Press [1] if this is the desired setting. When Wait for DC is the current selection, the Enter Time menu will display 24 as the time in hours.

Option 2, Enter Time, allows you to set the time when the AC fail report is sent. Press [2] if this is the desired setting.

AC FAIL DELAY 1- WAIT FOR DC 2- ENTER TIME Current Setting AC FAIL DLY ( ) (01-24 HRS): _____

(84)

V.

V.

System Programming

System Programming

PROG SYSTEM: Program Timers

If the condition is not rectified after an alarm is silenced

(automatically or manually), the alarm will sound again after 24

hours. The system must be reset after silencing to allow the alarmed

zones to restore and detect new alarms.

IMPORTANT!

IMPORTANT!

Program Timers: Auto Silence

Shortcut: 0- PROG, 3- PROG SYSTEM, 2- TIMERS, 3- AUTO SILENCE

This feature will silence the sounding of an alarm condition on selected NACs after a certain amount of time.

Program Timers Menu

TIMERS 1- SMOKE RESET 2- AC FAIL DLY 3- AUTO SILENCE 4- (reserved) 5- DISPLAY RATE

Enter the desired length of time (or 0 to disable) and press [#].

Entering 0 will disable the feature and the only way to turn off an alarm will be to manually silence it. Entering between 5 and 99 minutes means that the alarm will sound for that much time before automatically silencing.

Current Setting

From the Program Timers menu, press [3] for Auto Silence. AUTO SILENCE ( )

(85)

V.

V.

System Programming

System Programming

PROG SYSTEM: Program Timers

Program Timers: Display Rate

Shortcut: 0- PROG, 3- PROG SYSTEM, 2- TIMERS, 5- DISPLAY RATE

This feature allows you to set the speed at which menus are displayed on the LCD (in units of ¼ sec.).

Program Timers Menu

TIMERS 1- SMOKE RESET 2- AC FAIL DLY 3- AUTO SILENCE 4- (reserved) 5- DISPLAY RATE

Enter the desired value and press [#].

Current Setting

From the Program Timers menu, press [5] for Display Rate. AUTO SILENCE ( )

(86)

V.

V.

System Programming

System Programming

PROG SYSTEM: AC Line Synch

AC Line Synch

Shortcut: 0- PROG, 3- PROG SYSTEM, 3- AC LINE SYNCH

When AC power is available, the panel uses the line frequency to stabilize the real time clock. This setting must match the frequency of the local AC power (60 Hz in US).

Press the number key that corresponds to your selection and press [#]. From the PROG SYSTEM menu, press [3] for AC Line Synch.

PROG SYSTEM Menu

(87)

V.

V.

System Programming

System Programming

PROG SYSTEM: Option Bus

Be sure the device count displayed when this operation completes

matches the number of devices installed on both buses. Devices not

detected during the update bus operation will not operate and will

not be supervised.

IMPORTANT!

IMPORTANT!

Option Bus: Update Bus

Shortcut: 0- PROG, 3- PROG SYSTEM, 4- OPTION BUS, 1- UPDATE BUS

When devices are added or removed from the option buses, this feature queries both buses and updates the list of connected devices. This enables the new devices and removes supervision from devices no longer present.

From the PROG SYSTEM menu, press [4] for Option Bus. From the Option Bus menu, press [1] for Update Bus.

The above window will appear once the Update Bus operation is complete.

OPTION BUS Menu

OPTION BUS 1- UPDATE BUS 2- SETUP KEYPADS

(88)

V.

V.

System Programming

System Programming

PROG SYSTEM: Option Bus

Option Bus: Setup Keypad

Shortcut: 0- PROG, 3- PROG SYSTEM, 4- OPTION BUS, 2- SETUP KEYPAD

This feature tells the system how many keypads should be supervised. It automatically performs an update bus operation as it finishes.

From the OPTION BUS menu, press [2] for Setup Keypad. Enter the desired value and press [#].

OPTION BUS Menu

OPTION BUS 1- UPDATE BUS 2- SETUP KEYPADS

(89)

V.

V.

System Programming

System Programming

PROG SYSTEM: PIN Required?

Pin Required?: Local

Shortcut: 0- PROG, 3- PROG SYSTEM, 5- PIN REQUIRED?, 1- LOCAL

A PIN can be required before operations can be performed using the local, built-in keypad.

From the PROG SYSTEM menu, press [5] for Pin Required?.

From the Pin Required? menu, press [1] to require a PIN at the local keypad.

Press the number key that corresponds to your selection.

PIN REQUIRED? Menu

PIN REQUIRED? 1- LOCAL

2- REMOTE

LOCAL KEYPD PIN? ____ :YES (1) NO (2) Current

(90)

V.

V.

System Programming

System Programming

PROG SYSTEM: PIN Required?

A PIN can be required before operations can be performed using the

remote keypads on the option bus. If the remote keypads are not

otherwise secured, this option must be set to YES to comply with

NFPA and UL requirements.

IMPORTANT!

IMPORTANT!

Pin Required?: Remote

Shortcut: 0- PROG, 3- PROG SYSTEM, 5- PIN REQUIRED?, 2- REMOTE

A PIN can be required before operations can be performed using a DS9447 Remote LCD Keypad.

From the PROG SYSTEM menu, press [5] for Pin Required?.

From the Pin Required? menu, press [2] to require a PIN at the remote keypad.

Press the number key that corresponds to your selection.

PIN REQUIRED? Menu

PIN REQUIRED? 1- LOCAL

2- REMOTE

REMOTE KEYPD PIN? ____ :YES (1) NO (2) Current

(91)

V.

V.

System Programming

System Programming

PROG SYSTEM: Remote Programming

IMPORTANT!

IMPORTANT!

According to NFPA 72-1996, a complete functional checkout of the

control unit operation is required after any programming,

especially remote programming.

Remote Programming

Shortcut: 0- PROG, 3- PROG SYSTEM, 7- REMOTE PGM

Remote programming allows the panel to be called by phone from a remote site to reconfigure any of the programmable options. This option should be left set to DISABLE.

From the PROG SYSTEM menu, press [7] for Remote Programming.

Press [0] to select DISABLE, or [1] to ENABLE.

(92)

V.

V.

System Programming

System Programming

PROG INPUTS

Programming Tree for PROG INPUTS functions:

Level 1

(Main Menu) Level 2 Level 3 Level 4 Level 5

0 - FUNCTION 1 - ALARM/TROUBLE 2 - OUTPUT ZONE 3 - VERIFICATION 4 - LATCHING 5 - DESCRIPTION <DRILL> NEXT PNT

<HIST> PREV PNT 1 - FIRE

2 - WATERFLOW 3 - SUPERVISORY 4 - MONITOR 5 - RESET 6 - SILENCE 1 - LOCAL ONLY 2 - (reserved) 3 - SILENCEABLE 4 -LOOP RESPONSE 5 - (reserved) <DRILL> NEXT FCT <HIST> PREV FCT 0 - CONFIGURE 1- POINT NUMBER 2 - POINT FUNCTION

3 - POINT COPY 1- COPY FROM POINT ___

2 - COPY TO FIRST POINT ___ 3 - COPY TO LAST POINT ___

(93)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Number

Point Number

Shortcut: 0- PROG, 4- PROG INPUTS, 1- POINT NUMBER

Scrolling Menu

Press the number key that corresponds to your selection. Pressing the [DRILL] button will bring you to the next point (for example: If you are programming Point 2, the [DRILL] button will move you to Point 3).

Pressing the [HIST] button will return you to the previous point (for example: If you are programming Point 2, the [HIST] button will move you to Point 1).

Version 2.0 of the DS9400 firmware introduces the concept of “point functions”. Point functions allow for quick programming of similarly functioning points with common settings (for example: pull stations, smoke detectors).

PROG INPUTS 1- POINT NUMBER 2- POINT FUNCT 3- POINT COPY

PROG INPUTS Menu

(94)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Number

Assigning Point Functions

Shortcut: 0- PROG, 4- PROG INPUTS, 1- POINT NUMBER, 0- FUNCTION

This feature is for assigning each point to one point function. A point function is a set of characteristics that you can assign to selected points. There are 16 point functions to choose from.

POINT NUMBER Menu

PROG POINT 1- ALARM/TROUBL 2- OUTPUT ZONE 3- VERIFICATION 0- FUNCTION 4- LATCHING 5- DESCRIPTION <DRILL> NEXTPNT <HIST> PREV PNT

From the Point Number menu, press [0] to select Point Function. POINT FUNC. ( )

(01-16): _____

(95)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Number

Alarm/Trouble Status

Shortcut: 0- PROG, 4- PROG INPUTS, 1- POINT NUMBER, 1- ALARM/TROUBL

This feature allows you to program the system to an open loop condition. A shorted loop will always cause an alarm condition. ALARM: when a point goes into an open circuit state, the system alarms. TROUBLE: when the point goes into an open circuit state, the system responds with a trouble condition.

POINT NUMBER Menu

PROG POINT 1- ALARM/TROUBL 2- OUTPUT ZONE 3- VERIFICATION 0- FUNCTION 4- LATCHING 5- DESCRIPTION <DRILL> NEXTPNT <HIST> PREV PNT

From the Point Number menu, press [1] to select Alarm/Trouble Status.. OPEN STATUS ( )

1- ALARM

Press [1] to select ALARM on open loop and ALARM on shorted loop, or press [2] to Current Setting

(96)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Number

Output Zones

Shortcut: 0- PROG, 4- PROG INPUTS, 1- POINT NUMBER, 2- OUTPUT ZONE

POINT NUMBER Menu

PROG POINT 1- ALARM/TROUBL 2- OUTPUT ZONE 3- VERIFICATION 0- FUNCTION 4- LATCHING 5- DESCRIPTION <DRILL> NEXTPNT <HIST> PREV PNT

From the Point Number menu, press [2] to select Output Zone. OUTPUT ZONE ZZZ

(00-50): _____

Enter the point number you wish to program and press [#]. Press the number key that corresponds to your selection. ZZZ indicates the point being programmed.

(97)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Number

Verification

Shortcut: 0- PROG, 4- PROG INPUTS, 1- POINT NUMBER, 3- VERIFICATION

POINT NUMBER Menu

PROG POINT 1- ALARM/TROUBL 2- OUTPUT ZONE 3- VERIFICATION 0- FUNCTION 4- LATCHING 5- DESCRIPTION <DRILL> NEXTPNT <HIST> PREV PNT

From the Point Number menu, press [3] to select Verification. ALARM VERIF (ZZZ)

_____:YES (1) NO (2)

[1] to verify or [0] to not verify. ZZZ indicates the point being programmed.

Current Setting

(98)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Number

Latching

Shortcut: 0- PROG, 4- PROG INPUTS, 1- POINT NUMBER, 4- LATCHING

POINT NUMBER Menu

PROG POINT 1- ALARM/TROUBL 2- OUTPUT ZONE 3- VERIFICATION 0- FUNCTION 4- LATCHING 5- DESCRIPTION <DRILL> NEXTPNT <HIST> PREV PNT

From the Point Number menu, press [4] to select Latching. LATCHING? ZZZ

_____:YES (1) NO (2)

Press the number key that corresponds to your selection. ZZZ indicates the point being programmed.

Current Setting

(99)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Number

Point Description

Shortcut: 0- PROG, 4- PROG INPUTS, 1- POINT NUMBER, 5- DESCRIPTION

POINT NUMBER Menu

PROG POINT 1- ALARM/TROUBL 2- OUTPUT ZONE 3- VERIFICATION 0- FUNCTION 4- LATCHING 5- DESCRIPTION <DRILL> NEXTPNT <HIST> PREV PNT

From the Point Number menu, press [5] to select Point Description. PNT DSCRPTN ZZZ:

_________________

(100)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Function

Point Function

Shortcut: 0- PROG, 4- PROG INPUTS, 2- POINT FUNCTION

From the PROG INPUTS menu, press [2] to select Point Function. POINT FUNC. ( )

(01-16): _____

Enter the function number you wish to program and press [#].

There are 16 point functions, each of which has programmable features for configuration (fire, waterflow, etc.), local only operation, silencing and loop response.

PROG INPUTS Menu

PROG INPUTS 1- POINT NUMBER 2- POINT FUNCT 3- POINT COPY Current Setting PROG FUNCT 1- LOCAL ONLY 2- (reserved) 3- SILENCEABLE 0- CONFIGURE 4- LOOP RESPONS 5- (reserved) <DRILL> NXT FCT <HIST> PREV FCT

(101)

V.

V.

System Programming

System Programming

PROG INPUTS: Point Function

Configure

Shortcut: 0- PROG, 4- PROG INPUTS, 2- POINT FUNCTION, 0- CONFIGURE Fire: When activated, point displays “FIRE ALARM” on panel and keypads, activates selected

output devices and sends a fire alarm report (if programmed). Fire points are forced to a latching characteristic when first configured.

Waterflow: When activated, point displays “WATERFLOW ALARM” on panel and keypads,

activates selected devices and sends a waterflow alarm report (if programmed). Waterflow points are forced to a non-verify characteristic when first configured.

Supervisory: When activated, point displays “SUPERVISORY ALARM” on panel and

keypads, and sends a supervisory alarm report (if programmed). Supervisory points are forced to a non-verify characteristic when first configured.

Monitor: When activated, point displays “MONITOR ALARM” on panel and keypads, activates

selected devices and sends a fire alarm report (if programmed). If using the SIA format for communication to the central station, a “UA” alarm will be sent instead of an “FA” alarm.

Reset: When activated, point initiates a panel reset operation to clear alarms and reset

smoke detectors. Only Points 1-8 can be configured as reset points.

Silence: When activated, point initiates a panel silence operation to turn off sounders if the

References

Related documents

On January 31, 2014, the Staff issued a no-action let- ter (M&amp;A No-Action Letter) permitting certain “M&amp;A Brokers” to facilitate securities transactions in connection

IBM applied its decades of experience in building systems management solutions to build IBM Flex System Manager. Over 40 years of platform and virtualization management experience as

The current research describes the adaptation of an informant-rating instrument (the Extreme Demand Avoid- ance Questionnaire; O’Nions et al. 2014b ; EDA-Q) for use as a

[r]

Thousands of years ago, people in Mexico loved chocolate so much that, at times, they used it as money or for trade.. They even had a god of chocolate

T wo thousand years ago, kings called emperors ruled the city of Rome.. At that time, Rome was one of the strongest cities in

A superhero needs his own special physical abilities to help him fight enemies.. I want to draw my own

The Seckford Education Trust and our schools should be environments in which pupils and students or their parents/carers can feel comfortable and confident

This Service Level Agreement (SLA or Agreement) document describes the general scope and nature of the services the Company will provide in relation to the System Software (RMS

Although theoretically the likelihood of finding evidence that dumped imports have in- jured the domestic industry should fall as the industry increases its output, the results from

The present study aimed at comparing the neopterin level of idiopathic infertile and normospermic male groups as well as specifying its relationship with

Keypad Display Symbols 1 Keypad User Sheet 2-3 Programming Access Codes 4 Programming The Time &amp; Date 5 Trouble Shooting Guide 6-7 Using Your Keyfob 7 Alarm Protocol

All teachers and support staff undertake induction on taking up a post and this includes a meeting with the SENDCO to explain the systems and structures in place around the

TSCh1TEMP alarm persists after Warm Start recovery time (approx 3 minutes), contact your next level of technical support before proceeding. Cold Start the card raising

1 2 3 ENT CLR Main Menu 5 6 4 7 8 9 0 SYSTEM START SYSTEM STOP ALARM RESET ALARM SILENCE Main Menu &lt;0&gt; Mode=Direct Feed Hrs Since Start=000 System On LOW QUALITY HIGH

[r]

shapes of the AGN and star formation IR SEDs (see blue dashed and red solid curves in Fig. 2 ), which results in sources with a signif- icant contribution from the AGN component

At present the available ground improvement techniques are replacement of soil, vertical drains, stone columns, vibro compaction , dynamic compaction, soil

Current Research &amp; Teaching Interests: Trauma theory and pastoral care/communal trauma narratives in Southeast Asia; Conflict and peacebuilding; congregational studies research,

The UNO Assessment Committee is responsible for guiding the process of campus-wide academic assessment of student learning, and to that end it conducts regular reviews of

factors of firm and corporate governance characteristics associated with audit quality or bank-.. appointed auditors using of propensity-score matching

This model posits four types of health beliefs that affect an individual’s health behavior, in this case, the decision to seek mental health services: perceived

Using a nationwide database of hospital admissions, we established that diverticulitis patients admitted to hospitals that encounter a low volume of diverticulitis cases have