Fire Protection Of Ventilation Systems

DAMPERS & AIR TRANSFER

GRILLES

A PRESENTATION

BY

PHILLIP HORTON

OF

(2)

THE AIM OF THE WORKSHOP:

Provide assistance in the selection,

installation and operation of ventilation

fire protection products for those who

have the responsibility for meeting or

maintaining the requirements of

(3)

Section 1 - NEW LEGISLATION AND

GUIDANCE

1. The Regulatory Reform Order: 2005 is now in effect and brings in major changes particularly in responsibility and culpability.

– The “Responsible Person” will have to ensure that the fire safety of a building is in all respects compliant with the relevant codes etc.

– This includes risk assessment, selection of systems and products, correct installation, operating procedures and servicing.

– It is imperative that all procurements are accompanied by relevant performance, reliability and durability evidence.

– Installations shall be completed in accordance with the manufacturers instructions and relevant guidance documents or standards.

– Qualified persons adhere to a maintenance/servicing schedule.

Failure to comply may result in serious legal

consequences

(4)

NEW LEGISLATION AND GUIDANCE

2.

Approved Document ‘B’: 2007

has also undergone a major shift in emphasis.

It is no longer necessary to adhere to purely prescriptive solutions.

Performance based solutions must be backed with substantive evidence of ‘fitness for use’.

Encourages the use of certificated products and accredited installers.

Contains revised definitions. (e.g. P142 fire damper)

(5)

NEW LEGISLATION AND GUIDANCE

3. Health Technical Memorandum 05-02:

2007

Guidance in support of functional provisions for healthcare premises

(Firecode - fire safety in the NHS).

Competent persons – must understand their responsibilities

and take appropriate actions or decisions.

(This can only be achieved by an awareness of product and system limitations)

Certification schemes encouraged.

Definitions now clarify different damper and grille types.Greater emphasis on smoke control.

Fans continue to run in fire conditions.

(6)

Section 2 – DEFINITIONS

Air transfer grille–A device which provides a security and privacy screen for an aperture through which air

is passed as part of a ventilation system. The device may incorporate a means of diffusing the air stream. Applications include: walls, doors and low velocity duct termini that are not part of the boundary of a fire compartment.

Fire containment air transfer grille– A device that when activated by a rise in temperature of the air

stream provides containment of fire and hot gases in addition to the normal function of an air transfer grille but is not intended to control cold smoke.

Fire and cold smoke containment air transfer grille- A device which provides containment of

cold smoke, fire and hot gases by either interface with smoke sensors or by a rise in temperature of the air stream in addition to the normal function of an air transfer grille.

Fire damper– A device that when activated by a rise in temperature of the air stream in a ventilation duct will

close, thus preventing the spread of flame and hot smoke beyond the fire compartment boundary through which, the duct is passing.

Fire and smoke damper - A device that when activated either by interface with smoke sensors or by a

rise in temperature of the air stream in a ventilation duct will close, thus preventing the spread of cold smoke, flame and hot smoke beyond the fire compartment boundary through which, a ventilation duct is passing.

Smoke control damper– A device that may be normally open or closed and is designed to allow smoke

to be extracted or constrained through a range of temperatures up to 600OC. This product is usually fitted into

(7)

Section 3 – GENERAL PROBLEMS WITH VENTILATION SYSTEMS Limitations of the product selection process

• Fire resistance tests are always conducted with new specimens. • Debris, dust and grease soon build up in real installations.

• Mechanisms jam and thermal release devices become masked. • Bulky damper or air transfer grilles are often difficult to install in the

correct location.

• Once fitted limited accessibility discourages servicing.

• Problems of installation, location and accessibility for servicing makes reliability questionable.

• Often poor installation negates the initial purpose of fire protection. • In many installations the condition and location of dampers and air

transfer grilles are not even known. • The new regulations make it clear:

(8)

CONSEQUENCES

• Dampers with unproven durability and reliability may fail

when most needed.

• The failure of one damper may have catastrophic effects

on life safety.

• A damper dependent on one set of moving blades which

is not regularly serviced is unreliable.

• Where possible choose a fire and smoke damper that

has two separate modes of ‘fail safe’.

(9)

Section 4 -

CRITICAL SELECTION

CRITERIA

Establish the performance requirements for the particular application

(Fire integrity period, Aerodynamic characteristics, Leakage rate, Insulation value.)

Implications to the fire safety model if the air transfer grille or damper should fail - (Risk Analysis)

(Would there be a catastrophic failure to the buildings fire protection system?)

Product sizes compatible with installation in the correct

locations? (30% restriction of free area has no noticeable effect on pressure loss)

Ensure products are fit for use (reliability and durability)

(Insist on evidence to prove real time characteristics)

Insist on seeing test evidence for fire integrity, cold smoke containment where required and insulation performance if necessary

(Examine test evidence to ensure that the product has been tested for relevant applications in accordance with the appropriate standards and is still valid)

(10)

Section 5 – CHOICES

MECHANICAL OPTIONS AVAILABLE

Fire and hot gas containment mechanical air transfer grilles & dampers activated by thermal release mechanisms

Fire and cold smoke containment mechanical air transfer grilles & dampers electrically activated by interface with smoke sensors and backed up by thermal release

mechanisms

The above products can be in the form of:

(11)

INTUMESCENT BASED OPTIONS

AVAILABLE

Intumescent fire and hot smoke containment dampers & air transfer grilles in which the core material expands when exposed to a rise in temperature and fills the apertures through which air would normally flow

Intumescent fire and cold smoke dampers & air transfer grilles that incorporate an electrically activated mechanical system activated by interface with smoke sensors and

backed up by heat activated intumescent elements

The above products can be obtained in the form of:

Multi-slatted matrix; Honeycomb, Corrugated layers’ Perforated blocks.

Combined fire and smoke air transfer grilles & dampers are only available in multiple slat matrix types.

(12)

Section 6 - COMPARISONS

Fire and hot smoke

containment only

(13)

FACTORS THAT SHOULD INFLUENCE SELECTION

‘A’

Mechanical Thermal Release Air Transfer Grilles & Fire Dampers: • Failure to close can be caused by incorrect alignment or distortion

during installation or a build up of deposits during normal use. • No back up to the thermal release mechanism, failure to operate

means that fire and smoke travel unchecked.

• All mechanical systems need regular servicing & testing.

• Some Curtain blade dampers are guaranteed to close only in still air. • Single blade dampers of large area need long casings to

accommodate the blade when it is in the open position.

• Most purely mechanical systems suffer high leakage rates when closed.

(14)

FACTORS THAT SHOULD INFLUENCE SELECTION

‘B’

Intumescent Air Transfer Grilles & Fire Dampers:

• Intumescent products will activate at different temperatures dependent on the material used in their construction.

• Some designs are superior aerodynamically resulting in less pressure drop and minimising build up of deposits.

• Some products are better protected from moisture.

• No moving parts means nothing to jam in the open position

• Usually only require periodic inspection or cleaning in very hostile environments

• Distortion to the ductwork is unlikely to affect the fire performance • Slim section allows easy installation in difficult locations

• Good quality products give negligible leakage at high pressure differentials and will tolerate high air velocities

• Products relying only on intumescent activation are not designed to stop the spread of cold smoke

(15)

15

A Very Bad

Choice

(16)

A COMPARISON OF BEHAVIOUR IN FIRE CONDITIONS

It is popularly believed that because Fusible Link

or Thermal Release Mechanical dampers are

designed to activate at 74

O

C. they will operate

more quickly than Intumescent dampers that

activate at temperatures not less than 100

O

C. in

fire conditions.

The following diagrams show why this is

often not the case.

(17)

Thermal release

Mechanical Fire Damper

Fire Compartment Wall

The Coanda Effect

WHY DO THERMAL RELEASES SOMETIMES ACT SLOWLY?

COOL AIRSTREAM CAUSING FAILURE

(18)

Fire Compartment Wall

The Coanda Effect

Slat Type Intumescent

Damper

HOW DO INTUMESCENT DAMPERS COPE WITH THE COANDA EFFECT?

(19)

300 250 200 150 100 50 0 0 0.5 1.0 1.5 2.0 2.5 TIME IN MINUTES T E M P E R A T U R E D E G C LEGEND

Multi-blade mechanical damper Single blade mechanical damper Slatted intumescent damper

ODPM sponsored simultaneous mechanical and intumescent damper fire integrity test at BRE in 2004

COMPARATIVE CLOSING TIME OF DAMPERS

Intumescent damper closed

(20)

COMPARISON OF BEHAVIOUR IN FIRE

CONDITIONS

Systems using intumescent elements absorb

heat energy as intumescence occurs and

provide insulation performance when

activated, thereby limiting the rise in down

stream temperatures.

Steel mechanical systems absorb little heat

energy in the early stages of a fire but radiate

heat as the fire develops, and may cause

(21)

T E M P E R A T U R E D E G C 700 600 500 400 300 200 100 0 10 20 30 40 50 60 70 TIME IN MINUTES LEGEND

Multi-blade mechanical damper Single blade mechanical damper Slatted intumescent damper

ODPM sponsored simultaneous mechanical and intumescent damper

fire integrity test at BRE in 2004

COMPARATIVE DOWN STREAM TEMPERATURES

(22)

Section 7 - FUNCTION

INTUMESCENT VERSUS MECHANICAL

Why are good quality intumescent air transfer

grilles & dampers so reliable?

(23)

EXAMPLE OF INTUMESCENT SLAT

CONSTRUCTION

Intumescent core

Metallic protective skin

Steel edge guards

(24)

ACTIVATION PROCESS

Gases inflating outer skin Intumescent activating CROSS SECTION OF INTUMESCENT SLATS IN AN AIR TRANSFER GRILLE OR DAMPER

(25)
(26)
(27)

VALUE FOR MONEY

QUALITY MADE INTUMESCENT PRODUCTS CAN PROVIDE MORE RELIABILITY

THAN THEIR MECHANICAL COUNTER-PARTS BECAUSE THEY DO NOT JAM

INSTALLATION IS EASIER AND LESS CRITICAL TO FUNCTION

REQUIRE MUCH LESS ATTENTION IN NORMAL USE

INTUMESCENT SYSTEMS CAN ACTIVATE AS QUICKLY AS THERMAL

RELEASE TYPE MECHANICAL SYSTEMS

LOWER ‘DOWN STREAM’ AIR TEMPERATURES REDUCE THE RISK OF

SECONDARY IGNITION

GOOD QUALITY INTUMESCENT PRODUCTS HAVE EXCELLENT

AERODYNAMIC PERFORMANCE

THE OVERALL COST OF PROCUREMENT, INSTALLATION AND MAINTENANCE

(28)

Section 8 - CHOICES

FIRE AND COLD SMOKE

CONTAINMENT SYSTEMS

(29)

COLD SMOKE CONTAINMENT

• Temperatures in ventilation air streams

may rise slowly in real fires

• During this period cool smoke may spread

unhindered by thermally activated fire

dampers or air transfer grilles

• Correctly sited smoke sensors interfaced

with smoke containment systems are the

only way to prevent the spread of cool

(30)

SMOKE SENSING SYSTEMS OPTIONS

a) Mechanical thermal release fire damper

or air transfer grille with a second release

mechanism electrically interfaced with

smoke sensors

b) Intumescent fire damper or air transfer

grille incorporating a mechanical smoke

control system electrically interfaced with

smoke sensors

(31)

Section 9 - COMPARISONS OF FIRE & COLD SMOKE CONTAINMENT SYSTEMS

Vulnerability of purely mechanical

fire & smoke dampers

• If the electrically operated release mechanism fails the

thermal release should activate when the prescribed

temperature is achieved

If the moving plates are jammed neither fire or cold

smoke will be contained, no ‘back up’

• Dampers functioning by mechanical motion should be

cycled regularly

• Most mechanical fire and smoke dampers are not

designed for frequent operation such as auto-cycling

(32)

Section 9 - COMPARISONS OF FIRE & COLD SMOKE CONTAINMENT SYSTEMS

Aspects of good quality intumescent fire and

smoke dampers

• If the electrically operated mechanism fails to close, the

intumescent elements will activate when the prescribed

temperature is achieved

If the moving blades or plates are jammed the

intumescent elements will provide a fire stopping

‘back up’

• Quality fire and smoke air transfer grilles & dampers are

designed to survive a life of automatic cycling for at least

10 years

• Quality systems employ regular auto-cycling to keep

mechanisms clear and to identify faults

(33)

Section 10

UPGRADING FIRE PROTECTION

• Quality intumescent air transfer grilles and dampers are

of slim section and relatively easy to install in restricted

spaces

• Intumescent dampers can be fitted in line with existing

mechanical dampers as ‘back up’

• In most applications good intumescent fire dampers & air

transfer grilles can be fitted and forgotten

• Fire and smoke containment air transfer grilles and

dampers that incorporate an auto-cycling and status

reporting feature will provide confidence and reduce

operating costs

(34)

Section 11 - Standards

• Currently most fire dampers have only been tested to BS 476 part 20 which is now regarded as inadequate.

• EN 1366-2 : 2000 is the current European fire resistance test standard for mechanical dampers. EN 1366-2 is now under revision to remove the

anomalies discovered in the 2000 edition by practical experience. • A new prEN standard has been drafted which identifies the particular

requirements of fire dampers that incorporate intumescent materials. • ISO 10294-1 is the current International fire resistance test standard for

mechanical dampers and is similar to EN 1366-2.

• BS ISO 10294-5: 2005 is the first fire resistance test standard specifically for intumescent fire dampers.

• BS5588 Part 9 : 2000 clearly verifies the role of intumescent dampers and air transfer grilles.

• A draft ETAG 026 which will be the equivalent of a product standard for air transfer grilles has been completed, awaiting publication.

• A new ISO fire test standard for air transfer grilles has just been drafted. • BS9999 allows performance related solutions to compete with traditional

(35)

Section 12 - OVERALL COST CONSIDERATIONS

1. Establish the performance requirements of the various fire and smoke containment elements of a building’s ventilation system.

2. Now weigh the various cost options. 3. Assume a working life of 10 years

4. Add the procurement cost of the satisfactory product options to the costs of installation, commissioning, servicing and repair.

5. The overall costs may be surprising.

6. The higher procurement cost items may be significantly cheaper overall yet provide greater reliability.

(36)

Section 13 - RELIABILITY

TYPE FIRE DAMPERS & AIR TRANSFER GRILLES

FIRE & SMOKE DAMPERS & AIR TRANSFER GRILLES Options MECHANICAL DAMPER INTUMESCENT DAMPER ELECTRO-MECHANICAL INTUMESCENT & ELECTRO-MECHANICAL Damper function

Hot smoke & fire containment

Hot smoke & fire containment

Cold smoke, hot smoke & fire containment

Cold smoke, hot smoke & fire containment Actuation method Fusible link or other thermal release mechanism Intumescent action Combined thermal & electrical release

mechanism

Combined

intumescent action & electrical release mechanism Back up for mechanical jamming

None

No moving

parts to

jam

None

If electro-mechanical element fails, fire is

contained by the intumescent action

Frequency of service

Regularly Rarely Regularly Only when prompted

by the status reporting system

Most reliable

(37)

Section 14 - YOUR DECISION

• Be aware of your current responsibilities.

• Take account of your risk assessment.

• Re-examine the viable product options available.

• Make your choice by

logic

not

habit

.

• Ensure that what is specified is correctly installed.

• Conformance with prescription is no defence if things go

wrong and better choices were ignored.